SERVICE ASSEMBLIES ........................................................23
42132 Rev E JL10
JOB SPECIFICATION SHEET
NOTE: Some options may not be available depending on valve model or
other options chosen.
Circle and/or ll in the appropriate data for future reference.
1. System Type:
A. Meter Immediate
B. Time Clock Delayed
C. Volume Override Delayed
D. Volume Override Immediate
E. Meter Delayed Weekly Reserve
F. Meter Delayed Variable Reserve
G. Meter Delayed Fixed Reserve
2. Valve Type:
A. 56XT/6700
B. Proprietary C
3. Regenerant Flow:
A. Downow
B. Upow
C. Downow Double Backwash
D. Upow Backwash
E. Filter
F. Upow Variable Flow
4. Display Format:
A. U.S.
B. Metric (French Degrees, German Degrees, or PPM)
5. Unit Capacity: ��������� Grains/French Degrees/German Degrees/PPM
6. Water Hardness: �������Grains/French Degrees/German Degrees/PPM
7. Capacity Safety Factor: Zero or______________________________%
8. Volume Override: ����������������������������(Gallons or M
9. Regeneration Day Override:
A. Off
B. Every ______________________________________________ Days
10. Regeneration Time:
A. Delayed __________________________________________ AM/PM
B. Metered Immediate
c. Auxiliary Relay Start 2 _ _ : _ _ : _ _
d. Auxiliary Relay End 2 _ _ : _ _ : _ _
B. Disabled
16. Chemical Pump:
A. Enabled
B. Disabled
17. CPO Aux Relay Volume: ������������������������� (Gallons or M
18. CPO Aux Relay: _ _ : _ _ : _ _
19. Flow Meter Size:
A. 0.75" Paddle
B. 0.75" Turbine
20. Generic Flow Meter for Maximum Flow Rate:
Add_____Gallons every _ _
3
)
3
)
Page 2
INSTALLATION
Water Pressure
A minimum of 20 pounds (1.4 bar) of water pressure is required
for regeneration valve to operate effectively.
Electrical Facilities
An uninterrupted alternating current (A/C) supply is required.
Note: Other voltages are available. Please make sure your
voltage supply is compatible with your unit before installation.
Existing Plumbing
Condition of existing plumbing should be free from lime and
iron buildup. Piping that is built up heavily with lime and/or iron
should be replaced. If piping is clogged with iron, a separate
iron lter unit should be installed ahead of the water softener.
Location Of Softener And Drain
The softener should be located close to a drain to prevent air
breaks and back ow.
By-Pass Valves
Always provide for the installation of a by-pass valve if unit is
not equipped with one.
CAUTION
Installation Instructions
1. Place the softener tank where you want to install the unit
2. During cold weather, the installer should warm the valve to
3. All plumbing should be done in accordance with local
4. Refer to the dimensional drawing for cutting height of the
5. Lubricate the distributor O-ring seal and tank O-ring seal.
6. Solder joints near the drain must be done prior to
7. Teon tape is the only sealant to be used on the drain
8. Make sure that the oor is clean beneath the salt storage
9. Place approximately 1" (25 mm) of water above the grid
10. On units with a by-pass, place in by-pass position. Turn on
2 • JL10 Fleck 6700XTR Downow
Water pressure is not to exceed 125 psi (8.6 bar),
water temperature is not to exceed 110°F (43°C),
and the unit cannot be subjected to freezing
conditions.
making sure the unit is level and on a rm base.
room temperature before operating.
plumbing codes. The pipe size for residential drain line
should be a minimum of 1/2" (13 mm). Backwash ow rates
in excess of 7 gpm (26.5 Lpm) or length in excess of 20’
(6 m) require 3/4" (19 mm) drain line. Commercial drain
lines should be the same size as the drain line ow control.
distributor tube. If there is no dimensional drawing, cut the
distributor tube ush with the top of the tank.
Place the main control valve on tank. Note: Only use
silicone lubricant.
connecting the Drain Line Flow Control tting (DLFC).
Leave at least 6" (15 cm) between the DLFC and solder
joints when soldering pipes that are connected on the
DLFC. Failure to do this could cause interior damage to the
DLFC.
tting. The drain from twin tank units may be run through a
common line.
tank and that it is level.
plate. If a grid is not utilized, ll to the top of the air check
(Figure 1) in the salt tank. Do not add salt to the brine tank
at this time.
the main water supply. Open a cold soft water tap nearby
and let run a few minutes or until the system is free from
foreign material (usually solder) that may have resulted
from the installation. Once clean, close the water tap.
11. Slowly place the by-pass in service position and let water
ow into the mineral tank. When water ow stops, slowly
open a cold water tap nearby and let run until the air is
purged from the unit.
12. Plug unit into an electrical outlet. Note: All electrical
connections must be connected according to local codes.
Be certain the outlet is uninterrupted.
60002 Rev E
Figure 1 Residential Air Check Valve
TIMER OPERATION
Valve State
INI (Initializing)
INI will display on the screen for 30 to 45 seconds when
initializing after a power failure reset or programming.
RGQ (Regeneration Queued)
RGQ indicates that the reserve has been entered in a delayed
system and regeneration has been queued. When in service,
press the Extra Cycle button to toggle service (SRV) with RGQ.
Service (SRV)
SRV will display when the unit is in service.
LED Status Lights
Blue LED
Illuminates while the unit is in service and no errors exist. The
unit will always be in service unless a regeneration trigger has
occurred (green LED light will be displayed).
Green LED
Illuminates when the unit is in Regeneration mode, unless an
error condition exists.
Red LED
Illuminates when there is an error.
Page 3
WARNING:
TIMER OPERATION continued
Flow Indicator
A rotating line (appearing as a rotating star shape) will display
on the screen when ow is going through the the meter.
Regeneration
• A time initiated control valve regenerates when the
number of programmed days has been reached
• A ow initiated control valve regenerates when the
volume count is zero or is below reserve capacity
System TypeRegeneration Trigger
Time Clock
Delayed
Meter
Immediate
Meter Delayed
Fixed Reserve
Meter Delayed
Variable
Reserve
Meter Delayed
Weekly
Reserve
Volume
Override
Immediate
Volume
Override
Delayed
Setting the Time of Day
1. Press and hold the Up or Down button for 2 seconds.
2. Press the Shift button to select the digit you want to modify.
3. Press the Up or Down buttons to adjust the value.
4. Press the Extra Cycle button to return to the normal display
screen, or after a 5 second timeout.
NOTE: The “D” button (Diagnostic) can be pressed to exit
without saving.
Manually Initiating a Regeneration
1. When timer is in service, press the Extra Cycle button for 5
seconds on the main screen.
2. The timer advances to Regeneration Cycle Step #1, and
begins programmed time count down.
3. Press the Extra Cycle button once to advance valve to
Regeneration Cycle Step #2 (if active).
4. Press the Extra Cycle button once to advance valve to
Regeneration Cycle Step #3 (if active).
5. Press the Extra Cycle button once to advance valve to
Regeneration Cycle Step #4 (if active).
6. Press the Extra Cycle button once to advance valve to
Regeneration Cycle Step #5 (if active).
7. Press the Extra Cycle button once more to advance the
valve back to in service.
NOTE: A queued regeneration can be initiated by
pressing the Extra Cycle button. To clear a queued
regeneration, press the Extra Cycle button again
to cancel. If regeneration occurs for any reason
prior to the delayed regeneration time, the manual
regeneration request shall be cleared.
Day override parameter is reached
The time of day matches the regeneration day
override time
Regenerates as soon as the volume remaining
has been depleted
Volume remaining has been depleted to the xed
reserve volume
The regeneration time has been reached
Volume remaining has been depleted to the
variable reserve volume
The regeneration time has been reached
Volume remaining has been depleted to the
weekly variable reserve volume
The regeneration time has been reached
As soon as the programmed volume remaining
has been depleted from the tank
As soon as soon as the programmed volume
remaining has been depleted from the tank and
the regeneration time has been reached
Queued Regeneration (RGQ)
From the display screen, while the unit is in service, hold down
the Extra Cycle button until “RGQ” displays. The valve will
regenerate when the set regeneration time has been reached.
Timer Operation During Regeneration
In the main display screen, the timer shows the current
regeneration cycle and the time for that step. The green
LED light will display when the unit is in regeneration. Once
all regeneration steps are complete, the timer returns to
in service, displays a blue LED light, and resumes normal
operation.
Timer Operation During Programming
The timer enters program mode (unit must be in service).
While in the program mode the timer continues to operate
normally, monitoring water usage. Timer programming is stored
in memory permanently upon a normal exit from programming
mode.
Timer Operation During A Power Failure
All program settings are stored in permanent memory. Current
valve position, cycle step time elapsed, and time of day are
stored during a power failure, and will be restored upon power
re-application. Time is kept during a power failure, and time of
day is adjusted upon power up (as long as power is restored
within 12 hours).
NOTE: The time of day on the main display screen will
ash for 5 minutes when there has been a power
outage. The ashing of the time of day can be
stopped by pressing any button on the display.
Regeneration Day Override Feature
If the Day Override option is turned on and the valve reaches
the set Regeneration Day Override value, the Regeneration
Cycle starts at the programmed regeneration time.
Flow Meter Equipped Timer
As treated water is used, the Volume Remaining display
counts down from the calculated system capacity, less the
reserve volume. Once capacity reaches the reserve volume,
the system will regenerate based on the set regeneration
time. If set for an Immediate system, the unit will regenerate
immediately once it reaches zero capacity. If it is a Fixed,
Variable, or Weekly reserve, the unit will queue a regeneration
(RGQ) and count down Reserve Volume until the set
regeneration time.
NOTE: Reserve Volume is only available in a RGQ system.
Figure 2 Volume Remaining (Less Reserve)
Figure 3
Transformer must be grounded and ground wire
must be terminated to the backplate where grounding label is
located before installation.
Fleck 6700XTR Downow JL10 • 3
Page 4
MASTER PROGRAMMING MODE FLOW
CHART
Caution: Before entering Master Programming, please
Notes: Depending on current option settings, some
To Set Time Of Day:
Press and hold the Up and Down buttons for 2 seconds. Press
the Shift button to select the digit you want to modify.
Entering Master Programming Mode.
Press and hold the Shift and Up buttons for 5 seconds.
Set the Time of Day display to 12:01 P.M. or 12:01HR. Then go
to the main display screen, press the Up and Down buttons at
the same time for 5 seconds.
contact your local professional water dealer.
displays cannot be viewed or set.
OR
4 • JL10 Fleck 6700XTR Downow
Page 5
MASTER PROGRAMMING MODE FLOW
CHART continued
Fleck 6700XTR Downow JL10 • 5
Page 6
MASTER PROGRAMMING MODE
When the Master Programming Mode is entered, parameters
can be set to make the timer function as needed.
Notes: Depending on current option settings, some
displays cannot be viewed or set.
Entering Master Programming Mode
Press and hold the Shift and Up buttons for 5 seconds.
OR
Set the Time of Day display to 12:01 P.M. or 12:01HR. (See the
User Programming section to learn how to set the Time of Day)
Then go to the main display screen, press the Up and Down
buttons at the same time for 5 seconds.
Exiting Master Programming Mode
Press the Extra Cycle button once per display until all are
viewed. Master Programming Mode is exited and the normal
display screen appears.
To exit the Master Programming Mode without saving, press
the Diagnostic button.
NOTE: If no keypad activity is made for 5 minutes while
in the Master Programming Mode, or if there is a
power failure, no changes will be made, and the
unit will go back to the main display screen.
Resets
Soft Reset
Press and hold the Up and Down buttons for 25 seconds until
12:00PM (or 12:00HR) appears. This resets all parameters
except for the ow meter totalizer volume.
Master Reset
Hold the Shift button while powering up the unit. This resets
all of the parameters in the unit. Check and verify the choices
selected in Master Programming Mode.
4. Display Format
This program step selects the display format.
• Press the Up or Down buttons to adjust this value.
• Press the Extra Cycle button.
5. Unit Capacity
This program step selects the timer’s total capacity of hardness
that can be removed.
• Press the Shift button to select the digit you want to
modify.
• Press the Up or Down buttons to adjust this value.
• Press the Extra Cycle button.
6. Feed Water (Hardness)
This program step is used to set the feed water hardness. The
system will automatically calculate volume remaining based
on the unit capacity, capacity safety factor, and feed water
hardness entered.
• Press the Shift button to select the digit you want to
modify.
• Press the Up or Down buttons to adjust this value.
• Press the Extra Cycle button.
NOTE: Feed Water Hardness will not be shown in Volume
Override or Time Clock system types.
1. System Type
This program step selects the system type.
• Press the Up or Down buttons to adjust this value.
• Press the Extra Cycle button.
2. Valve Type
This program step selects the valve type.
• Press the Up or Down buttons to adjust this value.
• Press the Extra Cycle button.
3. Regenerant Flow
This program step selects how the regenerant ows through
the tank (must match cam). The selections available will vary
depending on the previously chosen valve model.
• Press the Up or Down buttons to adjust this value.
• Press the Extra Cycle button.
7. Capacity Safety Factor
This program step is used to set the reserve capacity of
the unit. This is a percentage by which the unit’s capacity
is reduced.
• Press the Shift button to select the digit you want to
modify.
• Press the Up or Down buttons to adjust this value.
• Press the Extra Cycle button.
8. Volume Override
This program step is used to set the volume override of the
unit.
• Press the Shift button to select the digit you want to
modify.
• Press the Up or Down buttons to adjust this value.
• Press the Extra Cycle button.
6 • JL10 Fleck 6700XTR Downow
Page 7
MASTER PROGRAMMING MODE
continued
9. Regeneration Day Override
This program step sets the maximum amount of time (in days)
the unit can be in service without a regeneration.
• Press the Shift button to select the digit you want to
modify.
• Press the Up or Down buttons to adjust this value.
• Press the Extra Cycle button.
10. Regeneration Time
This program step sets the time of day for the regeneration to
occur in delayed systems.
• Press the Shift button to select the digit you want to
modify.
• Press the Up or Down buttons to adjust this value.
• Press the Extra Cycle button.
11. Regeneration Cycle Step Programming
This program step programs the Regeneration Cycle step
times 1 through 5. Please refer to the chart below for
regenerant ow default cycle steps and times.
Regenerant
Flow
Down Flow
Back Wash
Filter
UF Back
Wash
Down Flow
Double Back
Wash
Up Flow
Upow
Variable Fill
Cycle 1TimeCycle 2TimeCycle 3Time
Back
10 Min
Wash
Back
15 MinDraw0
Wash
Back
10 Min
Wash
Back
10 Min
Wash
Brine
Rinse
Brine
Rinse
60Back Wash10
VariablePause60 Min
Brine &
Slow Rinse
Brine &
Slow Rinse
Brine &
Slow Rinse
60 Min
60 Min
60 Min
Rapid
Rinse
Settling
Rinse
Rapid
Rinse
Back
Wash
Rapid
Rinse
Brine
Rinse
10
Min
10
Min
10
Min
10
Min
10
Min
60
Min
12. Media Volume
This program step sets the volume of the media in the resin
tank.
• Press the Shift button to select the digit you want to
modify.
• Press the Up or Down buttons to adjust this value.
• Press the Extra Cycle button.
13. Salt Dosage
This program step sets the salt dosage in the unit.
• Press the Shift button to select the digit you want to
modify.
• Press the Up or Down buttons to adjust this value.
• Press the Extra Cycle button.
14. Brine Line Flow Control Size
This program step allows the selection of the desired brine line
ow control size in the unit (must match physical brine line ow
control).
• Press the Up or Down buttons to adjust this value.
• Press the Extra Cycle button.
15. Auxiliary Relay Output
The next two displays are part of a series of settings used to
program the optional relay output. The rst setting turns the
output on/off during regeneration only. The second turns the
output on during service only, every time a set volume of water
used has accumulated.
NOTE: When auxiliary outputs are in the OFF (default)
setting, press the Up or Down buttons to set the
rst setting. Then press the Extra Cycle button to
advance to the second setting.
A. Timed Auxiliary Relay Output Window (Start & End Time
Setting)
This option setting consists of two displays. The rst
display sets the turn-on time of the output, referenced
to the start of the rst regeneration cycle. The second
display sets the output turn-off time, referenced again to
the start of the rst regeneration cycle. An OFF setting
cancels this setting. All settings are in minutes and
output timing is synchronized with regeneration cycle
timing.
Start Time: Any time during regeneration.
End Time: At start time, and anytime during the
regeneration cycle.
Regenerant FlowCycle 4TimeCycle 5Time
Down Flow
Back Wash FilterRell0N/AN/A
UF Back Wash
Down Flow Double Back
Wash
Up Flow
Upow Variable Fill
Brine
Tank Fill
Brine
Tank Fill
Rapid
Rinse
Brine
Tank Fill
Back
Wash
12 MinN/AN/A
12 MinN/AN/A
10 Min
12 MinN/AN/A
12 MinRapid Rise10 Min
Brine Tank
Fill
12 Min
Fleck 6700XTR Downow JL10 • 7
Page 8
MASTER PROGRAMMING MODE
USER PROGRAMMING MODE & FLOW
continued
B. Chemical Pump Auxiliary Relay Output Window
This option setting consists of two displays. The rst
display sets the volume of water ow at which the
output turns on. The second display sets the on time (in
seconds) of the output.
• Activate output after volume set is reached.
• Press the Shift button to select the digit you want to
modify.
• Press the Up or Down buttons to adjust this value.
• Press the Extra Cycle button.
16. Flow Meter Size
This program step sets the size of the ow meter.
• Press the Up or Down buttons to adjust this value.
• Press the Extra Cycle button.
17. Maximum Flow Rate
This program step sets maximum ow rate of the generic ow
meter.
• Press the Shift button to select the digit you want to
modify.
• Press the Up or Down buttons to adjust this value.
• Press the Extra Cycle button.
18. Pulses per Gallon/Liter
This program step sets the pulses per gallon/liter for generic
ow meters.
• Press the Shift button to select the digit you want to
modify.
• Press the Up or Down buttons to adjust this value.
• Press the Extra Cycle button.
19.End of Master Programming Mode
Press the Extra Cycle button to save all settings and exit
Master Programming Mode.
CHART
NOTE: Depending on current settings, some displays
cannot be viewed or set.
1. Flow Meter Size
This program step sets the size of the ow meter.
• Press the Up or Down buttons for 5 seconds.
2. Set Feed Water Hardness
• Press the Shift, Up, and Down buttons to move the cursor
and change the value of the numbers.
• Press the Extra Cycle button to proceede to the next step.
NOTE: Feed Water Hardness will not be shown in
Volume Override or Time Clock system types.
3. Set Regeneration Day Override
• To turn on and set the days, press the Down button.
• Press the Shift, Up, and Down buttons to move the cursor
and change the value of the numbers.
• Press the Extra Cycle button to proceede to the next step.
8 • JL10 Fleck 6700XTR Downow
4. Regeneration Time
• Press the Shift, Up, and Down buttons to move the cursor
and change the value of the numbers.
• Press the Extra Cycle button to proceede to the next step.
5. End of User Programming Mode
Page 9
DIAGNOSTIC PROGRAMMING MODE
FLOW CHART
NOTE: Depending on current settings, some displays
cannot be viewed or set.
Entering Diagnostic Mode
1. Press and release the "D" button.
2. Press the Extra Cycle button once per display until all
displays are viewed and the normal display screen
appears.
3. Press and release the “D” button during this mode to exit
the Diagnostic Mode.
4. Depending on current option settings, some displays
cannot be viewed.
Fleck 6700XTR Downow JL10 • 9
Page 10
DIAGNOSTIC PROGRAMMING MODE
NOTE: Depending on current settings, some displays
cannot be viewed or set.
Overview Diagnostic Mode
The current Diagnostic Programming Mode screen will display
until either the Extra Cycle button is pressed through for each
screen, or the Diagnostic button is pressed. In the event of
regeneration occurring while in the Diagnostic Programming
Mode, the regeneration step and time remaining will be
displayed. When regeneration completes, the display will return
to the normal time of day display screen.
8. Previous Day’s Water Usage
This program step displays the previous day’s water usage.
• Press the Extra Cycle button.
9. Software Version
This program step displays the timer’s software program
version number.
• Press the Extra Cycle button to exit.
NOTE: Diagnostic Programming Mode will stop if the
system goes into a regeneration.
Entering and Exiting Diagnostic Mode
Press and release the “D” button to enter the Diagnostic
Programming Mode. Pressing the Extra Cycle button will move
to the next diagnostic screen. Press the Extra Cycle button
once per display until all are viewed. Pressing the Diagnostic
button while in Diagnostic Mode will cause the unit to leave the
Diagnostic Mode and return to the normal time of day display
screen.
1. Current Flow Rate
This program step displays the calculated ow rate for the
timer. The below ow rates are the maximum ow rate the
timer will read for each meter.
.75” Paddle: 15 gpm (0.06 m3/m)
.75” Turbine: 15 gpm (0.06 m3/m)
• Press the Extra Cycle button.
2. Peak Flow Rate
This program step displays the peak ow rate (1 minute
average) since the last regeneration.
• Press the Extra Cycle button.
3. Totalizer
This program step displays the total volume of treated water
that passes through the meter.
• Reset to zero by holding the Up and Down buttons for ve
seconds while in the totalizer screen.
• Press the Extra Cycle button.
10. End of Diagnostic Programming Mode
4. Hours Between Last Two Regenerations
This program step displays the time between the last two
regenerations saved.
• Press the Extra Cycle button.
5. Hours Since Last Regeneration
This program step displays the hours since the last
regeneration.
• Press the Extra Cycle button.
6. Volume Remaining
This program step displays the volume remaining. The timer
will regenerate if the volume remaining is set to zero. The
maximum ranges are the same as the maximum volume
calculated on the main screen.
• Press the Extra Cycle button.
7. Reserve Capacity
This program step displays the reserve capacity, ensuring soft
water is available at all times.
12 ..............2 ....... 10150 ................ Grommet, .30 Dia (included with
item 13)
13 ..............1 ....... 60068 ................ Float Assy, 2310, w/30” Rod
14 ..............1 ....... 60002 ................ Air Check, #500
42112 Rev A
Fleck 6700XTR Downow JL10 • 17
Page 18
TROUBLESHOOTING - TIMER
If an error is detected, an error screen will alternate with the
main display screen every few seconds, and the LED light will
be Red.
During an error condition, the unit continues to monitor the
ow meter and update the remaining capacity. Once an
error condition is corrected, the unit returns to the operating
status it was in prior to the error, and regeneration resumes
according to normal programming. If an error is cleared by
reprogramming the unit in the Master Programming Mode,
the volume remaining may be reset to the full unit capacity
(as though it had just regenerated). If an error is present,
a regeneration can only occur manually by pressing and
holding the Extra Cycle button for 5 seconds. If the unit was
in regeneration when the error occurred, it will complete the
regeneration cycle and go into service.
When the problem is corrected, and the error no longer
displays (it may take several seconds for the unit to stop
displaying the error message), the unit will return to normal
operation. The LED light will no longer be Red, and will
turn Green if the unit is regenerating, or Blue if the unit is in
service.
ProblemCorrection
Flashing/blinking
display
Unit not responding
after going into
regeneration
Unit displays
“ERROR CODE:
REPLACE UNIT”
(corrupted UAP)
Power outage has occurred. Either wait 5
minutes for blinking to stop, or press any key
on the keypad.
Verify the unit is congured correctly
(ex: wiring valve type). Perform a Master
Reset by holding the Shift button and cycling
power. Check and verify the choices selected
in Master Programming Mode.
Contact your local water treatment
professional
Error Display Screen Examples
Error Codes
Error
Code
Display MessageCorrection
01ERROR CODE:
PROGRAM UNIT
02ERROR CODE:
PROGRAM UNIT
03ERROR CODE:
SERVICE UNIT
04ERROR CODE:
SERVICE UNIT
05ERROR CODE:
SERVICE UNIT
Go through all screens in Master
Programming Mode.
Go through all screens in Master
Programming Mode.
Perform a Master Reset by holding
the Shift button and cycling power.
Go through all screens in Master
Programming Mode. Manually initiate
a regeneration cycle by pressing the
Extra Cycle button for 5 seconds.
Perform a Master Reset by holding
the Shift button and cycling power.
Go through all screens in Master
Programming Mode. Manually initiate
a regeneration cycle by pressing the
Extra Cycle button for 5 seconds.
Call your local water treatment
professional as soon as possible.
Leave the unit running (do not
unplug).
NOTE: If the above corrections do not work, please
contact your local water treatment professional.
18 • JL10 Fleck 6700XTR Downow
Page 19
TROUBLESHOOTING - CONTROL
VALVE
ProblemCause Correction
Water conditioner fails to
regenerate.
Hard water.By-pass valve is open.Close by-pass valve.
Unit used too much salt.Improper salt setting.Check salt usage and salt setting.
Loss of water pressure.Iron buildup in line to water conditioner.Clean line to water conditioner.
Loss of mineral through drain
line.
Iron in conditioned water.Fouled mineral bed.Check backwash, brine draw, and brine tank ll.
Excessive water in brine tank.Plugged drain line ow control.Clean ow control.
Softener fails to draw brine.Drain line ow control is plugged.Clean drain line ow control.
Control cycles continuously.Misadjusted, broken, or shorted switch.Determine if switch or timer is faulty and replace it,
Drain ows continuously.Valve is not programming correctly.Check timer program and positioning of control.
Electrical service to unit has been
interrupted
Timer is defective.Replace timer.
Power failure.Reset time of day.
No salt is in brine tank.Add salt to brine tank and maintain salt level
Injector screen plugged.Clean injector screen.
Insufcient water owing into brine tank.Check brine tank ll time and clean brine line ow
Hot water tank hardness.Repeated ushings of the hot water tank is
Leak at distributor tube.Make sure distributor tube is not cracked. Check
Internal valve leak.Replace seals and spacers and/or piston.
Excessive water in brine tank.See "Excessive water in brine tank".
Iron buildup in water conditioner.Clean control and add mineral cleaner to mineral
Inlet of control plugged due to foreign
material broken loose from pipes by recent
work done on plumbing system.
Air in water system.Assure that well system has proper air eliminator
Improperly sized drain line ow control.Check for proper drain rate.
Plugged injector system.Clean injector and screen.
Timer not cycling.Replace timer.
Foreign material in brine valve.Replace brine valve seat and clean valve.
Foreign material in brine line ow control.Clean brine line ow control.
Injector is plugged.Clean injector
Injector screen plugged.Clean screen.
Line pressure is too low.Increase line pressure to 20 psi
Internal control leakChange seals, spacers, and piston assembly.
Service adapter did not cycle.Check drive motor and switches.
Foreign material in control.Remove power head assembly and inspect bore.
Internal control leak.Replace seals and piston assembly.
Assure permanent electrical service (check fuse,
plug, pull chain, or switch)
above water level.
control if plugged.
required.
O-ring and tube pilot.
bed. Increase frequency of regeneration.
Remove piston and clean control.
control. Check for dry well condition.
Increase frequency of regeneration. Increase
backwash time.
or replace complete power head.
Replace power head assembly if not positioning
properly.
Remove foreign material and check control in
various regeneration positions.
Fleck 6700XTR Downow JL10 • 19
Page 20
TROUBLESHOOTING - CONTROL
VALVE continued
Error Codes
NOTE: Error codes appear on the In Service display.
Error CodeError TypeCauseReset and Recovery
0Cam Sense
Error
1Cycle Step
Error
2Regen
Failure
3Memory
Error
The valve drive took longer than
6 minutes to advance to the next
regeneration position
The control experienced an
unexpected cycle input
The system has not regenerated
for more than 99 days (or 7 days
if the Control Type has been set to
Day-of-Week)
Control board memory failurePerform a Master Reset and recongure the system via Master Programming
Unplug the unit and examine the powerhead. Verify that all cam switches are
connected to the circuit board and functioning properly. Verify that the motor
and drive train components are in good condition and assembled properly.
Check the valve and verify that the piston travels freely. Replace/reassemble
the various components as necessary.
Plug the unit back in and observe its behavior. The unit should cycle to
the next valve position and stop. If the error re-occurs, unplug the unit and
contact technical support.
Unplug the unit and examine the powerhead. Verify that all cam switches
are connected to the circuit board and functioning properly. Enter Master
Programming mode and verify that the valve type and system type are set
correctly with regard to the unit itself.
Step the unit through a manual regeneration and verify that it functions
correctly. If the error re-occurs unplug the unit and contact technical support.
Perform a Manual Regeneration to reset the error code.
If the system is metered, verify that it is measuring ow by running service
water and watching for the ow indicator on the display. If the unit does not
measure ow, verify that the meter cable is connected properly and that the
meter is functioning properly.
Enter a Master Programming Mode and verify that the unit is congured
properly. As appropriate for the valve conguration, check that the correct
system capacity has been selected, that the day override is set properly,
and that meter is identied correctly. If the unit is congured as a Day-ofWeek system, verify that at least one day is set ON. Correct the settings as
necessary.
Mode. After reconguring the system, step the valve through a manual
regeneration. If the error re-occurs unplug the unit and contact technical
support.
GENERAL SERVICE HINTS FOR METER
CONTROL
Problem: Softener delivers hard water
Reason: Reserve capacity has been exceeded.
Correction: Check salt dosage requirements and reset program
wheel to provide additional reserve.
Reason: Meter is not measuring ow.
Correction: Check meter with meter checker.
20 • JL10 Fleck 6700XTR Downow
Page 21
WATER CONDITIONER FLOW
DIAGRAMS
Service Position
Backwash Position
Rapid Rinse
Brine Tank Fill Position
Brine/Slow Rinse Position
Fleck 6700XTR Downow JL10 • 21
Page 22
VALVE WIRING DIAGRAM
22 • JL10 Fleck 6700XTR Downow
Page 23
SERVICE ASSEMBLIES
Air Check:
60002-34 ....................Air Check, #500, 34” Long