DOUBLE-POLE LINE-SENSING THERMOSTAT FOR HAZARDOUS LOCATIONS
INSTALLATION INSTRUCTIONS
DESCRIPTION
The E507S-2LS-2 thermostat is designed for controlling heattracing systems in hazardous locations. The thermostat functions
as a DPST switch. The DPST switch will enable and disable current
flow in both buses of the heat-tracing cable.
The E507S-2LS-2 can be used to control heat-tracing circuits in a
pipe-sensing mode (see Figure 1 on back page).
Note: Do not use this thermostat to control two separate heattracing circuits.
ADDITIONAL MATERIAL REQUIRED
ǩAT-180 aluminum tape
APPROVALS
Hazardous locations
Class I, Div. 1 and 2, Groups B, C, D
Class II, Div. 1 and 2, Groups E, F, G
Class III
SPECIFICATIONS
Enclosure NEMA 4, 7, 9, lacquer-coated cast-aluminum
housing, stainless-steel hardware
Entries One 3/4 in. NPT conduit hub
Set point range 25°F to 325°F (–4°C to 163°C)
Sensor exposure
limits
Housing exposure
limits
Switch DPST
Electrical rating 22 A at 208/240 Vac
Relay coil 208–240 Vac, 4 VA
Accuracy ±6°F (±3.3°C)
Deadband 2°F to 12°F (1.1°C to 6.7°C) above actuation
Set point
repeatability
Sensor type Fluid-filled (silicone) bulb and 9 ft (2.7 m)
Sensor material 300 series stainless steel
Connection
terminals
–40°F to 420°F (–40°C to 215°C)
–40°F to 140°F (–40°C to 60°C)
temperature
±3°F (±1.7°C)
capillary
Screw terminals, 10–14 AWG (2–5 mm
8.0 in
approx.
Terminal
3⁄4 in NPT conduit entry
4.5 in (114 mm)
4.0 in (102 mm)
Removable
knob cover
6.0 in (153 mm)
block
4.0 in
(102 mm)
Adjusting
knob
Ø.28 in (7 mm)
mounting hole
(4X)
4.5 in
(114 mm)
6.6 in
(168 mm)
1.2 in
(30 mm)
2.0 in
(50 mm)
2
)
WARNING:
This component is an electrical device. It must be installed
correctly to ensure proper operation and to prevent shock or
fire. Read these important warnings and carefully follow all the
installation instructions.
THERMAL MANAGEMENT SOLUTIONS EN-DigiTraceE507S2LS2-IM-H5691401/13
Component approvals and performance are based on the use of
specified parts only. Do not use substitute parts or vinyl electrical
tape to make connections.
1 / 2

INSTALLING THE THERMOSTAT
1. Verify that the thermostat is
suitable for the area where it is to
be installed.
2. Check the line voltage and the
heat-tracing load to ensure that
the thermostat ratings are not exceeded.
3. Mount the unit using unistrut or the Raychem universal
mounting bracket (UMB-263757) in a position that prevents
condensation from draining into the enclosure from the
connecting conduit (see diagram above).
POSITIONING THE SENSOR BULB
4. Position the bulb in the
lower quadrant of the pipe
as shown in the diagrams
to the left. Place the bulb
at least three feet from
pipe supports, valves, or
90
Single Traced
Heating cable
Control thermostat bulb
AT-180 tape
other heat sinks; protect
the capillary from kinks or
Double Traced
bends less than 1⁄2 inch in
radius.
Heating cable
Control thermostat bulb
AT-180 tape
WIRING
Conduit
drain
5. Tape the bulb firmly to the pipe with AT-180 aluminum tape,
making sure there is no air space between the bulb and pipe.
Do not overlap the bulb and heating cable with the same piece
of AT-180 tape.
6. For metal-tank-wall sensing, use the BCK-35 bulb clamp
(purchased separately from Raychem) and install the clamp
per the instructions provided. Make sure there is no air space
between the tank wall and the bulb.
For installation on plastic tanks, contact Pentair Thermal
Management at (800) 545-6258.
SETTING THE THERMOSTAT
7. Set the thermostat dial to the desired temperature, then finish
wiring.
8. Complete insulating. Do not turn the system on until the bulb is
covered with thermal insulation.
9. Fill the piping or tank. Once the thermostat has begun to cycle,
check the fluid temperature with an immersed thermostat
(best for plastic systems) or an accurate temperature indicator.
Adjust the dial setting, if necessary.
NORTH AMERICA
Tel: +1.800.545.6258
Fax: +1.800.527.5703
Tel: +1.650.216.1526
Fax: +1.650.474.7711
thermal.info@pentair.com
Power supply
GFEPD
ØØ
G
G
ØØ
Braid
Heating
cable
Figure 1. Heat-tracing control
EUROPE, MIDDLE EAST, AFRICA
Tel: +32.16.213.511
Fax: +32.16.213.603
thermal.info@pentair.com
208-V or 240-V supply – 240-V heater
Circuit1
Circuit2
Power
connection
Thermostat bulb
(see "Positioning"
instructions above
for mounting details)
Control
thermostat
Relay
ASIA PACIFIC
Tel: +86.21.2412.1688
Fax: +86.21.5426.2917
cn.thermal.info@pentair.com
WWW.THERMAL.PENTAIR.COM
LATIN AMERICA