Pentair Digitrace E507S-LS, DigiTrace AMC1B Installation Instructions Manual

E507S-LS
LINE-SENSING THERMOSTAT FOR HAZARDOUS LOCATIONS INSTALLATION INSTRUCTIONS
DESCRIPTION
The E507S-LS thermostat is designed for controlling heat-tracing systems in hazardous locations. The E507S-LS can be used to control heat-tracing circuits in a pipe-sensing mode (see Figure 1 on back page), to indicate low-temperature (see Figure 2) or high­temperature (see Figure 3) alarm conditions, or to control the coil on a contactor (see Figure 4).
APPROVALS
Hazardous locations
Class I, Div. 1 and 2, Groups B, C, D Class II, Div. 1 and 2, Groups E, F, G Class III
SPECIFICATIONS
Enclosure NEMA 4, 7, 9, lacquer-coated cast-aluminum
housing, stainless-steel hardware Entries One 3/4 in. NPT conduit hub Set point range 25°F to 325°F (–4°C to 163°C) Sensor exposure
–40°F to 420°F (–40°C to 215°C) limits
Housing exposure
–40°F to 140°F (–40°C to 60°C) limits
Switch SPDT Electrical rating 22 A at 125/250/480 Vac Accuracy ±6°F (±3.3°C) Deadband 2°F to 12°F (1.1°C to 6.7°C) above actuation
temperature Set point
±3°F (±1.7°C) repeatability
Sensor type Fluid-filled (silicone) bulb and 9 ft (2.7 m)
capillary Sensor material 300 series stainless steel Connection
Screw terminals, 10–14 AWG (2–5 mm terminals
8.0 in.
(202 mm)
Terminal
block
4.5 in. (114 mm)
4.0 in. (102 mm)
Adjusting knob
Removable knob cover
4.0 in. (102 mm)
4.0 in.
(102 mm)
2.0 in.
(50 mm)
Ø.28 in. (7 mm) mounting hole (4X)
4.5 in.
(114 mm)
6.6 in.
(168 mm)
1.2 in. (30 mm)
0.3 in. (9 mm)
2
)
3⁄4 in. NPT conduit entry
WARNING:
This component is an electrical device. It must be installed correctly to ensure proper operation and to prevent shock or fire. Read these important warnings and carefully follow all the installation instructions.
THERMAL MANAGEMENT SOLUTIONS EN-DigiTraceE507SLS-IM-H5691301/13
Component approvals and performance are based on the use of specified parts only. Do not use substitute parts or vinyl electrical tape to make connections.
1 / 2
INSTALLING THE THERMOSTAT
1. Verify that the thermostat is suitable for the area where it is to be installed.
2. Check the line voltage and the heat-tracing load to ensure that the thermostat ratings are not exceeded.
3. Mount the unit using unistrut or the Raychem universal mounting bracket (UMB-263757) in a position that prevents condensation from draining into the enclosure from the connecting conduit (see diagram above).
POSITIONING THE SENSOR BULB
4. Position the bulb in the lower quadrant of the pipe as shown in the diagrams to the left. Place the bulb at least three feet from pipe supports, valves, or
90
Single traced
Heating cable Control thermostat bulb AT-180 tape
other heat sinks; protect the capillary from kinks or bends less than 1⁄2 inch in radius.
Double traced
Heating cable Control thermostat bulb AT-180 tape
WIRING
GFEPD
ØØ
208-V or 240-V supply – 240-V heater
or
G
120-V supply – 120-V heater
N
Ø
277-V supply – 240-V heater
C
NO NC
Power
G
connection
Thermostat bulb
Braid
Figure 1. Pipe-sensing
(see "Positioning"
instructions above
for mounting details)
Heating Cable
Control thermostat
GFEPD
208-V or 240-V supply
ØØ
or
ØGN
120-V supply – 120-V heater 277-V supply – 240-V heater
C
NO NC
Alarm
Thermostat bulb
(see "Positioning"
instructions above
for mounting details)
Figure 2. Low-temperature alarm
Control thermostat
5. Tape the bulb firmly to the pipe with AT-180 aluminum tape, making sure there is no air space between the bulb and pipe. Do not overlap the bulb and heating cable with the same piece of AT-180 tape.
Conduit drain
6. For metal-tank-wall sensing, use the BCK-35 bulb clamp (purchased separately) and install the clamp per the instructions provided. Make sure there is no air space between the tank wall and the bulb.
For installation on plastic tanks, contact Pentair Thermal
Management at (800) 545-6258.
SETTING THE THERMOSTAT
7. Set the thermostat dial to the desired temperature, then finish wiring.
8. Complete insulating. Do not turn the system on until the bulb is covered with thermal insulation.
9. Fill the piping or tank. Once the thermostat has begun to cycle, check the fluid temperature with an immersed thermostat (best for plastic systems) or an accurate temperature indicator. Adjust the dial setting if necessary.
GFEPD
208-V or 240-V supply
ØØ
or
ØGN
120-V supply – 120-V heater 277-V supply – 240-V heater
C
NO NC
Alarm
Thermostat bulb
(see "Positioning"
instructions above
for mounting details)
Figure 3. High-temperature alarm
Control thermostat
GFEPD
GCNANBN
C
A
Braid
Heating cable A
Heating cable B
Figure 4. Contactor control
For switching heat-tracing loads greater than 22 A or switching multiple heat-tracing circuits.
120- V supply – 120-V heater or
Ø
ØBØ
C
277-V supply – 240-V heater
120-V or 277-V coil
Heating cable C
NONC
C
NONC
C
Thermostat bulb (see "Positioning" instructions above for mounting details)
Control thermostat
NORTH AMERICA
Tel: +1.800.545.6258 Fax: +1.800.527.5703 Tel: +1.650.216.1526
EUROPE, MIDDLE EAST, AFRICA
Tel: +32.16.213.511 Fax: +32.16.213.603
thermal.info@pentair.com Fax: +1.650.474.7711 thermal.info@pentair.com
Pentair and DigiTrace are owned by Pentair or its global affiliates. All other trademarks are the property of their respective owners. Pentair reserves the right to change specifications without prior notice.
© 2001-2013 Pentair. PN 137863
ASIA PACIFIC
Tel: +86.21.2412.1688 Fax: +86.21.5426.2917 cn.thermal.info@pentair.com
WWW.THERMAL.PENTAIR.COM
LATIN AMERICA
Tel: +55.11.2588.1400 Fax: +55.11.2588.1410 thermal.info@pentair.com
2 / 2THERMAL MANAGEMENT SOLUTIONS EN-DigiTraceE507SLS-IM-H5691301/13
Loading...