PEERLESS SERIES GM, GM-05, GM-06, GM-07, GM-08 Installation, Operation & Maintenance Manual

Page 1
GM
Boilers
Installation, Operation b
Maintenance Manual
PEEI_LESS*
Page 2
Packaged Residential/Commercial Gas Fired, Hot
4 Sizes 5-8 Sections 228.0 to 399.0 MBH Input 82% Combustion Efficiency
Natural Gas
Standing Pilot (5-6 section)
Honeywell SmartValve ® Intermittent Ignition (5-8 section)
Natural Draft (Chimney) Venting
Simplifies Installation
Steel Push Nipples
Provide a Permanent Water Tight Seal Between Sections
Unaffected by Petroleum and Other Contaminants
Deluxe Insulated Enameled Steel Jacket
Reduces Boiler Heat Loss
Completely Encloses Gas Valve, Burners and Controls for
Safe Operation
Front Located Controls and Return Piping
Ideal for modular and multiple boiler installations
Easy to service
Packaged Boiler
Reduces Installation Time
Vertical Draft Hood
Supports Combustion
Safety Controls
Vent Safety ShutoffSwilch
Flame RoUout Safety Shuto[]Switch
Honeywell SmartValve °-_Intermittent Ignition
Honeywell Operating Controls
30 PSI Sof('ty Relief Valve (unmounted)
Vent Damper (5-6 section)
Vertical Draft Hood
! STIIOI I_(llll{! iS II II'( ist(_r_,d Irademrlrk o[ t [I)IEt'IIH_I'II (_oI'lll)I I
Standing Pilot Ignition (5 6 section)
Toco 0010 & 0012 Circulators (unmounted)
Taco 0010 & 0012 Zoning Circulators with relay (unmounted)
50, 80 or 1O0 PSI Safety Reli@ Valve (unmounted)
Probe _]pe LWCO (unmounted)
Vent Dampt'r (7 8 section)
P_'t'll('ss I [t'tltt't ( ompatly is pleoscd _o _[1_'1 ont' qJ dle most COml)reh('nsiv_, it,arr(ully i)rograms
i. _l,,._,,,/.._.-v.AllI',.,.,I_.._._¢o,,_._._,._./(,t,(_,-,.._,(_,,,.i(a(...,_t,-o,6oil,.,__,,c!.d,,. l,,.i.,_, o,,,__j_.a_ pr=_r=_RLESS _
It,(ut(ult!l A linlit('(I. 1_'11 Ijcor it,ettTemt!l on IIl_" ('_l.*;t itz)tl ._;t'cliotls i_ procid(,(I [or(ill cotnm('r('i(d ))oilers. P_'_'rlt's_ I)rOi,M(,.s (t limit_'(l. !!f!'limt" iP(trr(ttll!l ()it tilt" ('(t.'_t irotl s('t'liotl.'_ Ql il.,_ r('siH{'r_ti(ll hol u,ot_'r
!)od_'1.'_. euld (t ltnlit_'(I. It'rl y('or w_trt(lllt!j ()It l/R' C(l_l it'otl .'%'cliotk'_ o] lt._ tt'aid('tllt(ll ._;l('(llll !)oi ('_._; ['_" _' CAST IRON BOILERS _ttl(I t('tl !l('(tt" <'.\l('tlcl('(I It'(It I(ttlli('.s o_1 p_trt.'¢ lul(I led)or (trt" c_t,ailcl])l_,.]_)_" I_olt_ ¢l'.'_i(l('tll[(ll _ttl(I conmlt,r(itd boik'rs, l)l(,(t_, cott._;tllt l'('('rl('ss l l_'(tt('r" (?OtlllXttly.Jbr (.oml)l(,t(, [t,ttttett_ll itl ()t'_llttltotL
Peerless Heater Company 231 North Walnut Street * Boyertown, PA 19512-I021 610-367-2153 * www.peerless-heater.com
FAB GM R2 {7'02 5M)
Pr,ltl.0 Irl U S A
Page 3
1=
USING THIS MANUAL 1
A. INSTALLATION SEQUENCE ............. 1
B. SPECIAL ATTENTION BOXES ........... 1
PREINSTALLATION 2
A. ACCESSIBILITY CLEARANCES .......... 2
B. CLEARANCE FROM COMBUSTIBLE
CONSTRUCTION ..................... 2
C. COMBUSTION AND VENTILATION AIR .... 2
D. INSTALLATION SURVEY ............... 4
E. CIRCULATORS ....................... 4
E PLANNING THE LAYOUT ............... 4
A. BOILER SUPPLY AND RETURN .......... 6
B. SAFETY RELIEF VALVE ................ 7
C. PIPING FOR ZONED SYSTEMS .......... 8
D. EXPANSION TANK .................... 9
E. INDIRECT-FIRED WATER HEATER ........ 9
E FREEZE PROTECTION ................. 9
4, VENTING .... _ :
10
A. DRAFT HOOD ...................... 10
B. AUTOMATIC VENT DAMPER .............
INSTALLATION - GENERAL ............ 11
C. VENT PIPING AND CHIMNEY .......... 11
D. BOILER REMOVAL FROM COMMON
VENTING SYSTEM ................... 12
5 _GAs _P|PJNG _':
A. WIRING ........................... 15
B. CIRCULATOR/ZONE VALVE WIRING ..... 15
C. LOW WATER CUTOFF ................ 15
A. GENERAL .......................... 21
B. CSD PART CF REQUIREMENTS ......... 21
C. CSD PART CW REQUIREMENTS ........ 21
D. CSD MODULAR AND MULTIPLE BOILER
REQUIREMENTS .................... 21
E. CSD PART CE ELECTRICAL
REQUIREMENTS .................... 22
23
A. COMPLETING THE INSTALLATION ...... 23
B. CONTROL DESCRIPTIONS ............. 27
C. ADJUSTMENT OF GAS PRESSURE
REGULATOR ....................... 27
D. CHECKING BURNER INPUT ............ 27
E. CHECK-OUT PROCEDURE ............. 28
A. SHUT-DOWN CAUSED BY PILOT OUTAGE,
VENT SAFETY SHUTOFF SWITCH OR
FLAME ROLLOUT SAFETY SHUTOFF
SWITCH ........................... 29
B. TROUBLESHOOTING GUIDES .......... 29
_O.MAINTENANCE 32
A. GENERAL .......................... 32
B. DAILY (WITH BOILER IN USE) .......... 32
C. WEEKLY (WITH BOILER IN USE) ........ 32
D. MONTHLY (WITH BOILER IN USE) ....... 32
E. ANNUALLY (BEFORE START OF HEATING
SEASON) .......................... 33
A. BASE ............................. 35
B. GAS MANIFOLD, ORIFICE SPUDS, AND
MAIN BURNERS ..................... 36
C. BLOCK AND FLUE COLLECTOR ......... 37
D. JACKET ........................... 38
E. CONTROLS, DRAFT HOOD AND
AUTOMATIC VENT DAMPER ........... 39
Page 4
Follow the installation instructions provided in this manual in the order shown. The order of these
instructions have been set in order to provide the installer with a logical sequence of steps that will
minimize potential interferences and maximize safety during boiler installation.
Indicates a condition or hazard which will cause severe personal injury, death or major property
damage.
_.'t',J:[I,] r__ I r*__l/ i _b?I i [o] L'_I:[o).'4 ::_
Throughout this manual you will see special attention boxes intended to supplement the instructions and make
special notice of potential hazards. These categories
mean, in the judgment of the Peerless Heater Company:
Indicates a condition or hazard which may cause severe personal injury, death or major property
damage.
Indicates a condition or hazard which will or can cause minor personal injury or property damage.
Indicates special attention is needed, but not directly related to potential personal injury or property damage.
Page 5
Theequipmentmustbeinstalledinaccordancewithinstallationrequirementsoftheauthorityhaving jurisdictionor,intheabsenceofsuchrequirements,tothecurrenteditionoftheNational Fuel Gas Code, ANSI
Z223.1/NFPA 54. Where required by the authority having jurisdiction, the installation must conform to American Society of
Mechanical Engineers Safety Code for Controls and Safety Devices for Automatically Fired Boilers, ASME CSD-I.
Carefully read these instTuctions before beginning work. Understand all aspects of the installation. Contact your Peerless Heater Company sales representative or customer service for help in answering questions.
This boiler must be installed by a qualified contractor. The boiler warranty can be voided if the boiler is not installed correctly.
r,_! P__] =k'-]_'tlHI l | &'J IN I!__,I ;5_,1=_IN =[<
Install boiler not less than 24" between the top and front of the boiler and adjacent wall or other appliance, when access is required for servicing.
Do not install boiler on carpeting. Boiler installation on carpeting is a fire hazard,
_e,]l [e,Zo]L'r_l:tlj.:']ld[o]_'Hf_,lL'111]Lrj:l_'_llllf,_'l/[o]L'_|:!l;
The design of this boiler is certified for alcove installation with the following clearances from combustible
construction:
I Sides: 2"
2. Top of Jacket: 36"
3. Draft Hood: 6"
4. Vent Pipe: 6" (1" for Type B vent)
5. Rear of Jacket: 6"
Do not install this boiler on combustible flooring. Boiler installation on combustible flooring is a fire
hazard.
6. If it is necessary to build a non-combustible floor pad
over top of an existing combustible floor, construct pad as stated in the .National Fuel Gas Code Handbook Part 6, Installation of Specific Equipment.
].
2.
Provide adequate facilities for combustion and ventilation air in accordance with Section 5.3, Air for
Combustion and Ventilation, .National Fuel Gas Code, or applicable provisions of the local building
code. Subsections 2 through 6 below are based on National Fuel Gas Code requirements.
Definitions:
Unconfined Space: a space whose volume is not less than fifty (50) cubic feet per 1000 Btu!hr of the
total input rating of all appliances installed in that space. Rooms communicating directly with the space
in which the appliances are installed, through
openings not furnished with doors, are considered part of the unconfined space.
Unusually Tight Construction: Construction
where:
a.
Walls and ceilings exposed to the outside atmosphere have a continuous water vapor retarder with a rating of 1 perm or less with openings gasketed or sealed, and
b. Weatherstripping has been added on openable
windows and doors, and
e.
Caulking or sealants are supplied to areas such as joints around window and door frames,
between sole plates and floors, between wall- ceiling joints, between wall panels, at
penetrations for plumbing, electrical and gas lines, and at other openings.
3. Appliances Located in Unconfined Spaces: For installations in unconfined spaces with other than unusually tight construction, the supply of air for combustion and ventilation can usually be considered adequate.
Page 6
=
'qll
4. Unusually Tight Construction: For equipment located in buildings of unusually tight
construction as defined on the previous page, provide air for combustion and ventilation using the
methods described in 5a or 5b below.
5 Appliances Located in Confined Spaces:
a. All air from inside the building: Provide two
permanent openings communicating directly with an additional room or rooms of sufficient volume
so that the combined volume of all spaces meets the criteria for an unconfined space. Use the total
input of all gas utilization equipment installed in
the combined space in making this determination.
Size each opening with a minimum free area of one square inch per i000 Btu!hr of the total rating of all gas utilization equipment in the
confined space, but not less than 100 square inches. Begin with one opening 12 inches from the top, and begin the other opening within 12 inches of the bottom of the enclosure. See Figure
1. Provide air openings with minimum dimensions not less than three (3) inches.
b. All air from outside the building. Connect the
confined space with the outdoors in accordance with methods i) or ii) below. Provide air openings with minimum dimensions not less than three (3) inches. Where ducts are used, make certain that they are the same cross-sectional area as the free area of the openings to which they connect.
Provide two permanent openings, one commencing within 12 inches of the top and one commencing within 12 inches of the
bottom of the enclosure. Connect the openings directly or by ducts, with the
outdoors or spaces (crawl or attic) that freely communicate with the outdoors.
Where directly communicating with the outdoors (see Figure 2) or where communicating to the outdoors through
vertical ducts (see Figure 3), size each opening with a minimum free area of one (I)
square inch per 4000 Btu/hr of total rating of all equipment in the enclosure.
Where communicating with the outdoors through horizontal ducts, size each opening with a minimum flee area of one (i) square
inch per 2000 Btu/hr of total input rating of
all equipment in the enclosure. See Figure 4.
12" max
TWO AIR OPENINGS:
Minimum
Free Area Each =
1 in2 per 1000 Btuh
at Least 100 in2
3" m{n
BUILDING
Mustcommunicatefreely
with outdoors
Must not beunder
negativepressure
3" mill
12" max
Figure 1: Air Openings - All Air from Indoors
TWO AIR OPENINGS:
Minimum
Free Area Each =
1 in2per 4000 Btuh
3" min __
12" max,_
Figure 2: Air Openings - All Air Directly from
Outdoors
[_L 12" max
3" rain TWO AIR OPENINGS:
Minimum
Free Area Each =
Figure 3: Air Openings - All Air from Outdoors
through Vertical Ducts
3
Page 7
| ill _T_t::]I_t--'_*]]_ [r_ITr_]
6,
7.
ii) Where the equipment has clearances of at
least one (I) inch from the sides and back and six (6) inches from the front of the appliance, the code allows one permanent opening, commencing within 12 inches of the top of the enclosure Connect the opening directly with the outdoors or through
a vertical or horizontal duct to the outdoors or spaces (crawl or attic) that freely
communicate with the outdoors, Size the opening with a minimum free area of one
square inch per 3000 Btu/hr of the total input rating of all equipment in the enclosure, and
not less than the sum of the areas of all vent connectors in the confined space.
In calculating tree area of an opening, take into account the blocking affect of louvers, grilles and screens. Do not use screens smaller than 1/4" mesh.
If the free area is known, use this value in calculating the size of the opening required. If it is not known, assume that wood louvers provide 20_25% free area, and metal louvers and grilles provide 60-75% free
area.
Remove sources of hydrocarbons (bleaches, cleaners, chemicals, sprays, paint removers, fabric softeners, etc.) from the boiler area. The vapors generated by these substances can contaminate the
combustion air and contribute to shortened boiler/vent system life.
12" max
TWO AIR OPENINGS:
Minimum
3" min Free Area Each =
1 in_per 2000 Btuh
3" rain
12"max
Figure 4: Air Openings - All Air from Outdoors
through Horizontal Ducts
Iwl IlO_.llt;lll_'_ll[e]_l _."[IJ;{fj:li"
For new and existing installations, a Water Installation Survey is available from Peerless Heater Company. The survey will provide information on how a hot water boiler works with your specific system and will provide an overview of hot water system operation in general.
You can also use this survey to locate system problems which will have to be corrected. To obtain copies of the Water Installation Survey. contact your Peerless
representative.
I:;l! [s,]I :{e,LI JI_,_llie];_
The Series GM boiler is not equipped with a circulator or a means to control circulator operation. Provide circulator and zone controls, such as Taco zoning circulator or Honeywell R845.
i;q "JIr±l L_IL_I1_[_1i i : 11 II:VLeI Ii
Prepare sketches and notes of the layout to minimize the possibility of interferences with new or existing equipment, piping, venting and wiring.
4
Page 8
--m__
I Provide a sound, level foundation. Locate boiler as
near to the chimney or outside wall as possible and centralized with respect to the heating system.
2. Locate boiler in front of installation position before removing crate.
3 Separate the wood shipping pallet from the boiler
base by removing two (2) hold-down bolts at each end of the boiler base.
4. Move boiler into final position.
5
Page 9
g! [_r_ll[:[;| ['.,ll;,11_[€Ir=q_im3[_s]_h II;[*]l!_.']
Design piping and size circulator(s) to suit the system. Refer to Hydronics Institute Installation Guide 2000 and the Peerless Water Installation Survey for guidance.
L'I I:{e]lg:l:t _.'llJ'.J',_l_'l:lL_lm];|:lllJ:|k_
Install boiler to protect the gas ignition system components from water (dripping, spraying, etc.) during appliance operation and service (circulator replacement, condensate hap, control replacements, etc.).
1. Remove shipping nipple from supply tapping.
2. Install temperature-pressure gage with tee in supply tapping. Nipple, tee, bushing and gage are located in trim carton. See Figure 5.
3.
Install drain valve. Remove jacket front panel. Install drain valve with tee in return tapping. Nipple, tee, bushing and drain valve are located in trim carton. See Figure 7. Tee may be installed with run
in either horizontal or vertical orientation.
4.
Install supply piping, return piping and circulator.
See Figure 6.
a. If boiler is installed above radiation level, provide
a low water cutoff device in the supply piping above boiler. See Figure 6.
TEMPERATURE PRESSURE GAGE
F1-1/2" TEE
7! 1/2" X 8"
NIPPLE
I/2"× 1/4"
BUSHING
Figure 5: Temperature-Pressure Gage Installation
COLD
WATER
FILL
Figure 6:
SUPPLY
ALTERNATE CIRCULATOR
LOCATION _
SHUTOFF_
VALVE PRESSURE/ / sHuToPE/F
REDUCNO / / VALVE J L
VALVE_ /
_AIR VENT
AIR ELIMINATOR
CHECK
VALVE _
-- .--_DD,-
RETURN I
CIRCULATOR ___
DRAIN
VAI VE _-.
Typical Supply and Return Piping
i_LOW WATER
/ CUTOFF
/
! DRAFN
6
Page 10
b,
c.
d,
When system return water temperature will be below 130°F,,pipe the boiler with a bypass
arrangement to blend the system return and hot supply to obtain at least 130°F entering the
boiler. For more information on bypass piping,
consult the Peerless Water Installation Survey.
If this boiler and dislTibution system is used in conjunction with a refrigeration system, pipe the chilled medium in parallel with the boiler and install the proper valve to prevent the chilled medium from entering the boiler. See Figure 8.
When the boiler is connected to heating coils located in air handling units where they may be exposed to refrigerated air circulation, install flow contzol valves or other automatic means to prevent gravity circulation of the boiler water during the cooling cycle.
I:m [__'W_=ISlk'4I;|:lll:l= krl'-11.rd
I. Locate safet_ relief valve and nipple in tzim carton.
2. Install safety relief valve in 3/4 NPT tapping behind supply tapping. Safety relief valve must be installed
with spindle in vertical position. See Figure 9.
Figure 7: Drain Valve Installation
CHECK VALVE
Pipe the discharge of safety relief valve to prevent injury in the event of pressure relief, Pipe the discharge to a drain. Provide piping that is the same size as the safety relief valve outlet,
LiN_
WATER tHrEE WAY
I_ci[LL[R VALVE
Figure 8: Parallel Hook-up with Water Chiller
SAFETY
SUPPLY _ RELIEF
VALVE
/
/
\
/ TO DRA_N
Figure 9: Safety Relief Valve Installation
7
Page 11
1. See Figures i0 and 11 for basic zoned system
layouts. Circulators may be installed in either supply
or return piping. Refer to Peerless Water Installation
Survey for additional information.
2. Run each zone pipe down then up to zone to prevent air accumulation in piping•
3. If required, provide means to isolate and drain each zone separately.
3
FROM SYSTEM
ZONE ZONE ZONE
1 2 5
TO
BALANCING
VALVES
CONNECT TO
RETURN
(CIRCULATOR INLET)
H
Figure 10: Zone Piping with Zone Valves
Z C'r,!E _'_:'-
i
i
' _ I 'F I
d - i
I i
f
t + 4
(_ :£) ['i bJE I :
Z! i L}
FROM SYS!EI',,/
I
!
I
,. , L, I .• _ .2.
....................... ] 0
' -: 'i :t;
[ }
l
Figure 11: Zone Piping with Circulators
8
Page 12
I_il 1:1t,1:1:1_4::in-.J:Telld:loCiiI [el _
1, Consult the tank manufacturer's instructions for
specific information relating to tank installation. Size the expansion tank for the required system volume
and capacity. See Table 5 in Section 11 for boiler's water content,
2.
Expansion tanks are available with built-in fill valves and check valves for reducing supply water pressure
and maintaining minimum system pressure. Check the design features of the tank and provide valves as
necessa_j.
Refer to Figure 6 for typical expansion tank piping.
€11 Ih_lD]lH=[t,,]ll_=l;lcID] |vA_U:_I/::Ilt I:1:!:_11_:
Boiler may be used as heat soume for indirect-fired water heater. Refer to Figure 12 for typical piping. Follow the instructions provided by the water heater manufacturer. Pipe the water heater as if a separate space heating zone.
For new or existing systems that must be freeze- protected:
Use only inhibited propylene glycol solutions of up to 50% by volume with water. Ethylene glycol is toxic and can attack gaskets and seals used in hydronic
systems,
1.
2.
3.
Glycol for hydronic applications is specially formulated with inhibitors which prevent the glycol
from attacking metallic system components. Make certain that the system fluid is checked for the correct glycol concentration and inhibitor level.
Antifreeze solutions expand more than water For example, a 50% by volume solution expands 4.8% in volume for a temperature increase from 32°F to
180°E while water expands 3% with the same temperature rise. Allowance must be made for this expansion in system design.
For more information, consult the Peerless Water Installation Survey and the antifreeze manufacturer.
SUPPLY TC
SYSTErvl
RE tURN FROV,
SYSTEbi
TTq I I
ZONE
CIRCU LA TORS[}_8.._
v
HOT DOMESTIC
SUP'PLY
IN[I:C'F:SI FIRED
Wi- TER HEATER
",:. _},
},k: I',"
.', TF{ i;vP Y
S
. - J
>
DRAIN
! F '
! :
I i
L
Figure 12: Typical Piping with Indirect-Fired Water Heater
Page 13
W! ID);_l_ilil[oIo]B
1,
2.
3.
The boiler is equipped with a draft hood designed to: a. provide for the ready escape of flue gases from
the boiler in the event of no draft.
b. prevent a backdraft from entering the boiler.
c. control stack draft during operation. The draft hood must be installed without alteration.
Make certain there are no obstructions to airflow to the relief opening.
Position draft hood with 1" diameter hole in conical portion of draft hood (for vent safety shutoff switch) towards front right corner of boiler. Secure to flue collector with sheet metal screws. See Figure 13.
The boiler is equipped with a vent safety shutoff switch. The switch is shipped in a cloth bag attached to the harness on the exterior of the boiler. Attach switch to holes in the conical portion of the draft hood using the screws provided in bag. See Figure 13.
Vent safety shutoff switch wiring harness must extend to vent safety shutoff switch without excessive slack. To adjust harness length, squeeze strain relief bushing to release from jacket. Adjust harness to proper length. Reinsert strain relief bushing.
VENT SAFETY
SHUTOFFSCREWSMETALSHEETSWITCH_x
VENT SAFETY '_ / SHUTOFF SWITCH "_ WlRINC HARNESS_
Figure 13: Draft Hood and Vent Safety Shutoff
Switch Installation
INCORRECT
I
L__,
,{},THEr_
k:_ _]IN,S
APPLIANCE-
CORRECT
Figure 14: Venting Multiple Appliances
10
Page 14
[e,lqkV4:lL'hlii:,]l:Jh,_felF_qL'_le][_:ilLVJh'q=h,
1.
2.
3.
4.
Do not use one vent damper to control two or more heating appliances. See Figure 14.
Follow these and the installation instructions included with the vent damper. Observe the cautions and
warnings that accompany all instructions.
Provide minimum 6 inch clearance between automatic vent damper and combustible
construction. Increase clearance if required by vent damper manufacturer's instructions. Provide
adequate space for vent damper access and service.
The automatic vent damper can be mounted directly
onto the draft hood outlet or in vent piping close to
the boiler. See Figure 15 for installation with vent damper
mounted in vertical position. See Figure 16 for installation with vent damper mounted in horizontal
position. Mount the unit to avoid excessive heat on the operator or condensation drips into the operator.
a. Orient the vent damper operator to facilitate
connection of the vent damper harness to knockout on right side of boiler. See Figure 19.
b. Orient vent damper direction arrow in direction
of vent gas flow. Direction arrow must be visible
from front of boiler.
i,
2.
3.
4,
5,
6.
7.
Install vent piping in accordance with Part 7, Venting of Equipment, National Fuel Gas Code, ANSI
Z223.1/NFPA 54 or applicable provisions of the local building codes.
Inspect the existing chimney and lining for structural soundness, corrosion and perforations. Repair as
necessary.
Install vent pipe to slope upward at least I/4" per lineal foot between the draft hood outlet and the
chimney.
Before connection of joints, inspect the vent pipe interior for foreign objects such as tools, equipment,
rags, etc. and remove if present.
Insert vent pipe into but not beyond the inside wall of the chimney flue.
Do not connect vent connectors serving appliances vented by natural draft into any portion of mechanical draft systems operating under positive pressure.
Support horizontal portions of the venting system to prevent sagging by use of metal strapping or equivalent means. Locate supports at no more than
four (4) foot intervals, or in accordance with vent system manufacturer's installation instructions.
SLOPE UP A MINIMUM
OF
PER FOOT_
\
AUTOMATIC VENT
DAMPER_
AS REQUIRED
DRAFT HOOD
RELIEF OPENING
\
\
"DRAFT HOOD
OUTLET
Figure 15: Venting with Vent Damper in Vertical Position
11
Page 15
AUTOMATIC /- VENT TO
SLOPE UP VENT /CHIMNEY
A MINIMUM DAMPER 7 OF 1/4" / [ I
PER FOOT _
NENN
7
O'CLOCK 1 O'CLOCK
POSITION_ , /-- POSITION
VJJ/// s DA',,'PER
HEAT ....-.'_ S OPERATOR
ZONEJ __O0_ECONDENSATION
O'CLOCK J _5 O'CLOCK
POSITION POSITION
DO NOT MOUNT DAMPER
OPERATOR IN SHADED REGION
SECTION A--A
Figure 16: Venting with Vent Damper in Horizontal Position
At the time of removal of an existing boiler, follow these steps with each appliance remaining connected to the common venting system placed in operation, while the other appliances remaining connected to the common venting system are not in operation:
a. Seal any unused openings in the common venting
system.
b.
Visually inspect the venting system for proper size and horizontal pitch and determine there is no blockage or restriction, leakage, corrosion and other
deficiencies which could cause an unsafe condition.
C. Insofar as is practical, close all building doors and
windows and all doors between the space in which the appliances remaining connected to the common venting system are located and other spaces of the building. Turn on any clothes dryers and any appliance not connected to common venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a summer exhaust fan. Close fireplace dampers.
d,
e.
g.
Place in operation the appliance being inspected. Follow the lighting instructions. Adjust thermostat so appliance will operate continuously.
Test for spillage at the draft hood relief opening after 5 minutes of main burner operation. Use the flame of a match or candle, or smoke from a cigarette, cigar, or pipe.
After it has been determined that each appliance remaining connected to the common venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas-burning appliance to their previous
conditions of use. Any improper operation of the common venting
system should be corrected so that the installation conforms with the National Fuel Gas Code, ANSI
Z223.1/NFPA 54. When resizing any portion of the common venting system, the common venting
system should be resized to approach minimum size as determined using the appropriate tables located in the chapter "Sizing of Category I Venting Systems,"
of the National Fuel Gas Code, ANSI Z223.1/NFPA 54.
12
Page 16
I. Size and install the gas supply piping to provide a
supply of gas sufficient to meet the maximum demand of all appliances without undue loss of pressure between the meter and the boiler. Maximum permissible gas supply pressure to the
boiler is 13.5 inches water column.
2. Determine the volume of gas to be provided to the boiler Obtain this value by dividing the Btu per hour rating (on the boiler rating plate) by the heating value of the gas in Btu per cubic feet. Obtain the heating value of the gas from the gas supplier. As an alternative, use Table 1 to obtain the volume of gas to be provided to the boiler.
Table 1: Input (Cubic Feet Per Hour)
Model Natural Gas
GM-05 228 GM 06 285
GM-07 342 GM-08 399
Natural gas based on I000 Btu/Cubic Foot.
3. Use the value obtained above as the basis for piping sizing. Size the gas piping in accordance with Table
2. Consult the National Fuel Gas Code for other sizing options.
Table 2: Capacity of Schedule 40 Pipe
Capacity of Schedule 40 pipe (cu. fl. per hour) with pressure drop of 0.3 in. and specific gravity of 0.60. No allowance for an ordinary number of fittings is required.
Pipe _/4_ 1_ 1t/4" 1½"
Length
Feet Pipe Pipe Pipe Pipe
I0 ! 278 I 520 1,050 1,600
20 190 i 350 I 730 I,i00 30 I 152 285 ; 590 890
40 130 ! 245 500 760 50 115 i 215 440 670
60 105 195 400 610
Multipliers to be used with the above table when the specific gravity of the gas is other than 0.60:
Specific Gravity , . .0,50 0.55 0.60 0.65 0.70
Multiplier ........ 1.10 1.04 1.00 0.962 0.926
4. Connection of boiler to the gas piping system may be made on the left side or top of the boiler. See Figure 41 for jacket opening locations.
Use a pipe joint sealing compound that is resistant to
the action of liquefied petroleum gas. A non-resistant
compound may lose sealing ability in the presence of
this gas, resulting in a gas leak and fire or explosion
potential.
5.
6.
7.
Install a sediment trap. See Figure 17. Locate a tee in the drop pipe at same elevation as the gas inlet
connection to the boiler Extend the drop pipe to a pipe cap. As an alternate, the sediment trap may be
located in the boiler vestibule. See Figure 18.
Install a ground joint union ahead of the gas control assembly to permit servicing of the control. Some
local codes require an additional equipment shutoff valve when using the combination gas controls. If your code requires such a valve, a suggested
location is shown in Figure 17 or 18.
Check piping for leaks. Use an approved gas detector, a non-corrosive leak detection fluid or other
leak detection method. If leaks are found, turn off all gas flow and repair as necessary.
When checking for leaks, do not use matches, candles, open flames or other methods that provide a source of ignition,This can ignite a gas leak, resulting in fire or explosion,
EQUIPMENT SHUTOFF
VALVE
JACKET OROUND
JOINT UNION __
SEDIMENT
TRAP _ FLOOR
lINE
x
\
I
Figure 17: Gas Connection to Boiler - External
13
Page 17
8. Disconnect the boiler and its individual shut-off valve from the gas supply piping system during any pressure testing of that system at test pressure in excess of 1/2 psig (3.5 kPa).
Isolate the boiler from the gas supply piping system by closing its individual service valve during any pressure testing of the gas supply piping system at test pressure equal to or less than 1/2 psig (3.5 kPa).
9. Minimum permissible supply pressure for purposes of
input adjustment (Inches Water Column):
_ GM-07
Standing Pilot 4.8 5,5 ........
Intermittent 4.5 4.5 4.6 4.9 Ignition
10. Maximum permissible supply pressure to the boiler (Inches Water Column):
All models 13.5"
Ec_'UIP'dk N
FiI,' - r_
_])IN r fz
' C/ J
- !
Figure 18: Gas Connection to Boiler - Internal
14
Page 18
,d
E.']II:lIF--[,._;IC,.I_g
This unit when installed must be electrically grounded in accordance with the requirements of the authority
having jurisdiction or, in the absence of such requirements, with the current edition of the National Electrical Code, ANSI/NFPA 70.
r;l ITl_JI;] Ib,_[€
I. See Figure 19 for location of wiring and controls, use
Figures 22 and 23 to connect the boiler to a power supply and the connect components to the boiler.
2. Connect the boiler to a separate, permanently live
electrical supply line with a fused switch.
3. Connect the vent damper harness to the polarized
connector in the boiler vestibule as shown in
Figure 19.
3. Figure 25 shows typical wiring for one or more circulators.
4. Figure 26 shows typical wiring for zone valves.
Do not power zone valves directly from the boiler transformer, Doing so will greatly reduce the life of
the transformer. Use a separate transformer sized to handle the total of all zone valve electrical loads.
:J [e,]I_'{HIJIf_,'llie] -'_Y_[e]L_I=kVl_,l&vj =liVid|I;| h_[€
:l[e|_A!JI_1!!'-_1/ =1;i[H Ij I[*] ;I
1. A zone control is required to operate circulator(s)
when using a low voltage thermostat.
2. Taco Zoning circulator(s) can be used instead of mounting separate circulator r_lay(s) (Figure 20).
Wire low water cutoff to turn off power to boiler. See Figure 21 for Hydroleve1550 low water cutoff. Refer to
manufacturer's instructions for other low water cutoffs.
POLARIZED CONNECTOR
DAMPER
HARNESS
THERMOSTAT
VOLTAGE
POWER SUPPLY
BOX WITH PLATE
MOUNTED TRANSFORMER
Figure 19: Wiring Details
15
Page 19
.a
[.11[=(M=[q,(;([_f-'1ml('4_i_rmi'
f FROM t
THERMOSTAT --
OR OPERATING
CONTROL
/
TO JUNCTION 115V 60HZ
BOX PINK AND POWER SUPPLY GREY W_RES.
Figure 20: Taco Zoning Circulator Wiring
I f:J v' E,QIZ
FO HAIN
DISCONNECT S_'vl ICH
t
L2 _/ GXD
A
/, TO TRAXSFORM P B[ A/,_ ,',!;F
WHFF WIltS [ :': ,'_:[S I _!l}
L2 SHO//'4 {}_J WI_N{] [}/ 1_'
Figure 21: Hydrolovel 550 Low Water Cutoff Wiring
16
Page 20
- [_iR =iai=[_ d;t [,@',_'_i![(_]
(HOT) ?
TRANSFORMER
120VAC
f_c'Nwww_
24VAC
"- l:
i i i i
VENT I i
i i FLAM E
SAFETy i
LIMIT S_TC H CONTROL S_TCH
....
DAMPER STUB HARNESS _ _
Y Y
GAS VALVE t i
!
I
_ _ ,
LADDER LEGEND L_
120 VAC _IRING (LINE) IGNITER L
..... 24 VAC WIRING (LOW) ELEMENT _ENSOR LGROUND
(pILOT
NOTES TUBING)
ALL _RING MUST COMPLY WrTH APPLICABLE CODES, ORDINANCES AND REGULATIONS
bF ANY OF THE ORIGINAL WIRE AS SUPPLIED _TH THE APPLIANCE MUST BE REPLACED, IT MUST BE REPLACED WITH WIRE AS SHOWN OR _TS EQUIVALENT
VENT SAFETy_CGY _( _____ DAMPER PLUG OR VENT DAMPER
SHUTOF_yS_TCH _ OU_ HARNESS (WHEN USED)
=-R ..... ; ; 'I_'_DAMPER STUB HARNESS
_1 _ o I-i
LIMIT i I _ I _ SERVICE FUSED
i i : S_TCH DISCONNECT
I , , ,' , J HOT
I I . ' L _ TOMAN
JUNC TION I I LiI I I , _ _SV 60HZ DSCONNEC
BOX----.._ , I # " I " I _2 _ SWITCH
i J r i ,
40VA i i t L._
7 }1, ,,,
_! ....
llllll .....
\
BR ' 2 J'
_ : i I \ THESE,TEMSTOeE
LJllllkr-- 1 T ! SURPUEDBY_NSTALLER
i
i p
_ ' PR',IRR FLA_E
ROLLOUTSWPTCH
WIRE CODE
RED
ORANGE BK BLACK BR BROWN W WHITE GY GREY
GRGYW GREE_GREYWMrTE STRIPE Pl PINK
pR PURPLE
PILO T
[
CONNECTION DIAGRAM LEGEND
24 VAC SiZE IB AWG TYPE CL2X WIPE
........ 120 VAC SIZE 14 AWG TYPE TW TgFN WIRE
......... 24 VAC SIZE 16 18 AWC TYPE TW/TFFN OR CL2X WiRE
HONEYWELL PILOT WIRING
Figure 22: Connection and Schematic Diagram, intermittent Ignition
1.
2.
3.
4.
5.
Thermostat calls for heat.
Limit senses boiler water temperature. Prevents operation until water temperature falls approximately 15°F below the cut-out temperature.
Automatic vent damper (if used) opens. Damper must be in open position when appliance main burner(s) is operating.
Gas valve energizes.
a. Igniter on. b. Pilot gas on, igniting pilot.
Pilot flame detected.
a. Igniter off.
b. Main gas on, igniting main burners.
Note: If pilot flame is not detected within 30 seconds, the igniter is turned off for 30 seconds, and then turned back on. If the pilot is not detected within 30 seconds, the igniter and pilot gas are turned off for 5 minutes. The sequence then resumes at Step 4a.
6. Call for heat ends. a. Pilot and main gas off, extinguishing pilot and
main burners.
b. Automatic vent damper (if used) closes.
17
Page 21
[.II _ [r4"a_al
(HOT)
fRANSFORMER
ltSVAC
24VAC
II II
VENT I I FLAME
SAFETY
H T FF OPERATING _ ROLLOUT
UMIT S_U ITOH CONTROL SWITCH
I
DAMPER STUB HARNESS _ I
L_DDER LEGEND
115 VAC WIRING (LINE)
- 24 VAC WIRING (LO_)
i i i
_mAP
THERMOCOUPLE
NOT[SH -
ALL WIRING MUST COMPLY WITH APPLICABLE CODES, ©_D_NANCES AND REGULATIONS
.F AN_ OF Trl_ ORIGINAL WiRE AS SUPPLIED WITH THE APPLIANCE MUST _E RFPLACED :T MUST BE REPLACED WITH _RE AS SHOWN OR ITS FCUIVALENT
?
VENT
SAFETY
S_TC H
Ou
OR VENT DAMPER
HARNESS
SER_CE FUSED ]
S_TCH DISCONNECT
TO MAIN
I15V-60HZ DISCONNECT
S_TCH I
I
OPERATING CONTROl.
SUPPLIED BY INSTALLER
I I
L I
WIRE CODE [
RE D
ORANGE
BK BLACK BR BROWN
_y WHITE
OREY
GY W GREY/WHITE STRIPE
GR GREEN
PI PINK pR PURPLE
PILOT
PR PR FLAME
_ ROLLOUTS_,_ TCH
[ BR THERMOCOL
CONNECTION DLAGRAM LEGEND
24 VAC SEZE 18 AWG T_PE CL2X WIRE
115 VAC SIZE 14 AW0 TYPE TW TFFN _RE
_-- 24 VAC SIZE 16 18 AWG TYpE TW/TFFN OR CL2X WIRE
Figure 23: Connection and Schematic Diagram, Standing Pilot
1.
2.
3.
4.
5.
Thermostat calls for heat.
Limit senses boiler water temperature. Prevents operation until water temperature falls approximately 15°F below the cut-out temperature.
Automatic vent damper opens.
Gas valve energizes. Pilot flame detected by thermocouple. Main gas on,
igniting main burners.
Note: if pilot flame is not detected, main and pilot gas are automatically turned off. Pilot must be manually relit. See Figure 36 for Lighting
Instructions.
6. Call for heat ends. a. Main gas off, extinguishing main burners.
b. Automatic vent damper closes.
18
Page 22
START
TRIAL
FOR J
IGNITION
MAIN L
BURNER OPERATION
I APPLY24 VAC I
TO APPLIANCE
L THERMOSTAT J
CALLS FOR HEAT
,p,
I_LA_c_S'_A'_NO'._YES
INTERNAL CHECK OKAY? [
I
_YES
PILOT VALVE OPENS I
m
IGNITER POWERED
I
[ uo
IS SENSED DURING TRIAL FOR IGNITION?
YES
IGNITER OFF |
l
MAIN VALVE OPENS
J
WAIT FOR FLAME SIGNAL
TO DISAPPEAR
PILOT VALVE/IGNITER
REMAIN OFF
"1
PILOT VALVE CLOSES /
IGNITER OFF
/
I FIVE-MINUTE RETRY IDELAY
J,
END
I FLAME SIGNAL LOST?
_NO
I THERMOSTAT CALL FOR I
HEAT ENDS
I"'A'NANOPIL VALVESCLOSEI
I
MAIN AND PILOT VALVES CLOSE I
I
FLAME LOST MORE THAN Ni NO
y--
FIVE TIMES IN ONE CALL FOR HEAT?
I YES
Z_ IGNITER WILL TURN OFF ABOUT 30 SECONDS INTO THE TRIAL FOR IGNITION.
IF THE PILOT FLAME HAS NOT LIT, IT WILL TORN BACK ON FOR THE FINAL 30 SECONDS OF THE 90 SECOND TRIAL FOR IGNmON. THE PILOT VALVE WILL BE ENERGIZED DURING THE ENTIRE TRIAL FOR IGNITION. THIS IS NORMAL OPERATION FOR THIS GAS IGNITION SYSTEM.
Figure 24: System Operating Sequence
19
Page 23
II 5V/6OHZ
TO MAIN
DISCONNECT
SWITCH
TO BOILER
JUNCTION BOX
PINK & GREY
_RES
L2
LI (HOT)
t F
ZONE
CIRCULATOR
L#
L
ZONE I
THERMOSTAT
24V O
ZONE 2
CIRCULATOR
ZONE 2
THERMOSTAT
24V (_)
I
FIELD INSTALLED
R845A
RELAY
L_ND
-- - LINE VOLTAGE LOW VOLTAGE
Figure 25: Circulator Wiring
115V/60HZ --L1 (HOT)
TO MAIN L2
DISCONNECT
SWITCH
f
I I
I I
I I FIELD
I INSTALLED I JUMPER
I
I I
! I
t I.... I-
I I I I I
._ _$__ I__ I....... ____I__
I I I I I
I F J I I r j
I I I I I
©i ©
I
ZONE 1 I ZONE 2
THERMOSTAT I THERMOSTAT
24V I 24V
f-
I
?----r ..... ?
R R R R
I I
ZONE 3 ZONE 4
THERMOSTAT I THERMOSTAT
24V I Z4V
TO BO+LE
JUNCTION
PINK & GF
WIRES
CIRCULATOR __+
FIELD MOUNTED
TRANSFORMER
24V 4OVA
4, ._-
NOTES." 1 ALL WIRING MUST COMPLY WITH APPLICABLE CODES, ORDINANCES
AND REGULATIONS.
2 IF CODES PERMtT, VBO43E AND VBO43F MAY BE USED
INTERCHANGEABLY WHEN _RED AS SHOWN.
3 DO NOT USE BOILER TRANB_-ORMER TO POWER ZONE VALVES
LggE_
-- - LINE VOLTAGE
.... LOW VOLTAGE
Figure 26: Zone Valve Wiring
2O
Page 24
P"_I Kit =lkH=1;_.'_,
This section is in regard to requirements of the ASME
CSD 1 1998 Code. Controls and Safety Devices for Automatically Fired Boilers, which may be in effect in your area Any omissions or discrepancies that may exist
between these instructions and the CSD-1 code itself, the code itself takes precedence. The CSD-I Code may
be ordered by calling 1-800-THE-ASME.
I I/2 ¢ROSS_
BUSHING
(MANUAL RESET)
I I/2 × 1
& I × 3/_.
:t! [e,_",le]IbV_,q;tl[el: I:l::[eleJl;t:;l_VAl::iL'qilK
The Series GM is CSA certified to ANSI Z21.13 and as such meets all CSD-I Part CF requirements for
combustion side controls for units under 400,000 btuh input. No other combustion side controls are required to
meet CSD-I.
Figure 27: CSD Piping, Using Cross Fitting
_ [e,_...'.lm]I:]±!;tEe4rilJ ;,l=[e).llll,l:lLV_l:l_/l_
CSD-I requires the following waterside controls to be
installed with the boiler:
1. Manual reset low water cut-off (LWCO), such as Hydrolevel 550SV Probe (29028)
2. Manual reset high limit, such as Honeywell L4006E1117 (50536).
Install these controls in the supply piping. Figures 27-29 show typical piping using a probe style low water cut-off.
See CSD-1 code for requirements when using a float i_pe low water cut-off.
No valves are allowed between these controls and the boiler supply connection.
Low water cut-off must be positioned higher than the top of the boiler. See figure 30 for wiring details. Follow
all instructions furnished by the control manufacturers.
Figure 28: CSD Piping, Vertical Using Tee's
I. Modular Boilers
a. CSD-1 requires a manual reset low water cut-off
and manual reset high limit to control the
modular boiler system. The individual boiler modules are not required to have a low water cut-off or manual reset high limit.
b. To be considered a modular boiler system, the
individual boiler modules are not allowed to be isolated from the main headers and controls with
stop valves.
2. Multiple Boilers CSD-I requires a manual reset low water cut-off and
manual reset high limit on each individual boiler.
For more information on modular and multiple boiler systems, see Peerless Flex-Heat manual or contact
Peerless Heater company.
HQN£ Y_LL L4006[
OMIT (MANUAl. R(_T)
Figure 29: CSD Piping, Horizontal
H_X _NG
550 SV
L'/_O (MANUAL RESET)
MAINTAIN 2" M4NIMUM CL[ARANC_ TO 0RAFT HO00. 4" "_ERTICAL
CL[ARANC_ BELOW
R(U(F _NING
21
Page 25
[r_ _-.t,_[o_e_ll_l::[olUJld=l,'_l=l;kn_ [_]_
Note the following elec'aical requirements per CSD-I Section CE-II0(a):
"A disconnecting means capable of being locked in the open position shall be installed at an accessible
location at the boiler so that the boiler can be disconnected from all sources of potential. This
disconnecting means shall be an integral part of the boiler or adjacent to it."
"A manually operated remote shutdown switch or circuit breaker shall be located just outside the boiler room door and marked for easy identification. Consideration should be given to the type and location of the switch to safeguard against
tampering. Ifthe boiler room door is on the building exterior, the switch should be located just inside the door. If there is more than one door to the boiler
room, there should be a switch located at each
door."
"The emergency shutdown switch or circuit breaker must disconnect all power to the burner controls."
TO BOILER
GROUND
SCREW
115V-6OHZ
TO MAIN
DISCONNECT SWITCH
(HOT) I
TO _ANSFORMER BLACK AND WHITE
WIRES. REPLACES L1 AND L2 SHOWN
ON BOILER WIRING DIAGRAM.
L%o"Oc%bA %SE'O
m
HONEYWELLUMIT
L4006E --_
115V-6OHZ
ALARM CIRCUIT
(WHEN REQUIRED)
Figure 30: CSD Low Water Cut-Off/Limit Wiring
22
Page 26
V±_o] _vfl_ IH_ilIIIL'I[e,.ImiI-"I_ IIL_[,."_1ir±lIIIIV_I[o] i
].
2.
3.
4_
5.
6.
7.
Confirm that all water, gas and electridty are turned off.
Inspect the boiler combustion chamber for foreign objects and remove if present,
Check physical condition of burners and pilot. Make certain that there are no unusual bends or
perforations in the burners or pilot. Replace components if necessary.
Veri_ that water piping, venting, gas piping and electrical wiring and components are installed properly. Refer back to previous sections of these instructtuns as well as equipment manufacturer's instructions as necessary.
Fill the boiler and system with water, making certain to vent all air from all points in the system. To check
water level in the system, open and close each vent in the system. Water should exit from each vent when
it is opened.
The pressure reducing valve on the fill line will typically allow the system to be filled and pressurized to 12 psi. Consult the valve and expansion tank manufacturer for more specific information.
Check joints and fittings throughout the system for leaks. If leaks are found, drain the system and repair
as required.
8. Connect a manometer to 1/8 NPT tapping provided on the manifold. See Figures 31 and 32.
9. Confirm that the gas supply pressure to the boiler is above the minimum and below the maximum values
for the gas being used. See the end of Section 5 for these values. If a supply pressure check is required,
isolate the boiler and gas valve before performing the
pressure check. If the supply pressure is too high or too low, contact the gas supplier,
I0. Turn on electricily and gas to boiler
11. Light the boiler by following the Lighting/Operating Instructions label mounted to the jacket panel. The
initial ignition may require several tries as the piping
is purged of air.
12. Use the sequence descriptions in Figures 22, 23 and 24 in Section 6 (Electrical) to follow light-off and shutdown sequences and to assist in diagnosing
problems. If the boiler does not function properly, consult Section 9, Troubleshooting.
13. The gas manifold and control assembly provided with this boiler meet with all criteria regarding safe lighting and performance as specified in ANSI
Z21.13, Gas-Fired Low Pressure Steam and Hot
Water Boilers. The gas manifold and control
assembly are made of gas-tight, completely factory assembled and installed components of the base
assembly. See Figure 31 and 32.
23
Page 27
MAIN BURNER
A
r GAS
VALVE /- PILOT
GAg _
MANIFOLD PILOT TUBING
SECTION A-A
Figure 31: Gas, Valve, Manifold and Burner Assembly, GM-05/06 (Standing Pilot shown, Intermittent
ignition similar)
MAIN BURNER
GAS VALVE
S PILOT
_ PILOT TUBING
SECTION A A
TEST TAPPING J
L__GAS MANIFOLD
ORIFICE SPUD
Figure 32: Gas. Valve, Manifold and Burner Assembly, GM-07/08 (Intermittent ignition)
]r : T
F: '-4 iRE
PRESSURE REGULATOR ADJUSTblENT (UNDER CAP SCREW) --
\ P i C'f '
*, T "id /
I)l )[ ,[ IUSTMENT
_lu F, k' ' AP SCREW)
Figure 33: Valve Tapping and Adjustment Screw
Locations, Intermittent ignition
24
OUTLET PRESSURE
rAP
z" WIRING
J FL ,MINA[ S
INLET I_ I_ OUTLET
/
THERbIS(t()UP i // COrINg(}: ON z
Figure 34: Valve Tapping and Adjustment Screw
Locations, Standing Pilot
Page 28
FOR YOUR SAFETY READ BEFORE OPERATING
I WARNING: If you do not follow these instructions exactly, a fire or explosion may result
I
causing property damage, personal injury, or loss of life
I
A. This appliance is equipped with an ignition device
which automatically lights the pilot, Do not try to
light the pilot by hand.
If you cannot reach your gas supplier, call the fire department
B.
BEFORE OPERATING smell all around the
appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.
WHAT TO DO OF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electric switch; do not use any phone in your building.
Immediately call your gas supplier from a neighbor's phone. Follow the gas
supplier's instructions.
C,
Use only your hand to slide the gas control switch.
Never use tools, If the switch will not slide by hand, don't try to repair it, call a qualified service technician Force or attempted repair may result in a fire or explosion,
D, Do not use this appliance if any part has been under
water. Immediately call a qualified service technician to inspect the appliance and to replace any part of
the control system and any gas control which has
been under water,
_ OPERATING INSTRUCTIONS
1. STOP! Read the safety information above on this label.
5. If the gas valve is not visible, remove control access panel.
2.
3.
4.
Set the thermostat to the lowest setting. Turn off all electric power to the appliance. This appliance is equipped with an ignition device
which automatically lights the pilot. Do not try to
light the pilot by hand.
/-GAS CONTROL
SWITCH
OUTLET _II _IIINLET
6. If the gas control switch is not in the "OFF" position, slide the switch to "OFF".
7. Wait five (5) minutes to clear out any gas. If you then smell gas, STOP! Follow "B" in the safety
information above this label. Ifyou don't smell gas,
go to the next step.
8. Slide the gas control switch to "ON".
9. Replace control access panel, if applicable.
10. Turn on all electric power to the appliance.
11. Set the thermostat to desired setting.
12. If the appliance will not operate, follow the instructions "To Turn Off Gas To Appliance" and call
your service technician or gas supplier.
TO TURN OFF GAS TO APPLIANCE
1, Set the thermostat to lowest setting. 4. Slide the gas control switch to "OFF".
2. Turn off all electric power to the appliance if service 5. Replace control access panel, if applicable. is to be performed.
3. If the gas valve is notvisible, remove the control access panel, sv9501/sv96019348
Figure 35: Operating Instructions
25
Page 29
FOR YOUR SAFETY READ BEFORE LIGHTING
I WARNING: If you do not follow these instructions exactly, a fire or explosion may I
result causing property damage, personal injury or loss of life. I
A. This appliance has a pilot which must be lighted by
hand. When lighting the pilot, follow these Instruc- tions exactly.
B. BEFORE OPERATING smell around the appliance
area for gas. Be sure to smell next to the floor because some gas Is heavier than air and will settle
on the floor.
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance
Do not touch any electric switch; do not use any phone in your building.
Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's
instructions.
If you cannot reach your gas supplier, call the
fire department.
C. Use only your hand to push in or turn the gas con-
trol knob. Never use tools. If the knob will not push in or turn by hand, don't try to repair It, call a quail- fled service technician. Force or attempted repair may result in a fire or explosion.
O.
Do not use this appliance if any part has been under water. Immediately call a qualified service techni-
cian to inspect the appliance and to replace any part of the control system and any gas control which
has been under water.
LIGHTING INSTRUCTIONS
1. STOP! Read the safety information above on this label.
2. Set the thermostat to lowest setting.
3. Turn off ell electric power to the appliance.
4. If the gas valve is not visible, remove control access panel.
5. If the gas control knob is not in the "OFF" position, turn the knob clockwise F_ to "OFF."
RED RESET BuI-rON
Gas Control Knob (shown in =OFF"
8. Find pilot--follow metal tube _n from gas valve. The pilot Is
between two burner tubes.
Pilot Burner
9. Turn the gas control knob counterclockwlse f'_to
"PILOT."
10. Push in red reset button all the way and hold In. Immediately light the pilot with a match. Continue to hold the reset button In for about one (1) minute
after the pilot is lit. Release button and it will pop back up. Pilot should remain lit. If it goes out, I_peat steps 5 through 10.
GAS
INLET
If button does not pop up when released, stop and Immediately call your service technician or
gas supplier.
If the pilot will not stay lit after several tries, turn the gas control knob to "OFF" and call
your service technician or gas supplier.
6. Walt five (5) minutes to clear out any gas. Then smell for gas, Including near the floor. If you smell
gas, STOP] Follow "B" in the safety Information
above on this label. If you don't smell gas, go to the
next step.
7. Remove the pilot access panel, if supplied, located below and behind the gas valve directly above burn-
er tubes
11. Replace pilot access panel, if applicable.
12. Turn gas control knob counterclockwise
to "ON."
13. Replace control access panel, if applicable.
14. Turn on all electric power to the appliance.
15. Set thermostat to desired setting.
_TO TURN OFF GAS TO APPLIANCE _
1. Set the thermostat to lowest setting.
2. Turn off all electric power to the appliance If service is to be performed.
3. If the gas valve is not vlslble, remove control access panel.
4. Turn the gas control knob clockwise F'_ to "OFF."
5. Replace control access panel, if applicable.
H24V VR8200 9177R
Figure 36: Lighting Instructions
26
Page 30
I:]q [e[o)l,_i d;{el I Ie):_'_ed;t I_ | [o]L'_:
See Figure 37 for locations of these devices.
1. FLAME ROLLOUT SAFETY SHUTOFF SWITCH A thermally activated switch located above the
burners on the inner front jacket panel The flame rollout safety shutoff switch will sense excessive temperature caused by continued flame rollout and shut down main burner gas. This is a non-recycling switch that must be replaced once activated.
2.
VENT SAFETY SHUTOFF SWITCH A thermally activated, manually resetable switch located on the
draft hood. If venting system becomes partially or totally blocked, the vent safety shutoff switch will
sense excessive temperature caused by flue products exiting the draft hood relief opening and shut down main burner gas.
lel [q-'l=(_][41L:[ctl:]lJ;t_l=l.'t IIL'_I:,LIII
3.
LIMIT - A thermally activated, manually adjustable switch located in the upper right side of boiler vestibule. The limit senses supply water temperature and will shut down main burner gas if the supply water exceeds the preset temperature limit. This is a recycling switch that will automatically reset when the supply water falls below the preset temperature.
4.
LOW WATER CUT-OFF (FOR GRAVITY SYSTEMS
OR HOT WATER BOILERS INSTALLED ABOVE
RADIATION LEVEL) - A level-sensing device (float or probe) located in supply piping near the boiler. If water level in the system drops below the control's position, it will shut down main burner gas. The
conhol will automatically reset once the water level rises above its position.
2.
3.
4,
To adjust gas pressure, turn adjusting screw of gas pressure regulator counterclockwise to decrease pressure, clockwise to increase pressure. Refer to
Figure 33 and 34 for location of gas pressure regulator, Replace the cap screw when adjustment is complete,
In no case should the final manifold pressure vary
more than +0.3 inches water column from the
above specified pressures. Any necessary major changes in the flow should be made by changing the size of the burner orifice spuds.
When adjustment is complete, turn off boiler, gas
flow and eleclricily to boiler Remove manometer
connection from valve and plug tapping with plug provided. Turn utilities back on and resume
checkout.
1. Refer to rating label mounted on the jacket top panel to obtain the rated BTU per hour input. In no case
shall the input to the boiler exceed the value shown
on the rating label.
2. Check input by use of the following formula (Peerless suggests reading meter for 2 Cu.Ft.):
BTU/Hr. Input-3600 x F x H
T
3600 - Seconds per hour
F - Cubic Feet of Gas Registered on Meter
H - Heat Value of Gas in BTU/Cubic Feet
T - Time in Seconds the Meter is Read
3. As an alternative, use Table 3. Use the heating value provided by gas supplier. Use a stopwatch to record the time it takes for 2 cubic feet of gas to pass through the meter. Read across and down to
determine rate.
I, Using the manometer setup installed in part 8A, set
manifold pressure.
3 VENT DAMPER
VENT SAFETY SHUTOFF SWITCH SAFETY RELIEF VALVE
JRE PRESSURE GAGE
LIMIT
GAS VALVE
FLAME ROLLOUT SWITCH
PILOT (NOT SHOWN)
Figure 37: Control Locations
27
Page 31
Table 3: Meter Conversion - Natural Gas
Burner inputs in Btu!hr for various meter timings and heat values. (Tables based on 2 cubic feet of gas through meter).
Time that Heat Value of Gas
meter is (Btu/cubic foot)
read (sec)
25 30 35 40 45
50 55 60 65
70 75
80
85 90 95
I00 I05
110 115 120 125
1000
288000 240000 205714
180000 160000 144000 130909
120000 110769 102857
96000 90000 84706 80000
75789 72000 68571 65455 62609 60000
57600
1025 1050
295200 302400 246000 252000 210857 216000
184500 189000
164000 168000 147600 151200 134182 137455
123000 126000 113538 116308
105429 108000
98400 100800 92250 94500
86824 88941 82000 84000
77684 79579 73800 75600
70286 72000 67091 68727 64174 65739 61500 63000 59040 60480
I_q [0_:I:[_][_o1111 I'] ;{o1_1:11]lJ.'t
1. After starting the boiler, be certain all controls are working properly. Check to be sure that the limit will
shut off the boiler in the event of excessive water temperature. This can be done by lowering the limit
setting until the main burners shut down. When proper limit function is confirmed, return the dial to
its previous setting.
2. To check operation of the ignition system safely
shut-off features: a. Standing Pilot:
i) Turn the gas control knob counterclockwise
to "PILOT". The main burner should go out
and the pilot should remain lit.
ii) Extinguish the pilot flame. Pilot gas flow
should stop within 2-1/2 minutes. Complete shutdown is proven since the safely shut-off
valve has stopped main and pilot gas flow.
iii) Reset the boiler by following Lighting
Instructions.
28
iv) Observe boiler operation through one
complete cycle.
b. Intermittent Ignition System:
i) Turn gas supply off.
ii) Set thermostat or controller above room
temperature to call for heat. Watch for igniter glow at pilot burner.
iii) Igniter will continue to glow for 30 seconds,
de-energize for 30 seconds, then re-energize and glow for another 30 seconds. It will then de energize for 5 minutes before restarting
the sequence.
iv) Turn gas supply on.
v) Reset the boiler and control by following
Operating Instructions.
vi) Observe boiler operation through one
complete cycle.
3.
4.
5.
6.
7.
8.
9.
10.
Low Water Cut-Off (if used) - Consult the manufacturer's instructions for the low water cut-off
operational check procedure.
Check the system to make sure there are no leaks or
overfilling problems which might cause excessive make-up water to be added. Make-up water causes liming in the boiler and brings in oxygen. Oxygen can cause severe damage to the boiler though
oxygen corrosion pitting.
Check the expansion tank and automatic fill valve (if used) to confirm that they are operating correctly. If either of these components causes high pressure in the system, the boiler relief valve will weep or open, allowing fresh water to enter the system.
Do not allow the system controls to subject the boiler to excessively low water temperatures, which would cause condensation of flue gases and corrosion of the boiler. Operate the boiler at a temperature above 130°E Adjust the boiler limit as required to maintain boiler temperature above this level.
Check the general condition of the system including piping support, joints, etc. Check cleanliness of the radiators, baseboard units and!or convectors. Clean them to the extent possible. If radiators do not heat evenly, vent any remaining air from them.
Review operation and User's Information Manual with end-user
Complete the Warranty Card and submit it to Peerless Heater Company.
Hang the Installation, Operation and Maintenance Manual and User's Information Manual in an
accessible position near the boiler.
Page 32
Intheeventofashut-downcausedbyapilotoutage, actionoftheventsafelyshutoffswitchorflamerollout safelyshutoffswitcheffectingashut-downofthemain
burners:
a. RefertotheLighting/OperatingInstructionsin
Figures35and36toproperlyturnoffthegastothe boiler.
b. Turnoffallelectricpowertotheboiler. c Callaqualifiedheatingserviceagencyorlocalgas
companyandhavethecauseoftheshut-down investigatedandcorrected.
d. RefertoLighting/OperatingInstructionstore-start
boiler.
I:l! I / ;{olll :tII :{.'l :[olo;I / IL_[€-I[_lll ID]@
Use Table 4 to assist in determining causes and
providing corrective actions to boiler problems. Refer
also to Figure 38 to troubleshoot the Intermittent Ignition
System Control. These guides must be used only by
qualified service technicians. These individuals must follow all applicable codes and regulations in repair of any boiler problems.
When servicing or replacing items that communicate with the boiler water, be certain that:
There is no pressure on the boiler.
The boiler is not hot.
The power is off.
When servicing the gas valve or pilot, be certain that:
The gas is off.
The electricity is off.
Do not use this appliance if any part has been under
water. Improper or dangerous operation may result.
Immediately call a qualified service technician to inspect the boiler and to replace any part of the
control system and any gas control which has been
under water.
Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing.
Should overheating occur or the gas supply fail to shut off, do not turn off or disconnect the electrical supply to the pump. This may aggravate the problem and increase the likelihood of boiler damage. Instead, shut off the gas supply at a location external to the appliance.
29
Page 33
Table 4: Boiler Troubleshooting Guide
Burners not functioning
1 No power.
2 Limit (aquastat) not working
3 Flame rollout switch open. 4 Blocked vent switch open
5 Gas oft at boiler gas valve.
6 Gas off external to boiler. 7 Plugged orifice spuds.
8. Defective gas valve.
9. Improper wiring.
10 Vent damper malfunctioning.
Burners will not shut 1 Defective gas valve.
down.
Flashback or burning at orifice spuds.
Delayed ignition
Excessive condensation in vent.
Boiler not heating
properly.
Fumes or gas odors
2. Short circuit.
1. Manifold gas pressure too low.
2. Improperly sized/drilled orifice spuds.
3. Leaking gas valve.
4. Burrs on orifice.
5. Low supply gas pressure.
6 Excessive downdraft or draft problems in
boiler room.
I. Insufficient pilot flame.
2. Pilot burner/orifice clogged.
3. Overfiring
4. Misaligned burners or pilot.
5. Draft problem in boiler room.
I. Underftring.
2. Limit (aquastat} set too low.
3. Vent pipe too long.
4. Inadequate chimney or venting system.
I. Underfiring.
2 Limit set too low. 3, Air in system.
4 Circulator malfunctioning.
5. Circulation system dogged.
6. Incorrect thermostat heat anticipator setting.
1 Leaks in gas piping or fittings.
2 Leaks in gas service line or meter. 3 Obstructed chimney. 4 Obstructed flueways or vent.
5. Undersized chimney or vent, high draft loss in vent.
6. Draft problem in boiler room.
7. OverfiPng. 8 Vent damper malfunctioning.
1 Check line voltage wiring and fuses.
2. Check wiring and contacts, relay, temperature setting. Clean and adjust as necessary
3. Replace switch. Locate cause and correct
4 Reset blocked vent switch Locate cause and correct, 5 Start boiler using Lighting/Operating
Instructions.
6. Check any gas valves in the line
7. Check, clean and re-install.
8. Use Figure 38 to troubleshoot intermittent ignition gas valve. Replace if necessary.
9. Check and correct in accordance with wiring
diagrams in Section 6.
10. Refer to vent damper manufacturer's instructions Replace if necessary.
1. Use Figure 38 to troubleshoot intermittent
ignition gas valve. Replace if necessary
2. Check and correct wiring,
1. Adjust to proper pressure
2. Install correct spuds.
3, Replace valve.
4. Remove bun's.
5. Contact gas supplier if natural gas. Adjust regulator if LP gas.
6. Check air supply, ventilation and venting system.
1 Increase pilot gas flow
2. Clean pilot burner and orifice
3. Reduce rate to input on rating label
4. Realign burners or pilot.
5. Check air supply, ventilation and venting system.
I. Increase rate to input on rating label.
2. Reset limit (aquastat) to higher setting.
3. Reposgion boiler to reduce length.
4. Check chimney and venting recommendations.
i. Increase rate to input on rating label
2. Reset limit (aquastat) to higher setting.
3. Vent air from all points in system.
4. Check circulator, replace if necessary.
5. Shut down and cool boiler, drain and flush system.
6. Adjust heat anticipator.
1. Locate and repair or replace.
2. Shut down boiler and notify gas provider.
3. Check, repair and/or clean chimney.
4. Clean flueways or vent and remove obstructions
5. Check National Fuel Gas Code and vent manufacturer's recommendations.
6. Check air supply, ventilation and venting system.
7. Reduce rate to input on rating label.
8. Refer to vent damper manufacturer's instructions.
Replace if necessary.
3O
Page 34
START
I TURN OFF GAS SUPPLY
ASSURE GAS VALVE SWITCH IS IN "ON" POSITION
DISCONNECT SYSTEM CONTROL
HARNESS
SET THERMOSTAT TO CALL FOR HEAT
CHECK FOR PROPER VOLTAGE NI NO_I
i
AT CONTROL HARNESS (SEE INSET
YJ
A). VOLTAGE SHOULD BE 24V BETWEEN THERMOSTAT AND 24V COMMON, AND 24V BETWEEN
24V COMMON AND 24V HOT.
YES !
PLUG HARNESS INTO GAS VALVE CONTROL. WAIT FOR INTERNAL
CHECK DELAY
/
IGNITER WARMS_UP AND NO _ I
IVES I
I e TURN ON GAS SUPPLy _-_
PILOT BURNER LIGHTS
YES
YES
I
'r
SYSTEM IS OKAy
I
I
CHECK:
LINE VOLTAGE POWER
LOW VOLTAGE TRANSFORMER
LIMIT CONTROLLER
THERMOSTAT
WIRING
VENT DAMPER IS OPEN AND END
SWITCH MAKES
UNPLUG PILOT BURNER CABLE.
I"
MEASURE VOLTAGE AT GAS VALVE HSI ELEMENT OUTPUT (SEE INSET B)
24V NOMINAL
_ YES
REPLACEIGNITER/FLAME ROD ASSEMBLY I I
I
RECONNECT PILOT BURNER CABLE 1
I
CHECK THAT PILOT GAS IS FLOWING. I NO]1_._.__]1_'
WAIT TO ASSURE PILOT GAS TUBING
I '
IS PURGED.
_ YES
M_ESURE VOLTAGE BETWEEN 24V _
HOT AND 24V COMMON LEADS TO GAS
[,
VALVE. MUST MEASURE AT LEAST
19.5 VAC WITH IGNITER POWERED.
SEE INSET A TO IDENTIFY PROPER
LEAD. THtS CHECK MUST BE DONE WITH THE GAS VALVE CONNECTED
AND IGNITER POWERED.
YES
REPLACEIGNITERJFLAME RODASSEMBLY I
CHECK THAT PILOT FLAME MAKES GOOD CONTACT WITH PILOT BURNER
FLAME ROD.
CHECK FOR GOOD ELECTRICAL CONNECTION THROUGH THE PILOT TUBING
IF BOTH OF THE ABOVE ARE GOOD, REPLACE IGNITER/FLAME ROD
ASSEMBLY.
CYCLE THERMOSTAT OFF AND BACK ON I
MAIN BURNER LIGHTS
I I
INSET A
END VIEW OF
24 VOLT CONTROL THERMOSTAT HARNESS
CONNECTOR
VOLTS
24 VOLT 24 VOLT COMMO
VOLTS HOT
CHECK FOR DAMAGED OR MISSING TERMENALS IN CONNECTOR
INSET B
[]
REPLACE GAS VALVE I
CABLERECONNECTPILOT BURNER I
REPLACE GAS VALVE I
CHECK TRANSFORMER AND ILINE VOLT SUPPLY
REPLACE GAS VALVE 1
Figure 38: Intermittent Ignition System Troubleshooting Sequence
31
Page 35
i.
2_
Disconnect this boiler from the gas supply piping during any pressure testing of the gas system.
Check pipes adjacent to cold walls or in unheated spaces. Insulate and tape them if necessary to be sure they can't freeze up. Keeping the water moving at all times will reduce the likelihood of freezing. See
Section 3 for antifreeze instructions.
3,
4.
If there is considerable foreign matter in the boiler water, the boiler should be shut down and allowed to cool, then drained and thoroughly flushed out. Use
the drain valve at the bottom of the return connection to drain the boiler. Pipe the drain cock to
a suitable drain or containment device if antifreeze is used. Flush the system to remove remaining matter.
If there is evidence that hard scale has formed on the internal surfaces, the boiler should be cleaned by
chemical means as prescribed by a qualified water treatment specialist.
There must not be signs of continuous wetness at the chimney. If signs of continuous wetness are
observed, a qualified service agency must be consulted to modify the vent configuration to prevent
the formation of condensate.
Daily boiler observation can be performed by the owner. If any potential problems are found, a qualified installer
or service technician/agency must be notified.
I,
Remove any combustible materials, gasoline and other flammable liquids and substances that generate flammable vapors from the area where the boiler is
contained. Make certain that the boiler area has ample air for combustion and ventilation and that
there are no obstructions to the free flow of air to and from the boiler.
2.
3.
Observe general boiler conditions (unusual noises, vibrations, etc.)
Observe operating temperature and pressure on the combination gauge located on the left side of the boiler. Boiler pressure should never be higher than 5 psi below the rating shown on the safety relief valve (25 psig maximum for a 30 psig rating, 45 psig maximum for a 50 psig rating). The valve rating can
be found on the top of the safety relief valve (see Figure 5 for location of the safety relief valve). Boiler
temperature should never be higher than 250 ° E
4. Check for water leaks inboiler and system piping.
5. Smell around the appliance area for gas. If you smell gas, follow the procedure listed in the Lighting/Operating Instructions in Section 8.
[4vA_l _ _ [4 li'mLIivli i" i :[o) IH_ :| I LII_.'_ _
1. Flush float type low water cut-off (if used) to remove sediment from the float bowl as stated in the
manufacturer's instructions.
I iJLVj[o] _/ / :Ik'ii_i_j / i: i :{o] II _-I h_Ill..-1:
1. Check boiler room floor drains for proper functioning.
2. Check function of the safety relief valve (monthly unless specified otherwise by manufacturer) by performing the following test:
a. Check valve piping to determine that it is
properly installed and supported.
b. Check boiler operating temperature and pressure.
c. Lift the try lever on the safety relief valve to the
full open position and hold it for at least five seconds or until clean water is discharged.
d.
Release the try lever and allow the valve to close. If the valve leaks, operate the lever two or three times to clear the valve seat of foreign matter It may take some time to determine if the valve has shut completely.
e. If the valve continues to leak, it must be replaced
before the boiler is returned to operation.
fi Check that operating pressure and temperature
have returned to normal.
g. Check again to confirm that valve has closed
completely and is not leaking.
3. Test low-water cut-off (ifused) as described by the
manufacturer.
4. Test limit as described in Section 8E, "Check-Out
Procedure."
5. Test function of gas safety shut-off features as
described by gas valve and ignition control manufacturer.
6. Cycle the boiler at least once and check operation of
the vent damper.
32
Page 36
When servicing or replacing components, be absolutely certain that the following conditions are met:
Water, gas and electricity are off.
The boiler is at room temperature.
There is no pressure in the boiler.
1. Check flueways and burners for cleanliness and clean if necessary. Use the following procedure if cleaning is required:
a. Refer to the Lighting/Operating instructions in
Figures 35 and 36 to properly turn off the gas to the boiler.
b. Turn off all electrical power to the boiler.
c. Remove burners and brash gas outlet ports
lightly using a soft bristle brush.
d. Remove the vent pipe, automatic vent damper (if
used), draft hood, top jacket panels, flue collector and flue baffles..
e. Brush flueways with wire brush.
To the extent possible, inspect inside of vent pipe
and vent damper for obstructions in flow or vent
damper movement. Remove or replace as
necessary,
g,
Re-install baffles. When replacing the flue collector, be certain that the blanket seal between the flue collector and top section makes a tight seal to prevent leakage of the products of combustion.
h. Re-install the top of the jacket, draft hood, vent
damper (if used) and vent pipe.
i. Connect blocked vent switch wiring harness to
blocked vent switch.
k. Re-install burners.
,OLJT[R (ON[
/ DARK _lllE
!'_ rot rR
-, -
d n _T
_'_ [ " " ,h'l,* _ IE,_[Z _-"
-iiii __J I i
L_ JH
Figure 39: Standing Pilot and Main Burner Flame
OUTER CONE IS
/DARK BLUE
IN COLOR_
INNER CONE BLUE
IN COLOR_.
FLAMES
Figure 40: Intermittent Pilot and Main Burner
Flame
2. inspect entire venting system for corrosion, support and joint integrity. Repair as necessary.
3. Check the pilot and main burner flame. See Figures 39 and 40. The pilot should provide a steady flame enveloping 3/8" to I/2" of the flame sensor. If required, adjust the pilot as stated in the gas valve manufacturer's instructions. The main burner flame
inner cone should be approximately I-1/2" high and
should have a very sharp, blue color characteristic.
4. Systems with antifreeze. Check for correct concentration and inhibitor level.
33
Page 37
INLET
-12 1/2
1 I/2
RELIEF VALVE
Figure 41: Boiler Views
Table 5: Series GM Boiler Dimensions
_']JlI,II ;_.'][¢J_ n ;[O)III :1:g H I_ I_1_.[,.I [e)_[,
_ Jacket Left of Jacket Front of Jacket ; Vent
Boiler to Centerline of : to Centerline of Top of Jacket to i Connector Water
Model i Width Depth Top to Floor Vent Connector Vent Connector Vent Connector : Size Content
Number 'W' "B .... C" i "D .... E .... F" I "G" (Gallons)
GM-05 19]/4" 253/g" 35V4" ! 93/4" 16V2" 29" _ 7" [ 6.15 GM-06 _ 223,4" 25¾" . 351/4" i _11 a/f" " 16V2" 30" ____ 8" l 7.20
GM-07 26¾" 253/4" 35V," 131/( ' . 16W" 31" _ 9" i 8.25
GM-08 _ 29sA" 253A" 35'A" ! 15" 16'/z" " 31 ;_ '-- 9" - 9.30
Table 6: Series GM Boiler Ratings
Boiler Combustion Model Input Efficiency 2
Number Mbh %
GM-05 228
GM-06 285
GM-07 342 -- 82.0
GM-08 399 -- 82.0
__;I:t I;_.'l[tl_ g :{O] III =1:| :!:_ i I_[t_
Standing
DOE Net I=B=R Pilot
Heating Ratings Seasonal
Capacity Output Water Efficiency
Mbh I Mbh 2 Mbh 3,g (AFUE)_
187 163 810
231 -- 201 800
-- 280 243 --
-- 327 284 --
Intermittent
Ignition
Seasonal Efficiency
(AFUE) 1
82.1
81.1
Heating Capacity and Annual Fuel Utihzation Efficiency (AFUE) ratings are based on U S Government test Output rating and combustion efficiency determined in accordance with ANSI 7.21 13, Gas Rred Low Pressure Steam and Hot Water Boilers. Net I-B_R water ratings based on an allowance of 115 Consult factory before selecting a boiler for installations having unusual pipin 9 and pickup requirements, such as intermittenl system operation,
extensive piping systems, et¢
34
Page 38
Repair parts are available from your installer or by contacting Peerless Heater Company, Boyertown, PA 19512-1021. Use the figures and tables on pages 35-39 to assist in ordering parts.
Note: Remember to include boiler model number and serial number when ordering parts.
I Base
2 Burner Access Panel
3 Base Blanket Seal
Specify length
50867 50867 50867
Figure 42: Base
35
Page 39
6
5
Gas Manifold 50712 50713 i 50714 50715 Main Burner Specify quantity 50192 50192 50192 50192
Main Burner w/Pilot Clip 1 per boiler See Table below Orifice Spud, #40 Natural Gas, 0-2000 ft. 7157 7157 7157 7157
elevation (specify qty)*
*For elevations over 2,000 feet above sea level contact Peerless Heater Company.
Figure 43: Gas Manifold, Orifice Spuds, and Main Burners
I 2 3 4
Honeywell Q314A3505 Pilot Thermocouple Johnson K15DA-36
Natural Gas
Natural Gas 51688 1 per boiler 50839
Figure 44: Gas Valve and Pilot, Standing Pilot
36
Page 40
" EP_ I;I =I_±II;I I_7_._;la_"] [_!}1
1
2 i Honeywell SV9601M4167 Gas Valve Natural Gas i 51683 3 Honeywell Q3480BI041 Pilot ! Natural Gas 51295
Figure 45: Gas Valve and Pilot, Intermittent Ignition
8 Block
9 Flue Baffle 10 Flue Collector II Flue Collector Blanket Seal
Figure 46: Block and Flue Collector
I per flueway
Specify length
91042 91043
90975 i 90976 , 90977 90978 50866 50866 50866 ! 50866
37
Page 41
/ _I2G::
12 Jacket Assembly
*Complete Jacket Consists of:
12A Left Side Panel 12B Right Side Panel
12C Rear Panel 12D Inner Front Panel
I
12E I Removable Front Panel 12F Lower Front Panel
12G Top Panel
, Complete jacket* with
insulation and screws
Figure 47: Jacket
38
Page 42
20
I \
I
: \15
\ 16
13 3/4" Drain Valve*, Conbraco 31-602-04 50517 50517 ! 50517 50517 14 Flame Rollout Safely Shutoff Switch 51587 51587 51587 51587
0
15 ! Transformer, 4OVA, Johnson Y65T42-O _ 51040 i 51040 51040 51 40 16 Honeywell L4080B1261 Limit 50539 50539 i 50539 50539
17 Temperature-Pressure Gage (30, 50 psi safety relief valve) 51774 5i774 i 51774 51774
Temperature-Pressure Gage (80, 100 psi .safety relief valve} 55845 i 55845 i 55845 55845
] 50501 ! 50501 i S0801 50501
18 i Safety Relief Valve, 30 psi*
Safety Relief VaLve, 50 psi* 99950 99950 99950 99950
! 99502
Safely Relief Valve, 80 psi* [ 99502 99502 99502
j Safely Relief Valve, 100 psi* 50118 50118 50118 50118
19 Blocked Vent Switch {Vent Safely Shutoff) 51590 51590 51590 51590
20 Draft Hood 90992 90993 90994 90994 21 Automatic Vent Damper 90610 90611 50167 50167
*Available from distributor
Figure 48: Controls, Draft Hood and Automatic Vent Damper
39
Page 43
Series GM
Gas
Boilers
Installation, Operation {_
Maintenance Manual
TO THE INSTALLER:
This manua/ is the property of the owner and must
be affixed near the boiler for future reference.
TO THE OWNER:
This boi/er shou/d be inspected annual/y by a
Qualified Service Agency,
e®@ei
HI Division ASME
of gama
PEERLESS _
PEERLESS HEATER COMPANY
231 NORTH WALNUT STREET BOYERTOWN, PA 19512 1021 ° PHONE 610-367-2153
vwvw.peerless-heater.com
THE PREFERRED HEATING CHOICE
@2002 Peerless Heater Company GM8065 R4 (11/02-3M)
Printed in U.S.A.
Loading...