KSolutions To Common Problems.......................................................................78
Pelco Manual C1515M-A (11/01)5
IMPORTANT SAFEGUARDS AND WARNINGS
1. Read, keep, and follow these instructions.
2. Heed all warnings.
3. There are no user-serviceable parts inside this unit. Only authorized service personnel
may open the unit.
4. Installation and servicing should only be done by qualified service personnel and
conform to all local codes.
5. WARNING: To reduce the risk of fire or electric shock, do not expose this unit to rain
or moisture if this unit is designed for indoor use only.
6. Unless this unit is specifically marked as a NEMA Type 3, 3R, 3S, 4, 4X, 6 or 6P
enclosure, it is designed for indoor use only and it must not be installed where
exposed to rain or moisture.
7. Do not expose this unit to dripping or splashing. Do not place objects filled with liquids,
such as vases, on this unit.
8. Do not block any ventilation openings. Install in accordance with the manufacturer’s
instructions.
9. The installation method and materials should be capable of supporting four times the
weight of the unit and equipment.
10. Do not install near any heat source.
11. Only use attachments/accessories specified by the manufacturer.
12. Clean only with dry cloth.
13. Do not defeat the safety purpose of the polarized or grounding-type plug.
14. Protect the power cord from being walked on or pinched, particularly at plugs,
convenience receptacles, and the point where they exit from the unit.
15. Unplug this unit during lightning storms or when unused for long periods of time.
The product and/or manual may bear the following marks:
This symbol indicates that dangerous
voltage constituting a risk of electric shock
is present within this unit.
This symbol indicates that there are
important operating and maintenance
instructions in the literature accompanying
this unit.
Please thoroughly familiarize yourself with the information in this manual prior to installation
and operation.
FOR QUALIFIED SERVICE PERSONNEL ONLY
1.Only use replacement parts recommended by Pelco.
2.After replacement/repair of this unit’s electrical components, conduct a resistance
measurement between line and exposed parts to verify the exposed parts have not
been connected to line circuitry.
CAUTION:
RISK OF ELECTRIC SHOCK.
DO NOT OPEN.
3.CAUTION: Danger of explosion if battery is incorrectly replaced.
Replace only with the same or equivalent type.
Battery should only be replaced by authorized service personnel.
6Pelco Manual C1515M-A (11/01)
DESCRIPTION
Pelco’s CM6800 Matrix Switcher/Controller is a cross-point video matrix switcher. The
CM6800 provides switching and control for 48 video inputs and eight monitor outputs from
any one of up to 18 keyboards, PCs, and other devices. All 48 video inputs can be used to
control other devices, such as multiplexers. Forty inputs allow for looping to other devices.
The CM6800 can be controlled from a local or remote keyboard, used with a multiplexer to
display multiple camera views on a monitor, and programmed from a personal computer
using the CM6800-MGR software package. The CM6800 can also be controlled with ASCII
commands.
The CM6800 features menu-driven, password-protected programming. Programming can
also be done remotely, with the CM6800-MGR software package. Programming menus are
provided in six languages: English, French, German, Italian, Portuguese, and Spanish.
Multiple ports are provided on the CM6800 for pan/tilt/zoom (PTZ) control, keyboards, and
peripheral components. A single data line can accommodate various types of equipment,
such as external alarm interface units and relay boxes.
Description
ESPRITô
CC3500H-2
Æ
GENEX MULTIPLEXER
CAMCLOSUREô
SPECTRA
KBD300
Æ
HZ
75
3736353433
VCR
MAIN SPOT
IN COM OUT N N H
SVHS
ALARMS
1 2 34 5 6 7 8 9 10 11 14 15 16 12 13
O C C S
OUT IN
AUX
SVHS
38
110-240V 50/60 Hz
8
7654321
24
23222120191817
41 42 43 44
45
40
39
ALTERNATE SOURCE INPUTSVIDEO OUTPUTS
MONITOR
CM9505UPS
KBD300
1514131211109
5
1
6
2
3231302928272625
7
3
8
4
4321
8765484746
CONTROL
PTZ
AT+T
R
-
+
OUT
1
COM 1
5
4
3
6
2
7
8
1
WALL
BLOCK
12 VAC
TRANSFORMER
T+T
R
R-B
R
-
-
+
F
3
2
120/230~
50/60 HZ
25 WATTS
5
4
6
3
2
7
8
1
ALARM
12345678
COM
16
4
3
2
1
VIDEO TO
SWITCHER
SPECTRA
5
6
7
8
Æ
PC
5
4
3
6
2
7
1 8
KBD960
KBD100
KBD200
KBD300
Figure 1. CM6800 Application
Pelco Manual C1515M-A (11/01)7
Description
KEYBOARDS
Up to 16 keyboards from the KBD100/200/300 Series and 2 keyboards from the KBD960/
KBR960 Series can be connected to the CM6800, allowing monitoring stations that share a
common monitor to each have a keyboard. Camera positioning can be programmed and
controlled from the KBD200/300 and KBD960/KBR960 Series keyboards. Keyboard types
can be mixed in a system. Refer to
SEQUENCES, MACROS, PRESETS, PATTERNS, AND ZONES
Special programmed operations include sequences, macros, and camera control, such as
presets, patterns, and zones. All programming (except the scratchpad sequence) ispassword-protected.
A sequence allows operators to see a routine of 72 camera views on any system monitor
over and over again. The sequence can be operated automatically or manually. The order
in which the camera views appear and the time each view remains can be programmed.
The CM6800 also provides a scratchpad sequence, which allows a sequence to be run
from an individual monitor. The scratchpad sequence can be accessed without entering the
password-protected programming menus.
A macro is a sequence of commands or steps. When a macro is run, the steps programmed
into that macro are performed. Macros can be operated automatically or manually. Automatic
operation can be based on specific times or dates.
The following operations are available only with positionable cameras:
A preset allows operators to direct a PTZ (camera positioning system) to move to a
predetermined scene on keyboard command or as a result of an alarm. In addition to
moving the camera, a descriptive title can appear on the screen. The number of
presets available is determined by the camera positioning system. (Presets are not
available with the KBD100 keyboard.)
Associated Equipment
for keyboard descriptions.
With a pattern operators can program a camera positioning system to move around
its viewing area in a repeating pattern. The number and time length of patterns varies
with different positioning systems. (Patterns are not available with the KBD100
keyboard.)
A zone is a user-defined, physical location to which (1) a label is attached and (2) a
camera is associated. When the associated camera is panned through or remains
within this defined zone, the zone label appears on the monitor. (Zones are not
available with the KBD100 keyboard.)
INTERFACE CONTROL
The CM6800 interfaces with the following:
•Coaxitron® standard mode (15-bit) and extended mode (32-bit) protocol receivers
•Pelco’s D and P protocol receivers (RS-422)
•Pelco’s M protocol devices (RS-485)
PARTIONING AND PRIORITY
The CM6800 provides four ways to partition your system:
•Camera to Monitor: Cameras can be assigned to specific monitors for viewing.
•Keyboard to Monitor: Keyboards can be assigned to control specific monitors.
•Camera to Keyboard:
-Viewing: Keyboards can be assigned view-only access to specific cameras (no
PTZ control).
- Control: Keyboards can be assigned PTZ control and viewing access to specific
cameras.
The CM6800 provides eight levels of priority control. Each level defines the ability of a
keyboard to control a camera positioning system and to access programming screens.
8Pelco Manual C1515M-A (11/01)
ALARM INPUTS
The CM6800 can accommodate 136 alarm inputs.
Eight internal alarm inputs are provided on the rear panel of the matrix switcher/controller.
These internal alarm inputs are programmable to associate any camera to any input.
The CM6800 provides numerous alarm handling and display options. For example, alarms
can:
•cause a system monitor display to switch automatically to the camera with the alarm.
•activate patterns or go to presets.
•operate auxiliary outputs.
Also, up to two ALM2064 Alarm Interface Units can be connected to the CM6800. Each
alarm interface unit can handle up to 64 alarms, for a total of 128 external alarms.
AUXILIARY OUTPUTS
Three internal auxiliary outputs are provided on the back of the CM6800. Two are relay
outputs, and one is an open collector (TTL) output. You can also connect up to two
REL2064 Relay Interface Units for a maximum capacity of 128 auxiliaries.
Auxiliary outputs are activated at the keyboard (except KBD100).
POWER, MOUNTING METHODS
The CM6800 operates on 120V or 230V, 50/60 Hz. The case mounts in three rack units
(5.25 inches or 13.34 cm) of vertical space in a universal mount, such as a 19-inch (48.26
cm) equipment bay, or to a wall or tabletop.
CONTINUOUS OPERATING DEVICE
The CM6800 is a self-contained video surveillance system designed specifically for use in
security applications. As such, the CM6800 is intended for continuous duty operation. Once
installed, there are no user or service technician items that require intervention which would
require the system to go off-line or have the power turned off under normal operation.
There are two methods for system programming: direct menu control and indirect control,
using a Windows
®
-based setup program supplied by Pelco. Both of these methods are
noninvasive and do not require the cycling of power in order for storage or execution of new
software settings. The communication ports use standard low voltage interfaces such as
RS-232, RS-422 and RS-485, and all connections and disconnections do not require
rebooting or power cycling. Video connections or changes of termination state do not
require rebooting or power cycling.
Description
Pelco Manual C1515M-A (11/01)9
MODELS
Models
CM6800-48X8Matrix switcher/controller with 48 video inputs and 8 monitor outputs,
120/230V, 50/60 Hz
CM6800-48X8-XMatrix switcher/controller with 48 video inputs and 8 monitor outputs,
120/230V, 50/60 Hz
ASSOCIATED EQUIPMENT
KBD100Desktop keyboard with full switching and programming capabilities,
+12 VDC or 12V 50/60 Hz
KBD200Desktop keyboard with full switching and programming capabilities,
plus push-button control of PTZ functions, +12 VDC or 12V 50/60 Hz
KBD300Desktop keyboard with full switching and programming capabilities,
plus joystick control of PTZ functions, +12 VDC or 12V 50/60 Hz
KBD960-XSame as KBD960, PAL-configured for 230V, 50/60 Hz operation
KBR960Full-function rack mount variable-speed keyboard; 120V, 50/60 Hz
KBR960-XSame as KBR960, PAL-configured for 230V, 50/60 Hz operation
KBDKITWiring kit for connecting KBD100, KBD200, and KBD300 keyboards to
remote keyboard port; includes two RJ-45 wall blocks and a
transformer to convert 120V, 60 Hz to 12V, 60 Hz for keyboard power
KBDKIT-XWiring kit for connecting KBD100, KBD200, and KBD300 keyboards to
remote keyboard port; includes two RJ-45 wall blocks and a
transformer to convert 230V, 50 Hz to 12V, 50 Hz for keyboard power
CM9505UPSUniversal Power Supply for KBD960/KBR960 keyboards
MX4000Genex® Series Multiplexer; available in color or monochrome duplex,
CM9760-CDU-TCode distribution unit; 16-channel RS-422 transmit only (transmit wire
ALM2064Alarm interface unit, provides alarm monitoring capabilities for up to 64
REL2064Relay interface unit, provides 64 relays for operating peripheral
CM9760-MDAMaster distribution amplifier with time, date, and title, 120V, 60 Hz
and in color or monochrome simplex
and ground) distributor; primarily used for connecting up to 16 PTZ
receivers in a “star” or “home run” configuration
alarm inputs, 100-240V, 50/60 Hz
equipment, 100-240V, 50/60 Hz
10Pelco Manual C1515M-A (11/01)
INSTALLATION
00615
Unpack and inspect all parts carefully. The following parts are supplied:
NOTE:
There are no userserviceable parts inside this
unit. Only authorized service
personnel may open the
unit.
MOUNTING
POSITION BRACKETS FOR
RACK MOUNTING (REAR)
1CM6800 Switcher/Controller
410-32 x .750-inch pan head screws
4.500” OD nylon washers
1Power cord
46-foot (1.8 m) straight data cables with RJ-45 connectors
16-foot (1.8 m) reversed data cable with RJ-45 connectors
4RJ-45 wall block terminals
1.Select a suitable location for the CM6800. It occupies 5.25 inches (13.34 cm) of
vertical space, or three rack units (RUs), in a universal mount. The CM6800 must be
within 6 feet (1.8 m) of a suitable electrical outlet.
Follow proper installation practices and leave 1 RU above and below the
CM6800 for ventilation.
Do not connect the power until the installation is complete. Refer to the
Start-Up
section.
System
2.The CM6800 is shipped with the rack ears installed at the front. Reposition as needed
for your application. If the ears are not required, remove them.
POSITION BRACKETS FOR
UNDER-TABLE MOUNTING
Installation
NOTE: EACH CM6800 COMES
WITH 2 RACK EARS
3.Use supplied pan head screws and washers to mount the CM6800 in a standard 19inch (48.26 cm) equipment rack or wood or sheet metal screws to mount against a flat
surface, according to your installation requirements.
POSITION BRACKETS FOR
RACK MOUNTING (FRONT)
POSITION BRACKETS FOR
FLUSH MOUNTING
(WALL AND TABLE TOP)
Figure 2. Installing Rack Ears
Figure 3. Mounting the CM6800 Matrix Switcher/Controller
00624
Pelco Manual C1515M-A (11/01)11
Installation:
Video Sources
VIDEO SOURCES
The CM6800 offers 48 full-function video inputs which support Coaxitron PTZ control and
video loss detection. Forty video inputs, labeled 1 through 40, can be used for looping
video connections with terminating and unterminating switches on the back panel. The
eight alternate source inputs, labeled 41 through 48, are terminated inputs. They do not
have loop-through connectors or selectable termination switches, but otherwise they offer
the same functionality as video inputs 1 through 40.
All 48 video inputs also provide the ability to view and interface with other devices, such as
Genex multiplexers. If control of the device connected to the video input is required,
connect a data cable between the multiplexer and the CM6800. Refer to the
Genex Multiplexers
multiplexer.
section for instructions on connecting and controlling video from a
Connecting
00625
Figure 4. CM6800 Video Inputs
1.Connect video cables at the appropriate video input BNC receptacles on the back of
the CM6800. For best results, use crimp-on BNCs only. Do not use screw-on BNCs;
these typically do not provide adequate ground and signal connections.
Refer to Table A for video coaxial wiring requirements.
Table A. Video Coaxial Cable Requirements
Cable Type*Maximum Distance
RG59/U750 ft (229 m)
RG6/U1,000 ft (305 m)
RG11/U1,500 ft (457 m)
* Minimum cable requirements:
75 ohms impedance
All-copper center conductor
All-copper braided shield with 95% braid coverage
12Pelco Manual C1515M-A (11/01)
2.On video inputs 1 through 40, set the terminating switches according to your system
requirements. Video inputs 41 through 48 cannot be used for loop-through connections.
Terminating switches are used to terminate or unterminate the video input. The factory
default has the switches set in the terminated (75-ohm) position.
If you are connecting only a camera to an input, leave the switch in the terminated
position.
00626
Video Sources
Installation:
NOTE:
The end point of
any video cable run must be
terminated in 75 ohms.
Figure 5. Connecting Terminated Video Sources
If you are looping the input to another device, set the rear panel switch in the
unterminated (Hi-Z) position. Terminate at the final device.
00627
Figure 6. Connecting Looping Video Sources
Pelco Manual C1515M-A (11/01)13
NOTE:
receivers cannot be mixed
on the same communication
port but you can use D on
one port and P on the other.
Installation:
Control Lines
NOTE:
system installation and
power-up, you must configure the CM6800 and the
camera/receiver. Refer to
the
System Start-Up
D and P protocol
After completing
section.
CONTROL LINES
You cannot connect a Coaxitron camera to the PTZ-A or PTZ-B ports. If your video sources
are all controlled by Coaxitron, skip this section.
Connect camera control lines to receivers. If any of your video sources are using D or P
protocol via RS-422 communications, they will connect at the PTZ-A and PTZ-B connectors
on the back of the CM6800.
Daisy-chaining (going from one receiver to another) is recommended but not always possible.
A maximum of 16 receivers can be daisy-chained from each port. If more than 32 receivers
are required for your system, or if you do not want to daisy-chain the receiver connections,
use the CM9760-CDU-T. You can connect up to four CM9760-CDU-T units to the
CM6800-48X8.
00628
Figure 7. PTZ Control Connections
14Pelco Manual C1515M-A (11/01)
MONITORS
The CM6800 supports eight monitors.
1.Install monitors according to the instructions provided with them.
2.Connect the monitor cables at the appropriate video output BNC receptacles on the
back of the CM6800.
3.Terminate cables at the monitors. If you are looping to other devices, unterminate all
but the last device.
Figure 8. Connecting Monitors
Installation:
Monitors
00629
Pelco Manual C1515M-A (11/01)15
ALARMS
Alarms
Installation:
The CM6800 provides numerous alarm handling options. Refer to the
for a detailed description.
1.Connect wires from the sensors to the respective alarm input points on the connectors
at the back of the CM6800. Each sensor requires two wires – one wire to the alarm
input terminal and a return wire to one of the ground terminals on the connector. The
CM6800 supports eight internal alarms.
Alarm sensors can be either N.O. (normally open) or N.C. (normally closed) contacts.
The CM6800 is set to N.O. as a factory default.
2.If your system requires more than eight alarms, connect an ALM2064 unit to the
system. Refer to the
M Devices
section.
Programming
section
00631
Figure 9. Connecting Alarms
16Pelco Manual C1515M-A (11/01)
CONNECTING DEVICES THROUGH THE COMMUNICATION PORTS
NOTE:
Connection instructions for other peripheral
devices, such as the
CM9760-MDA or
CM9760-CDU-T, are
provided as Pelco Technical
Tips, available from the
Pelco web site or from a
Technical Support representative (1-800-289-9100). For
more information, go to
www.pelco.com and select
Resources. Then select
Technical Tips.
The CM6800 Matrix Switcher/Controller provides eight communication ports on the rear
panel for connecting peripheral components. You can connect a wide variety of devices,
such as keyboards, a personal computer (for either the CM6800 MGR package or ASCII
control), alarm and relay boxes, and multiplexers. Instructions are provided in this section
for the most commonly used connections.
The CM6800 communication ports are labeled COM 1 through 8. Port 1 is available either
as a DB9 connection, or as an RJ-45 connection. Ports 2 through 8 are RJ-45 connections.
In the programming menus these are referred to as serial ports 1 through 8.
COM PORTS 7, 8
RS-485 (PROGRAMMABLE
TO RS-232), RJ-45
PIN 1
PIN 8
1-----Rx+
2-----Rx3
-----NC
4
-----NC
5-----GROUND
6-----NC
7-----Tx8-----Tx+
RS-232 FUNCTIONRS-485 FUNCTION
1-----Rx
-----NC
2
-----NC
3
-----NC
4
5-----GROUND
6-----NC
7-----NC
8-----Tx
Installation:
Data Ports
COM PORT 1
RS-232,DB9
PIN 6
1-----NC
2-----Rx
3-----Tx
4
-----NC
5-----GROUND
6
-----NC
7
-----NC
8-----NC
9-----NC
PIN 5PIN 1
PIN 9
COM PORTS 1, 2
RS-232, RJ-45
PIN 1
PIN 8
1-----Rx
2-----NC
3-----NC
4
-----NC
5-----GROUND
6
-----NC
7
-----NC
8-----Tx
COM PORT 3
M, RS-485 , RJ-45
PIN 1
PIN 8
1-----Rx+
2-----Rx3
-----NC
4
-----NC
5-----GROUND
6-----NC
7-----Tx8-----Tx+
NC = NO CONNECTION
COM PORT 4
RS-485, RJ-45
PIN 1
PIN 8
1-----Rx+
2-----Rx3
-----NC
4
-----NC
5-----GROUND
6-----NC
7-----Tx8-----Tx+
Figure 10. Communication Port Connections and RJ-45 Connector Pin-Outs
PortDefault DeviceWiringProgrammable to Other Device(s)
COM 1PC Setup – CM6800MGR programRS-232ASCII device
(accessible with a DB9
connection or an RJ-45
connection)
COM 2ASCII deviceRS-232No
Data Ports
Installation:
COM 3M devices — ALM2064, REL2064,RS-485No
COM 4Genex multiplexerRS-485CM9760-MDA, ASCII
COM 5Keyboard (direct powered) –RS-485 plus powerNo
COM 6Keyboard (direct powered) –RS-485 plus powerNo
COM 7ASCII deviceRS-232 or RS-485CM9760-MDA, keyboards
COM 8ASCII deviceRS-232 or RS-485MDA, keyboards
The communication ports are wired for either RS-232 or RS-485 (the wiring can be selected
for COM 7 and 8). Refer to the following tables for the CM6800 default communication port
settings. Some ports can be programmed for other devices; this will be done when you
program the CM6800.
Table B. Communication Port Devices and Wiring
KBD960
KBD100, 200, & 300
KBD100, 200, & 300
(KBD100, 200, & 300)
(KBD100, 200, & 300)
NOTE:
Refer to the
Programming
section for
instructions on changing
Serial Port settings.
Table C. Default Port Settings
PortDefault Settings
COM 1MGR, RS-232, 56000 baud, no parity, 8 data bits, 1 stop bit
COM 2ASCII, RS-232, 9600 baud, no parity, 8 data bits, 1 stop bit
COM 3M, RS-485, 19200 baud, no parity, 8 data bits, 1 stop bit
COM 4MUX, RS-485, 9600 baud, odd parity, 8 data bits, 1 stop bit
COM 5, 6KBD-300, RS-485, 9600 baud, odd parity, 8 data bits, 1 stop bit
COM 7, 8ASCII, RS-485, 9600 baud, no parity, 8 data bits, 1 stop bit
18Pelco Manual C1515M-A (11/01)
COM 1
PC SETUP (RS-232)
USE DB9 CONNECTION
OR ALTERNATE RJ-45 CONNECTION
BOTH CANNOT BE USED SIMULTANEOUSLY
PC RJ-45 CONNECTION
COM 2
(RS232)
ASCII CONTROL ONLY
ALTERNATE EQUIPMENT
PC DB9 CONNECTION
RS-232 NULL MODEM CABLE
COM 5 & 6
LOCAL KEYBOARDS (RS-485)
KBD100/200/300 SERIES
MAX # OF DEVICES = 8
COM
1
5
2
6
3231
3
7
4
43
87
VIDEO OUTPUTS
8
ALARM
12345 678
CONTROL
PTZ
AT+T-R+R-T+T-R+R-B
OUT
1
2
COM 1
NOTE: TOTAL NUMBER OF
KBD100/200/300 SERIES
KEYBOARDS CONNECTED
TO THE CM6800 CANNOT
EXCEED 16
F
3
120/230~
50/60 HZ
25 WATTS
Installation:
Peripherals
COM 3
M DEVICES (RS-485)
MAX # OF DEVICES = 6
MAXIMUM DISTANCE FROM CM6800 = 3,940 FT (1,200 M)
USING 24 AWG COPPER, UNSHIELDED TWISTED PAIR; 16 pF PER FT (pF =PICO FARADS)
5
4
3
6
2
7
8
1
ALM2064
NUMBER SUPPORTED = 2
64 ALARMS X 2 = 128 ALARMS
4
3
2
1
5
4
3
6
2
7
8
1
TRANSFORMER
12V 50 Hz
CM9505UPS
POWER SUPPLY
4
3
2
1
5
6
7
8
STRAIGHT
CABLES
COM 4
GENEX (RS-485)
ALSO PROGRAMMABLE FOR CM9760-MDA OR ASCII
MAX # OF DEVICES = 8
5
4
3
6
2
7
8
1
5
4
3
6
2
7
8
1
5
4
3
6
2
7
8
1
5
4
3
6
2
7
8
1
KBD960
REL2064
NUMBER SUPPORTED = 2
64 RELAYS X 2 = 128
KBD960
NUMBER SUPPORTED = 2
Figure 11. CM6800 Communication Port Connections and Options
5
6
COM 7 & 8
7
(RS-485 OR RS-232)
8
PROGRAMMABLE FOR KBD100/200/300 SERIES,
ASCII CONTROL, OR CM9760-MDA
5
4
3
6
2
7
1 8
5
4
3
6
2
7
1 8
5
4
3
6
2
7
1 8
Pelco Manual C1515M-A (11/01)19
Keyboards
Installation:
KBD100, KBD200, AND KBD300 SERIES KEYBOARDS
You can connect up to eight KBD100/200/300 Series keyboards to any of the following ports:
•COM 5 (1 direct-powered keyboard or up to 8 remotely connected keyboards)
•COM 6 (1 direct-powered keyboard or up to 8 remotely connected keyboards)
•COM 7 (up to 8 remotely connected keyboards)
•COM 8 (up to 8 remotely connected keyboards)
The total number of KBD100/200/300 Series keyboards connected to the CM6800 cannot
exceed 16.
KBD100, KBD200, and KBD300: Direct-Powered Keyboards
Use COM 5 and 6 (Serial Ports 5 and 6) for direct-powered local keyboards. Each port can
power one KBD100/200/300 Series keyboard.
If you are connecting more than one keyboard to COM 5 or 6, a KBDKIT(-X) is required for
each keyboard. Refer to the
1.Using the 25-foot (7.62 m) straight data cable supplied with the keyboard, plug one
end into the RJ-45 connector on the rear of the keyboard.
KBD100, KBD200, and KBD300: Remote Keyboards
section.
NOTE:
If distance between
CM6800 and keyboard
exceeds 25 feet, use
KBDKIT(-X).
00603
Figure 12. Data Cable Plugged into Local Keyboard
2.Plug the other end of the data cable into either COM 5 or 6 on the CM6800.
00604
Figure 13. Data Cables Plugged into COM 5 and 6
20Pelco Manual C1515M-A (11/01)
3.Set the keyboard DIP switches for the desired address for the local keyboard (refer to
Figure 12 and Table D).
Table D. Keyboard Addresses: KBD100/200/300 Series Keyboards
Table E. Switch Settings—KBD200/300 Keyboards Only
KeyboardSwitch
5678
KBD200OFFOFFOFF (NOT USED)OFF
KBD300OFFON or OFF*OFF (NOT USED)OFF
* Switch 6 enables/disables turbo pan (can be switched while keyboard is on).
Installation:
Keyboards
Pelco Manual C1515M-A (11/01)21
NOTE:
KBDKIT-X is required to
connect remote keyboards.
The KBDKIT consists of two
RJ-45 wall blocks and one
120V, 60 Hz to 12V, 60Hz
transformer. The KBDKIT-X
has a 230V, 50 Hz to 12V,
50 Hz transformer. Use one
wall block for each keyboard.
Keyboards
Installation:
NOTE:
connect keyboards to
COM 7 or 8, either port can
be used for a CM9760-MDA
or an ASCII device.
Connection instructions for
CM9760-MDA are provided
as a Pelco Technical Tip.
Refer to the note on page
17. For ASCII devices, refer
to the documentation that
comes with the equipment.
A KBDKIT or
If you do not
KBD100, KBD200, and KBD300: Remote Keyboards
Use COM 5, 6, 7, or 8 for remote keyboard connections. Each port can support up to eight
KBD100/200/300 Series keyboards. Do not exceed a total capacity of 16 keyboards
connected to the CM6800.
If using COM 7 or 8, you will need to change the settings (the default setting is for an ASCII
device.) Refer to the
1.Select a suitable location for each keyboard and wall block. Wall blocks must be within
6 feet (1.8 m) of a suitable electrical outlet. Do not mount the wall blocks yet.
2.Connect each keyboard to a wall block, using the keyboard data cable supplied with
the keyboard.
3.Remove the wall block covers and wire the connections between each wall block.
Connect to a final wall block (which will be connected to the CM6800).
Communication to the keyboards is RS-485. Pelco recommends using four-conductor,
shielded 18-gauge twisted pairs, such as Belden 9418 or similar cable, that meets or
exceeds the basic requirements for EIA RS-485 applications.
4.At each wall block, wire the KBDKIT(-X) transformer to pins 3 and 4. Polarity is
unimportant.
5.Replace the cover on the wall block. Secure the wall block to a suitable surface. A
double-sided sticky pad is provided to mount the wall block.
6.Set the address switches for each keyboard according to Table D.
7.Connect the final wall block to COM 5, 6, 7, or 8 on the CM6800, using a straight data
cable (supplied with the CM6800).
Programming
section for instructions.
00605
Figure 14. Remote Keyboards
22Pelco Manual C1515M-A (11/01)
M DEVICES
M protocol devices (KBD960/KBR960 keyboards, ALM2064 Alarm Interface Units, and
REL2064 Relay Interface Units) can be connected to COM 3 on the CM6800.
If only one device is to be connected to COM 3, use the instructions for that device in the
following sections.
NOTE:
If you wish to use
the partitioning and priority
features of the CM6800, you
must number KBD960/
KBR960 keyboards within a
range of 1-8.
If more than one device is to be connected to COM 3, refer to the
Multiple M Devices
section.
Connect M devices to the CM6800 with straight cables. Four straight cables and one
reversed cable are supplied with the CM6800 (save the reversed cable for connecting a
Genex Multiplexer, if applicable).
M Devices Addressing
Each M device connected to the CM6800 must have a unique local address within a range
of 1-16. Use the hardware DIP switches to set the appropriate ALM2064 and REL2064
local addresses. Specify the appropriate KBD960/KBR960 local address through the
keyboard Setup Mode after you complete the system installation (refer to the
Up
section).
For use with the CM6800, Pelco recommends numbering M devices in a sequential order.
In a sample application, with two of each M device, you might assign local addresses as
follows:
M device local addresses:DefaultRecommended for CM6800
KBD960/KBR960:11, 2
REL2064:13, 4
ALM2064:15, 6
COMPARED "COLOR RUN"
IS IN SAME DIRECTION
BROWN BROWN
STRAIGHT CABLE
COMPARED "COLOR RUN"
IS IN OPPOSITE DIRECTION
BROWN BROWN
REVERSED CABLE
TO IDENTIFY A CABLE
TYPE, PHYSICALLY
ORIENT THE RJ-45
CABLE AS DEPICTED
IN THE ILLUSTRATIONS.
ORIENT THE CONNECTORS
SIDE BY SIDE. TAB
SIDE DOWN. USE
THE COLOR RUN
OF THE WIRES TO
DETERMINE CABLE
TYPE.
System Start-
Installation:
M Devices
00612
Figure 15. RJ-45 Cable Types
Pelco Manual C1515M-A (11/01)23
M Devices
Installation:
Connecting a Single KBD960/KBR960 Keyboard
To connect a single KBD960/KBR960 Keyboard to the CM6800:
1.Connect the keyboard to the CM9505UPS using the straight cable supplied with the
keyboard.
2.Connect the CM9505UPS to COM 3 on the CM6800 using the 6-foot (1.8 m) straight
data cable supplied with the CM6800.
NOTE:
After completing
system installation and
power-up, you must configure the KBD960/KBR960
settings. Refer to the
Start-Up
section.
System
00607
Figure 16. Connecting a KBD960/KBR960 to the CM6800
24Pelco Manual C1515M-A (11/01)
Connecting a Single ALM2064 Alarm Interface Unit
To connect a single ALM2064 Alarm Interface Unit:
1.Connect the ALM2064 OUT port to COM 3 on the CM6800 using the 6-foot (1.8 m)
straight data cable supplied with the CM6800.
2.Set SW2, DIP switches 1-8 to the appropriate positions for the local address (default
address setting is 1). Refer to the ALM2064 Alarm Interface Unit Installation/Operation
Manual for instructions.
Installation:
M Devices
Figure 17. Connecting a Single ALM2064 Alarm Interface Unit
00608
Pelco Manual C1515M-A (11/01)25
00609
M Devices
Installation:
Connecting a Single REL2064 Relay Interface Unit
To connect a single REL2064 Relay Interface Unit:
1.Connect the REL2064 OUT port to COM 3 on the CM6800 using the 6-foot (1.8 m)
straight data cable supplied with the CM6800.
2.Set SW2, DIP switches 1-8 to the appropriate positions for the local address (default
address setting is 1). Refer to the REL2064 Relay Interface Unit Installation/Operation
Manual for instructions.
Figure 18. Connecting a Single REL2064 Relay Interface Unit
26Pelco Manual C1515M-A (11/01)
Loading...
+ 60 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.