Sample Specifications
AXD/AXB - Axcentrix Bifurcator Fan
1.1 Fans shall be tested and rated in accordance with AMCA air and sound methods and standards.
1.2 All motors and electrical components shall comply with NEMA, UL or other governing group.
Belt Drive
PRODUCT
2.1 Fan shall be of axial/centrifugal, mixed flow type,
configuration.
2.2 Fan shall be belt drive and sized for 1.5 service factor.
Motor is mounted internally but out of airstream.
2.3 Fan housing shall be of all welded construction with
a flanged inlet and outlet, and shall be constructed
completely of carbon steel, stainless steel (type 316
or 304) or aluminum as specified on fan schedule.
2.3.1 The fan housing shall have an integrally designed
removable section to allow for impeller inspection or
removal while the fan assembly remains installed.
2.3.2 The fan shall be capable of supporting additional duct
stack height of up to 20 feet if the application requires
such due to building envelope, local codes or regional
codes. Additional stack shall be properly guy wired.
2.4 Motor shall be separated from the air stream and is
located in an easily accessible and visible chamber. This
chamber bifurcates the fan housing and the air stream.
2.5 When required, the fan shall be equipped to be capable
of continuous operation at 250°F, 450°F, 750°F, 900°F or
1000°F, as indicated on the fan schedule.
2.5.1 The fan shall perform at the elevated temperatures
without any additional external cooling fans other than
its own integral mounted cooling wheels.
2.6 Impeller shall be of mixed flow type consisting of welded
construction that shall be of carbon steel, stainless steel
or aluminum, as indicated on the fan schedule.
2.6.1 Impeller shall produce an operation curve that does not
produce any dip in the fan curve, with stable operation
over its full curve operating range.
2.7 The electric motor shall be as specified on fan schedule
and is available in any enclosure as made available
from the motor vendors. The motor shall be of a typical
NEMA-T frame type and standard in nature with the
motor industry and is readily available, unless specified
otherwise due to application warranting such.
2.8 Fan shall be of AMCA spark resistant construction when
required and as indicated on the fan schedule as either
AMCA “A”, “B” or “C”.
2.9 Fan shall be coated with air dry enamel as standard or
any other available coating as made available by coating
suppliers and as indicated on the fan schedule.
2.10 The final complete fan assembly shall be vibration
tested and mechanically balanced as per AMCA 204
Grade BV-3 / ANSI S2.19 G 6.3 and the results recorded
on a label placed on the fan assembly.
ACCESSORIES
3.1 Fan manufacturer shall supply a NEMA rated disconnect
when required as shown on the fan schedule.
3.2 The motor chamber shall have either louvered or
birdscreen covers as shown on the fan schedule.
3.3 The fan manufacturer shall supply a galvanized roof
curb with rigid insulation and a wood nailer as shown
on the fan schedule.
PENNBARRY
22
Direct Drive
PRODUCT
2.1 Fan shall be of axial/centrifugal, mixed flow type,
configuration.
2.2 Fan shall be direct drive as shown on schedule.
2.3 Fan housing shall be of all welded construction with
a flanged inlet and outlet, and shall be constructed
completely of carbon steel, stainless steel (type 316 or
304) or aluminum as specified on fan schedule.
2.3.1 The fan housing shall have an integrally designed
removable section to allow for impeller inspection or
removal while the fan assembly remains installed.
2.3.2 The fan shall be capable of supporting additional duct
stack height of up to 20 feet if the application requires
such due to building envelope, local codes or regional
codes. Additional stack shall be properly guy wired.
2.4 Motor shall be separated from the air stream and is
located in an easily accessible and visible chamber. This
chamber bifurcates the fan housing and the air stream.
2.5 When required, the fan shall be equipped to be capable
of continuous operation at 250°F, 450°F, 750°F, 900°F or
1000°F, as indicated on the fan schedule.
2.5.1 The fan shall perform at the elevated temperatures
without any additional external cooling fans other than its
own integral mounted cooling wheels.
2.6 Impeller shall be of mixed flow type consisting of welded
construction that shall be of carbon steel, stainless steel
or aluminum, as indicated on the fan schedule.
2.6.1 Impeller shall produce an operation curve that does not
produce any dip in the fan curve, with stable operation
over its full curve operating range.
2.7 The electric motor shall be as specified on fan schedule
and is available in any enclosure as made available
from the motor vendors. The motor shall be of a typical
NEMA -T frame type and standard in nature with the
motor industry and is readily available, unless specified
otherwise due to application warranting such.
2.8 Fan shall be of AMCA spark resistant construction when
required and as indicated on the fan schedule as either
AMCA “A”, “B” or “C”.
2.9 Fan shall be coated with enamel as standard or any other
available coating as made available by coating suppliers
and as indicated on the fan schedule.
2.10 The final complete fan assembly shall be vibration tested
and mechanically balanced as per AMCA 204
Grade BV-3 / ANSI S2.19 G 6.3 and the results recorded
on a label placed on the fan assembly.
ACCESSORIES
3.1 Fan manufacturer shall supply a NEMA rated disconnect
when required as shown on the fan schedule.
3.2 The motor chamber shall have either louvered or
birdscreen covers as shown on the fan schedule.