Pentair FLECK 5800, FLECK 5810, FLECK 5812 Service Manual

FLECK 5800/5810/5812 XTRI (CONNECTED XTR2)
SERVICE MANUAL
pentair.com
TABLE OF CONTENTS
OPERATING PARAMETERS ............................................................ 2
JOB SPECIFICATION SHEET .......................................................... 2
INSTALLATION ............................................................................... 3
START-UP INSTRUCTIONS/FLUSHING & CONDITIONING ...........5
SYSTEM DISINFECTION ................................................................. 5
TOUCHSCREEN CONTROL FEATURES.......................................... 6
TOUCHSCREEN SETUP ................................................................. 7
MASTER SETTINGS PROGRAMMING ............................................ 9
ADDITIONAL FEATURES ................................................................ 13
REGENERATION ............................................................................. 14
CONTROL OPERATION ................................................................... 14
MASTER RESET ............................................................................. 14
DIAGNOSTICS ................................................................................ 15
ALARMS AND ERRORS .................................................................. 15
USB CONNECTION FOR FIELD PROGRAMMING ..........................16
TROUBLESHOOTING ......................................................................17
PENTAIR PRO: APP SETUP ...........................................................18
MASTER SETTINGS REFERENCE CHART ..................................... 23
5800/5810/5812 CONTROL VALVE -PART NUMBERS ...................24
POWERHEAD ASSEMBLY............................................................... 25
5800 CONTROL VALVE ASSEMBLY ................................................26
5810 CONTROL VALVE ASSEMBLY ................................................27
5812 CONTROL VALVE ASSEMBLY ................................................28
5800/5810/5812 CONTROL VALVE ACCESSORIES ......................... 29
5800/5810/5812 CONTROL VALVE ASSEMBLIES ..........................30
5800 TURBINE METER ASSEMBLY ................................................ 31
5800 PADDLE METER ASSEMBLY .................................................31
5800 BYPASS VALVE ASSEMBLY (METAL) ..................................... 32
5800 BYPASS VALVE ASSEMBLY (PLASTIC) ..................................32
SAFETY BRINE VALVE .................................................................... 33
WATER CONDITIONER FLOW DIAGRAMS .....................................34
5800 DIMENSIONAL DRAWINGS ................................................... 40
5810 DIMENSIONAL DRAWINGS ................................................... 41
5812 DIMENSIONAL DRAWINGS ................................................... 42
WIRING DIAGRAM .......................................................................... 43
INJECTOR FLOW DATA .................................................................. 44
5800 PERFORMANCE DATA ..........................................................45
5810 PERFORMANCE DATA ..........................................................46
5812 PERFORMANCE DATA ..........................................................47
IMPORTANT PLEASE READ:
The information, specications and illustrations in this manual are based
on the latest information available at the time of release. The manufacturer reserves the right to make changes at any time without notice.
This manual is intended as a guide for service of the valve only. System
installation requires information from a number of suppliers not known at the time of manufacture. This product should be installed by a plumbing professional.
This unit is designed to be installed on potable water systems only.
This product must be installed in compliance with all state and municipal
plumbing and electrical codes. Permits may be required at the time of installation.
It is established that when daytime water pressure exceeds 80 psi (5.5
bar), the maximum pressure rating of 125 psi (8.6 bar) can be exceeded. A
pressure regulator must be installed on this system or warranty is voided.
Do not install the unit where temperatures may drop below 32°F (0°C) or
above 120°F (52°C).
Do not place the unit in direct sunlight. Black units will absorb radiant heat,
increasing internal temperatures.
Do not strike the valve or any of the components.
2 • FLECK 5800/5810/5812 XTRI Service Manual
Warranty of this product extends to manufacturing defects. Misapplication
of this product may result in failure to properly condition water, damage to product, or personal injury.
A prelter should be used on installations in which free solids are present.
In some applications local municipalities treat water with Chloramines. High
Chloramine levels may damage valve components.
Correct and constant voltage must be supplied to the controller to maintain
proper function.
The system is intended to treat potable water only. The system is not
intended to be used for treating water that is microbiologically unsafe or of unknown quality without adequate disinfection before and after the system.
This system is not intended for use by persons (including children) with
reduced physical, sensory, or mental capabilities, or lack of experience
and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety.
Children shall not play with the system.
Cleaning shall not be made by children without supervision.
Periodic cleaning and maintenance may be required to function properly.
See disinfection instructions on page 5.
OPERATING PARAMETERS
Minimum Pressure 20 psi/1.4 bar/138 kPa Maximum Pressure 125 psi/8.61 bar/861 kPa Minimum Water Temperature 34°F/1°C Maximum Water Temperature 110°F/43°C Minimum Ambient Temperature 34°F/1°C Maximum Ambient Temperature 120°F/52°C Maximum Humidity 75% Input Voltage 100-240 VAC Input Frequency 50/60 Hz Output Voltage 12 VDC Output Current 2.0 amps Maximum Altitude 2,000 meters
JOB SPECIFICATION SHEET
Job Number: ___________________________________________________
Model Number: _________________________________________________
Water Hardness: _______________________________________ ppm or gpg
Capacity Per Unit: _______________________________________________
Mineral Tank Size: ______________ Diameter: ________ Height: _________
Regenerant Flow: Downow Upow Backwash Downow 2x Backwash Filter Upow Variable Rell Custom Downow Custom Upow
1. Meter Size:
A. 3/4" Paddle Wheel Turbine
B. 1" Paddle Wheel Turbine
C. 1-1/2" Paddle Wheel Turbine
D. 2" Paddle Wheel
E. 3" Paddle Wheel
F. Generic_________Pulse Count__________Meter Size__________
2. System Type:
A. System #4: 1 Tank, 1 Meter, Immediate, or Delayed Regeneration
B. System #4: Time Clock
3. Cycle Settings:
A. Backwash: ____________________________________ Minutes
B. Brine and Slow Rinse: ___________________________ Minutes
C. Rapid Rinse: ___________________________________ Minutes
D. Brine Tank Refill: _______________________________ Minutes
E. Pause Time: ___________________________________ Minutes
F. Second Backwash: ______________________________ Minutes
4. Drain Line Flow Control:_____________________________ gpm
5. Brine Line Flow Control: ____________________________ gpm
6. Injector Size#: ________________________________________
7. Battery Install/Change Date: ______________________________
CAUTION
INSTALLATION
CAUTION
WARNING:
Water Pressure
A minimum of 20 psi (1.4 bar) of water pressure is required for the regeneration valve to operate effectively.
Electrical Facilities
An uninterrupted power supply is required. The control uses a transformer to supply 12 VDC. Please make sure your voltage supply is compatible with your unit before installation.
Existing Plumbing
Condition of existing plumbing should be free from lime and iron buildup. Piping that is built up heavily with lime and/or iron should be replaced. If piping is clogged with iron, a separate iron filter unit should be installed ahead of the system.
Location of System and Drain
You must have an air gap on the drain line to prevent back flow of drain water into the system. A 2x the drain line pipe diameter air gap (Figure 1) is required with a minimum 1" air gap.
Air Gap
Drain
Figure 1
Installation Locations
FOR DRY LOCATIONS ONLY.
Bypass Valves
Always provide for the installation of a bypass valve if unit is not equipped with one.
Water pressure is not to exceed 125 psi (8.6 bar),
water temperature is not to exceed 110°F (43°C), and the unit cannot be subjected to freezing conditions.
The system must be depressurized before
removing any connections for servicing.
6. Soldering of joints near the drain port must be done prior to connecting the Drain Line Flow Control fitting (DLFC). Leave at least 6" (15 cm) between the DLFC and solder joints when soldering pipes that are connected on the DLFC. Failure to do this could cause interior damage to the DLFC.
7. Plumber tape is the only sealant to be used on the drain fitting.
8. Make sure that the floor is clean beneath the salt storage tank and that the tank is level.
9. Place approximately 1" (25 mm) of water above the grid plate. If a grid is not utilized, fill to the top of the air check (Figure 2) in the salt tank. Do not add salt to the brine tank at this time.
If grid plate is used, cut air check height just below
the grid plate. This is critical on 6", 7", 8" and 9" tanks. The brine refill water must come above the grid plate and make contact with the salt.
10. On units with a bypass, place in bypass position. Turn on the main water supply. Open a cold soft water tap nearby and let run a few minutes or until the plumbing is free from foreign material (usually solder) that may have resulted from the installation. Once clean, close the water tap.
11. Slowly place the bypass in service position and let water flow into the mineral tank. When water flow stops, slowly open a cold water tap nearby and let water run until the air is purged from the plumbing lines.
12. Plug the transformer into an electrical outlet.
NOTE: All electrical connections must be connected according
to local codes. Be certain the outlet is uninterrupted.
Installation Instructions
1. Place the media tank where you want to install the unit. Make sure the unit is level and on a firm base.
2. During cold weather, the installer should warm the valve to room temperature before operating.
3. All plumbing should be done in accordance with local plumbing codes. The pipe size for a residential drain line should be a minimum of 1/2" (13 mm). Backwash flow rates in excess of 7 gpm (26.5 Lpm) or drain line length in excess of 20' (6 m) require 3/4" (19 mm) drain line. Commercial drain lines should be the same size as the drain line flow control.
NOTE: The tank should have the distributor tube installed
and have the proper amount of regenerant in place.
4. Refer to the valve spec sheet for cutting height of the distributor tube.
5. Lubricate the distributor O-ring seal and tank O-ring seal. Place the main control valve on tank. Note: Only use silicone lubricant.
60002 Rev E
Figure 2 Residential Air Check Valve
Electrical Connection
The controller operates on 12-volt DC power supply. Do not operate the controller with a power supply other than the one supplied by the manufacturer for this model. For installation location assistance, see Transformer Port Location on page 4. When installing IOT, a WiFi connection is important. See IOT BOARD POSITIONING OPTIONS on page 4. These positions will provide maximum connection locations.
NOTE: The power source should be constant. Be certain the power adapter is not on a switched outlet. Power interruptions longer than eight hours may cause the controller to lose the time setting. When power is restored, the time setting must then be re-entered.
FLECK 5800/5810/5812 XTRI Service Manual • 3
INSTALLATION continued
Outside
Outside
Bath TubLavatoryToilet Kitchen
Typical Residential System Plumbing
Faucet
- Side Mount -
Pump
or
Meter
Hot Water
Outlet
Water Heater
Grounding
Strap
Bypass
Drain Line
Laundry Tubs
Softener
Figure 3 Softened Water Flow
TRANSFORMER PORT LOCATIONIOT BOARD POSITIONING OPTIONS
Soft Water
Faucet
Hard Water
Brine Tank Overow Drain (Optional)
Floor Drain
Air Gap
- Top Mount -
4 • FLECK 5800/5810/5812 XTR I Service Manual
START-UP INSTRUCTIONS/
SYSTEM DISINFECTION
FLUSHING & CONDITIONING
The water softener should be installed with the inlet, outlet, and drain connections made in accordance with the manufacturer’s recommendations, and to meet applicable plumbing codes.
1. Program the valve control according to instructions shown in this manual.
2. Start an immediate regeneration by holding the Extra Cycle button for five seconds. Position the valve to backwash. Ensure the drain line flow remains steady for 10 minutes or until the water runs clear.
3. Position the valve to the brine draw/slow rinse position. Ensure the unit is drawing water from the brine tank (this step may need to be repeated).
4. Position the valve to the rapid rinse position. Check the drain line flow, and run for five minutes or until the water runs clear.
5. Position the valve to the start of the brine tank fill cycle. Ensure water goes into the brine tank at the desired rate. The brine valve drive cam will hold the valve in this position to fill the brine tank for the first regeneration.
6. Replace control cover.
7. Put salt in the brine tank.
NOTE: Do not use granulated or rock salt.
Disinfection of Water Softeners
The materials of construction of the modern water softener will not support bacterial growth, nor will these materials contaminate a water supply. During normal use, a softener may become fouled with organic matter, or in some cases with bacteria from the water supply. This may result in an off-taste or odor in the water.
Some softeners may need to be disinfected after installation and some softeners will require periodic disinfection during their normal life.
Depending upon the conditions of use, the style of softener, the type of ion exchanger, and the disinfectant available, a choice can be made among the following methods.
Sodium or Calcium Hypochlorite
Application
These materials are satisfactory for use with polystyrene resins, synthetic gel zeolite, greensand and bentonites.
5.25% Sodium Hypochlorite
These solutions are available under brand names of household bleach. If stronger solutions are used, such as those sold for commercial laundries, adjust the dosage accordingly.
1. Dosage A. Polystyrene resin; 1.2 fluid ounce (35.5 ml) per cubic
foot.
B. Non-resinous exchangers; 0.8 fluid ounce (23.7 ml) per
cubic foot.
2. Salt tank softeners A. Backwash the softener and add the required amount
of hypochlorite solution to the well of the salt tank. The salt tank should have water in it to permit the solution to be carried into the softener.
B. Proceed with the normal recharge.
Calcium Hypochlorite
Calcium hypochlorite, 70% available chlorine, is available in several forms including tablets and granules. These solid materials may be used directly without dissolving before use.
1. Dosage A. Two grains (approximately 0.1 ounce [3 ml]) per cubic
foot.
2. Salt tank softeners A. Backwash the softener and add the required amount of
hypochlorite to the well of the salt tank. The salt tank should have water in it to permit the chlorine solution to be carried into the softener.
B. Proceed with the normal recharge.
FLECK 5800/5810/5812 XTR I Service Manual • 5
TOUCHSCREEN CONTROL FEATURES
Features of the XTRI Touchscreen Control
• Full-featured easy to use graphical touchscreen interface for programming, servicing, and diagnostics.
• Non-linear programming no longer requires cycling through every parameter when programming/servicing.
Buttons and Symbols
NOTE: Not all buttons appear on all screens.
Regeneration Cycle Wheel
• Displays the regeneration cycle step the system is currently in. The wheel rotates with each step so that the current step is shown in green.
On metered units, the "Treatment" step on the Regeneration
NOTE:
Cycle Wheel will flash when water is flowing through the unit.
Assistance:
for unit service.
USB Connect:
via a USB cable for field programming or download of diagnostic parameters via PC (Field Programmer application required).
Displays a name and phone number to call
Allows you to connect the control to a PC
Screen Navigation Arrows: Displayed in the
upper-left and upper-right corners of the screen, these arrows allow you to navigate from one screen to another.
NOTE: Settings on previous screen are not saved unless
is pressed.
Settings Arrows: These arrows allow you to change
the values of certain settings when programming the control.
Alarm: Displayed when an alarm has been triggered;
accompanied by an audible alarm. Press to silence the audible alarm.
Home: Displays the Home screen.
Regeneration: Displays the Regeneration screen, which
allows you to start a regeneration and manually cycle through the regeneration steps.
Settings: Displays the Settings screen, which allows
you to adjust commonly used settings. Pressing this button while in the Settings screen provides access to the Master Settings screen, which allows you to fully program the valve.
NOTE:
Due to the complexity of these settings and the
potential for errors, Master Settings should only be accessed by your local water professional.
Diagnostics: Displays the Diagnostic screen, which can
assist in performing maintenance and troubleshooting performance issues with the valve.
Brightness/Sound: Displays the Brightness/Sound
screen, which allows you to adjust the backlight of the control screen and allows you to mute the alarms of the control.
Error: Displayed when an error has occurred. Press
to display the Error screen for more detailed error information.
Advance: This arrow allows you to advance through
cycle steps during a regeneration.
Reset: Displayed in the Diagnostics screen to reset
Totalizer and Peak Flow data and in Master Settings to reset parameters to factory or non-factory settings.
Accept: Press to save or accept changes in
control configuration.
Cancel: Press to cancel configuration and exit to
previous screen without saving.
Alert: Will display when there is no internet
connection.
Vacation Mode: Halts all scheduled regenerations
when pressed; press again to resume normal operation. When Vacation Mode is on, the 100 day regeneration error will be suspended.
6 • FLECK 5800/5810/5812 XTRI Service Manual
WIFI: Represents signal strength to WiFi router.
Bluetooth: When displayed in black, bluetooth signal
is open. When displayed in white, bluetooth connection is engaged.
TOUCHSCREEN SETUP
The XTRI control was designed to be easy to set up and begin using right out of the box. The following simple procedure can be used to set up the system and begin treating water in most typical applications.
NOTE: Steps 2 and 3 are optional and are not required to start
NOTE: Press
1. After plugging in the unit, the Format screen (Figure 4) is
the system. All control settings may be changed after the unit is in service.
on any Quick Start screen to reset the screen
back to its default settings.
displayed.
Using the keypad, type the name of the water treatment professional or company that the homeowner may call for system service (optional).
To enter a letter using the keypad, quickly press the keypad button the number of times that correspond with the position of the correct letter on the button. For example, to enter the letter "C", quickly press the ABC button three times. Press
3. After pressing (Figure 6) is displayed.
when finished.
, the Assistance/Mainten. Phone screen
Figure 4 Format Screen
Press the language button to adjust the system's displayed language (international version only): English, French, German, Italian, Spanish, or Dutch. Press
Press the units button to adjust the system's units of measure (either U.S. or metric). Press
Press the hardness units button to adjust the system's hardness units of measure (grains per gallon, mg/L or ppm, German degrees, French degrees, or English degrees). Press if metric units are selected.
NOTE: If the screen is blank after plugging in the unit, touch
2. After pressing (Figure 5) is displayed.
when finished. Hardness units are adjustable only
the screen to turn the screen on.
, the Assistance/Mainten. Name screen
Figure 5 Assistance/Mainten. Name Screen
when finished.
when finished.
Figure 6 Assistance/Mainten. Phone Screen
Enter the phone number of the water treatment professional or company that the homeowner may call for system service (optional). Press
4. After pressing (Figure 7) is displayed.
Figure 7 Assistance/Mainten. Interval Screen
Use the Assistance/Mainten. Interval screen to set the interval in which the homeowner will need to call a water treatment professional for system service (optional). The assistance interval can be based on a set number of months (month based) or a number of regenerations (regen based).
Press the interval button to select a month-based or regen­based assistance interval, then press the month or regen button (depending on your previous selection), and select the number of months (up to 60) or regenerations (up to 2000) until the homeowner will need to call for service. Press
, the Assistance/Mainten. Interval screen
when finished.
when finished.
. Press either
FLECK 5800/5810/5812 XTRI Service Manual • 7
TOUCHSCREEN SETUP (continued)
5. After pressing , the Home screen (Figure 8) appears.
Next Scheduled
Day and Time
Regeneration Cycle Wheel
Regeneration
Current Cycle
Step
Settings
The Settings screen allows you to change basic control settings including time of regeneration and water hardness. These settings improve the operational efficiency of the system and can be adjusted independently from other control settings without needing to enter Master Settings.
From the Home screen, press the Settings button Settings screen is displayed.
. The
Vacation
Assistance
Figure 8 Home Screen
The Day and Time button will be flashing, indicating that the day of the week and time need to be set. If the date and time are incorrect, press the Day and Time button to update to the correct day and time. The Day and Time screen (Figure
9) appears.
Day
Month
Hour
Minute
Figure 9 Day and Time Screen
Press the Day of Week, Hour, Minute, and AM/PM/HR buttons to adjust the values to the correct day of week and time. Setting the value of the AM/PM/HR button to HR changes the display to a 24 hour clock. Press the Day, Month, and Year buttons to adjust the values to the correct date. Press the Home screen. Press without saving.
button when finished to return to the
Diagnostics
to return to the Home screen
Regeneration
Settings
Year
Day of Week
AM/PM/HR
Brightness/Sound
Figure 10 Settings Screen
• Bluetooth button should be turned on to open bluetooth signal during programming will automatically turn to off when WiFi connected.
• Press day override to adjust the number of days since last regeneration in which a new regeneration will automatically be run whether one is scheduled or not.
• Press regen time to adjust the time of day that an automatic regeneration cycle will begin.
• Press hardness to adjust the hardness setting. This value should match the hardness of the incoming untreated water supply.
NOTE: Changing the hardness setting recalculates treatment
Additional features may be accessed from the Settings screen by pressing the buttons at the bottom of the screen. (see Figure 14):
volume and regeneration interval. This setting should only be changed on the advice of a professional.
• Press the Home screen.
to save your changes or press to return to
Master Settings
8 • FLECK 5800/5810/5812 XTRI Service Manual
• Master Settings: Displays the Master Settings screen,
CAUTION
which allows you to fully program the valve.
• Brightness/Sound: Displays the Brightness/Sound screen, which allows you to adjust the backlight of the control screen and allows you to mute the alarms of the control.
NOTE: Due to the complexity of these settings and the
NOTE: Settings can not be accessed during a regeneration.
potential for errors, Master Settings should only be accessed by your local water professional.
If a regeneration starts while in the settings menu, the screen will return to the main screen and all parameters will be voided.
Master Settings
The Master Settings screens include all configurable parameters available in the control.
Improperly adjusting master settings may cause
the system to operate incorrectly. Before entering master settings please contact your professional water dealer.
From the Settings screen, press the Settings button A warning message appears.
Figure 11 Master Settings Warning Screen
.
After entering the correct password and pressing , the main Master Settings screen is displayed.
.
Figure 13 Main Master Settings Screen
While in the Master Settings screens, press set parameters to a custom profile (see "NONFACTORY SETTINGS" on page 13 or press the Home button to the Home screen.
Features of the Master Settings screens are described below. See MASTER SETTINGS PROGRAMMING and MASTER SETTINGS REFERENCE CHART for more detailed information.
• format: Contains settings for Language, Units, Hardness Units, Assistance Name, Assistance Phone, and Assistance Interval.
• valve: Contains settings for System, Valve, and Regeneration Type.
• regen: Contains settings for Regen Flow.
• relay: Contains settings for Aux 1 and Aux 2 relays.
• meter: (except for time clock systems) Contains settings
for Meter Types, emergency regeneration.
• settings review: Displays a summary of all programmed settings.
to save all
to return
Press return to the Home screen.
The Password screen displays a numeric keypad.
to continue to the Password screen or press to
Figure 12 Password Screen
• Enter the master settings password 1201 and press continue to the main Master Settings screen, or press to return to the Home screen.
to
MASTER SETTINGS PROGRAMMING
FLECK 5800/5810/5812 XTRI Service Manual • 9
CAUTION
MASTER SETTINGS PROGRAMMING
(continued)
The following is a detailed overview of settings available in Master Settings. Please see the MASTER SETTINGS REFERENCE CHART for the complete set of values and ranges available to program while in Master Settings.
Format Screen
From the main Master Settings screen (Figure 13) press the format button to display the Format screen.
Figure 14 Format Screen
• language: Displays the language used on the control (international version only): English, French, German, Italian, Spanish, or Dutch.
• units: Contains settings for the unit type (either US or Metric) to be used in the control.
• hardness units: Contains settings for hardness units of measure (grains per gallon, mg/L or ppm, German degrees, French degrees, or English degrees). Hardness units are adjustable only if metric units are selected.
NOTE: Degree hardness units are converted to ppm upon
• Press the screen navigation arrows at the upper-right
• Press
input. Degree inputs may be rounded up or down to the nearest ppm equivalent.
and left of the screen to navigate to the Assistance Name, Assistance Phone, and Assistance Interval screens.
to save changes.
Valve Screen
From the main Master Settings screen (Figure 13) press the valve button to display the Valve screen.
Figure 15 Valve Screen
• system: Displays the system type. Type 4 (single system) is currently the only available selection.
• valve: Contains settings to select the valve model installed with the control.
• regen type: Contains settings for the type of regeneration to use for the system. Regeneration types are described in detail below.
Regeneration Types
The XTRI control supports several different Regeneration Types. The Regeneration Type defines the method of automatic regeneration for the system. Each type is explained below.
Time Clock
Triggers a regeneration on a timed interval. The control will initiate a regeneration cycle at the selected Regeneration Time when the number of days since the last regeneration equals the Day Override value. The Day Override can be set from 1 - 99 days as well as partial day intervals of 4, 8, 12, 16 and 20 hours.
Softener Immediate
Measures water usage and regenerates the system as soon as the calculated system capacity is depleted. The control calculates the system capacity by dividing the unit capacity by the feed water hardness. Softener Immediate systems do not use a reserve volume. The control will also start a regeneration cycle at the programmed regeneration time if a number of days equal to the Day Override pass before water usage depletes the calculated system capacity. The Day Override parameter default is OFF, and REGEN TIME will be grayed out unless the day override value has been modified.
When setting the system for softener immediate
regeneration, setting the capacity to a value lower than that of feed water hardness may cause the system to constantly regenerate. If this occurs, disconnect the motor from the control and correct the capacity and feed water hardness values in Master Settings.
Softener Delayed
Measures water usage and regenerates the system at the selected Regeneration Time after the calculated system capacity is depleted. The control calculates the system capacity by dividing the unit capacity by the feed water hardness and subtracting the reserve.
10 • FLECK 5800/5810/5812 XTRI Service Manual
The reserve should be set to ensure that the system delivers
CAUTION
treated water between the time the system capacity is depleted and the actual regeneration time. Reserves can be set at a Fixed Volume, Fixed Percentage of capacity, a Variable Reserve based on the previous calendar day's water usage, or a Weekly Reserve based on the average water usage for the current day of the week. The default for the day override parameter is OFF, and the default reserve type is Weekly Reserve.
A Softener Delayed control will also start a regeneration cycle at the selected Regeneration Time if a number of days equal to the Day Override pass before water usage depletes the calculated system capacity.
If the regen type is changed from Softener Immediate to Softener Delayed (or vice-versa), all parameters within those types will be reset to factory default.
Filter Immediate
Regenerates the system immediately after the selected Volume Override value is depleted. A Filter Immediate control will also start a regeneration cycle at the selected Regeneration Time if a number of days equal to the Day Override pass before water usage depletes the calculated system capacity.
Filter Delayed
Regenerates the system at the selected Regeneration Time after the selected Volume Override value is depleted. A Filter Delayed control will also start a regeneration cycle at the selected Regeneration Time if a number of days equal to the Day Override pass before water usage depletes the calculated system capacity.
NOTE: If Filter Immediate or Filter Delayed are selected,
Regenerant Flow selections are limited to Filter, Upflow Filter, Custom Filter, and Custom Upflow Filter.
• regen flow: Contains settings for the type of regenerant
flow to be used in the valve. Changes to this setting affects the cycle steps displayed in the Regeneration Cycle Wheel on the Home screen. Regenerant flow cycle steps are described below.
• downflow: Cycle steps are as follows: Backwash, Draw, Rapid Rinse, Tank Refill
• upflow: Cycle steps are as follows: Draw, Backwash, Rapid Rinse, Tank Refill
• downflow 2X backwash: Cycle steps are as follows: Backwash, Draw, Backwash, Rapid Rinse, Tank Refill
• custom upflow / downflow / filter: Allows for up to 20 programmable cycle steps.
• variable refill: (softener delayed only) Cycle steps are as follows: Refill, Pause, Draw, Backwash, Rinse. Variable refill calculates refill time based on salt dosage, media volume, and BLFC size.
Relay Output Screen
From the main Master Settings screen (Figure 13) press the
relay button to display the Relay Outputs screen.
Regeneration Screen
From the main Master Settings screen (Figure 13) press the regen button to display the Regeneration screen.
Figure 16 Regeneration Screen
Adjusting Regeneration settings will turn any set
relays off. Any required relays will need to be reprogrammed in the Relay Output screen.
• auxiliary 1 / auxiliary 2: Contains settings for
programming up to two auxiliary relay outputs. There are three types of relays that can be programmed:
• Cycle Based: The relay will turn on when the valve moves to the specified regeneration cycle steps. To program, select each cycle step button for which the relay should turn on.
• Time Based: The relay will turn on and off at up to two specified start and end times. If water saving regeneration is on, this is not an available option.
• Volume Based: The relay will turn on when the valve has treated a specified volume of water. Duration can be set for up to two hours.
• Alarm Based: The relay will turn on when the specified alarm condition (or any alarm condition) is met. The relay will turn off when the alarm is cleared.
FLECK 5800/5810/5812 XTRI Service Manual • 11
MASTER SETTINGS PROGRAMMING
(continued)
Meter Screen
From the main Master Settings screen (Figure 13) press the meter button to display the Meter screen.
Figure 17 Meter Screen
• meter type: Contains settings for the type of meter installed with the system. The 5810/5812 valve uses an internal 1.25" turbine meter.
• generic: A generic option is available if the installed meter does not match any other selection. Requires setting the number of pulses per volume to ensure proper metering.
• emergency regen: When on, the emergency regen feature causes a regen to occur immediately when 105% or greater of the capacity (e.g., volume plus reserve)
Continuous Flow Detect Screen
From the Meter screen (Figure 19) press to display the Continuous Flow Detect screen.
is used.
Settings Review
From the main Master Settings screen (Figure 13) press the settings review button to display the Settings Review screens, which display a read-only summary of all programmed settings in the control. Use the navigation arrows at the top of the screen to scroll through the parameters currently set in the control. The Settings Review screens are formatted similarly to the corresponding screen where each parameter was set. Press
to return to Master Settings.
Non-Factory Settings
After all parameters in Master Programming have been set, these settings can be saved to a custom profile by pressing on the main Master Settings screen (Figure 13). After pressing
, the Non-Factory Settings screen appears.
Figure 19 Non-Factory Settings Screen
Press to non-factory settings. At any point, the control can be reset to these saved custom settings. By performing a custom reset, any setting that is subsequently programmed without saving to non-factory settings will be reset to the previously saved non­factory settings in the control.
to save all programmed Master Settings parameters
Figure 18 Continuous Flow Detect Screen
• continuous flow detect: When active, triggers an alarm when continuous flow of 0.5 GPM or 1 LPM is detected by the flow meter over an 8-hour period.
• Press the screen.
12 • FLECK 5800/5810/5812 XTRI Service Manual
button when finished to return to the Home
ADDITIONAL FEATURES
Press the screen navigation arrow at the top right of the Master Settings screen (Figure 13) to navigate to the secondary Master Settings screen.
Figure 20 Secondary Master Settings Screen
• water saver regen: Contains settings for setting regenerations to save water by reducing backwash and rinse time on a particular interval
• remote regen: Contains settings for triggering a regeneration via a remote input
• cl generation/low salt: (international version only) Contains settings to trigger chlorine generator for the control
Water Saver Regeneration
From the secondary Master Settings screen (Figure 22) press the water saver regen. button to display the Water Saver Regen screen (Figure 23).
From the secondary Master Settings screen (Figure 22) press the remote regen button to display the Remote Regen screen.
Figure 22 Remote Regeneration Screen
• remote regeneration duration: Contains settings for triggering a regeneration via a remote input. Select a value in seconds that the remote switch must be closed in order to trigger the regeneration.
Connect a remote switch (such as a differential pressure switch) to the remote start input terminals on the back of the XTRI control board. When the remote switch remains closed for the number of seconds specified in the Remote Regen screen, a regeneration will be triggered regardless of volume, capacity, or time remaining until the next scheduled regeneration.
Chlorine Generation/Low Salt (international version only)
From the secondary Master Settings screen (Figure 22) press the cl generation/low salt button to display the Chlorine Gen/ Low Salt screen (Figure 25).
Figure 21 Water Saver Regen Screen
• water saver regen: reduces backwash and rapid rinse times on a particular interval. The reduced backwash time is 50% less than the backwash time (rounded down to the nearest minute, e.g. if the backwash time is set to 10 minutes, enabling the water saver regen function will reduce the backwash time to 5 minutes).The reduced rapid rinse time is 66% less than the rapid rinse time (rounded down to the nearest minute, e.g. if the rapid rinse time is set to 10 minutes, enabling the water saver regen function will reduce the backwash time to 3 minutes).
• range: 1-25 regenerations (for example, a setting of 3 will produce 1 normal regeneration then 3 reduced water saving regenerations).
Figure 23 Chlorine Gen/Low Salt Screen
• cl generation/low salt: Contains settings to trigger chlorine generator for the control (on/off)
• regen interval range: 1 to 255 regenerations
FLECK 5800/5810/5812 XTRI Service Manual • 13
REGENERATION
CAUTION
Start a regeneration by pressing the Regeneration button . The Regeneration screen appears (Figure 26).
Figure 24 Regeneration Screen
• Press now to begin a regeneration immediately, or press at regen. time to queue the regeneration for the programmed regeneration time (2:00 AM default for softeners, 12:00 AM default for filters). Pressing at regen. time again will cancel the manual regeneration.
• During Regeneration, press the advance to the next cycle step. Once in regeneration, the volume or time will be displayed below the
For softener systems, put salt in the brine tank before starting a regeneration.
NOTE: Do not use granulated or rock salt.
The unit is now fully programmed and ready to treat water. This quick setup uses the control's default settings, which are appropriate for most residential applications.
button to immediately
button.
CONTROL OPERATION
Control Operation During Regeneration
During regeneration, the Regeneration Cycle Wheel shows the regeneration step the valve is advancing to, or has reached, and the time remaining in that step. Once all regeneration steps are complete the valve returns to treatment position and resumes normal operation. The time remaining in regeneration will be displayed on the home screen in hours and minutes.
Pressing the immediately advances the valve to the next cycle step position and resumes normal step timing. The when the valve is in position and the motor has stopped. Pressing the
button during a regeneration cycle
button is only shown
button will cancel the regeneration.
are stored in a non-volatile memory and are stored indefinitely with or without power. After a long power outage, the Time of Day button may flash indicating it needs to be reset. Press the button to stop the Time of Day from flashing and reset time if needed. If power fails while the unit is in regeneration, the control will save the current valve position before it shuts down. When power is restored, the control will resume the regeneration cycle from the point where power failed. If power remains off for more than eight hours, upon power restoration the regeneration is canceled and the piston returns to service.
If power fails during a regeneration cycle, the
valve will remain in its current position until power is restored. The valve system should include all required safety components to prevent overflows resulting from a power failure during regeneration.
The control will not start a new regeneration cycle without power. If the valve misses a scheduled regeneration due to a power failure, it will queue a regeneration. Once power is restored, the control will initiate a regeneration cycle the next time that the Time of Day equals the programmed regeneration time. Typically, this means that the valve will regenerate one day after it was originally scheduled. If the treated water output is important and power interruptions are expected, the system should be set up with a sufficient reserve capacity to compensate for regeneration delays.
Remote Lockout
If a remote switch is installed, the control will not allow the system to go into regeneration until the regeneration lockout input signal to the control is cleared. This requires opening the contact closure to clear the lockout condition. The recommended gauge wire is 20 with a maximum length of 500 feet. See "WIRING DIAGRAM" on page 43.
Sleep Mode
The control will go into sleep mode if no button is pressed after five minutes. All other control functions will continue to operate. The display will wake from sleep mode when any part of the display is touched.
MASTER RESET
Press the button while in the Master Settings main screen (Figure 13) to display the Reset screen.
Control Operation During Programming
The control can only be programmed with the valve in treatment. While being programmed the control continues to operate normally, monitoring water usage and keeping all displays up to date. Control programming is stored in memory permanently until reset.
Control Operation During a Power Failure
The XTRI includes internal power backup. In the event of power failure, the control shifts into a power-saving mode. The control stops monitoring water usage. The display and motor shut down, but it continues to keep track of the time and day for a minimum of eight hours. The system configuration settings
14 • FLECK 5800/5810/5812 XTR I Service Manual
Figure 25 Reset Screen
Press the factory button to reset all control parameters to their factory defaults, or press the non-factory button to reset control parameters to previously saved custom settings (see "NONFACTORY SETTINGS" on page 13). A warning screen appears before parameters are reset. Press reset or press
to return to Master Settings.
to confirm the
DIAGNOSTICS
The control records and displays a variety of diagnostic data to assist with troubleshooting performance issues and fine-tuning system efficiency. Press the Diagnostics button Master Settings or Home screens to view the Diagnostic screen.
Figure 26 Diagnostic Screen
• Press the screen navigation arrows at the upper-right and left of the screen to view each diagnostic parameter.
• Press the Error Log button
to access the Error Log (Figure 29) screen. To clear the Error Log, press the Reset button then the Reset button again on the Clear All Error Logs screen, then enter "1201" at the password prompt screen, then press the Accept button to confirm.
from the
NOTE: If a regeneration occurs while in the Diagnostic screen,
the unit will return to the main screen.
Parameter Description
Flow Rate Displays the current flow rate.
Peak Flow* Displays maximum flow rate of water along
,
Totalizer*
Last Regen Displays when last regeneration occurred.
Software Version Displays the software version installed on
No of Regens Displays how many manually and system
Regen Interval Displays the average length of time between
Daily Usage Displays average water usage for each day of
Usage Since Regen Displays water usage since last regeneration.
Last Setting Change Displays the date and time of the last update
** Displays total volume of water used since
Reserve Displays the reserve volume based on the
with date and time of occurrence, since last
reset.
last reset.
reserve type selected under master settings.
*This parameter is only available for meter
delayed regeneration type.
the controller.
initiated regenerations the system has gone
through since last reset.
regenerations based on the past four
regenerations.
the week based on the usage on that day for
the past six weeks.
to Master Settings.
NOTE*: Only Peak Flow and Totalizer can be changed - they
can be reset to zero.
NOTE**: Totalizer has a maximum value of 99,999,999. If this
number is reached, the Totalizer must be reset to zero to continue tracking this value.
Figure 27 Error Log Screen
Press the Home button
to return to the Home screen.
ALARMS AND ERRORS
If an error in valve or control function occurs, an alarm will sound and the Home screen will display the Error
Alert button
• Press the Alarm button to mute the alarm.
• Press the Error Alert button to view information about the error.
and the Alarm button .
Error Alert
Alarm
Figure 28 Alarm and Error Alert
FLECK 5800/5810/5812 XTRI Service Manual • 15
Loading...
+ 33 hidden pages