PennBarry PNB User Manual

Sample Specifications - PND/PNB
1.1 Fans shall be tested and rated in accordance with AMCA air and sound methods and standards.
1.2 Fans shall conform to AMCA 99 Standards.
1.3 All motors and electrical components shall comply to NEMA, UL or other governing body.
Panel Fan
Belt Drive - Series PNB
PRODUCT
2.1 The fan shall be of an axial flow propeller, panel fan mount, belt driven configuration.
2.2 The fan shall be belt driven with the motor mounted directly in the air stream.
2.2.1 The drive sheaves shall be cast iron with appropriately sized and aligned belt to attain 1.5 service factor.
2.3.1 The fan panel shall have an integrally die formed, deep shroud for smooth air entry into the propeller.
2.3.2 The fan’s motor and bearing support consist of a rigid steel formed structure welded directly to the fan panel.
2.4 The fan shaft shall be steel, ground for precision fit to bearings and keyed for driving the impeller and drive sheave.
2.5 Fan bearings shall be cast iron housing, self-aligning ball, re-lubricatable bearings.
2.5.1 Fan bearings shall have a minimum L by AFBMA of 35,000 hours.
2.6 The propeller shall be constructed of cast aluminum blades fastened directly to a cast aluminum hub assembly. The hub is designed to incorporate a taper lock bushing and keyed directly to the fan shaft.
2.7 The motor mounting base is configured to allow for various frame sizes and designed to allow for belt tension adjustment.
2.8 The fan mounting panel assembly shall be coated with enamel as standard or optional other available coating as made available by coating suppliers and as indicated on the fan schedule. The propeller is uncoated.
2.9 The final complete fan assembly is vibration tested and balanced as per AMCA 204, grad BV-3.
3.0 The motor shall be of a typical NEMA-T frame type and typical with the motor industry. The electric motor shall be as indicated on the fan schedule and as available from the motor vendors.
PRINCIPALS AND FUNCTIONS
4.1 Fan performance rating shall be based on methods as developed by AMCA standard 210.
4.2 Form, function and application of the fan shall be as defined by ASHRAE, AMCA and SMACNA in regard to air system design in compatibility with the fan.
ACCESSORIES
5.1 The fan shall have front and/or rear safety guards as indicated on the fan schedule.
5.2 The fan shall be of a fixed, reversed air flow configuration with a double entry bell on the fan panel as indicated on the fan schedule.
5.3 The fan shall be of a reversible air flow configuration for supply or exhaust with a double entry bell on the fan panel as indicated on the fan schedule.
life as defined
10
Direct Drive - Series PND
PRODUCT
2.1 The fan shall be of an axial flow propeller, panel fan mount, direct driven configuration.
2.2 The fan shall be direct driven with the propeller mounted to the motor shaft.
2.3.1 The fan panel shall have an integrally die formed, deep shroud for smooth air entry into the propeller.
2.3.2 The fan’s motor support consist of a rigid steel formed structure welded directly to the fan panel.
2.4 The propeller shall be constructed of cast aluminum blades fastened directly to a cast aluminum hub assembly. The hub is designed to incorporate a taper lock bushing and keyed directly to the motor shaft.
2.5 Fan mounting panel assembly shall be coated with enamel as standard or optional other available coating as made available by coating suppliers and as indicated on the fan schedule. The propeller is uncoated.
2.6 The final complete fan assembly is vibration tested and balanced as per AMCA 204, grad BV-3.
2.7 The motor shall be of a typical NEMA-T frame type and typical with the motor industry availability. The electric motor shall be as indicated on the fan schedule and is available from the motor vendors.
PRINCIPALS AND FUNCTIONS
3.1 Fan performance rating shall be based on methods as developed by AMCA standard 210.
3.2 Form, function and application of the fan shall be as defined by ASHRAE, AMCA and SMACNA in regard to air system design in compatibility with the fan.
ACCESSORIES
4.1 The fan shall have front and/or rear safety guards as indicated on the fan schedule.
4.2 The fan shall be of a fixed, reversed air flow configuration with a double entry bell on the fan panel as indicated on the fan schedule.
4.3 The fan shall be of a reversible air flow configuration for supply or exhaust with a double entry bell on the fan panel as indicated on the fan schedule.