PennBarry C25, MV250, C75, C45, MV750 Installation Instructions Manual

...
INSTALLATION INSTRUCTIONS
MV75-2ERV
SUPERSEDES 10-05-11
JUNE 4, 2012
EN ERGY RE COV ERY WHEEL
INSTALLATION INSTRUCTIONS FOR MINI VENTILATOR (MV) WITH FACTORY INSTALLED OPTIONS
(LOW AMBIENT, ROTATION SENSOR AND CLIMATE SMART [PATENT PENDING])
USED AS A STAND ALONE OR WITH SPLIT SYSTEMS UNITS
Energy recovery COMPONENT certified to the AHRI Air-to-Air Energy Recovery Ventilation Equipment Certification Program in accordance with AHRI Standard 1060-2000. Actual performance in packaged equipment may vary.
ETL Certified per UL 1995 and CSA 22.2
I - Ship ping And Pack ing List
Package 1 of 1 contains:
1 - Mini Ventilator Assembly (See Figure 1)
II - Ship ping Dam age
Check unit for shipping damage. Receiving party should contact last carrier immediately if shipping damage is found.
III - Gen eral
IV - Re quire ments
When installed, the unit must be electrically wired and grounded in accordance with local codes or, in the absence of local codes, with the current National Electric Code, ANSI/NFPA No. 70.
V - Ap pli ca tion
Mini Ventilators (MV) are used as stand alone. These ventilators conserve energy by mixing warmer air with cooler air in the following manner:
Re cov ery Wheel Mode
The Recovery Wheel mode is accomplished by two blowers providing continuous exhaust of stale indoor air and replacement by equal amount of outdoor air. Energy recovery is achieved by slowly rotating the energy recovery wheel within the cassette frame work. In winter, the MV adsorbs heat and moisture from the exhaust air stream during one half of a complete rotation and gives them back to the cold, drier intake air supply during the other half rotation. In summer, the process is automatically reversed. Heat and moisture are absorbed from incoming intake air supply and transferred to the exhaust air stream. This process allows outdoor air ventilation rates to be increased by factors of three or more without additional energy penalty or increase in size of heating or air conditioning systems.
VI - Rig ging Unit For Lift ing
1. Maximum weight of unit is
Model# C25 / MV250 C45 / MV450 C75 / MV750
Net Weight 195 195 225
Ship Weight 215 215 261
2. Remove carton.
3. All panels must be in place for rigging.
CAUTION
Danger of sharp metallic edges. Can cause injury. Take care when servicing unit to avoid accidental contact with sharp edges.
WARNING
Electric shock hazard. Can cause injury or death. Before attempting to perform any service or maintenance, turn the electrical power to unit OFF at disconnect switch(es). Unit may have multiple power supplies.
Figure 1
PAGE 1
VII - In stal la tion
The unit can be installed using two different intakes general configurations. The unit is shipped in horizontal intake configuration. Please refer to the following diagrams for installation instructions:
Note: All duct work and flex connectors are field supplied.
A - Hor i zon tal Configuration Duct Work In stal la tion
1. Attach Flexible Duct Collar to the MV fresh air intake and secure with screws. See Figure 2.
2. Attach fresh air supply duct work to fresh air supply Flexible Duct Collar and secure with screws. See
Figure 2.
3. Attach Flexible Duct Collar return air exhaust and secure with screws. See Figure 2.
4. Attach return air exhaust duct work to return air exhaust Flexible Duct Collar and secure with screws.
See Figure 2.
RE TURN AIR EX HAUST
RE TURN AIR EX HAUST
FLEX I BLE DUCT COLLAR
DUCT WORK
RE TURN AIR INTAKE
FLEX I BLE DUCT COLLAR
RE TURN AIR INTAKE
DUCT WORK
FRESH AIR INTAKE
FRESH AIR INTAKE DUCT WORK
FLEX I BLE DUCT COLLAR
Figure 3
4. Attach return air exhaust duct work to return air exhaust Flexible Duct Collar and secure with screws.
See Figure 2.
5. Remove fresh air intake duct collar from lateral intake.
See Figure 4.
6. Remove return air intake duct collar from lateral intake. See Figure 4.
FRESH AIR SUPPLY
FRESH AIR SUPPLY DUCT WORK
FLEX I BLE DUCT COLLAR
Figure 2
5. Attach Flexible Duct Collar to MV fresh air intake and secure with screws. See Figure 3.
6. Attach fresh air intake duct work to fresh air intake Flexible Duct Collar and secure with screws. See
Figure 3.
7. Attach Flexible Duct Collar to return air intake and secure with screws. See Figure 3.
8. Attach return air intake duct work to return air intake Flexible Duct Collar and secure with screws. See
Figure 3.
B - Top/Bottom Configuration Duct Work Installation
1. Attach Flexible Duct Collar to the MV fresh air intake and secure with screws. See Figure 2.
2. Attach fresh air supply duct work to fresh air exhaust Flexible Duct Collar and secure with screws. See
Figure 2.
3. Attach Flexible Duct Collar return air exhaust and secure with screws. See Figure 2.
7. Remove cover panel from top fresh air intake. See
Figure 4.
8. Remove cover panel from bottom return air intake.
See Figure 4.
RE TURN AIR INTAKE
DUCT COLLAR
FRESH AIR INTAKE
COVER PANEL
FRESH AIR INTAKE DUCT COLLAR
Figure 4
RETURN AIR INTAKE COVER PANEL
9. Attach fresh air duct collar to top fresh air intake and secure with provided screws. See Figure 5.
10. Attach return air duct collar to bottom return air intake and secure with provided screws. See Figure 5.
11. Attach fresh air cover panel to lateral fresh air intake and secure with provided screws. See Figure 5.
12. Attach return air cover panel to lateral return air intake and secure with provided screws. See Figure 5.
PAGE 2
RE TURN AIR IN TAKE
COVER PANEL
FRESH AIR IN TAKE
DUCT COL LAR
FRESH AIR INTAKE COVER PANEL
Figure 5
RE TURN AIR INTAKE DUCT COLLAR
13. Attach Flexible Duct Collar to the MV fresh air intake and secure with screws. See Figure 6.
14. Attach fresh air intake duct work to fresh air intake Flexible Duct Collar and secure with screws. See
Figure 6.
15. Attach Flexible Duct Collar to return air intake and secure with screws. See Figure 6.
16. Attach return air intake duct work to return air intake Flexible Duct Collar and secure with screws. See
Figure 6.
FRESH AIR IN TAKE
DUCT WORK
FRESH AIR IN TAKE
FLEX I BLE DUCT COL LAR
VIII - Op er a tion
How It Works
The unit contains an Mini Ventilator that is a new concept in a rotary air-to-air heat exchanger. Designed as a packaged unit for ease of installation and maintenance, only connection of electrical power is required to make the system operational. The concept consists of a unique rotary energy recovery wheel that rotates in and out of fresh air streams within a heavy duty, permanently installed blower cabinet that provides ready access to all internal components. The Energy Recovery Wheel contains spirally wound polymeric material that is coated and permanently bonded with a silica gel desiccant for transfer of sensible and latent heat. The wheel is belt driven by one motor and stretch urethane perimeter drive belt.
When slowly rotating through counter flowing exhaust and intake air streams the MV adsorbs sensible heat and latent heat from the warmer air stream and transfers this total energy to the cooler air stream during the second half of its rotating cycle. Rotating the wheel provides constant flow of energy from warmer to cooler air stream. The large energy transfer surface and laminar flow through the wheel causes this constant flow of recovered energy to represent up to 85% of the difference in total energy contained within the two air streams.
Sensible and latent heat are the two components of total heat. Sensible heat is energy contained in dry air and latent heat is the energy contained within the moisture of the air. The latent heat load from the outdoor fresh air on an air conditioning system can often be two to three times that of the sensible heat load and in the winter it is a significant part of a humidification heat load.
During both the summer and winter, the MV transfers moisture entirely in the vapor phase. This eliminates wet surfaces that retain dust and promote fungal growth as well as the need for a condensate pan and drain to carry water.
Because it is constantly rotating when in the air stream, the MV is always being cleared by air, first in one direction then the other. Because it is always dry, dust or other particles impinging on the surface during one half cycle, are readily removed during the next half cycle.
RE TURN AIR INTAKE
FLEX I BLE DUCT COLLAR
RE TURN AIR INTAKE
DUCT WORK
Figure 6
PAGE 3
In the heating season, when outdoor air temperatures are below 10oF, it is recommended to use the (optional) low ambient kit (factory installed 02 models only). At these conditions you will need to determine the frost threshold parameters.
The frost threshold is the outdoor temperature at which frost will begin to form on the MV wheel. For energy recovery ventilators, the frost threshold is typically below 10oF. Frost threshold is dependent on indoor temperature and humidity. The table shows how the frost threshold temperatures vary depending on indoor conditions.
FROST THRESH OLD TEM PER A TURE
IN DOOR RH AT 70oF
FROST THRESH OLD
TEM PER A TURE
20% 0oF 30% 5oF 40% 10oF
Because Mini Ventilators have a low frost threshold, frost control options are not necessary in many climates. Where outdoor temperatures may drop below the frost threshold during the MV operational hours, exhaust only frost control option is available.
IX - Standard Features
Low Am bi ent Kit
Extremely cold outdoor air temperatures can cause moisture condensation and frosting on the energy recovery wheel (ERW). The outside temperature below which frost will begin to accumulate is referred to as the Frost Threshold Temperature, and is a function of both the indoor DB temperature and the indoor relative humidity See Table #2. Frost formation causes reduction of airflow through the ERW; therefore, without frost control, energy recovery and airflow may be significantly reduced.
A thermostat control is provided to shut down the supply blower when outdoor temperature drops to a field-selected frost control setting. The thermostat is located within the outdoor air intake hood. To avoid depressurization of the conditioned space, automatic or pressure operated fresh air dampers may be required as part of the ventilation system. Factory setting is 20oF.
FROST THRESH OLD TEM PER A TURE (OD DB)
IN DOOR
RH (%)
20
30
40
50
60
IN DOOR DB TEMPERATURE
70oF 72oF 75oF 80oF
-14 -13 -11 -8
-3 -2 -1 3
5 7 9 11
13 13 15 18
18 19 21 26
Table #2
Rotation Sensor
The circuit indicates the absence of pulses, within a specified time range, provided by a magnetic sensor detecting a magnet mounted on wheel surface. After the initial time delay of approximately 5 seconds from circuit power up, if the sensor fails to provide a signal pulse (no wheel rotation) within approximately 5 additional seconds, the alarm relay will activate the latch (until circuit powers down) providing a 5 amp contact closure output. This would indicate no wheel rotation and/or magnet in the system has stopped at the magnetic sensor pickup point. If the pulse (wheel rotation) is detected within the approximately 5 second time period, the alarm relay will remain open. No field timing adjustment of any type will be required.
of the circuit board. The following diagram details the jumper location for each mode of operation:
Temperature Control (See Figure 7)
The temperature mode of operation incorporates one sensor located in the fresh air intake of the ERV. The Start Stop Jog sequence is activated when the outside air temperature is between 70°F and 40°F. The SSJ module provides two potentiometers in order to adjust the Low and High temperature range of the start stop jog sequence. To adjust the High temperature range, place a Multimeter on the COM and HIGH test points. Use a screw driver to adjust the potentiometer to the desired VDC representing the temperature. The Low temperature range is adjusted by placing a Multimeter on the COM and LOW test points with the adjustment of the potentiometer to the desired VDC representing temperature. The VDC can be calculated for a desired temperature using the following formula: VDC = 0.1429 x (Temperature) - 5.7143.
Figure 7
Enthalpy Control (See Figure 8)
The enthalpy mode of operation incorporates one enthalpy sensor located in the fresh air intake of the ERV. The SSJ module compares the outdoor enthalpy to a preselected set point. The value of the set point can be identified on a psychometric chart with the standard control curves as A, B, C or D. The set point can be selected as an aggressive set point A for higher levels of free cooling or a conservative set point D for lower levels of free cooling. The Enthalpy sensor provides a 4-20 mA (0-100%) signal proportional to the selected control curve A, B, C, or D. The SSJ module begins the start stop jog sequence when the Enthalpy sensor reports 60%. The Enthalpy 60% setpoint for each control curve is detailed in the following table:
Climate Smart [Patent Pending]
There are three modes of control strategies available. Temperature, Single Enthalpy, or Enthalpy and Temperature control.
Mode of Operation
The mode of operation is selected with the adjustment of a jumper. The jumper is located at the lower center position
Figure 8
PAGE 4
Loading...
+ 7 hidden pages