PennBarry SX User Manual

Page 1
WWW.PENNBARRY.COM
©PENNBARRY 2009
24
PENNBARRY
TM
Centrifugal Inline Fans
e n
t r e x
I
n
l
i n e r
Engineering Specifications
›
Model
SX = Centrifugal Fan
›
Unit Size
085 100 120 155 205 275 420
095 115 125 165 225 335
›
Drive Type
D = Direct Drive B = Belt Drive
›
Motor Tap
QC = 1550 RPM RC = 1300 RPM SC = 1050 RPM
VC = 1650 RPM
Q1C = 1725 RPM Q2C = 1725 RPM
›
Motor Speed
1 = Single Speed
2 = 2S2W 1800/1200 3 = 2S1W 1800/900
›
Horse Power
1/50 1/12 1/5 3/4 3 1/30 1/11 1/4 1 5 1/25 1/7 1/3 1 1/2 7 1/2 1/20 1/6 1/2 2 10
›
Enclosure
0 = Open Drip Proof
T = Totally Enclosed
E = Explosion Proof
X = Special
›
Voltage
A = 110V G = 230V N = 440V B = 115V H = 240V P = 460V C = 120V J = 277V Q = 480V D = 200V K = 380V R = 575V E = 208V L = 400V S = 600V F = 220V M = 415V X = Special
›
Phase
1 = Single
3 = Three
›
Cycle
5 = 50 Hz 6 = 60 Hz
›
Efficiency
S = Standard
H = High Efficiency
›
Paint / Coating
0 = None
F = Epoxy Powder Coat* G = Epoxy Powder Coat with UV* H = Hi-Temp Powder Coat* J = Non-stick Powder Coat* K = Phenolic Powder Coat* L = Phenolic Powder Coat with UV*
N = Polyester Powder Coat X = Special
* Not available with choice of color.
›
Color
0 = None
50 = Chrome Green 53 = Williamsburg Blue
55 = Pale Green
56 = Dove Gray 61 = White 63 = Oxford Beige 65 = Dover White 66 = Desert Tan 70 = Black 73 = Smoke Gray 77 = Brick Red
79 = Peppercorn 81 = Pale Brown
83 = Chocolate Brown 85 = Timeless Bronze 94 = Charcoal
X = Special
›
Damper
0 = None
BDD = Gravity Backdraft Damper
X = Special
›
Aluminum Housing
0 = None A = Aluminum Housing
›
Motor Cover
0 = None M = Motor
›
Inlet Angle Ring
0 = None R = Ring
›
Inlet Guard
0 = None G = Guard
›
Support Channel
0 = None
S = Support Channel
›
Extended Lube Lines
0 = None
L = Extended Lube Lines
›
Sound Insulation
0 = None
G = Gasket
›
Vibration Isolation
0 = None
RF = Rub in Shear Floor RH = Rub in Shear Hanger SC = Supp. Chann w/ Rubber Floor
SF = Spring Floor SH = Spring Hanger
›
Thermal Overload Protection
0 = None
P = Thermal Overload Protection
›
Disconnect Switch
0 = None 1 = Nema 1 3R = Nema 3R 4 = Nema 4 7 = Nema 7 9 = Nema 9
›
Internal Wiring
0 = None 1 = Nema 1 3R = Nema 3R
›
Transformer
0 = None T = Transformer
›
Speed Controller
0 = None L = Loose M = Mounted
›
Firestat Switch
0 = None
F = Switch
›
High Pressure Wheel
0 = None
H = High Pressure Wheel
Configuration
Centrex Inliner
Page 2
WWW.PENNBARRY.COM
©PENNBARRY 2009
PENNBARRY
25
TM
Centrifugal Inline Fans
e n
t r e x
I n
l
i n e r
Specifications
Centrex Inliner
›
Direct Drive Fans
›
Belt Drive Fans
Direct drive Centrifugal Square Inline fan shall be Centrex Inliner SX, manufactured by PennBarry, Richardson, TX 75081. The housing shall utilize galvanized steel “corner post” framework and panels. Units shall be equipped with three removable access panels. Units shall be pre-wired to a junction box on the exterior and equipped with an electrical disconnect switch (not Explosion Proof). Two support angles shall be provided.
Statically and dynamically balanced backward inclined centrifugal wheels shall be aluminum, spark-resistant, nonoverloading, and matched to deeply spun venturis. Motors shall be continuous duty, permanently lubricated, multispeed (for applicable models), have thermal overload protection, mounted out of the main airstream (except Totally Enclosed), be easily accessible for service, and furnished at the specified voltage, phase, and enclosure. Each fan shall bear the AMCA Licensed Ratings Seal for Air and Sound Performance, and shall be UL
and CSA listed.
Belt driven Centrifugal Square Inline fan shall be Centrex Inliner SX, manufactured by PennBarry, Richardson, TX 75081. The housing shall utilize galvanized steel (aluminum optional some sizes) “corner post” framework and panels. Units shall be equipped with three removable access panels. Units shall be pre-wired to a junction box on the exterior and equipped with an electrical disconnect switch (not Explosion Proof). Two support angles shall be provided.
Statically and dynamically balanced backward inclined, centrifugal wheels shall be aluminum, spark-resistant, nonoverloading, and matched to deeply spun venturis. Motors shall be continuous duty, ball bearing design, permanently lubricated, mounted out of the main airstream, and furnished at the specified voltage, phase, and enclosure. Shafts shall be turned, ground and polished. Heavy duty ball bearings are rated for a minimum L50 life exceeding 200,000 hours. Pulleys shall be adjustable, cast iron, machined, keyed, securely attached, and sized for 150% of the horsepower at its rated maximum speed. Each fan shall bear the AMCA Licensed Ratings Seal for Air and Sound Performance, and shall be UL and CSA listed.
Engineering Specifications