PennBarry FMX User Manual

TM
Engineering Specifications
Fumex
Configurations
Model
FX = Centrifugal Fan WFX = Wall Mounted Centrifugal Fan FMX = High Capacity Centrifugal Fan
Unit Size
08 11 13 16 24 30 50 10 12 14 18 27 36
Drive Type
D = Direct Drive B = Belt Drive
Motor Tap
Q = 1725 RPM R = 1550 RPM S = 1300 RPM V = 1050 RPM Q1 = 1650 RPM Q2 = 1725 RPM
Motor Speed
1 = Single Speed 2 = 2S2W Single & Three Phase 3 = 2S1W Three Phase
Horse Power
1/50 1/12 1/5 3/4 3 1/30 1/11 1/4 1 5 1/25 1/7 1/3 1 1/2 7 1/2 1/20 1/6 1/2 2 10
Enclosure
O = Open Drip Proof T = Totally Enclosed E = Explosion Proof X = Special
Voltage
A = 110V G = 230V N = 440V B = 115V H = 240V P = 460V C = 120V J = 277V Q = 480V D = 200V K = 380V R = 575V E = 208V L = 400V S = 600V F = 220V M = 415V X = Special
Phase
1 = Single 3 = Three
Cycle
5 = 50 Hz 6 = 60 Hz
Efciency
S = Standard H = High Efciency
©PENNBARRY 2009
Paint / Coating
Sizes 08 - 36
0 = None F = Epoxy Powder Coat* G = Epoxy Powder Coat with UV* H = Hi-Temp Powder Coat* J = Non-stick Powder Coat* K = Phenolic Powder Coat* L = Phenolic Powder Coat with UV* N = Polyester Powder Coat X = Special
* Not available with choice of color.
Size 50
0 = None B = Epoxy* C = Heresite* D = Heresite with UV* Q = Enamel* X = Special
* Not available with choice of color.
Color
0 = None 50 = Chrome Green 53 = Williamsburg Blue 55 = Pale Green 56 = Dove Gray 61 = White 63 = Oxford Beige 65 = Dover White 66 = Desert Tan 70 = Black 73 = Smoke Gray 77 = Brick Red 79 = Peppercorn 81 = Pale Brown 83 = Chocolate Brown 85 = Timeless Bronze 94 = Charcoal X = Special
AMCA Spark Rating
0 = None C = Standard B = Optional
Damper
0 = None BDD = Gravity Backdraft Damper MD1 = Gravity Backdraft Damper 115V MD2 = Gravity Backdraft Damper 230V MD4 = Gravity Backdraft Damper 460V ED1 = Explosion Proof Motor Operated Damper 115V
Screen
0 = None B = Bird Screen S = Insect/Bird Screen
Roof Curb
0 = None K = UCA18 V = UG18 A = UCG8 L = UG12 W = URA12 B = UCG12 M = SA16 Y = URA18 C = UCG18 N = SFG12 1 = URG12 D = UCA8 P = SFG18 10 = SFA8 E = UCA12 Q = SG16 11 = USCG F = SFA12 R = SRA16 12 = USCA G = SFA18 S = SRG16 2 = URG18 H = SCG16 T = UA12 4 = UVA18 J = SCA16 U = UA18 5 = UVG18
Slope
0 = None S = Single D = Double
Metal Liner
0 = None L = Metal Liner
Damper Holding Plate
0 = None P = Damper Holding Plate
Neoprene Gasket
0 = None G = Gasket
No Wooden Nailer
0 = None N = No Wooden Nailer
Curb Paint/Coating
B = Air Dried Epoxy Q = Enamel
Hinged Sub-base
0 = None H = Hinged Sub-base
Mounting Pedestal
0 = None P = Mounting Pedestal
Floating Hinge Kit
0 = None H = Floating Hinge Kit
Aluminum Base
0 = None A = Aluminum Base
Thermal Overload Protection
0 = None P = Thermal Overload Protection
Continued, next page.
Centrifugal Fans
m
WWW.PENNBARRY.COM
PENNBARRY
27
TM
Engineering Specifications
Fumex
Engineering Specifications
Disconnect Switch
0 = None 1 = Nema 1 Disconnect Switch 3R = Nema 3R Disconnect Switch 4 = Nema 4 Disconnect Switch 7 = Nema 7 Disconnect Switch 9 = Nema 9 Disconnect Switch
Internal Wiring
0 = None
Centrifugal Fans
1 = Nema 1 Internal Wiring 3R = Nema 3R Internal Wiring
Transformer
0 = None T = Transformer
Speed Controller
0 = None L = Loose M = Mounted
Firestat Switch
0 = None F = Firestat Switch
Fatrap
0 = None F = Fatrap
Heat & Smoke Removal
0 = None
-HS = Heat & Smoke Removal
Wall Mount
0 = None W = Wall Mount
High Pressure Wheel
0 = None H = High Pressure Wheel
High Wind Construction
0 = None M = Miami Dade Approved
Belt Drive Fans
Belt drive centrifugal roof exhaust upblast fan shall be Fumex FX/FMX, manufactured by PennBarry, Richardson, TX 75081. The housing shall be weatherproof, utilize heavy-gauge spun aluminum construction with a large rolled bead for strength, with galvanized (aluminum optional except FMX) base, with rigid galvanized steel internal support structures. Housing shall not provide any of the internal structural support. Large diameter cooling tube shall provide ambient air to ow over motor. Units shall be equipped with an oversized electrical conduit chase through the curb cap and into the motor compartment for ease of wiring (except Explosion Proof). Units shall be prewired to a junction box mounted in the motor compartment and equipped with an electrical disconnect device (except Explosion Proof).
Statically and dynamically balanced backward inclined, centrifugal wheels shall be
aluminum, spark-resistant, nonoverloading, and be matched to deeply spun ven-
turis. Motors shall be continuous duty, ball bearing design, permanently lubricated, mounted out of the main airstream, and furnished at the specied voltage, phase, and enclosure. Shafts shall be turned, ground and polished. Heavy duty ball bearings are rated for a minimum L50 life exceeding 200,000 hours. Pulleys shall be adjustable, cast iron, machined, keyed, securely attached, and sized for 150% of the horsepower at its rated maximum speed. Each fan shall bear the AMCA Certied Ratings Seal for Air and Sound Performance (FX) or for Air performance (FMX), and shall be UL (UL Std. 705, UL Std. 762 optional) and CSA listed. If specied (Fatrap option), fan shall additionally provide UL 762 Listing rated at 400º F. (300º F. FMX), motor pre-wired to a weather-proof junction box, and drain connection leading into a grease collector/ separator box. If specied (heat and smoke removal option), fan shall additionally provide UL listing rated for 500°F at 4-hours and 1000°F at 1 hour, including steel wheel and additional cooling tube.
Direct Drive Fans
Direct drive centrifugal roof exhaust upblast fan shall be Fumex FX, manufactured by PennBarry, Richardson, TX 75081. The housing shall be weatherproof, utilize heavy
gauge spun aluminum construction with a large rolled bead for strength, with galva­nized (aluminum optional) base, with rigid galvanized steel internal support struc-
tures. Housing shall not provide any of the internal structural support. Units shall be equipped with an oversized electrical conduit chase through the curb cap and into the motor compartment for ease of wiring (except Explosion Proof). Units shall be pre-wired to a junction box mounted in the motor compartment and equipped with an electrical disconnect device (except Explosion Proof).
Statically and dynamically balanced backward inclined, centrifugal wheels shall be aluminum, spark-resistant, nonoverloading, and matched to deeply spun venturis. Motors shall be continuous duty, permanently lubricated, multispeed (for applicable models), have thermal overload protection, mounted out of the main airstream, be
easily accessible for service, and furnished at the specied voltage, phase and en­closure. Each fan shall bear the AMCA Certied Ratings Seal for Air and Sound Per-
formance, and shall be UL (UL Std. 705, UL Std. 762 optional applicable models) and CSA listed. If specied (Fatrap option), fan shall additionally provide UL 762 Listing
rated at 400º F., motor pre-wired to a weather-proof junction box, and drain connec-
tion leading into a grease collector/separator box.
m
28
PENNBARRY
Product Conguration
Reference PennBarry’s selection software to congure a Fumex product today.
WWW.PENNBARRY.COM
©PENNBARRY 2009
Loading...