PennBarry WFX08 Installation Manual

Operation and Maintenance Manual
TM
Please read and save these instructions. Read carefully before attempting to assemble, install, operate or maintain the product described. Protect yourself and others by observing all safety information. Failure to comply with instructions could result in personal injury and/or property damage! Retain instructions for future reference.
Fumex (Standard, Heat & Smoke & Restaurant Exhaust) Centrifugal Roof & Wall: Direct & Belt Drive Exhausters
Description
Designed for severe service removing foul air from industrial and commercial buildings, laboratory fume hoods. Housing and wheel constructed of aluminum; heat and smoke removal utilizes a steel wheel. Motor compartment externally cooled and located out of the discharge airstream. Power ventilators suitable for Restaurant Exhaust Appliances (YZHW) are accordingly labeled. Power ventilators suitable for smoke removal are ac­cordingly labeled. These units require installation according to NFPA-96 standards, lo­cal codes and general practices. Up to Model 24B are available wall mounted (WFX).
DAMPERS: ROOF MOUNTING
When required, install dampers prior to mounting the unit on the curb or frame.
Dampers are sized to t within the roof
opening. Secure using standard hardware. If the damper is installed on the inside of the curb, a piece of wood may be required as a “spacer”. Do not twist or distort the damper frame. Damper frame must be reasonably level on all sides. Check for free operation. If dampers are motor operated type, ascer­tain that proper voltage is applied on motor terminals.
ANCHORING AND INSTALLING THE VENTILATOR
Roof mounting may be in accordance with the latest edition of NFPA-96 and local
codes. If not specied by codes), secure
unit to curb through pre-punched holes in the ventilator base vertical ange (see Fig­ure 1 below).
In order to complete some installations, spe-
cically kitchen exhaust, you will require an
18” high curb as well as a weather resistant junction box and hinge assembly.
Guy down large units installed in areas sub-
ject to high winds or unusual eld con-d it
ions. If the installer removes any ventilator parts to facilitate installation or electrical connection, reassemble all parts by replac­ing all spacers, washers, nuts, bolts, fasten­ers and components exactly as they were found prior to removal. Draw all fasteners tight and secure.
Roof Curb
PennBarry fans are carefully inspected be­fore leaving the factory. When the unit is received, inspect the carton for any signs of tampering. Inspect the unit for any dam­age that may have occurred during transit and check for loose, missing or damaged parts. Mishandled units can void the war­ranty provisions. If units are damaged in transit, it is the responsibility of the receiv­er to make all claims against the carrier. PennBarry is not responsible for damages incurred during shipment.
Avoid severe jarring and/or dropping. Handle units with care to prevent damage
to components or nishes. If the unit is
scratched due to mishandling, the protec­tive coating may be damaged. Incorrect lifting may damage the fan and void the warranty.
Storage
Long-term storage requires special atten­tion. Store units on a level, solid surface, preferably indoors. If outside storage is necessary, protect the units against mois­ture and dirt by encasing the cartons in plastic or in some similar weatherproof material. Periodically inspect units and rotate wheels to spread bearing lubricant. Failure to rotate wheels results in reduced bearing life and may void the manufac­turer’s warranty. If the unit will be stored for an extended time, remove belts. Belts which remain under tension in a stationary position for extended periods are likely to have a reduced operating life.
Unpacking
Place the carton in an upright position and remove the staples or use a sharp (knife edge) tool to carefully cut or scribe the sealing tape on both sides at the top of
the carton. Open carton aps. Remove any cardboard and wooden ller pieces,
as well as loose components or accesso­ries shipped with the unit.
Carefully remove the unit from the carton. Inspect the unit for any damage that may have occurred during transit and check for loose, missing or damaged parts.
Installation
When the unit is installed on a sloped roof, suitable footing and/or other safety devices must be provided around the ventilator for normal maintenance. Depending upon the site conditions, the hinging of the ventilator off the curb during maintenance should be either parallel to the roof ridge or toward the roof ridge, but NOT away from the ridge.
NFPA-96 recommends t h at da m p ers sh o u ld not be installed when exhauster is used for the removal of smoke and grease laden vapors from commercial cooking equipment. Consult state and local codes for detailed requirements.
NOTE
be installed per instructions on page 5.
Figure 1: Roof Curb Installation
Fastener
For instalation in high veloci­ty hurricane zones, Unit must
Base
1401 North Plano Road, Richardson, Texas 75081 Phone: 972-234-3202 Fax: 972-497-0441
Revised MAR 09 PART #59368-0
Operation & Maintenance Manual Fumex Centrifugal Roof & Wall: Direct & Belt Drive Exhausters
FLOATING HINGE INSTRUCTIONS
1. If any gasket is to be eld installed, this
should be completed before installing the oating hinge. If a grease collec­tion box will be installed, it should be
installed after installing the oating
hinge, and not on either the hinge or handle sides of the unit.
2. If this item is provided, hardware is included. Review gure 2 for illustra­tions regarding this installation. De­tailed instructions should be provided with the hinge kit, which are summa­rized below. The hinge kit instructions take precedence over these instruc­tions.
3. Take back plate and position inside the pedestal to allow for the pedestal
metal thickness, ush with both the
top and rear vertical surfaces. Use this plate as a template to mark the hole locations. Drill two clearance holes. Do this for both sides of the pedestal.
4. Bolt both back plates in place INSIDE the pedestal. Slide bushing over the rear most back plate bolt.
Figure 2: Floating Hinge Installation
Figure 3: Wall Mount Installation
Table 1: Wall Mount Dimensions
Model E
WFX08 24 9
WFX10–WFX13 11 & 24 11 1/2
WFX8B–WFX14B 27 1/4 16 1/4
WFX16 24 40 1/4
WFX16B–WFX18B 29 1/2 20
WFX24B 35 7/8 25
DIA
Wo
5. Insert 2 bolts through pre-punched holes on each side of the ventilator base.
6. Position the ventilator on top of the
pedestal. Install the oating hinge
by aligning the slotted hole over the bushing (on rear most bolt) and onto the two bolts on the ventilator base. Fasten with nuts and tighten. Install nut over bushing. The forward back plate bolt functions as a stop; nothing is attached to it.
7. Install the lift handle and hold down lugs to ventilator base through the pre-punched holes.
8. Using the hold down lug as a tem­plate, drill on both sides of the pedes­tal to install wing nut hardware.
When installed, tighten rmly.
WALL MOUNTING
Fumex fans are available with round bases to facilitate wall mounting through size 24B (WFX), If installing these units, ensure the wall mounting surface is leak-
SQ
free. To assure weather-tightness, coat the entire rear side (that portion which mates
with the wall) of the mounting ange with
a suitable caulking compound or an ap­proved waterproof mastic sealer.
On masonry walls, attach the base ange
with lead cinch type anchors and a non­ferrous bolt. On sidings, use nonferrous lag bolts. Washers are recommended to be used under the bolt heads.
Table 2: Floating Hinge Parts List
Ref. # Description
1 Floating Hinge
2 Back Plate
3 Lifting Angle
4 Hold Down Lug (short)
5 Bottom Lug (long)
6 Thumb Screen
7 Plastic Washer for Screw
8 Metal Hold Washer for Screw
9 Retaining Clip
10 3/8”-16 X 1 1/2 Whiz Bolt
11 3/8”-16 Whiz Nut
12 1/2-3/8 X 3/8 Lg. Bushing
13 10-32 X 1/2 Whiz Bolt
14 10-32 Whiz Nut
2 PENNBARRY 1401 North Plano Road, Richardson, Texas 75081
Phone: 972-234-3202 Fax: 972-497-0441
Fumex Centrifugal Roof & Wall: Direct & Belt Drive Exhausters
Operation & Maintenance Manual
Positioning and Running Power Lines
ROOF MOUNTING
Power is normally brought from within the building through proper conduit lines and placed inside the curb. Feed power through the ventilator to the (Disconnect Switch or Junction Box) motor. Wiring can be brought through the cooling tube from the outside; this is the method to be used for NFPA96, as well as smoke controll systems installations if an external discon­nect junction box is not already provided.
WALL MOUNTING
Power is normally brought up from within the building through proper conduit lines to the wall opening, then fed to the (Discon­nect Switch or Junction Box) motor. Wiring can be brought through the cooling tube from the outside; this is the method to be used for NFPA96 installations if an exter­nal disconnect junction box is not already provided.
Start-Up and Operation
Carefully inspect the unit before startup. All motor bearings should be properly lu­bricated and all fasteners should be se­curely tightened. Rotate centrifugal wheel by hand to insure free movement. Before placing hand on centrifugal wheel or belts, lock out the power source. Check all set-screws and keys. Tighten when necessary. Check the condition of belts and the amount of tension prior to start-up. DO NOT overtighten, as bearing dam-age will occur.
Recommended belt tension should permit deection of 1/64” per inch of span. Exer­cise extreme care when adjusting belts as not to mis-align pulleys. Any misalignment will cause a sharp reduction in belt life and can produce excess belt noise. (see Fig­ure 4). On units equipped with two groove pulleys, adjust all belts with equal tension.
Figure 4: Pulley Alignment & Tension
WRONG WRONG CORRECT
Not to exceed 1/64” per inch of span
Belts must be adjusted after approx. 40 hours of operation.
Whenever belts are removed or
installed, never force belts over pulleys
without loosening motor rst to relieve
belt tension.
Make sure inlets and approaches to the unit are free from obstruction. To assure maximum air movement, make sure ad­equate supply air is available to ventilated space.
When power lines are brought up to the unit, provide a generous amount of slack to allow for motor adjustments and to per­mit movement of motor for belt tension ad­justments. Ground motor adequately and securely. Protect power lines from sharp objects. Do not kink power line or permit it to contact hot surfaces, chemicals, grease or oil. Use only UL recognized electrical parts, rated for proper voltage, load and environment.
Before putting fan into operation, complete the following check list:
a. Turn off and LOCK OUT
the power source.
b. Make sure installation
is in accordance with manufacturer’s instructions.
c. Check and tighten all fasteners.
d. Spin centrifugal wheel
to see if rotation is free.
e. Check all set-screws and keys:
tighten if necessary.
f. Torqued set screws have a colored
Torque Seal mark indicating the cor­rect torque has been applied.
g. Check belt or direct drive coupling
for alignment
h. Check belt for proper belt tension
i. Make sure there is no foreign or
loose material in ductwork leading to and from fan or in the fan itself.
j. Properly secure all safety guards.
k. Secure all access doors to fan
and ductwork.
l. Check line voltage with
motor nameplate.
m. Check wiring.
On single phase mot ors, t he t ermin al block must be set up in accordance with the name­plate instructions and/or wiring diagram. This set up must match the line voltage. If the mo­tor is multi-speed or multi-voltage, the wind­ing leads must be grouped and connected as shown on the motor wiring diagram. The line voltage must correspond with proper group­ing of motor leads. The wiring diagram must be followed explicitly or serious motor or starter damage will occur.
Do not operate models from line frequen­cies higher than 60Hz + or -5% with stan­dard motors.
The ventilator has been checked at the fac­tory prior to shipment for mechanical nois­es. If mechanical noises should develop:
a. Check rotating component for
adequate clearance and direction of rotation. See page 6 for the wheel alignment procedure. See top of plate for wheel direction.
b. Check proper belt tension
and pulley alignment.
c. Check installation and anchoring.
d. Check fan bearings.
e. Check that cooling tube is in place
and well sealed.
Incorrect rotation overloads motor severely and results in serious motor damage. To change rotation of three phase units, inter­change any 2 of the 3 line leads. On single phase units, change the terminal block set-up following the wiring diagram on the motor.
1401 North Plano Road, Richardson, Texas 75081 Phone: 972-234-3202 Fax: 972-497-0441
PENNBARRY 3
Operation & Maintenance Manual Fumex Centrifugal Roof & Wall: Direct & Belt Drive Exhausters
f. Check motor and bearing tempera-
ture for excessive heat.
Use care when touch-
ing the exterior of an operating motor. Modern motors normally run hot. They are designed to operate at higher temperatures. This is a normal con­dition but they may be hot enough to be painful or injurious to the touch.
If any problem is indicated, TURN OFF POWER TO UNIT IMMEDIATELY. Lock out the electrical supply, check carefully for the cause of the trouble and correct as needed. Even if the fan appears to be operating satisfactorily, shut down after a brief period and check all fasteners, set­screws and keys for tightness.
During the rst eight (8) hours of opera­tion, check the fan periodically for exces­sive vibration or noise. At this time, also check motor input current and motor bearing temperatures to insure that they do not exceed manufacturer’s recommen­dations. After eight hours of satisfactory operation, shut down the fan and lock out the electrical power to check the following items and adjust if necessary:
a. All set-screws, keys and fasteners.
b. Belt alignment.
c. Belt tension.
Maintenance
Do not attempt maintenance on the fan until the electrical supply has been com­pletely disconnected. If a disconnect switch has not been provided, remove all fuses from the circuit and lock the fuse panel so they cannot be accidentally re­placed.
Lubrication is a primary maintenance re­sponsibility. Check all bearings periodi­cally. Inspect belts for tightness. If the fan is installed in a corrosive or dirty atmo­sphere, periodically clean the centrifugal wheel, inlet, motor housing and other moving parts.
FAN SHAFT LUBRICATION
Fan shaft bearing pillow blocks are fur­nished in either the pre lubricated sealed­for-life type or the greasable type. The prefabricated type requires no servicing for 7 to 10 years of normal use. Follow the lubricating schedule recommended by the factory. This practice should not super­sede any safety considerations.
Use low pressure
grease guns only. High pressure guns tend to blow out or unseat bearing seals, leaving the bearing open to collect grime, dust and foreign particles.
LUBRICATION SCHEDULE
Always follow the bearing manufacturer’s recommended lubrication schedule. If none is available use the following gen­eral schedule.
a. Under average conditions where
ambient temperatures do not exceed 120°F, lubrication is required 1 to 2 times a year.
b. Under dirt laden atmosphere where
there is a temperature range of 120°F to 150°F, lubrication is required from 3 to 6 times a year.
c. Under extreme temperature condi-
tions and extremely dirty atmos­pheres, lubrication should be sched­uled at least once or twice a month.
d. Belt drive units maximum tempera-
ture should not exceed 160°F. Direct driven models have tempera­ture range stamped on motor.
MOTOR LUBRICATION
In general, standard motors are furnished with prelubricated, sealed-for-life ball bear­ings which require no lubrication for 7 to 10 years of normal service. Where motors have been ordered with greasable bear­ings, these bearings are factory lubricated and require no attention for one year under
normal conditions. If grease relief ttings
are provided, remove them when perform-
ing maintenance to allow grease to ow
out. Whenever possible, apply grease while the motor is running. This practice should not supersede any safety consider­ations. DO NOT OVER-GREASE, as most lubricants deteriorate motor windings, thereby reducing motor life.
Table 3: Recommended Lubricants
Manufacturer Product Temp. Range
BP LG-#P-1
Gulf Gulfcrown EP-1
Imperial Oil Unirex EP-1
Shell Alvania R-1
BP
Gulf Gulfcrown EP-2
Imperial Oil Unirex EP-2
Shell Alvania R-3
Sun Oil Sun Prestige 42
Texaco Regal AFB2
Energrease,
MPMK11
Below 32°F
(0°C)
32°F to 150°F
(0°C to 66°C)
Guards
All fans have moving parts which require guarding in the same way as other moving machinery.
Where the fan is accessible to untrained per­sonnel or the general public, use maximum safety guards, even at the cost of some performance loss. Unprotected fans locat-
ed less than 7’ above the oor also require guarding as specied in the Occupational
Safety and Health Act (OSHA). PennBarry strongly recommends the use of guards on all exposed nonducted fans, ceiling and wall mounted.
Centrifugal fans may be connected directly to ductwork which will prevent contact with the internal moving parts, but when the in­let or outlet is exposed, install a suitable guard.
Replacement Parts
Replace parts with components which du­plicate original parts correctly. Incorrectly sized shafts, belts, pulleys, etc. can damage the fan.
Spare or replacement parts and prices are available upon request. Please supply the following information: Factory Order Num­ber, Customer’s Name and Order Number and Date. If this information is not available, furnish a complete description of the part re­quired. Names of parts are shown on page 7. To order motors provide the HP, RPM, volt­age, phase, hertz and type of enclosure.
4 PENNBARRY 1401 North Plano Road, Richardson, Texas 75081
Phone: 972-234-3202 Fax: 972-497-0441
Loading...
+ 7 hidden pages