PennBarry | Your Single Source for Commercial & Industrial Supply & Exhaust Fans | www.pennbarry.com
Page 2
TABLE OF CONTENTS
INTRODUCTION 3
CERTIFICATIONS & LISTINGS 4
FEATURES & BENEFITS 5-6
OPTIONS & ACCESSORIES 7-12
MOTOR AVAILABILITY 13-14
DIRECT DRIVE | DIMENSIONS 15
BELT DRIVE | DIMENSIONS 16
FAN SELECTIONS 17-18
www.PennBarry.com 2
Page 3
INTRODUCTION
Fumex Series of Centrifugal Fans
Fumex centrifugal fans are designed for medium to high pressure applications and are available in a range of capacities. They can be
either roof or wall mounted. While suitable for general ventilation, Fumex fans are specically designed to discharge contaminated or
grease-laden air or fumes up and away from building surfaces. The optional “Fatrap” (UL762) restaurant grease exhaust conguration
(see Fatrap Conguration) makes Fumex fans particularly suited for all food service applications and chemical fume hoods. The optional
heat and smoke removal conguration (see Smoke Removal) makes Fumex fans especially prepared for heat and smoke control systems.
The optional high wind construction makes Fumex fans well-tted for high wind hurricane zones.
Fumex fans feature a weather-resistant, seamless spun aluminum housing which provides ample drainage and works in conjunction
with a patented wheel design and deeply spun inlets to provide smooth quiet airow through the ventilator. The centrifugal wheels are
aluminum, non-overloading, backward inclined, robotically welded, and dynamically balanced.
Direct Drive Units
Model: FX (V/S/R/Q/Q1/Q2)
• Static pressure up to 1.5” wg.
• Flow capacity up to 4,489 CFM.
• Fatrap (FT) option available on sizes 13, 16, and 18.
• High Wind Construction (-HW) option available.
High Pressure Belt Drive Units
Model: FX (BH)
• Static pressure up to 3.0” wg.
• Flow capacity up to 8,623 CFM.
• Fatrap (FT) option available.
• Heat & Smoke Removal (-HS) option available.
• High Wind Construction (-HW) option available.
www.PennBarry.com 3
Centrex Direct Drive
Standard Duty Belt Drive Units
Model: FX (B)
• Static pressure up to 2.5” wg.
• Flow capacity up to 21,511 CFM.
• Fatrap (FT) option available.
• Heat & Smoke Removal (-HS) option available.
• High Wind Construction (-HW) option available.
Page 4
CERTIFICATIONS & LISTINGS
AMCA Certications
PennBarry certies that the Fumex direct drive and belt drive models FX, FXBH, and FXBHFT shown herein are licensed
to bear the AMCA Seal. The ratings shown are based on tests and procedures performed in accordance with AMCA
Publication 211 and Publication 311 and comply with the requirements of the AMCA Certied Ratings Program. FX27B
is not AMCA Certied.
cULus Certication
Fumex fans carry the UL label, UL705 (ZACT/ ZACT7), le #E28413. Fumex fans with the “Fatrap” option carry the UL
label, UL762 (YZHW/ YZHW7), le #MH10684. Fumex fans with the heat and smoke removal option carry the UL label,
UL793 (ZAXH/ZAXH7), le #MH19473
Both direct drive and belt drive models are available with a wide range of voltages and enclosures (see Motor Selection for a complete
listing). Standard belt drive Open Drip Proof (ODP) ball bearing motors are selected using a conservative portion of the NEMA service
factor. Standard direct drive ODP motors have Class B insulation and internal overload protection. Overload protection is available as an
option on belt drive models. Each size is carefully engineered to match the motor to the wheel capacity.
Sound Performance
Fumex units deliver outstanding air performance with minimal noise and have the lowest AMCA licensed sound performance in the
industry.
Curb Caps (Base)
Curb caps for direct drive and standard duty belt drive models are available in galvanized steel (standard) or aluminum (optional). Curb
caps for high capacity belt drive models are available only in aluminum. All curb caps have fully welded corners and are pre-punched to
ensure a leak-tight and easy installation.
Forced Motor Cooling
Motors and drive components are located out of the airstream in a separate compartment. A cooling tube between the motor dome and
discharge apron enables fresh air to be drawn into the motor housing during fan operation. This positive cooling promotes longer life
for motor and drive components.
Easy Maintenance Access
By removing the fasteners, the motor dome lifts o for complete access to all the drive components.
Vibration Isolators
Multidirectional, rubber-in-shear vibration isolators mitigate residual vibration transmission from the unit to the building.
Structural Integrity
Durable housings of spun aluminum have a high strength-to-weight ratio and incorporate a rolled bead for additional strength. There
are no welds to break or seams to leak. The heavy-gauge motor mounting platform provides positive rigidity between all components
of the power train assembly.
Internal Bracing
Tri-Strut™ supports transfer the weight of the motor mounting platform directly to the curb mounting surface. The aluminum spun
housing, therefore, is not used to support any weight. For grease laden applications, there is less surface for grease build-up during
normal operation.
Solid Steel Shafts
Sized so the rst critical speed is a minimum of 130% of maximum cataloged operating speed, shafts are precision ground and polished.
Self-Aligning Bearings
Heavy-duty bearings are sized for a minimum L50 life in excess of 200,000 hours of operation. One hundred percent factory tested, they
are designed for air handling applications.
Drives and Belts
Pulleys are pre-set to the specied RPM. Cast iron variable pitch pulleys are adjustable, allowing for eld balancing based on actual eld
conditions. All pulleys are sized for at least 150% of the driven horsepower.
Conduit
Both direct and belt drive units include a large 1” nominal conduit chase (not available on heat and smoke removal units; wiring is run via
the cooling tubes) for easy installation of wiring from the motor dome to below the curb cap. Fatrap units are factory wired to an external
NEMA 3R junction box.
www.PennBarry.com 5
Page 6
FEATURES & BENEFITS
Reverse Venturi
Reverse venturi reduces turbulence and improves distribution of the air as it enters the wheel
inlet and is “captured” by the blades.
Wheels
Fumex fans oer patented wheel designs. Carefully matched, highly-tooled venturis enhance the performance of these backward inclined
and non-overloading centrifugal wheels. Made of advanced aluminum alloys, the various wheel components provide superior strength
and durability, as well as spark resistant construction. The heat and smoke removal conguration utilizes steel construction.
Silent Wheel (Direct Drive)
• Blades’ highly curved leading edges provide unsurpassed low sound numbers with excellent
air performance.
• Backplate and inlet are stamped for consistency, plus dynamic balancing ensure smooth,
vibration-free operation.
• Riveted or riveted and welded construction ensure superior dependability over other wheel
designs.
Standard Duty, All Welded Wheel
(Standard Duty & High Pressure Belt Drive)
• Blades are curved for improved air performance while increasing their strength and rigidity.
• Backplate and inlet are stamped for consistency. They include a perimeter rim which enhances strength and improves balancing.
• Wheel assembly is robotically welded to provide extremely durable and consistent performance.
• Wheel is dynamically balanced. Balancing weights are mechanically attached to the inside of the rims of both the backplate and
wheel inlet. This allows a precise placement of the weights anywhere within a full 360º range on two separate planes, without the
possibility of detachment.
Enhanced Direct Drives
These enhanced units have Gplus™ motor selection up to 2 HP (available on single phase and three phase) and are available up to size
24. Design enhancements to Direct Drive Fumex models signicantly improve air performance, while Gplus™ EC motors oer higher
eciency, and quieter, more reliable operation. Combined with PennBarry’s patented, backward inclined, centrifugal wheel, these fan
units deliver low noise and high eciency performance.
Internal Wiring
All direct and belt drive models with ODP motors feature a polarized disconnect plug which is factory wired from the motor to the
junction box. This provides a positive method of electric shut-o as required by most codes without requiring the traditional disconnect
switch. In addition, weather resistant NEMA 3R wiring is available for selection.
www.PennBarry.com 6
Page 7
OPTIONS & ACCESSORIES
Spare Belt
One or two extra sets of spare belts are available for selection.
iQ Controllers
There are two types of iQ controllers available:
• iQ-IPCM (Intelligent Pressure Control Module), with Duct Sentry™ technology is designed to maintain constant pressure 24/7 within
a duct system by controlling fan motor speed
• iQ-MS (Multi-Speed Controller), with dual set-point interface allows the user to set and remotely switch among two dierent motor
speeds.
Both of them provide motor control signal output of 0-10 VDC for seamless integration with today’s advanced motor technologies to
provide substantial energy savings and peace of mind.
Extend Lube Lines
Preloaded at the factory, lube lines allow bearing maintenance when easy access to the bearings is unavailable.
Stainless Steel Hardware
If another material is desired for the unit’s hardware, stainless steel hardware is available for selection.
Variable Frequency Drives
Variable frequency drives (VFDs) are designed to meet performance requirements while increasing eciency. By varying the fan
motor input frequency and voltage, the VFD controls the motor speed and torque, helping to improve productivity and lower energy
consumption. The VSC and VSA are ideal for both new and retrot fan applications. Shipped loose and separately.
0-10 Output Potentiometer
Potentiometers are always paired with Green Plus motors. With the potentiometer, the Green Plus motors can be turned down to as low
as 80% the max operating speed while maintaining 90% eciency through the operating range. Additionally, the Green Plus can accept
0-10V input to tie to building management systems, not only allowing for savings in direct fan energy consumption but reducing the
exhaust of conditioned air during o peak hours as well
Stainless Steel Shaft
If another material is desired for the motor shaft, stainless steel shafts are available for selection.
Transformers
To meet local requirements 277V transformers are available for all direct drive units. The transformers are step-down and will step the
voltage down to 120V. Shipped loose for eld installation.
Finishes
Coatings such as Polyester Powder Coat, Epoxy Powder Coat, Phenolic Epoxy Powder Coat, and others are available. See the coatings
brochure for details.
www.PennBarry.com 7
Page 8
OPTIONS & ACCESSORIES
Mounting Pedestal
The 12” high mounting pedestal, available in aluminum or galvanized steel, incorporates a removable access panel for easy inspection
and service of motor operated backdraft dampers. It provides solid ventilator support and a weather resistant seal that does not injure or
disturb ashing. This item should not be used with Fatrap units.
Hinged Sub-Base
Hinged sub-bases provide access to the curb well for damper service or the clean out for grease applications. Constructed with a rust
proof hinge arrangement and low height, (3 ½”) the assembly is easily manipulated and reduces the impact on overall installation height.
This accessory is available for use with most models for either factory built or existing roof curbs.
Fumex
Base
Floating Hinge Kit
A oating hinge kit is also available for eld installation. This assembly connects
the exhauster directly to the roof curb and provides the same level of access as
the hinged sub-base.
Floating Hinge Plate
Back Plate
(Inside Curb/Pedestal)
Ventilator
Curb/Pedestal
Bushing
Aluminum Bird & Insect Screen
Bird screens are available for all direct and belt drive models. An aluminum insect screen with a smaller mesh than the standard bird
screen is also available. However, please note that NFPA 96 installations do not allow the use of bird or insect screens. The requirements
of local codes must be reviewed to determine if there are any conicts.
Internal Wiring
NEMA 3R wiring is available for both direct and belt drive models.
Backdraft Dampers
Backdraft dampers are available for either gravity or motorized operation (motor kit optional). Dampers feature square galvanized steel
frames and multi-leaf, roll formed aluminum blades with nylon bearings. Backdraft dampers should not be used when venting kitchen
hoods. NFPA 96 installations do not allow the use of dampers. The requirements of local codes must be reviewed to determine if there
are any conicts.
Safety Service Switch
Safety service switches are available to allow positive electrical shut-o and
safety. Switches are factory mounted when factory wiring is requested. Wiring
is only run from the motor to the junction box. (Factory wiring of explosion
proof applications is not available.) A wide range of NEMA rated enclosures
with service switches are available for indoor, outdoor, and explosion proof
installations. Service switches are to be eld wired by a licensed electrician.
Firestat Switch
Firestat switch automatically disconnects the unit when the temperature of the
air being exhausted exceeds a preset rating.
www.PennBarry.com 8
Page 9
OPTIONS & ACCESSORIES
Time-Delay Switch
(For select direct drive models only) The Airminder Model AM12 switch is a
UL recognized and CSA certied time-delay relay that operates both the fan
and room light to ventilate an area even after the occupants depart. In the
“On” position, the Airminder turns the light and fan on immediately. In the “O”
position, the light goes o immediately, and the fan is in operation for a period
of time as preset from 1 to 60 minutes. Suitable only for 1/3 HP maximum at
120/1/60.
Speed Controllers
The Lek-TrolTM controller allows adjustment in speed to a maximum of 50%
reduction, which results in a very cost eective means for system balancing. The
device can be located under the fan dome to prevent unauthorized tampering
or on the wall for ease of operation by the building occupants. (Available on
direct drive units with ODP motors and some select TE motors. See reference
table under Motor Availability)
Automatic Belt Tensioner
The factory mounted Automatic Belt Tensioner accessory eliminates the need for re-tensioning the belt after start-up. It is constructed
from 10 gage galvanized steel and incorporates ve torsion springs to automatically position the motor and maintain proper belt tension.
Additional benets include reduced belt and pulley wear and simplied belt replacement without tools. The Automatic Belt Tensioner is
available for Fumex models FX08B, FX10B, FX12BH, FX13B,
FX13BHFT and FX14B with 1/4, 1/2, 3/4, and 1 HP ODP motors. It can also be used with 1.5 HP, 3-phase ODP motors.
Spark Resistant Construction
AMCA ‘B’ construction is available as standard construction on direct drive units and as an option on belt drive units (not available on heat
and smoke removal units). If required, an explosion proof motor and service switch may be selected as options.
Wall Mounting
This option is provided as a separate product line, whose models include a “W” prex. Product line includes models up to size 24, motors
up to 2HP, and round bases (not available on heat and smoke removal units).
Prefabricated Curb
A variety of sizes of prefabricated roof curbs are available. Galvanized steel unibeam curbs are the most popular. For a complete listing
of all curb types and sizes available, see the latest PennBarry Ventilation Curb brochure. Please note that NFPA 96 installations require a
specic curb height. See Fatrap conguration on the next page.
www.PennBarry.com 9
Page 10
OPTIONS & ACCESSORIES
Fumex Curb
w/Cant
T (s q.)
Vented S elf
Fl ashing
18 " MIN.
1 1 /2"
H
Standa rd
R o (sq.)
A (sq.)
ModelE
FX08S/R18.5172598.7518
FX10S/R18.5172511.511.2518
FX11V/S/R/Q18.5172511.511.2518
FX13V/S/R/Q18.5172511.511.2518
FX16V/S/R/Q1/Q220.519271615.7518
FX18V28.527352019.7518
FX08B to FX14B24.7523.2531.251615.7518
FX12BH24.7523.2531.251615.7518
FX13BHFT24.7523.2531.251615.7518
FX16B and FX18B28.527352019.7518
FX18BH28.527352019.7518
FX24B33.532402524.7518
FX24BH33.532402524.7518
FX27B and FX30B36.535432827.7518
FX36B44.543513635.518
(4)
SQT
(2)
SQA SQRo(3) SQDamper Size SQGalv. Steel Gauge
Standard heights “H” are 8”, 12”, and 18” including wood nailer. ”T” dimension of curb is 1 1/2” less than the dimension of inside base of fan (“E”). “Ro”
refers to Roof Opening. “E” dimension is inside base of fan. For FT (Fatrap) units, curbs are cantless, 18” high and optionally vented.
Exploded View
SAFETY
DISCONNECT
SWITCH
ALUMINUM
BIRD AND INSECT
SCREEN
HINGED
SUB-BASE
PREFABRICATED
CURB
BACKDRAFT
DAMPER
www.PennBarry.com 10
Page 11
OPTIONS & ACCESSORIES
Fatrap Conguration
Fatrap congured fans are ideal for use in commercial kitchens over grilles, charcoal broilers, deep fat fryers, steam tables, ranges,
dishwashers, and other appliances. Fumex fans are specially congured for food service applications with the addition of a group of
accessories that either meets a requirement or eases installation requirements according to NFPA 96. NFPA 96 “Standard for Ventilation
Control and Fire Protection of Commercial Cooking Operations” is the generally recognized authority nationwide for restaurant installation
requirements. However, local codes may vary.
Included in the units are the following.
• UL 762 Listing: Fatrap congured Fumex fans are listed at 400°F — 100°F higher than UL requirements. The high temperature rating
is the result of the fan’s highly ecient forced motor cooling capability. Three direct drive (sizes 13 – 18) and all belt drive models are
listed.
• Pre-wired Junction Box: A weather-proof junction box is factory wired and mounted to the housing exterior. An appropriately sized
service switch is commonly selected as an additional option. These items meet the code requirements for positive electric shut-o.
• Grease Collector/Separator Box: Designed for easy installation, the grease is routed from a single swiveling collection spout to an
amply sized durable galvanized steel box, trapping grease and residue and avoiding discharge onto the roof surface. Additionally,
these boxes separate the water from the grease, prolonging the time required between periodic maintenance.
Additional Fatrap Accessories
Ventilated Curbs and Pedestals: For buildings two stories or higher NFPA 96 requires the use of ventilated mounting curbs or pedestals to
provide an approved arrangement for connecting a range hood and duct work to the roof fan. PennBarry’s ventilated mounting curbs and
pedestals, 18” high, comply with that standard when properly installed. Ventilated curbs have a at mounting ange for fastening directly
to the roof deck. This ange should be securely fastened and ashed to ensure weather tightness. Ventilated pedestals are designed to
t on an existing curb. They provide cap ashing when so installed.
ADDITIONAL
COOLING TUBE
STEEL WHEEL
PREFABRICATED
CURB
www.PennBarry.com 11
Page 12
OPTIONS & ACCESSORIES
Heat & Smoke Removal Conguration
While Fumex fans are commonly used for general ventilation, they are also designed to discharge contaminated or grease-laden air
or fumes up and away from building surfaces with the Fatrap option. When equipped with the Heat and Smoke Removal option, this
series of fans incorporates features exclusively designed to exhaust heat and smoke in the event of re. During these emergencies, the
fans are designed to operate at the temperature and time limits stated below. To maintain power to these fans during emergencies,
special consideration must be made for eld power supply. In the event of an emergency, if power is maintained, the units will operate
for the times and temperatures indicated, after which they will continue to operate until they are destroyed by the extreme temperature
generated during an actual re, or their roof structure collapses.
For smoke control systems, Heat and Smoke Removal congured fans are listed per UL for emergency smoke removal, referencing UL705,
UL793, Industrial Risk Insurers (IRI), and Southern Building Code Congress International (SBCCI).
The UL standard requires the fan to run at 500°F for 4 hours (IRI) and 1000°F for 15 minutes (SBCCI). PennBarry Heat and Smoke Removal
congured Fumex units are listed at 500°F for 4 hours and 1000°F for 1 hour. The additional 45 minutes at 1000°F will buy precious time
in the event of a re.
Steel Wheel: The wheel is a standard duty, all-welded wheel (standard duty and high pressure belt drive). The blades are curved for
improved air performance while increasing their strength and rigidity. The wheel assembly is fully welded to provide extremely durable
and consistent performance. The wheel is dynamically balanced. Balancing weights are mechanically attached to the inside of the rims
of both the backplate and wheel inlet. This allows a precise placement of the weights anywhere within a full 360° range on two separate
planes, without the possibility of detachment.
Forced Motor Cooling: Motors and drive components are located out of the airstream in a separate compartment. Two cooling tubes
are located between the motor dome and discharge apron which enables fresh air to be drawn into the motor compartment during fan
operation. This allows the cooler outside air to wash over the motor and bearings. This positive cooling promotes longer life for the motor
and drive components.
High Wind Construction
High wind construction Fumex fans are specically designed for high wind hurricane zones (HWHZ). The Fumex models are designed
to withstand 150 MPH winds in accordance with Miami-Dade and Florida Building Code standards. The units are 3rd party tested and
certied through a 3rd party Professional Engineer (P.E.) to meet these strict standards. Installation details are provided and since there are
no tie downs or external braces required for attaching the unit to the roof or curb this makes installation simple and easy. A wide range
is oered to meet all of your ventilation needs which includes all belt and direct drive sizes 36 and under.
Belt Drive Fumex CutawayDirect Drive Fumex Cutaway
Product Certications:
18) Miami-Dade NOA # 14-0311.03
19) Florida Product Approval #12339
20) Texas Department of Insurance # RV-48
www.PennBarry.com 12
Page 13
MOTOR AVAILABILITY
Green Plus Electronically Commutated Motor
The Green Plus (GP) option utilizes EC motors to provide signicantly greater
eciency, exibility, and controllability over standard direct drive permanent split
capacitor (PSC) motors. Using the included potentiometer, the Green Plus motors
can be turned down to as low as 80% the max operating speed while maintaining
90% eciency through the operating range. Additionally, the Green Plus can accept
0-10V input to tie to building management systems, not only allowing for savings in
direct fan energy consumption but reducing the exhaust of conditioned air during
o peak hours as well. All Green Plus motors come in open enclosure for usage with
115V-208V/230V, single phase, 50/60 Hz applications.
G
plus
ModelHP
FX08VGP1/6-XX
FX08S/RGP1/6-XX
FX08QGP1/6-XX
FX10VGP1/6-XX
FX10S/RGP1/6-XX
FX10QGP1/6-XX
FX11V/S/RGP1/6-XX
FX11QGP1/4-XX
FX13V/S/RGP1/6-XX
FX13QGP1/4-XX
FX16VGP1/6-XX
FX16S/RGP1/3XXX
FX16Q1GP1/2XXX
FX16Q2GP3/4X-X
FX18VGP3/4XXX
ODP
110-120V
1-Phase
TE
110-120V
208-480V
TE
www.PennBarry.com 13
Page 14
MOTOR AVAILABILITY
Variable Speed Motor Control
PennBarry oers Lek-Trol™ solid state controllers to alter the high speed of most direct drive motors by as much as 50%. If variable speed
is required, check the Lek-Trol™ availability table below to verify that controllers exist for the fan model selected. Remember, Lek-Trol™
controllers are currently only available for direct drive motors including all standard Open Drip Proof (ODP) 60 Hz motors. Not all totally
enclosed motors are currently available with variable speed control. Inverter rated motors suitable for use with variable frequency drives
can be supplied for belt drive models. Contact your local PennBarry representative for availability.
Available Lek-Trol™ Speed Controls
60 Hz50 Hz
Model
FX08S--------
FX08RLT25-------
FX10S--------
FX10RLT30LT30LT35LT35LT35LT30LT35LT35
FX11V--------
FX11S--------
FX11RLT30-------
FX11QLT50-------
FX13V--------
FX13S--------
FX13RLT30LT30LT35LT35LT35LT50LT35LT35
FX13QLT45LT50LT35LT35LT35LT50LT35LT35
FX16V--------
FX16S--------
FX16RLT50-------
FX16Q1LT40-------
FX16Q2LT75-------
FX18VLT60-------
Lek-Trols™ indicated for multi-speed models (eg., FX16V/S/R) are applicable only for the high speed. Do not use on low or medium speed for multi-speed
models. Items noted with ( - ) are not applicable.
ODPTotally EnclosedTotally Enclosed
115V115V200V208V230V110V220V240V
www.PennBarry.com 14
Page 15
DIRECT DRIVE | DIMENSIONS
L DIA
Fumex direct drive models are available with single and multi-speed motors.
A single Fumex fan may be made suitable for several requirements by a simple wiring change. This feature provides exibility for a variety
of reasons, including energy savings, o hours requirements, future expansion, or unexpected eld variations. When compared to belt
drive models, direct drive fans require less maintenance, have a simpler construction, cost less, and are lighter in weight.
Fumex direct drive models are available in six sizes (8, 10, 11, 13, 16, and 18). Their capacities are up to 4500 CFM, with static pressures up
1 = 380V/1PH/50HZ
2 = 400V/1PH/50HZ
3 = 415V/1PH/50HZ
4 = 460V/1PH/60HZ
B = 110V/1PH/50HZ*
C = 115V/1PH/60HZ
D=120V/1PH/60HZ*
F = 208V/1PH/60HZ
G = 208V/3PH/60HZ
H = 220V/1PH/50HZ*
J = 220V/3PH/50HZ*
K = 230V/1PH/60HZ
L = 230V/3PH/60HZ
M = 240V/1PH/50HZ*
N = 240V/3PH/50HZ*
P = 277V/1PH/60HZ*#
Q = 380V/3PH/50HZ*
R = 380V/3PH/60HZ*
S = 400V/3PH/50HZ*
T = 415V/3PH/50HZ*
U = 440V/3PH/50HZ*
V = 460V/3PH/60HZ
W = 480V/3PH/60HZ*
X = Special
Y = 575V/3PH/60HZ
* Non-standard offering subject to
longer lead times and price adjustment
# 277V applications require a
transformer
www.PennBarry.com 17
Page 18
FAN SELECTIONS
Electrical Accessories
Controllers
0 = None
A = 0-10V output potentiometer
1 = Lek-Trol solid state speed
controller (mounted)
2 = Lek-Trol solid state speed
controller (loose)
3= Multi speed controller, iQ-MS
(ECM only)
4 = iQ-IPCM-no power supply (ECM
only)
5 = iQ-IPCM with 115V/230V power
supply (ECM only)
6 = iQ-IPCM with 277V power supply
(ECM only)
Options and Accessories
Construction Accessories
0 = None
A = Aluminum curb cap (standard)
F = Floating hinge kit (aluminum base)
G = Floating hinge kit (steel base)
H = Hinged sub-base (aluminum base)
J = Hinged sub-base (steel base)
S = Steel curb cap
W = Wall mounted adaptor
Curb
0 = None
C = Curb
Note: Curbs ordered separately on all
PLOPs
Damper
00 = None
D = Damper
XX = Special
Extended Lube Lines
0 = None
L = Extended lube lines
Guard/Screen
0 = None
B = Bird screen
Paint/Coating
0 = None
F = Epoxy powder coat (light gray)
7 = Provided by others
V = VFD (belt drive only)
Note: VFD can be ordered separately
Service Switches and ITW*
0 = None
1 = NEMA 1 ITW only
3 = NEMA 3R ITW only
A = NEMA 1 - loose
C = NEMA 1 - mounted and wired
D = NEMA 3R - loose
F = NEMA 3R - mounted and wired
G = NEMA 4 - loose
N = NEMA 7 - loose
Q = NEMA 9 - loose
G = Epoxy powder coat with UV
protection (gray)
H = Hi-temp powder coat (black)
J = Non-stick powder coat (clear)
K = Phenolic epoxy powder coat
(gray)
L = Phenolic epoxy powder coat with
UV protection (gray)
N = Polyester powder coat*
X = Special
* Colors only available in Polyester
Powder Coat
Paint Color*
00 = None
50 = Chrome green
55 = Pale green
56 = Dove gray (PPC standard)
61 = White
63 = Oxford beige
65 = Dover white
66 = Desert tan
70 = Black
73 = Smoke gray
77 = Brick red
79 = Peppercorn
81 = Pale brown
83 = Chocolate brown
85 = Timeless bronze
94 = Charcoal
X = Special
* Colors only available for polyester
powder coat
X = Special
* ITW - Internal wiring not provided on
explosion proof motors
Switches / Sensors
0 = None
A = Airminder switch (time delay)
B = Airminder+restat
F = Firestat switch
Transformer
0 = None
B = 277Vx115V
Pedestal
0 = None
A = Galvanized pedestal
B= Galvanized vented pedestal
C = Aluminum pedestal
D = Aluminum vented pedestal