TA1 Temperature and Alarm Sensor
Installation Guide
Failure to follow these instructions can damage the product or cause a hazardous condition. Disconnect power during the installation of this product. All wiring must conform to local codes and ordinances. The TA1 sensor is designed for use with a 24 VAC Pelican thermostats only. After installation, if the TA1 Sensor does not show up on your Pelican Site Manager you will need to contact Pelican Wireless Support and request a thermostat TS200(H) upgrade.
Mount the back plate of the TA1 sensor to a flat surface. Position it so that wires can be fed through either the oval opening in the back or the small opening on the bottom of the TA1 sensor. Drill 3/16" holes into the wall at the provided mounting locations on the TA1 sensor. Insert anchors into the wall and attach the back plate to the wall using the included mounting screws. Follow the wiring instructions on page 2.
After the TA1 sensor is mounted simply line up the front cover to the back cover and snap into place. To remove the front cover from the back plate, use a flat head screw driver and lightly twist in the provided slots on each side of the TA1 sensor.
The Temperature and Alarm sensor is an add-on accessory to the Pelican TS200 and TS200H Thermostats.
Uses:
1. External Temperature Sensing
2. Refrigeration Monitoring & Control
3. Dry Contact Alarm Interface
Wall Mounted Back Plate
Face Cover
Internal Temperature Sensor
D
D
Mounting Hardware
Hardware Provided
Wall Mounting
1
Pelican
Wireless Systems
Pelican
Wireless Systems
Pelican
Wireless Systems
The TA1 sensor requires 3-wires for power and communcation with a TS200(H); as shown in the diagram above. In many situations you will be able to simply mount the TA1 sensor on a wall and use the provided 10K internal temperature sensor to detect the temperature at the desired location.
Follow the guide on page 3 for alternate installation options for the TA1 sensor. The TA1 sensor can be installed at a maximum distance of 500' from a TS200(H). A 10K external temperature probe can be connected to the TA1 sensor up to 100' away.
We always recommend using a Pelian certified external temperature probe. Contact your local Pelican Wireless distributor for assistance.
Note:
2
Wiring Diagram
Thermostat TA1 Sensor
R
23-26V
10K Temperature Sensor
*Range -20˚F to 180˚F
(-28˚C to 82˚C)
+
-
+
-
C
D
R
C
D
T
Terminal Designations
T
D
C
R
R − 24 VAC Power
C − Common 24 VAC
D − Data Line
T − 10K Temperature Sensor