Pentair Raychem Green Leaf, GREEN LEAF Installation Instructions Manual

THERMAL MANAGEMENT SOLUTIONS EN-RaychemGreenLeaf-IM-EU0209 R1
GREEN LEAF
PROGRAMMABLE THERMOSTAT FOR ELECTRICAL FLOOR HEATING INSTALLATION INSTRuCTIONS
2
CONTENTS
1. DESCRIPTION ..................................................3
2. MOUNTING AND INSTALLATION ......................4
3.USING THE THERMOSTAT ................................. 9
Display in manual on/off programme ...................9
Display in timer programme ..............................10
4. SETTING THE CLOCK .....................................14
5. PROGRAMMING THE TIMER PROGRAMME ....15
6. INSTALLER MENU .........................................17
7. TROUBLESHOOTING ......................................21
8. TECHNICAL SPECIFICATION .......................... 22
3
1. DESCRIPTION
The Raychem Green Leaf Thermostat is a Programmable Thermostat designed for Electrical Floor Heating. The thermostat is designed to control your Electrical Floor Heating in order to give you the best possible comfort and the lowest possible energy usage.
The Thermostat can work in 3 different temperature sensing modes:
• Floor Sensing mode
• Room Sensing mode
• Room Sensing mode with floor temperature limiter
The Thermostat has 2 programs to choose from:
• Manual ON/OFF (Constant Single temperature)
• Timer programme (4 timer events/day) To change from one programme to the other,
just press on the intelligent leaf button“
”.
4
2. MOUNTING AND INSTALLATION
Mounting the Thermostat
Green Leaf is intended for flush mounting in a wall box. It should be positioned approximately 1.5 meters above the floor, protected from direct sunlight and draughts. All electrical conduits passing into the wall box that contain cables must also be sealed to protect the thermostat against draughts, e.g. with a piece of insulation in the conduit outlet.
Step 1: Switch off the power supply Step 2: Detach the metallic support from the
Thermostat using a screwdriver
5
Step 3: Screw the metallic support frame to the in-wall box
Step 4: Install the floor sensor (mandatory for floor sensing mode or room sensing mode with floor temperature limiter). The floor sensor should be installed in a separate flexible conduit all the way to the end, covering the end of the sensor, for easy replacement and to avoid possible signal disturbance on the sensor. For best control performance, position the floor sensor between two heating cables as close as possible to the top floor surface.
Do not position the floor sensor tip closer than 3 cm to the heating cable.
The floor sensor cable can be extended up to 100 m with a separate standard installation cable 2 x 1.5 mm
2
(230VAC).
6
Step 5: Connect the electrical power supply, the sensor and the cold lead of the electrical floor heating system to the Green Leaf according to the electrical diagram. If you connect heating cables exceeding 13A for constant wattage or 10A for self-regulating cables you must use a contactor with an integrated suppression device.
For the earth connection of the floor heating, you must use a separate earth terminal connection block.
PENTAIR Green Leaf
230VAC-50H
Z
T40
13A
IP20
sensor
7
NTC
Floor
Sensor
Heating cable
230 VAC
Max. 13A*
Power supply
230 VAC
Direct connection - e.g. single heating circuit
* Max 13A for constant wattage cable, Max 10A for self-regulating cables
10K
N
L
L N
PE
PE
PE
NTC
Floor
Sensor
Connection via contactor - e.g. 3 heating circuits
Do not use contactor without suppression device.
10K
L N
L1
PE
A1
A2K1
Power supply
230 VAC
K1: contactor with
suppression device
NTC
Floor
Sensor
Power supply
heating cables
Connection via contactor - e.g. 3 heating circuits
Do not use contactor without suppression device.
10K
L N
L1
12345
6
L2 L3PEN
N N N
L L L
PE
A1
A2K1
Power supply
230 VAC
K1: contactor with
integrated
suppression device
8
Step 6: Click the Green Leaf into the metallic support frame.
Step 7: Switch on the power again
Product specific information
The thermostat is compatible with CeraPro, T2QuickNet, T2Blue, T2Red heating solutions.
T2QuickNet
T2QuickNet heating mats are approved with the Green Leaf thermostat working in floor sensor mode. Be aware that the floor sensor must be installed and activated for any installation with T2QuickNet.
T2Red
Self-regulating heating cables have an inrush current when the floor is cold. In order to guarantee the life time of the thermostat, the maximum load of the self-regulating application in nominal conditions is limited to 10A.
A 13A self-regulating load will reduce the life time of the relay contacts.
9
3.USING THE THERMOSTAT
The Display
Display in manual on/off programme
The following icons are visible in the Manual ON/OFF:
Active sensor display
• Floor sensing mode (
)
• Room Sensing mode (
)
• Room Sensing mode with Floor temperature limiter (
)
Heating display
The heating display is flashing when the heating is on.
10
Temperature
The temperature on the display depends on the selected sensing mode.
• Floor sensing mode => Floor temperature on the display
• Room sensing mode => Room temperature on the display
• Room sensing with floor temperature limiter mode => Room temperature on the display
Remark: When pushing on the “
” or “ ” button, the set point temperature appears on the display blinking for 5 seconds
Installer Menu
• Press on the M button for 5 seconds to enter the Installer Menu
Display in timer programme
The following icons are visible in the Timer Programme:
11
Time and day
The actual day is displayed on the screen with the 3 letters (MON-TUE-WED-THU-FRI-SAT-SUN).
The time can be set in 24H or 12AM/PM mode (see INSTALLER MENU).
4 Event display
The 4 events are displayed with the symbols:
Event 1
Event 2
Event 3
Event 4
The manual on/off programme
When switching on the thermostat for the first time (pressing on the Green Leaf button for 2 seconds), it will start in MANUAL ON/OFF programme using the floor sensing mode as a standard (see INSTALLER MENU to change the sensing mode).
You will see the following screen:
12
Press the “ ” or the “ ” to show the set point temperature. It will blink for 5 seconds.
1. Press the “
” within the 5 seconds => set point =
set point - 0.5°C
2. Press the “
” within the 5 seconds => set point =
set point + 0.5°C To switch from Manual ON/OFF to Timer Programme,
press on the “
” button once.
To switch off the thermostat, press on the “
” button for 2 seconds.
The timer programme
The Green Leaf can be programmed with 4 events per day. Different temperatures can be maintained for each event of the day. The days can be programmed independently or per cluster of days.
The default Timer Programme is shown on the graph below. You can easily adapt the programme to your needs (see PROGRAMMING THE TIMER PROGRAMME)
25
20
15
10
5
0
0:00
1:00
2:00
3:00
4:00
5:00
6:00
7:00
8:00
9:00
10:00
11:00
12:00
13:00
14:00
15:00
16:00
17:00
18:00
19:00
20:00
21:00
22:00
23:00
MON-TUE-WED-THU-FRI SAT-SUN
16
23
23
16
16
13
25
20
15
10
5
0
0:00
1:00
2:00
3:00
4:00
5:00
6:00
7:00
8:00
9:00
10:00
11:00
12:00
13:00
14:00
15:00
16:00
17:00
18:00
19:00
20:00
21:00
22:00
23:00
0:00
1:00
2:00
3:00
4:00
5:00
6:00
7:00
8:00
9:00
10:00
11:00
12:00
13:00
14:00
15:00
16:00
17:00
18:00
19:00
20:00
21:00
22:00
23:00
25
20
15
10
5
0
MON-TUE-WED-THU-FRI SAT-SUN
16
16
23
23 23
16
16
• Press on the “ ” button to set the clock and day of the week
• Press on the “
” button for 3 seconds to program
the timer programme (see page 14 for more details).
• Press on the “
” button for 5 seconds to enter
the Installer Menu
• Press on the “
” button to switch from Timer to
Manual ON/OFF mode
• Press on the “
” button for 2 seconds to put the
Thermostat into OFF (standby) mode
• Press the “
” or the “ ” to show the set
point temperature. It will blink for 5 seconds
3. Press the “
” within the 5 seconds =>
set point = set point - 0.5°C
4. Press the “
” within the 5 seconds =>
set point = set point + 0.5°C
Remark: The adapted temperature is valid until the next timer Event.
14
4. SETTING THE CLOCK
• Press on the “ ” button to set the clock and day of the week
• Press the “
” or the “ ” to change
the hours
• Press on the “
” button to validate
• Press the “
” or the “ ” to change
the minutes
• Press on the “
” button to validate
• Press the “
” or the “ ” to change
the day of the week
• Press on the “
” button to validate
Remark: In case of battery drainage after long period of power failure, you might have to re-programme the clock
15
5. PROGRAMMING THE TIMER PROGRAMME
• Press on the “ ” button for 3 seconds to program the Timer Programme
• Press the “
” or the “ ” to choose the day
(or the sequence of days) you want to program
• Press on the “
” button to validate
Day Sequences are:
MON
TUE WED THU FRI SAT SUN
MON TUE WED THU FRI
SAT SUN
MON TUE WED THU FRI SAT SUN
16
For Event 1
• Press the “ ” or the “ ” to change hours of Event 1
• Press on the “
” button to validate
• Press the “
” or the “ ” to change the
minutes of Event 1
• Press on the “
” button to validate
• Press the “
” or the “ ” to change the
set point temperature for Event 1
• Press on the “clock” button to validate
For Event 2, 3 and 4
• Repeat the actions for event 1 for the Events 2, 3 and 4
Press on the “
” button, at any time during the programming, to save your changes and return to the Timer Programme.
If needed, you can repeat the complete procedure to program other days or sequences of days.
17
6. INSTALLER MENU
Press on the “ ” button for 5 seconds to enter the installer Menu
# Description Range Default
setting
1 Sensing mode
selection
Floor sensing mode Room sensing mode Room sensing mode with
floor temperature limiter
Floor Sensing mode
2 12 vs 24 hours
display
12 / 24 24
3 Motion sensor.
When getting close to the thermostat (5cm range) the display lights up automatically
ON / OF ON
4 Floor sensor
calibration (Floor sensor on display = Real Floor sensor °C – OFFSET)
0 .. 10°C 4°C
18
# Description Range Default
setting
5 Room sensor
calibration
Measured sensor temperature +/- 5°C
Measured sensor temperature
6 Minimum
temperature set point for the
Floor Sensor
Floor sensing mode: 5 .. 15°C
Room sensing mode: OF Room sensing mode
with floor temperature limiter: OF
5°C
OF OF
7 Maximum
temperature set point for the
Floor Sensor
Floor sensing mode: Minimum temperature set point floor sensor (installer menu 6) +5°C .. 35°C
Room sensing mode: OF Room sensing mode
with floor temperature limiter: 10 .. 35°C
35°C
OF 27°C
8 Minimum
temperature set point for the
Room Sensor
Floor sensing mode: OF Room sensing mode:
5 .. 15°C Room sensing mode
with floor temperature limiter: 5 .. 15°C
OF 5°C
5°C
19
# Description Range Default
setting
9 Maximum
temperature set point for the
Room Sensor
Floor sensing mode: OF Room sensing mode:
Minimum temperature set point room sensor (installer menu 8) +5°C .. 40°C
Room sensing mode with floor temperature limiter: Minimum temperature set point room sensor (installer menu 8) +5°C .. 40°C
OF
40°C
40°C
10 Adjustable
hysteresis
0.5 .. 2.0°C 1.0°C
20
Floor sensor calibration
The temperature of the floor surface can differ from the temperature measured by the floor sensor due to the floor construction, the floor type and the position of the floor sensor. In order to calibrate your thermostat to this difference you can use the floor sensor calibration OFFSET in installer Menu 4.
After the temperature on the floor is stabilized, place a thermometer on the floor surface in order to sense the real temperature on the surface (Tsurface). Read the floor sensor temperature (Tsensor) on the thermostat and adjust the OFFSET accordingly to the formula:
Tsensor
Tsurface
OFFSET = Tsensor - Tsurface
Room sensor calibration
If the value measured by the room sensor in the thermostat differs from the real room temperature, it is possible to calibrate the room sensor using the installer Menu 5.
After the temperature in the room is stabilized, place a thermometer close to the wall in order to sense the real room temperature. If this value differs from the one shown by the thermostat, adjust Menu 5 using the “
” or the “ ” until the thermostat shows the same
value as the reference thermometer.
21
7. TROUBLESHOOTING
In the event of damage or malfunction of one of the temperature sensors, the heating output cuts off (fail safe) and an error code is displayed.
Error Code Description
ER1 Short circuit on floor sensor ER2 Open circuit on floor sensor /
Missing floor sensor ER3 Short circuit on room sensor ER4 Open circuit on room sensor ER5 Check sensing mode
The floor sensor can be replaced by a new one. In the event of malfunction of the room sensor, the entire thermostat must be replaced.
The floor sensor has got the following temperature/ resistance values:
Temperature Resistance
15°C 15.8 kΩ 20°C 12.5 kΩ 25°C 10.0 kΩ 30°C 8.0 kΩ 35°C 6.5 kΩ
Error 5 occurs if the thermostat is set in Room Sensing Mode and the floor sensor is installed.
To resolve the error change the sensing mode in Floor sensing or Room sensing with floor temperature limiter. Otherwise, remove the floor sensor to work in room sensing mode.
22
8. TECHNICAL SPECIFICATION
Supply voltage 230VAC, +10%, –15%, 50Hz Power consumption (Stand-by) 3 VA Relay output 230V, maximum 13A resistive
load (max. 3000W)
Ambient temperature – operation 0 .. 40°C, 5-95% RH (non
condensing) Ambient temperature – transport –10 .. +60°C Temperature range, floor sensor +5 .. +35°C Temperature range, room sensor +5 .. +40°C Switching hysteresis 1°C (Factory settings adjustable
between 0.5-2.0°C) Control modes Floor sensing
Room sensing
Room sensing with floor
temperature limiter Temperature control Manual ON/OFF
Timer programme Protection class IP 20 Terminals Max. 2,5 mm² Floor sensor with 3 m cable NTC, 10KΩ / 25°C Maximum length of floor sensor Cable
100 m, 2 x 1,5 mm² (230VAC
cable type)
Approvals CE
23
THERMAL MANAGEMENT SOLUTIONS EN-RaychemGreenLeaf-IM-EU0209 R1
PCN 1244-013904
WWW. PENTAIRTHERMAL.COM
All Pentair trademarks and logos are owned by Pentair or its global affiliates. Pentair reserves the right to change specifications without prior notice.
© 2013 Pentair.
EuropEan hEadquartErs
Tel: +32 16 21 35 02 Fax: +32 16 21 36 04 salesbelux@pentair.com
unItEd KInGdoM
Tel: +0800 96 90 13 Fax: +0800 96 86 24 salesthermaluk@pentair.com
Loading...