Pentair DigiTrace E104, DigiTrace E304, DigiTrace E307 Installation Instructions Manual

E104E304E307
Three pole conTacTor InsTallaTIon InsTrucTIons
E104
Interior view Side view
13.0 in (330 mm)
10.5 in (267 mm)
9.2 in
(234 mm)
Nonhazardous locations
8.5 in
(216 mm)
6.0 in
(152 mm)
0.312 in (9 mm) mounting hole (4X)
40-A Three-pole Contactor for
100-A Three-pole Contactor for
E304
Interior view
9.0 in (229 mm)
6.5 in (165 mm)
7.2 in
(183 mm)
Nonhazardous locations
®
Nonhazardous Locations
Side view
6.5 in
(165 mm)
4.0 in
(102 mm)
0.312 in (9 mm)
mounting hole (4X)
6.7 in
(170 mm)
1 in conduit through hole (2X).
6.7 in
(168 mm)
1 in (25 mm) conduit through hole (2X).
Second hole is opposite this hole.
1.9 in (48 mm)
4.3 in
(109 mm)
1.9 in
(48 mm)
3.3 in
(84 mm)
DESCRIPTION
The E104 is a three-pole 100 amp per pole contactor housed in a NEMA 4X enclosure.
SPECIFICATIONS
Enclosure NEMA 4X Power Connection Pressure lugs for 14-4 AWG wire Contactor Rating 100 A per pole, 600 Vac maximum,
UL Recognized, CSA Certified
Order with appropriate coil Coil Rating Catalog Number
110-120 Vac E104-100-120 208-240 Vac E104-100-208/240 277 Vac E104-100-277 480 Vac E104-100-480 600 Vac E104-100-600
DESCRIPTION
The E304 is a three-pole 40 amp per pole contactor housed in a NEMA 4X enclosure.
SPECIFICATIONS
Enclosure NEMA 4X Power Connection Pressure lugs for 14-4 AWG wire Contactor Rating 40 A per pole, 600 Vac maximum,
UL Recognized, CSA Certified
Order with appropriate coil Coil Rating Catalog Number
110-120 Vac E304-40-120 208-240 Vac E304-40-208/240 277 Vac E304-40-277 480 Vac E304-40-480 600 Vac E304-40-600
E307
6.9 in
(175 mm)
5.9 in
(150 mm)
(175 mm)
0.3 in (8 mm) (2X)
Hazardous Locations
8.1 in
(206 mm)
6.9 in
Side viewTop view
(163 mm)
(130 mm)
THERMAL MANAGEMENT SOLUTIONS
40-A Three-pole Contactor for
DESCRIPTION
The E307 is a three-pole 40 amp per pole contactor housed in a NEMA 4, 7, 9 aluminum enclosure that is approved for hazardous locations.
6.4 in
5.1 in
2.8 in (71 mm)
3.5 in
(89 mm)
1-in NPT (2X). Second hole is opposite this hole
EN-DigiTraceE104E304E307-IM-H5878301/13
SPECIFICATIONS
Enclosure NEMA 4,7,9
Power Connection Pressure lugs for 14-4 AWG wire Contactor Rating 40 A per pole, 600 Vac maximum,
Order with appropriate coil Coil Rating Catalog Number
FM Approved for Class I, Div. 1 & 2, Groups B, C, D; Class II, Div. 1 & 2, Groups E. F, G; Class III
UL Recognized, CSA Certified
110-120 Vac E307-40-120 208-240 Vac E307-40-208/240 277 Vac E307-40-277 480 Vac E307-40-480 600 Vac E307-40-600
1 / 2
Installing the Contactor
1. Verify that the contactor is suitable for the area where it is to be installed.
2. Check the line voltage and the heat-tracing load to ensure that the contactor ratings are not exceeded.
3. Mount the enclosure in a position that prevents condensation from draining into the enclosure from the connecting conduit (see diagram at right).
Wiring
Conduit drain
GFEPD
Ø1AØ1BØ
G G
NANBN
Braid
1C
C
Heating
cable A
Ø
2A
Ø
Heating
cable B
Ø
Ø
2B
Ø
B
A
Heating
cable C
208/240-V supply – 240-V heater or
2C
120-V supply – 120-V heater or
Ø
C
277-V supply – 240-V heater
120-V or 208/240-V
C
or 277-V coil
NONC
C
NONC
C
Figure 1.
Contactor control for switching heat-tracing loads greater than 22 A or switching multiple heat-tracing circuits.
Control thermostat
480-V & 600-V heater Control voltage
G
N
To heating cable
GFEPD
Ø
A
Ø
B
GFEPD
G N/Ø
Ø
C
Coil to match
C
control voltage
T-stat & coil supply
Ø
120-V or 277-V supply
NONC
C
NONC
C
Figure 2.
Contactor control for switching heating cable On/Off.
Control thermostat
NORTH AMERICA
Tel: +1.800.545.6258 Fax: +1.800.527.5703 Tel: +1.650.216.1526
EuROpE, MIddlE EAsT, AfRICA
Tel: +32.16.213.511 Fax: +32.16.213.603
thermal.info@pentair.com Fax: +1.650.474.7711 thermal.info@pentair.com
Pentair and DigiTrace are owned by Pentair or its global affiliates. All other trademarks are the property of their respective owners. Pentair reserves the right to change specifications without prior notice.
© 2011-2013 Pentair. PN 601607-000
AsIA pACIfIC
Tel: +86.21.2412.1688 Fax: +86.21.5426.2917 cn.thermal.info@pentair.com
EN-DigiTraceE104E304E307-IM-H5878301/13
WWW.THERMAl.pENTAIR.COM
lATIN AMERICA
Tel: +55.11.2588.1400 Fax: +55.11.2588.1410 thermal.info@pentair.com
2 / 2THERMAL MANAGEMENT SOLUTIONS
Loading...