Pentair Digitrace E507S-2LS-2, Raychem E507S-2LS-2 Installation Instructions Manual

E507S-2LS-2
DOUBLE-POLE LINE-SENSING THERMOSTAT FOR HAZARDOUS LOCATIONS INSTALLATION INSTRUCTIONS
DESCRIPTION
The E507S-2LS-2 thermostat is designed for controlling heat­tracing systems in hazardous locations. The thermostat functions as a DPST switch. The DPST switch will enable and disable current flow in both buses of the heat-tracing cable.
The E507S-2LS-2 can be used to control heat-tracing circuits in a pipe-sensing mode (see Figure 1 on back page).
Note: Do not use this thermostat to control two separate heat­tracing circuits.
ADDITIONAL MATERIAL REQUIRED
ǩAT-180 aluminum tape
APPROVALS
Hazardous locations
Class I, Div. 1 and 2, Groups B, C, D Class II, Div. 1 and 2, Groups E, F, G Class III
SPECIFICATIONS
Enclosure NEMA 4, 7, 9, lacquer-coated cast-aluminum
housing, stainless-steel hardware Entries One 3/4 in. NPT conduit hub Set point range 25°F to 325°F (–4°C to 163°C) Sensor exposure
limits Housing exposure
limits Switch DPST Electrical rating 22 A at 208/240 Vac Relay coil 208–240 Vac, 4 VA Accuracy ±6°F (±3.3°C) Deadband 2°F to 12°F (1.1°C to 6.7°C) above actuation
Set point repeatability
Sensor type Fluid-filled (silicone) bulb and 9 ft (2.7 m)
Sensor material 300 series stainless steel Connection
terminals
–40°F to 420°F (–40°C to 215°C)
–40°F to 140°F (–40°C to 60°C)
temperature
±3°F (±1.7°C)
capillary
Screw terminals, 10–14 AWG (2–5 mm
8.0 in
approx.
Terminal
3⁄4 in NPT conduit entry
4.5 in (114 mm)
4.0 in (102 mm)
Removable knob cover
6.0 in (153 mm)
block
4.0 in
(102 mm)
Adjusting knob
Ø.28 in (7 mm) mounting hole (4X)
4.5 in
(114 mm)
6.6 in
(168 mm)
1.2 in (30 mm)
2.0 in
(50 mm)
2
)
WARNING:
This component is an electrical device. It must be installed correctly to ensure proper operation and to prevent shock or fire. Read these important warnings and carefully follow all the installation instructions.
THERMAL MANAGEMENT SOLUTIONS EN-DigiTraceE507S2LS2-IM-H5691401/13
Component approvals and performance are based on the use of specified parts only. Do not use substitute parts or vinyl electrical tape to make connections.
1 / 2
INSTALLING THE THERMOSTAT
1. Verify that the thermostat is suitable for the area where it is to be installed.
2. Check the line voltage and the heat-tracing load to ensure that the thermostat ratings are not exceeded.
3. Mount the unit using unistrut or the Raychem universal mounting bracket (UMB-263757) in a position that prevents condensation from draining into the enclosure from the connecting conduit (see diagram above).
POSITIONING THE SENSOR BULB
4. Position the bulb in the lower quadrant of the pipe as shown in the diagrams to the left. Place the bulb at least three feet from pipe supports, valves, or
90
Single Traced
Heating cable Control thermostat bulb AT-180 tape
other heat sinks; protect the capillary from kinks or
Double Traced
bends less than 1⁄2 inch in radius.
Heating cable Control thermostat bulb AT-180 tape
WIRING
Conduit drain
5. Tape the bulb firmly to the pipe with AT-180 aluminum tape, making sure there is no air space between the bulb and pipe. Do not overlap the bulb and heating cable with the same piece of AT-180 tape.
6. For metal-tank-wall sensing, use the BCK-35 bulb clamp (purchased separately from Raychem) and install the clamp per the instructions provided. Make sure there is no air space between the tank wall and the bulb.
For installation on plastic tanks, contact Pentair Thermal
Management at (800) 545-6258.
SETTING THE THERMOSTAT
7. Set the thermostat dial to the desired temperature, then finish wiring.
8. Complete insulating. Do not turn the system on until the bulb is covered with thermal insulation.
9. Fill the piping or tank. Once the thermostat has begun to cycle, check the fluid temperature with an immersed thermostat (best for plastic systems) or an accurate temperature indicator. Adjust the dial setting, if necessary.
NORTH AMERICA
Tel: +1.800.545.6258 Fax: +1.800.527.5703 Tel: +1.650.216.1526 Fax: +1.650.474.7711 thermal.info@pentair.com
Power supply
GFEPD
ØØ
G
G
ØØ
Braid
Heating
cable
Figure 1. Heat-tracing control
EUROPE, MIDDLE EAST, AFRICA
Tel: +32.16.213.511 Fax: +32.16.213.603 thermal.info@pentair.com
208-V or 240-V supply – 240-V heater
Circuit1
Circuit2
Power connection
Thermostat bulb
(see "Positioning"
instructions above
for mounting details)
Control thermostat
Relay
ASIA PACIFIC
Tel: +86.21.2412.1688 Fax: +86.21.5426.2917 cn.thermal.info@pentair.com
WWW.THERMAL.PENTAIR.COM
LATIN AMERICA
Tel: +55.11.2588.1400 Fax: +55.11.2588.1410 thermal.info@pentair.com
Pentair and DigiTrace are owned by Pentair or its global affiliates. All other trademarks are the property of their respective owners. Pentair reserves the right to change specifications without prior notice.
© 2001-2013 Pentair. PN 235288-000