This manual provides IntelliTouch® i-Link™ software control commands for
IntelliTouch system equipment such as lights, pumps etc. For additional
information about the IntelliTouch control system, refer to the IntelliTouch User’s
Guide (P/N 520102).
IntelliTouch i-Link Adapter
Software Commands
Start-up Sequence
Each time the IntelliTouch i-Link adapter is powered up a start-up initialization
sequence is sent to the Home Automation system via the RS-232 port and the
current command characters display. These special command characters are also
user definable and may differ from the default characters show below. The
default command character set displays after a start-up sequence. To display these
characters power down/up or reset the IntelliTouch i-Link adapter. For the RST (reset)
command information, see page 4.
IntelliTouch i-Link Adapter Default Command Characters
Pentair Water Pool and Spa - IntelliTouch i-Link Protocol InterfaceAdapter v1.0
CMDCHR = #
NRMCHR = !
ERRCHR = ?
SETCHR = =
INQCHR = ?
Acquiring System Data
!READY
The IntelliTouch system implements an addressing method upon power
up. For most systems the initialization is automatic. The IntelliTouch i-Link
adapter will automatically lock on to the address within two minutes after
power is applied.
Note:
If there is an IntelliTouch MobileTouch® wireless control panel installed,
the MobileTouch Transceiver screw terminal connector needs to be removed
from the Transceiver circuit board before the IntelliTouch i-Link adapter
initialization sequence. Refer to Start-up with MobileTouch Control Panel, see
page 25 for details.
All examples given in this document assume default characters are being used.
‘#’ Prefixes all Commands
‘!’ Prefixes all successful command/query responses
‘?’ Prefixes all error messages/responses
‘=’ is used as the SET operator
‘?’ is used as the Query operator
Command Forms
[Prefix][Label][Operator][Value]<cr>
Example: #SPA=1<cr> (Turn SPA ON)
Where the Prefix is “#” (factory default – may be changed with CMDCHR)
Where the Label or Command is “SPA”
Where the Operator is “=” i.e. set this circuit to value
Where the Value is “1” i.e. ON
2
The Prefix and the Operator must be the correct symbols. The Label must
be exact spelling from the command list. Though it may be Upper or lower
case, or any combination. The Value must be one of the valid options, and
valid for that command.
‘ON’ values are “1”, “ON”, “Y” or “YES”, “T” or “TRUE”.
‘OFF’ values are “0”, “OFF”, “N” or “NO”, “F” or “FALSE”,
A single space may or may not be used between the Label and Operator,
the Operator and Value, the Value and ,<cr>. No space(s) is allowed
between the Prefix and the Label.
Where the Prefix is “#” (factory default – may be changed with CMDCHR)
Where the Label or Command is “SPA”
Where the Operator is “?” i.e. Query
The Prefix and the Operator must be the correct symbols. The Label must be exact
spelling from the command list using upper or lower case, or any combination. A
single space may or may not be used between the Label and Operator, and the
Operator and <cr>.
No space(s) is allowed between the Prefix and the Label.
Error Messages/Responses Form
[Prefix][Error Number][Message]<cr>(RSPFMT = 0)
[Prefix][Error Number]<cr>(RSPFMT = 1)
Example: ?02 BAD COMMAND FORM
Where the Prefix is “?” (factory default – may be changed with ERRCHR)
Where the Error Number “02”
Where the Message is “BAD COMMAND FORM”
If RSPFMT is terse (RSPFMT = 1) only the Prefix and Error Number are
returned
Adapter commands are used to set required or preferred actions and responses
for a given application. Such as the ‘RSPFMT’ command that is used to determine
the type of response expected by the computer or home automation system.
RST:Reset Adapter
Command:#RST<cr>
Response:Pentair Water - i-Link Protocol Interface Adapter v1.0
CMDCHR = #
NRMCHR = !
ERRCHR = ?
SETCHR = =
INQCHR = ?
Acquiring System Data
!READY
RSPFMT:Set/Query Command Response Format
Query:#RSPFMT ?<cr>
Response:!00 RSPFMT = x<cr>
Where x is 1 or 0.
4
0 indicates a verbose response (as shown).
If the RSPFMT is set to terse the response would appear as !00 x<cr>
System commands differ in various ways. Some may be used to set a state, toggle
a state, or query a state. Others may be query only, or Set and Query but not
Toggle.
Where x is 1 or 0, and 1 indicates ON, 0 indicates OFF
Where ‘xx’ is 1 through 8, and 11 through 50.
AUX1 through AUX8 control up to eight (8) auxiliary circuits in the main power center.
This is also where the Spa & Pump (pool) circuits reside.
AUX11 through AUX20 Control up to ten (10) auxiliary circuits in the second power
center.
AUX21 through AUX30 Control up to ten (10) auxiliary circuits in the third power center.
AUX31 through AUX40 Control up to ten (10) auxiliary circuits in the third power center
AUX41 through AUX50 Control up to ten (10) feature or macro that exist in most
systems.
Note:
The adapter will not verify the existence of a given circuit. For example, if a
command is given for AUX22, and no such circuit exists in the system, no indication is
given. The state and status will appear normal. It is the installer/operators responsibility
to insure circuits exist.
POOLHT2:Enable/Disable High Pool Heater
SPAHT:Enable/Disable Spa Heater
SOLHT:Enable/Disable Pool Solar
SPASOLHT:Enable/Disable Spa Solar
SOLPREF:Enable/Disable Pool Solar Preferred
SPASOLPREF: Enable/Disable Spa Solar Preferred
The following describes unsolicited changes in the heating source information. For
example, the user might change the heating source selection on the Pool from Heater
to Solar using the IntelliTouch Indoor Control Panel. Messages will be sent to the Ilink
using the formed response that would be received if the change had been initiated
from the Ilink. There are slight differences. Since only one heat source selection can be
active at any given time, if a change is made which sets the heating selection to OFF,
the message will be formed as if the Ilink had instructed the Heater to go OFF even if
the change was from for example Solar to No Heat.
The unsolicited messages (included in Ilink firmware version 1.021) are as follow:
Pool Heating:
!00 POOLHT = 0 Pool Heating Selection has changed to OFF (No Heat)
!00 POOLHT = 1 Pool Heating Selection has changed to ON (Heater)
!00 SOLHT = 1Pool Heating Selection has changed to Solar Only
!00 SOLPREF = 1 Pool Heating Selection has changed to Solar Preferred
Spa Heating
!00 SPAHT = 0 Spa Heating Selection has changed to OFF (No Heat)
!00 SPAHT = 1 Spa Heating Selection has changed to ON (Heater)
!00 SPASOLHT = 1Spa Heating Selection has changed to Solar Only
!00 SPASOLPREF = 1SpaHeating Selection has changed to Solar
Preferred
The Single Body Single Equipment Units (I9+3S & I5+3S aka I5S) use a
slightly different labeling scheme to maintain minimum compatibility with
an older interface.
Low Temperature Selection Heating:
!00 POOLHT = 0 Heating Selection has changed to OFF (No Heat)
!00 POOLHT = 1 Heating Selection has changed to ON (Heater)
!00 SOLHT = 1Heating Selection has changed to Solar Only
!00 SOLPREF = 1Heating Selection has changed to Solar Preferred
High Temperature Selection Heating:
!00 POOLHT2 = 0 Heating Selection has changed to OFF (No Heat)
!00 POOLHT2 = 1 Heating Selection has changed to ON (Heater)
!00 SPASOLHT = 1Heating Selection has changed to Solar Only
!00 SPASOLPREF = 1Heating Selection has changed to Solar Preferred
Special COMMAND Only commands for: IntelliBrite LED Lights and
MagicStream Laminars
The following lighting commands support IntelliBrite LED lights and MagicStream
laminars. For more information, also see COLORSYNC, COLORSET, and
COLORSWIM commands (see page 15). The following commands for the
IntelliBrite LED light and the MagicStream Laminar are as follows:
Note: The following commands require i-Link version 1.021 or higher. The
MagicStream laminar commands for Random, Sync, and Party require IntelliTouch
outdoor control panel version 1.132 or higher.
COLORSWIM:Colored Lights Control
COLORSET:
COLORSYNC:
The above color commands only operate lights configured in the special
Note:
IntelliTouch "Lights" screen.
Sam, Sal, PG2000 Fiber Optic lights and IntelliBrite LED lights
The following commands support the Sam, Sal, PG2000 Fiber Optic Unit and
IntelliBrite LED light.
These commands do not support the MagicStream laminar.
COLORSWIM:Start a Color Swim Sequence
COLORSET:Set Lights to pre-selected Colors
COLORSYNC: Synchronize All Color Lights
The following commands only support the IntelliBrite LED lights.
IB_PARTYSet ALL IntelliBrite Units to PARTY mode
IB_ROMANCESet ALL IntelliBrite Units to ROMANCE mode
IB_CARIBBEANSet ALL IntelliBrite Units to CARIBBEAN mode
IB_AMERICANSet ALL IntelliBrite Units to AMERICAN mode
IB_SUNSETSet ALL IntelliBrite Units to SUNSET mode
IB_ROYALTYSet ALL IntelliBrite Units to ROYALTY mode
IB_BLUESet ALL IntelliBrite Units to BLUE
IB_GREENSet ALL IntelliBrite Units to GREEN
IB_REDSet ALL IntelliBrite Units to RED
IB_WHITESet ALL IntelliBrite Units to WHITE
IB_MAGENTASet ALL IntelliBrite Units to MAGENTA
IB_HOLDCommand ALL IntelliBrite Units to Hold/Stop/Freeze
IB_RECALLCommand ALL IntelliBrite Units to Recall last setting
The following commands only support MagicStream laminars:
MS_THUMPERToggle ALL MagicStream Thumpers ON or OFF
MS_HOLDCommand ALL MagicStream Units to Hold/Stop/Freeze
MS_RESETReset ALL MagicStream units
MS_MODEToggle Mode on ALL MagicStream Units Random,
Party, Sync
MS_SYNCSet ALL MagicStream units to SYNC Mode
MS_RANDOMSet ALL MagicStream units to RANDOM Mode
MS_PARTYSet ALL MagicStream units to PARTY Mode
Testing IntelliTouch iLink via Hyper Terminal in Windows XP
The basic function of an iLink can be tested/checked out using a computer and a
program such as “Hyper Terminal,” which is included in all Windows XP systems.
To test the iLink:
1. Plug the iLink into the computer RS-232 Serial port. Normally this will be “COM
1.” Connect the other side of the iLink cable to the IntelliTouch system.
2. To access the Hyper Terminal screen, from the Windows XP desktop, click the
3. The Hyper Terminal new connection screen will pop up. Enter any name in the
connection description box. Click OK. The “Connect To “ box will pop up.
4. In the lower selection box labeled “Connect Using” select COM1. Click OK and
the port settings box will pop up.
Parity None, Stop Bits 1, Flow Control None.
5. Click OK.
6. In the Hyper Terminal window, click “File” and select and click “Properties.”
7. Click the “Settings” tab.
8. Click “ASCII Setup.”
9. Click to place a check mark in “Send Line Ends with Line Feeds Echo Typed
Characters Locally Append Line Feeds to Incoming Line Ends.”
10. Click OK. Click OK again.
11. Now in the Hyper Terminal window type #RST<enter>
It will take approx 10 seconds for the iLink to complete a reset process. The screen
will then display some start up text similar to:
Bits Per Second 9600, Data Bit 8,
Pentair Water - i-Link Protocol Interface Adapter v1.023
CMDCHR = #
NRMCHR = !
ERRCHR = ?
SETCHR = =
INQCHR = ?
Acquiring System Data
After 15 to 20 seconds while the device collects system information.
The system will display “!READY” some other information may display if the
COSMSGS is set to true.
You may now simply type in commands, and see the responses.
#AUX1 = 1<enter> will switch on Auxiliary #1 and create a response similar to
!00 AUX1 = 1
#AUX1 = 0<enter> will switch off Auxiliary #1 and create a response similar to
!00 AUX1 = 0
All of the commands and queries listed in the iLink manual may be operated
on the computer via Hyper Terminal. This allows testing of the various commands
and assists in troubleshooting.
If the “?01 INVALID COMMAND” message is received, the command has been
entered incorrectly.
This section provides installation information for the IntelliTouch
Protocol Interface Adapter. For additional information about the IntelliTouch
control system, refer to the IntelliTouch User’s Guide (P/N 520102).
The following items are included in the IntelliTouch i-Link Protocol Interface
Adapter kit.
•Small flat-blade screwdriver (for opening the IntelliTouch i-Link adapter
case)
•Wire Stripping Tool (for stripping cable wires)
®
i-Link
18
™
Summary Information
For connection options, refer to the IntelliTouch i-Link Adapter Connection
Diagram, page 19. The recommended connection steps for the
IntelliTouch i-Link adapter are:
Switch power off to the IntelliTouch Load/Power Center: Before
1
connecting cables to the IntelliTouch i-Link adapter, switch off the power
source to the Load/Power Center.
Connecting to the Home Automation Interface (page 20): Connect the
2
Home Automation interface RS-232 cable to the IntelliTouch i-Link Protocol
Interface adapter.
Connecting to the Indoor Control Panel (page 23): Connect a cable from
IntelliTouch i-Link Protocol Interface adapter to the Indoor Control Panel.
3
Connecting to the Personality Board (page 24): Connect a cable from
IntelliTouch i-Link Protocol Interface adapter to the Personality board
4
(Power/Load Center).
Start-up Sequence (page 1): Power-up and initialize the IntelliTouch i-Link
The IntelliTouch i-Link Protocol Interface adapter allows homeowner’s using
Home Automation systems such as Crestron
others to control IntelliTouch pool and spa functions via their Home Automation
control interface, including switching pumps on, activating valves, switching
heaters or auxiliary relays on, and adjusting thermostat settings.
Connection
The IntelliTouch i-Link adapter (DB-9S) connects to a third party home
automation computer via
RS-232 port and to a RS-485 communication port on the IntelliTouch Personality
Board
(Load Center or Power Center) via a Serial cable (four-wire). This connection
provides power to the IntelliTouch i-Link adapter. For wiring and connection
details, see the Connection Diagram below.
The IntelliTouch i-Link adapter operates at 9.6 kbps (9600 kilobits per second)
using 8 data bits, 1 start bit, 1 stop bit, and no parity.
IntelliTouch i-Link Adapter Location
The IntelliTouch i-Link adapter is for indoor use only and should be located
within 25 feet of the home automation system.
®
, AMX®, Vantage®, Lutron® and
Serial RS-232 (DB-9S)
Connect to Home Automation
Interface or PC
The IntelliTouch i-Link Protocol Interface adapter is identified as a RS-232 Data
Communications Equipment (DCE) device. The IntelliTouch i-Link adapter DB-9S
connector can use straight-through wiring to connect to a DTE (Data Terminal
Equipment) device such as a Home Automation interface or PC/Laptop DB-9S
Serial port connector. Other DTE devices may require non straight-through wiring.
For connection details, see page 19.
IntelliTouch i-Link RS-232 (DB-9S) Signal Description
The IntelliTouch i-Link adapter RS-232 (DB-9S) connector pin-outs and signal
names:
Note: (*) Pins 1, 4, and 6 connected. Pins 7 and 8 connected.
The IntelliTouch i-Link adapter can be connected to either the IntelliTouch
Indoor Control Panel or directly to the IntelliTouch Load or Power Center at the
equipment pad. The four-wire cable can also be connected at any point along
the communication cable that connects the Indoor Control Panel to the
Personality board. Before connecting the cable to the i-Link adapter, first
determine the length of cable required for the connection. For connection
details, see Connection Diagram, page 19.
To connect the four conductor cable to the IntelliTouch i-Link adapter (see
Figure 1):
1. Run a four conductor cable (22 AWG UL approved) from either the
Indoor Control Panel or the Power/Load Center location to the
IntelliTouch i-Link adapter.
2. Using a small flat-blade screw driver, insert the blade into one of the
side notches and pry apart the case (not completely). Remove the
screwdriver blade from the notch and insert the blade into the other
notch and pry apart to separate the two halves of the adapter case.
3. Remove the screw terminal connector from the circuit board. Please
observe Electrostatic Sensitive Device (ESD) handling precautions
when removing the connector.
4. Strip back the four cable conductors ¼ inch. Insert the four wires into the
screw terminals. Secure the wires with the four screws. Make sure to
match the color coding of the wires with the pin colors indicated on the
circuit board: RED = +15, YEL = +DT, GRN = -DT, and
BLK = Ground. Refer to the wiring table below.
5. Insert the screw terminal connector onto the pins on the circuit board.
Note that the connector is keyed for the correct orientation.
6. Snap the two halves of the adapter case together. Make sure the wire
exits out of the wire exit hole.
7. Proceed with either of the following cable connections:
To connect the i-Link communication cable to the Indoor Control Panel:
1. Switch the main power OFF to the Load/Power Center.
2. Route the four conductor cable from the IntelliTouch i-Link adapter to
the location of the Indoor Control Panel.
3. Remove the control panel front cover: From the front of the control
panel, insert the tip of a small flat-blade screwdriver into the notch on
the top edge of the control panel cover and gently pry the cover off from
the control panel base.
4. Remove the two control panel base retaining screws.
5. Carefully lift the control panel base up from the wall-mounted sheave
and remove the base from the wall.
6. Turn the base over and disconnect the four screw terminal plug from the
circuit board.
1 GND BLACK
2 -D GREEN
3 +D YELLOW
4 15V RED
Indoor Control Panel (rear view)
7. Strip back the four cable conductors ¼ in. Insert the four wires into the
each of the screw terminals with the existing wires. Secure the wires
with the four screws. Make sure to match the color-coding of the wires:
Red = +15 VDC, Yellow = +DT, Green = -DT, and
GND = Black. Wiring details are shown above.
8. Insert the screw terminal connector onto the pins on the circuit board.
Note that the connector is keyed for the correct orientation.
9. Place the control panel base onto the wall-mounted sheave and secure
in place with the two retaining screws.
10. Carefully snap-on the control panel front cover to the base plate.
11. Switch on the power source to the Power/Load Center.
Read the following WARNING information before removing the Power/Load
Center enclosure high voltage cover-panel.
WARNING - It is required that the main power into the home be switched
OFF at the main circuit breaker box whenever the high voltage cover-panel is
removed. The main power must also be switched OFF to access the Power/
Load Center enclosure low voltage raceway.
The following steps describe how to connect the four conductor cable to the
Personality board that connects directly to the IntelliTouch i-Link adapter.
To connect the cable to the Personality board:
1. Switch the main power OFF to the Load/Power Center.
2. Unlatch the front door spring latche(s), and open the front door of the
Power/Load Center.
3. Remove the screws securing the high voltage cover-panel. Remove the
cover-panel from the enclosure.
4. Loosen the two upper access screws from the Outdoor Control Panel.
5. Lower the Outdoor Control Panel down to access the Personality
board.
6. Route the four conductor cable (22 AWG) cable up through the low
voltage raceway to the Personality board.
Use the following procedure if the IntelliTouch system includes a MobileTouch
wireless control panel. Before the i-Link adapter initializes the start-up
procedure, the MobileTouch® transceiver module cable needs be
disconnected. After the initialization process has been completed the
transceiver can be reconnected.
To disconnect the MobileTouch transceiver screw terminal connector:
1. Switch the main power off to the IntelliTouch Load/Power Center.
2. Remove the two retaining screws from the transceiver case. Slide the
case up to remove.
3. Remove the transceiver screw terminal connector from the transceiver
circuit board.
4. Switch the main power on to the Load/Power Center.
5. The i-Link adapter will power up and initialize the start-up procedure
and assign an “address” to the installed equipment. This process may
take up to two minutes. To initialize the adapter, you can also use the
RST (reset) command (refer to page 4 for more information).
6. Switch the main power off to the Load/Power Center.
7. Reconnect the transceiver screw terminal connector onto the
transceiver board.
8. Slide the case on to the transceiver back plate. Secure the transceiver
case with the two retaining screws.
9. Switch the main power on to the Load/Power Center. The i-Link adapter
start-up procedure is complete.
7. Strip back the cable conductors ¼ in. Insert the four wires into the screw
terminals on either COM PORTS (J7 and J8) plugs located on the left
side of the Personality board. Secure the wires with the four screws.
Make sure to match the color-coding of the wires: Red = +15 V,
Yellow = +DT, Green = -DT, and GND = Black. Wiring details are shown
below.
Note:
Multiple wires may be inserted into a single screw terminal.
CAUTION Do NOT short GND or +15VDC connections (Red or Black) to
data lines (Green or Yellow). The Personality board may be permanently
damaged. Do NOT reverse GND or +15V or system will not operate.
8. Install the cover-panel and secure with the two retaining screws.
9. Close the hinged Outdoor Control Panel and secure with the two
access screws.
10. Close the front door of the Power/Load Center. Fasten the spring
latche(s).
11. Switch on the power source to the Power/Load Center.
Use the following procedure if the IntelliTouch system includes a MobileTouch
wireless control panel. Before the i-Link adapter initializes the start-up
procedure, the MobileTouch® transceiver module cable needs be
disconnected. After the initialization process has been completed the
transceiver can be reconnected.
To disconnect the MobileTouch transceiver screw terminal connector:
1. Switch the main power off to the IntelliTouch Load/Power Center.
2. Remove the two retaining screws from the transceiver case. Slide the
case up to remove.
3. Remove the transceiver screw terminal connector from the transceiver
circuit board.
4. Switch the main power on to the Load/Power Center.
5. The i-Link adapter will power up and initialize the start-up procedure
and assign an “address” to the installed equipment. This process may
take up to two minutes. To initialize the adapter, you can also use the
RST (reset) command (refer to page 4 for more information).
6. Switch the main power off to the Load/Power Center.
7. Reconnect the transceiver screw terminal connector onto the
transceiver board.
8. Slide the case on to the transceiver back plate. Secure the transceiver
case with the two retaining screws.
9. Switch the main power on to the Load/Power Center. The i-Link adapter
start-up procedure is complete.
Feature Circuits: Programmable circuits that may control relays and/or valve
actuators. For details, see the IntelliTouch Systems User’s Guide (P/N 520102)
High Voltage Compartment: Large lower right compartment of Load Center for
all high voltage wiring including circuit breakers, relays, and GFCI.
Indoor Control Panel: A 14 button remote controller with LCD (liquid crystal
display) wired to the Personality board in the Power/Load Center. The indoor
control panel can be wall mounted inside a house to control IntelliTouch control
system.
IntelliBrite® LED Light: Underwater pool or spa LED (light-emitting diode) color
light.
Load Center: Metal enclosure with power relays, transformer, and circuit
breakers. The Load Center is Installed prior to Personality Kit installation. Used
for distributing power for controlling IntelliTouch Systems. Also known as the
“sub-panel.”
Low Voltage Compartment: Top compartment of Load Center for all low voltage
wiring.
Low Voltage Raceway: Vertical space in the left side of Power/Load Center for
low voltage cabling.
MagicStream® Laminar: Water effect designed to provide a clear, turbulencefree stream of water that can be lit with a fiber optic cable, or an LED light
engine.
28
Outdoor Control Panel: Control panel with flexible hinge installed in upper
portion of Power/Load Center to control IntelliTouch systems.
Personality Board: The circuit board mounted on top of the Outdoor Control
Panel motherboard. The Personality board defines the system capabilities.
Power Center: Same as Load Center with the exception of the circuit breaker
base.
Screw Terminal: Removable connector that may attach to circuit board with
multiple sockets (anywhere from 2 to 12) to receive wires from controllers and
sensors; wires held by screw terminals;