PennBarry HF User Manual

WWW.PENNBARRY.COM
©PENNBARRY 2008
14
PENNBARRY
Hi-Ex Roof Ventilators
TM
H
i
­E x
Engineering Specifications
Engineering Specifications
Model
HC = Standard Height; Cast Aluminum Propeller HF = Standard Height; Cast Aluminum Propeller;
AMCA Certied
HX = Standard Height; Fabricated Steel Propeller HS = HiteSaver; Cast Aluminum Propeller HZ = HiteSaver; Fabricated Steel Propeller
Unit Size
24 36 48 60 30 42 54 72
Drive Type
D = Direct Drive B = Belt Drive
Motor Tap
M = 690 RPM Q = 1750 RPM Q1 = 1750 RPM Q2 = 1750 RPM T = 1140 RPM T1 = 1140 RPM T2 = 1140 RPM T3 = 1140 RPM W = 860 RPM W1 = 860 RPM W2 = 860 RPM W3 = 860 RPM
Motor Speed
1 = Single Speed 2 = 2S2W 1800/1200 3 = 2S1W 1800/900
Horse Power
1/4 3/4 2 7 1/2 1/3 1 3 10 1/2 1 1/2 5 15 0 = None X = Special
Enclosure
O = Open Drip Proof T = Totally Enclosed E = Explosion Proof X = Special
Voltage
B = 115V E = 208V P = 460V D = 200V G = 230V R = 575V X = Special
Phase
1 = Single 3 = Three
Cycle
5 = 50 Hz 6 = 60 Hz
Efciency
S = Standard P = Premium
Paint / Coating
0 = None B = Epoxy* C = Heresite* D = Heresite with UV* Q = Enamel* X = Special
* Not available with choice of color.
Color
0 = None 00 = Standard Gray 50 = Chrome Green 53 = Williamsburg Blue 55 = Pale Green 56 = Dove Gray 61 = White 63 = Oxford Beige 65 = Dover White 66 = Desert Tan 70 = Black 73 = Smoke Gray 77 = Brick Red 79 = Peppercorn 81 = Pale Brown 83 = Chocolate Brown 85 = Timeless Bronze 94 = Charcoal X = Special
AMCA Spark Rating
0 = None C = Standard B = Optional
Damper
0 = None BDD = Gravity Backdraft Damper MD1 = Gravity Backdraft Damper 115V MD2 = Gravity Backdraft Damper 230V MD4 = Gravity Backdraft Damper 460V ED1 = Explosion Proof Motor Operated Damper 115V
Screen
0 = None B = Bird Screen S = Insect/Bird Screen
Roof Curb
0 = None J = SCA16 T = UA12 A = UCG8 K = UCA18 U = UA18 B = UCG12 L = UG12 V = UG18 C = UCG18 M = SA16 W = URA12 D = UCA8 N = SFG12 Y = URA18 E = UCA12 P = SFG18 1 = URG12 F = SFA12 Q = SG16 2 = URG18 G = SFA18 R = SRA16 H = SCG16 S = SRG16
Slope
0 = None S = Single D = Double
Metal Liner
0 = None L = Metal Liner
Damper Holding Plate
0 = None P = Damper Holding Plate
Neoprene Gasket
0 = None G = Gasket
No Wooden Nailer
0 = None N = No Wooden Nailer
Curb Paint/Coating
0 = None B = Air Dried Epoxy Q = Air Dried Enamel X = Special
Thermal Overload Protection
0 = None P = Thermal Protection
Disconnect Switch
0 = None 3R = Nema 3R Disconnect Switch 4 = Nema 4 Disconnect Switch 7 = Nema 7 Disconnect Switch 9 = Nema 9 Disconnect Switch X = Special
Internal Wiring
0 = None 3R = Nema 3R Internal Wiring 4 = Nema 4 Internal Wiring X = Special
Firestat Switch
0 = None F = Firestat Switch
Extended Lube Lines
0 = None E = Lube Lines
Aluminum Housing
0 = None H = Aluminum
Roof Pitch Adapters
0 = None S = Single Slope D = Double Slope
WWW.PENNBARRY.COM
©PENNBARRY 2008
PENNBARRY
15
TM
H
i
­E x
Engineering Specifications
Hi-Ex Roof Ventilators
Engineering Specifications
Remote Drive with Cover
0 = None C = Remote
Belt / Bearing Cover
0 = None B = Cover
Mag Damper Latch
0 = None L = Latch
Inlet Guard
0 = None G = Guard
Heat / Smoke Kit
0 = None H = Heat / Smoke
Helper Spring
0 = None H = Helper Spring
Torsion Spring
0 = None T = Torsion Spring
› HC
Direct Drive Units
Direct Drive Axial Upblast Roof exhaust fan shall be Hi-Ex HC, manufactured by PennBarry; Richardson, TX 75081.
Units shall be weather resistant and designed to withstand prevailing wind velocities. A heavy gauge galvanized motor mounting panel shall be securely fastened to heavy gauge galvanized air­shaft. Airshaft shall be welded to a heavy gauge galvanized base with welded cor­ners, pre-punched mounting holes, and a deeply spun venturi. A ribbed reinforced galvanized windband shall be securely fastened to air shaft and shall include
automatic buttery dampers which open
and close with the start and stop of the fan. No portion of fan shall protrude be­low the roof line.
Statically and dynamically balanced pro­pellers shall be cast aluminum and airfoil shaped. Motors shall be continuous duty, ball bearing design, positively cooled,
and furnished at the specied voltage
and phase.
› HX
Direct Drive Units
Direct Drive Axial Upblast Roof exhaust fan shall be Hi-Ex HX, manufactured by PennBarry; Richardson, TX 75081.
Units shall be weather resistant and designed to withstand prevailing wind velocities. A heavy gauge galvanized motor mounting panel shall be securely fastened to heavy gauge galvanized air­shaft. Airshaft shall be welded to a heavy gauge galvanized base with welded cor­ners, pre-punched mounting holes, and a deeply spun venturi. A ribbed reinforced galvanized windband shall be securely fastened to air shaft and shall include
automatic buttery dampers which open
and close with the start and stop of the fan. No portion of fan shall protrude be­low the roof line.
Statically and dynamically balanced pro­pellers shall be cast aluminum and airfoil shaped. Motors shall be continuous duty, ball bearing design, positively cooled,
and furnished at the specied voltage
and phase.
Belt Drive Units
Belt Drive Axial Upblast Roof exhaust fan shall be Hi-Ex HC, manufactured by PennBarry; Richardson, TX 75081.
Units shall be weather resistant and designed to withstand prevailing wind velocities. A heavy gauge galvanized motor mounting panel shall be securely fastened to heavy gauge galvanized air­shaft. Airshaft shall be welded to a heavy gauge galvanized base with welded cor­ners, pre-punched mounting holes, and a deeply spun venturi. A ribbed reinforced galvanized windband shall be securely fastened to air shaft and shall include
automatic buttery dampers which open
and close with the start and stop of the fan. No portion of fan shall protrude be­low the roof line.
Statically and dynamically balanced pro­pellers shall be cast aluminum and airfoil shaped. Motors shall be continuous duty, ball bearing design, positively cooled,
and furnished at the specied voltage,
phase, and enclosure. Shafts shall be turned, ground, polished, and rust pro­tected. Pulleys shall be adjustable, cast iron, machined, keyed, securely at­tached, and sized for 150% of the horse­power at its rated maximum speed.
Belt Drive Units
Belt Drive Axial Upblast Roof exhaust fan shall be Hi-Ex HX, manufactured by PennBarry; Richardson, TX 75081.
Units shall be weather resistant and designed to withstand prevailing wind velocities. A heavy gauge galvanized motor mounting panel shall be securely fastened to heavy gauge galvanized air­shaft. Airshaft shall be welded to a heavy gauge galvanized base with welded cor­ners, pre-punched mounting holes, and a deeply spun venturi. A ribbed reinforced galvanized windband shall be securely fastened to air shaft and shall include
automatic buttery dampers which open
and close with the start and stop of the fan. No portion of fan shall protrude be­low the roof line.
Statically and dynamically balanced pro­pellers shall be cast aluminum and airfoil shaped. Motors shall be continuous duty, ball bearing design, positively cooled,
and furnished at the specied voltage,
phase, and enclosure. Shafts shall be turned, ground, polished, and rust pro­tected. Pulleys shall be adjustable, cast iron, machined, keyed, securely at­tached, and sized for 150% of the horse­power at its rated maximum speed.
WWW.PENNBARRY.COM
©PENNBARRY 2008
16
PENNBARRY
Hi-Ex Roof Ventilators
TM
H
i
­E x
Engineering Specifications
Engineering Specifications
› HZ
Direct Drive Units
Direct Drive Axial Low Contour Upblast Roof exhaust fan shall be Hi-Ex HZ, manufactured by PennBarry; Richardson, TX
75081. Units shall be weather resistant and designed to withstand pre-
vailing wind velocities. A heavy gauge galvanized motor mount­ing panel shall be securely fastened to a ribbed reinforced galvanized windband. Windband shall be securely attached to a heavy gauge galvanized base with welded corners, pre­punched mounting holes, and a deeply spun venturi, and shall
include automatic buttery dampers which open and close with
the start and stop of the fan. Statically and dynamically balanced propellers shall be cast alu-
minum and airfoil shaped. Motors shall be continuous duty, ball
bearing design, positively cooled, and furnished at the specied
voltage, phase, and enclosure.
Belt Drive Units
Belt Drive Axial Low Contour Upblast Roof exhaust fan shall be Hi-Ex HZ, manufactured by PennBarry; Richardson, TX 75081.
Units shall be weather resistant and designed to withstand pre­vailing wind velocities. A heavy gauge galvanized motor mount­ing panel shall be welded and securely fastened to a ribbed reinforced galvanized windband. Windband shall be securely attached to a heavy gauge galvanized base with welded cor­ners, pre-punched mounting holes, and a deeply spun venturi,
and shall include automatic buttery dampers which open and
close with the start and stop of the fan. Statically and dynamically balanced propellers shall be cast alu-
minum and airfoil shaped. Motors shall be continuous duty, ball
bearing design, positively cooled, and furnished at the specied
voltage, phase, and enclosure. Shafts shall be turned, ground, polished, and rust protected. Pulleys shall be adjustable, cast iron, machined, keyed, and securely attached, and sized for the 150% of the horsepower at its rated maximum speed.
› HF
Belt Drive Units
Belt Drive Axial Upblast Roof exhaust fan shall be Hi-Ex HF, manufactured by PennBarry; Richardson, TX 75081.
Units shall carry UL705 listing and be CSA certied. Units shall
be weather resistant and designed to withstand prevailing wind velocities. A heavy gauge galvanized motor mounting panel shall be securely fastened to heavy gauge galvanized airshaft. Airshaft shall be welded to a heavy gauge galvanized base with welded corners, pre-punched mounting holes, and a deeply spun venturi. A ribbed reinforced galvanized windband shall be securely fastened to air shaft and shall include automatic butter-
y dampers which open and close with the start and stop of the
fan. No portion of fan shall protrude below the roof line. Statically and dynamically balanced propellers shall be of fab-
ricated steel. Motors shall be continuous duty, ball bearing de-
sign, positively cooled, and furnished at the specied voltage,
phase, and enclosure. Shafts shall be turned, ground, polished, and rust protected. Pulleys shall be adjustable, cast iron, ma­chined, keyed, securely attached, and sized for 150% of the horsepower at its rated maximum speed.
› HS
Belt Drive Units
Belt Drive Axial Low Contour Upblast Roof exhaust fan shall be Hi-Ex HS, manufactured by PennBarry; Richardson, TX
75081. Units shall be weather resistant and designed to withstand pre-
vailing wind velocities. A heavy gauge galvanized motor mount­ing panel shall be welded and securely fastened to ribbed reinforced galvanized windband. Windband shall be securely attached to a heavy gauge galvanized base with welded cor­ners, pre-punched mounting holes, and a deeply spun venturi,
and shall include automatic buttery dampers which open and
close with the start and stop of the fan. Statically and dynamically balanced propellers shall be heavy
gauge steel. Motors shall be continuous duty, ball bearing de-
sign, positively cooled, and furnished at the specied voltage,
phase, and enclosure. Shafts shall be turned, ground, polished, and rust protected. Pulleys shall be adjustable, cast iron, ma­chined, keyed, securely attached, and sized for 150% of the horsepower at its rated maximum speed.
Each model HS fan shall bear the AMCA Licensed Ratings Seal for Air and Sound Performance (30-48), and shall be UL (UL Std. 705, UL Std. 793 optional).
If specied, Heat and Smoke option, fan shall additionally pro­vide UL 793 Listing (500ºF for 4 hrs./1000ºF for 15 min.), ped­estal mounting, remote motor mounting, and damper springs activated by fusible links.
Loading...