PEERLESS PT-30, PT-40, PT-60, PT-80, PT-50 Installation, Operation & Maintenance Manual

...
Partner
®
Water Heater
PT-30 PT-40 PT-50 PT-60 PT-80 PT-120
Peerless
®
Indirect-Fired
Installation, Operation & Maintenance Manual
USING THIS MANUAL 1
A. INSTALLATION SEQUENCE . . . . . . . . . . . . . .1
B. SPECIAL ATTENTION BOXES . . . . . . . . . . . . .1
PRODUCT & SAFETY INFORMATION 2
1. PREINSTALLATION 3
A. CODES COMPLIANCE . . . . . . . . . . . . . . . . . . .3
B. CODES RESTRICTIONS . . . . . . . . . . . . . . . . . .3
C. OPERATING RESTRICTIONS . . . . . . . . . . . . . .3
D. LOCATING WATER HEATER . . . . . . . . . . . . . .3
E. PRODUCT SELECTION . . . . . . . . . . . . . . . . . .4
F. RECOMMENDED CLEARANCES . . . . . . . . . . .5
2. INSTALLATION - PIPING 6
A. TEMPERATURE & PRESSURE (T&P)
RELIEF VALVE . . . . . . . . . . . . . . . . . . . . . . . . .6
B. DRAIN VALVE . . . . . . . . . . . . . . . . . . . . . . . . . .6
C. AUTOMATIC AIR VENT . . . . . . . . . . . . . . . . . .7
D. THERMAL EXPANSION . . . . . . . . . . . . . . . . .7
E. WATER HAMMER . . . . . . . . . . . . . . . . . . . . . .7
F. VACUUM BREAKER . . . . . . . . . . . . . . . . . . . . .7
G. GENERAL PIPING . . . . . . . . . . . . . . . . . . . . . . .7
H. DOMESTIC PIPING . . . . . . . . . . . . . . . . . . . . . .7
I. THERMOSTATIC MIXING VALVE . . . . . . . . . .8
J. RECIRCULATION PIPING . . . . . . . . . . . . . . . . .8
K. MULTIPLE WATER HEATER SYSTEMS . . . . .8
L. BOILER PIPING . . . . . . . . . . . . . . . . . . . . . . . . .8
3. INSTALLATION - PIPING DRAWINGS 9
4. INSTALLATION - WIRING 16
A. WIRING REQUIREMENTS . . . . . . . . . . . . . . .16
B. CIRCULATORS . . . . . . . . . . . . . . . . . . . . . . . .16
C. ZONE VALVES . . . . . . . . . . . . . . . . . . . . . . . .16
D. SNAPSET CONNECTION . . . . . . . . . . . . . . . .16
5. INSTALLATION - WIRING DRAWINGS 17
6. WATER HEATER START-UP 22
A. FILLING THE INNER (DOMESTIC WATER)
TANK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
B. FILLING THE OUTER (BOILER WATER)
TANK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
C. GENERAL NOTES . . . . . . . . . . . . . . . . . . . . .23
D. ADJUSTING THE WATER HEATER
THERMOSTAT . . . . . . . . . . . . . . . . . . . . . . . .23
7. WATER HEATER MAINTENANCE 24
A. MAINTENANCE SCHEDULE . . . . . . . . . . . . .24
B. FILLING WATER HEATER . . . . . . . . . . . . . . .24
C. DRAINING WATER HEATER . . . . . . . . . . . . .24
D. DRAINING INNER (DOMESTIC WATER)
TANK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
E. DRAINING OUTER (BOILER WATER)
TANK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
8. TROUBLESHOOTING 26
9. REPAIR PARTS 27
10. WATER HEATER DIMENSIONS & RATINGS 29
11. PERFORMANCE RATINGS 30
TABLE OF CONTENTS
TABLE OF CONTENTS
A. INSTALLATION SEQUENCE
Follow the installation instructions provided in this manual in the order shown. The order of these instructions has been set in order to provide the installer with a logical sequence of steps that will minimize potential interferences and maximize safety during boiler installation.
B. SPECIAL ATTENTION BOXES
Throughout this manual special attention boxes are provided to supplement the instructions and make special notice of potential hazards. The definition of each of these categories, in the judgement of PB Heat, LLC are as follows:
USING THIS MANUAL
Indicates special attention is needed, but not directly related to potential personal injury or property damage.
NOTICE
Indicates a condition or hazard which will or can cause minor personal injury or property damage.
CAUTION
DANGER
Indicates a condition or hazard which will cause severe personal injury, death or major property damage.
Indicates a condition or hazard which may cause severe personal injury, death or major property damage.
WARNING
1
USING THIS MANUAL
2
PRODUCT SAFETY & INFORMATION
PRODUCT SAFETY & INFORMATION
DANGER
HOT WATER CAN SCALD!
• Water temperatures over 125ºF can cause severe
burns instantly or death from scalding.
• Children, disabled and elderly are at highest risk of being scalded.
• Never leave them unattended in or near shower, bathtub or sink.
• Never allow small children to use a hot water faucet or draw their own bath.
• If anyone using hot water in the building fits the above description or if local codes or state laws require specific water temperatures at hot water faucet, it is recommended:
– to install a thermostatic mixing valve at this
appliance or at each water faucet.
or
– to set the thermostat knob for the lowest
temperature which satisfies your hot water needs.
• Water drained from the system drain valves may be extremely hot. To avoid injury:
– Make sure all connections are tight.
– Direct water flow away from any person.
Protection must be taken against excessive temperature and pressure!
• Installation of a Temperature & Pressure (T&P) relief valve is required.
WARNING
To prevent damage to the inner tank, the installer must:
• Always fill inner tank prior to outer tank and always drain outer tank prior to inner tank.
• Relieve primary system pressure below 15 psig prior to draining inner tank.
CAUTION
3
1. PREINSTALLATION
A. CODES COMPLIANCE
Water heater installation must conform with the instructions in this manual and where applicable:
• local, state, provincial, and national codes, laws, regulations and ordinances.
• in Canada - CAN / CGA B149.1 or B149.2 Installation Code.
Peerless
®
Partner®water heaters are exempt from ASME Section VIII, Division 1 Code construction per Interpretation VIII-86-136. Check with local codes for applicability.
Where recommendations in this manual differ from local, or national codes, the local or national codes take precedence.
B. CODES RESTRICTIONS
1. Single wall heat exchanger in the Peerless®Partner
®
water heater complies with National Standard Plumbing Code, provided that:
a. boiler water (including additives) is practically
non-toxic, having toxicity rating or class of 1, as listed in Clinical Toxicology of Commercial Products, and
b. boiler water pressure is limited to maximum 30
psig by approved relief valve.
2. Single wall heat exchangers are permitted under the
Uniform Plumbing code - Paragraph L3.2. and L3.3 if they satisfy all of the following requirements.
a. The heat transfer medium is potable water or
contains only substances which are recognized as safe by the U.S. Food and Drug Administration.
b. The pressure of the heat transfer medium is
maintained less than the normal minimum operating pressure of the potable water system
Exception: Steam complying with section #1 above.
c. The equipment is permanently labeled to indicate
that only additives recognized as safe by the FDA shall be used in the heat transfer medium.
Other heat exchanger designs may be permitted where approved by the Administrative Authority.
C. OPERATING RESTRICTIONS
1. Maximum domestic hot water temperature is 194ºF for commercial applications and 140ºF for residential applications.
2. Maximum boiler water temperature is 210ºF.
3. Maximum working pressure for inner (domestic water) tank is 150 psig.
4. Maximum working pressure for outer (boiler water) tank is 45 psig.
5. pH and chloride limits for water heaters are:
a. chloride, less than 150 mg/l (ppm)
b. pH value min. 6 - max. 8
D. LOCATING WATER HEATER
1. This water heater is not intended for outdoor installations.
2. Keep distance between boiler and water heater to a minimum to:
a. reduce piping heat loss
b. provide minimal friction loss
3. Locate water heater so that any leakage from the tank or water connections will not cause damage to the area adjoining the water heater or to lower floors in the structure.
When such a location is unavoidable, a suitable drain pan with adequate drainage, should be placed under the water heater.
4. The Peerless
®
Partner®water heaters are designed for
vertical installation only.
Peerless®Partner®water heaters will absorb less than 200,000 BTU/hr when domestic water outlet temperature is 210°F and boiler water supply temperature is 240°F. Listed outputs are based on ASME Section VIII Interpretation VIII-1-86-136.
NOTICE
Do not install the water heater on any application if the boiler piping contains non-oxygen barrier tubing or if the boiler piping is considered an “open system”. Exposing the outer tank of the water heater to oxygen contamination will lead to premature tank failure and denial of the warranty.
NOTICE
Any water conditioning system must be installed and maintained in accordance with manufacturer’s specifications.
NOTICE
PREINSTALLATION
4
E. PRODUCT SELECTION
1. The following guidelines apply to residential systems only. For commercial or institutional installations contact your local PB Heat, LLC representative.
2. Determine the quantity of domestic hot water required. Factors to consider:
a. Estimate typical peak hour demand. Determine
the general time of day (morning, noon, evening) when the most hot water is used. Use chart below to determine potential maximum usage.
b. Estimate unusual peak draw demand.
Whirlpool baths, hot tubs, and multiple head showers require large quantities of hot water in a short period of time. Contact fixture manufacturer for quantity of water required. Generally speaking, these circumstances can only be met with larger storage volumes.
c. Domestic Water Temperature. Most residential
usage will be satisfied with 119°F water, the temperature setting recommended by the Consumer Product Safety Commission. Some applications such as laundry and dishwashers may require a higher temperature.
Ratings can be improved by increasing Peerless
®
Partner®thermostat setting and using a mixing valve to temper the hot water to the proper temperature. When temperatures greater than 119°F are required, use a mixing valve at the outlet of the water heater or anti-scald fittings at point of use.
d. Domestic water priority. First hour ratings may
be less than published when boiler output is shared with space heating. Generally a consumer will notice a drop in domestic water temperature before a drop in space heating temperature. Giving domestic water production priority by directing entire boiler output to Peerless
®
Partner
®
will maximize domestic water output. However, prioritization controls could result in an unacceptable drop in space heating temperature when large quantities of domestic hot water are used, and a prioritization control malfunction could result in loss of space heating.
3. Multiple Water Heaters. Peak domestic water usage (first hour rating) or unusual peak draw may not be met with a single water heater. Multiple units can be installed as either a bank of tanks acting as a single unit, or as multiple individual units sized and located for specific draw situations.
PREINSTALLATION
Estimate of Peak Domestic Hot Water Usage
Average Gallons of Times Used During Gallons Used in
Use Hot Water per Usage One Hour One Hour
Shower 20 x _____________ = _____________
Bath 20 x _____________ = _____________
Shaving 2 x _____________ = _____________
Hands and Face Washing 4 x_____________ = _____________
Hair Shampoo 4 x_____________ = _____________
Hand Dish Washing 4 x _____________ = _____________
Automatic Dish Washing 14 x _____________ = _____________
Food Preparation 5 x_____________ = _____________
Wringer Clothes Washer 26 x _____________ = _____________
Automatic Clothes Washer 32 x _____________ =
Total Peak Hour Demand = __________
The Peerless®Partner®indirect-fired water heater is deemed to be used in a "commercial setting" if at any time the unit is operated at a temperature over 150°F. Refer to warranty for additional information.
NOTICE
DANGER
Water temperatures over 125°F can cause severe burns instantly, or death from scalds.
Children, disabled, and elderly are at the highest risk of being scalded.
See instruction manual before setting temperature at water
heater. Feel water before bathing or showering. Temperature limiting valves are available, see
manual.
5
PREINSTALLATION
F. RECOMMENDED CLEARANCES
1. Water heater should be installed to allow adequate clearance for servicing.
2. Zero clearance is permissible to any side of the Peerless
®
Partner®water heater, but information labels
may be hidden.
3. Recommended top or vertical clearance is 12" minimum.
4. Refer to boiler manual for boiler clearances.
5. See Figure 1.1 for recommended service clearances.
Figure 1.1: Recommended Clearances
6
2. INSTALLATION – PIPING
A. TEMPERATURE & PRESSURE (T&P)
RELIEF VALVE
1 Every Peerless®Partner®water heater must be
protected with a T&P relief valve.
2 Determine T&P relief valve size by the following
specifications, unless they conflict with local codes:
a. Peerless
®
Partner®30/40/50: 3/4" NPT with an AGA Rating of 100,000 BTU/hr and a maximum pressure rating of 150 psig. (Watts 100XL-8 or equivalent).
b. Peerless
®
Partner®60/80/100/120: 3/4" NPT with an AGA Rating of 200,000 BTU/hr and a maximum pressure rating of 150 psig. (Watts 40XL-8 or equivalent).
3. Standard Installation: Install T&P relief valve in the Auxiliary connection located behind the air vent on the top of the water heater (Figure 3.1).
or
Install the T&P relief valve in the run (straight through leg) of a tee located at the domestic hot water outlet when using the Auxiliary connection for a recirculation return (Figure 3.2).
4. Commonwealth of Massachusetts Installation: Follow this procedure for jurisdictions requiring a vacuum breaker to be installed on the domestic cold water inlet.
• Install the T&P in the run (straight through leg) of tee located at the domestic hot water outlet. Use a long element T&P relief valve (Fig. 3.4).
5. T&P Relief Valve Discharge Piping: T&P relief valve discharge piping must be:
• made of material serviceable for temperatures of 250ºF or greater.
• directed so that hot water flows away from all persons.
• directed to a suitable place for disposal.
• installed so as to allow complete draining of the T&P relief valve and discharge line.
T&P relief valve discharge piping must not be:
• excessively long. Using more than 2 elbows or 15 feet of piping can reduce discharge capacity.
• directly connected to a drain. Terminate the discharge piping within 6" from a drain and within 6" of the floor. Refer to local codes.
• plugged, reduced or restricted.
• subject to freezing.
B. DRAIN VALVE
Drain valve and fittings are supplied by others.
1. Standard Installation a. Install a tee connection at the domestic cold water
inlet (Fig. 3.1 and 3.2).
b. Pipe the drain piping with drain valve from the tee
connection to:
i. a suitable place for disposal
or
ii. terminate within 12" of the floor
2. Commonwealth of Massachusetts Installation a. Use the drain tube assembly supplied in the tank
carton.
b. Thread a 3/4" close nipple onto the Auxiliary
connection and insert an open-end dip tube into the Auxiliary connection on top of water heater. As shown in Fig. 3.3.
c. Install a 3/4" NPT elbow to the Auxiliary
connection, see Fig. 3.4.
d. Pipe the drain piping with drain valve from the
elbow connection to:
To reduce risk of excessive pressures and temperatures in the water heater, install temperature and pressure protective equipment required by local codes, but no less than a combination temperature and pressure relief valve certified by a nationally recognized testing laboratory that maintains periodic inspection of production of listed equipment or materials, as meeting the requirements for Relief Valves and Automatic Gas Shutoff Devices for Hot Water Supply Systems, ANSI Z21.22. This valve must be marked with a maximum working pressure of the water heater.
CAUTION
For proper operation of the T&P and to prevent the T&P from activating due to boiler water temperature, use a T&P relief valve with extended element. Recommended, an 8" minimum length.
NOTICE
Do not install any valve between T&P relief valve and tank connection or on T&P relief valve discharge piping. Do not plug T&P relief valve or discharge piping. Improper placement and piping of T&P relief valve can cause severe personal injury, death or substantial property damage.
WARNING
INSTALLATION - PIPING
7
i. a suitable place for disposal
or
ii. terminate within 12" of the floor
C. AUTOMATIC AIR VENT
1. Remove plastic shipping cap from 1/2" NPT pipe fitting on top center of water heater.
2. Install 1/2" x 1/8" reducer bushing provided with water heater, using suitable pipe dope or tape.
3. Install automatic air vent provided with water heater, using suitable pipe dope or tape.
4. Unscrew vent cap on air vent one full turn. Leave cap unscrewed one turn for normal venting.
D. THERMAL EXPANSION
If a backflow preventer, check valve or pressure reducing valve is piped on cold water supply piping of water heater, install an expansion tank on cold water supply line to prevent normal thermal expansion from repeatedly forcing open T&P relief valve.
E. WATER HAMMER
Dishwashers, clothes washers and fast-closing positive shut-off valves incorporated in the system all contribute to creating water shock. Install a water hammer arrester to prevent damage to pipes and appliances. See device manufacturer’s instructions for application and installation.
F. VACUUM BREAKER
Installing a vacuum breaker Watts N36-M1 or equivalent on the domestic cold water inlet will prevent damage to the inner tank if a negative pressure is developed in the domestic supply line. See manufacturer’s instructions for application and installation of the vacuum breaker.
G. GENERAL PIPING
1. For domestic water piping diagrams, see Figures 3.1 through 3.4.
2. See Figures 3.5 through 3.9 for boiler water piping
3. See Figures 3.10 and 3.11 for multiple water heater domestic piping.
4. See Figure 3.12 for multiple water heater boiler piping.
5. See Table 1.1 for domestic and boiler piping connection sizes.
6. All plumbing must meet or exceed all local, state and national plumbing codes.
7. Use pipe dope or tape suitable for potable water systems.
8. Use isolation valves to isolate system components.
H. DOMESTIC PIPING
1. Union on domestic hot water outlet should be piped at a higher elevation than domestic water drain valve. This will make draining the water heater easier.
2. Install unions for easy removal of water heater. Use dielectric unions or couplings to protect hot and cold water fittings from corrosion when connecting dissimilar materials such as copper and galvanized iron pipe.
3. If copper pipe is used for domestic water connections, first solder pipe to a threaded adapter and then screw adapter into cold water inlet on top of water heater. Inlet contains an internal plastic dip tube which can be damaged by heat from soldering.
Water hammering within the domestic piping system can cause premature failure of the inner tank of the water heater. This type of failure is NOT covered under warranty.
NOTICE
T&P relief valve is not intended for constant duty, such as relief of pressure due to repeated normal system expansion. Correct this condition by installing a properly sized expansion tank in domestic water system. Refer to expansion tank manufacturer’s installation instructions for proper sizing.
CAUTION
Table 1.1:
Water Heater Model
Number
Connections - NPT Recirculation Dip Tube Draining Dip Tube
Recommended
Minimum
Boiler Piping
Domestic
Water
Inlet/Outlet
Boiler Water
Supply/
Return
Auxiliary
Connection
Length
(inches)
Diameter
(inches)
Length
(inches)
Diameter
(inches)
Diameter
(inches)
PT-30 3/4 1 3/4 34 3/4 34 3/4 1
PT-40 3/4 1 3/4 43 3/4 43 3/4 1
PT-50 3/4 1-1/4 3/4 25 3/4 52 3/4 1-1/4
PT-60 3/4 1-1/4 3/4 34 3/4 62 3/4 1-1/4
PT-80 1-1/2 1-1/2 1-1/2 25 1-1/2 48 1-1/2 1-1/2
PP-120 1-1/2 2 1-1/2 32 1-1/2 61 1-1/2 2
INSTALLATION - PIPING
8
4. When the water supply pressure is higher than 70 psig, it is recommended to install a pressure reducing valve on cold water supply line to prevent water loss through T&P relief valve.
5. If water heater will replace tankless coil in boiler, disconnect piping to coil. Allow water to drain from coil. Do not plug tankless coil.
I. THERMOSTATIC MIXING VALVE
1. It is recommended to install an optional mixing valve on the domestic hot water outlet.
2. Mixing valve should comply with ASSE 1017.
J. RECIRCULATION PIPING
1. T&P relief valve must be installed in run (straight through leg) of tee located at domestic hot water outlet of water heater.
2. It is recommended that the recirculation dip tube be installed in auxiliary connection using a close nipple assembly as shown Fig. 3.3, page 9. See Table 1.1 page 6 for diameter and length of dip tube.
3. A stainless steel or bronze circulator is recommended.
4. Install automatic mixing valve either at the hot water outlet of water heater or each hot water faucet.
K. MULTIPLE WATER HEATER SYSTEMS
1. Parallel Pipe Recirculation Systems - Manifold recirculation return to all water heaters.
2. Series Piped Systems - Piped return to the leading (cold water inlet) water heater.
3. Install automatic mixing valve either at the hot water outlet of water heater or each hot water faucet.
L. BOILER PIPING
1. If plastic pipe is used for boiler water piping, it must have a maximum oxygen diffusion rate of 0.1 mg/liter-day for boiler and water heater protection.
2. Boiler water (including additives) must be practically non-toxic, having toxicity rating or class of 1, as listed in Clinical Toxicology of Commercial Products.
If antifreeze is used in boiler system, local codes may require a backflow preventer on cold water supply line. Use antifreeze specifically intended for hydronic heating systems. Inhibited propylene glycol is recommended at a maximum 50/50 mixture.
WARNING
Do not use automotive, ethylene glycol or petroleum­based antifreeze. Do not use any undiluted antifreeze. This can cause severe personal injury, death or substantial property damage.
DANGER
Plugging tankless coil inlet and outlet will result in severe personal injury, death, or substantial property damage.
Do not apply heat to the cold water inlet when making sweat connections to water heater. Sweat tubing to adapter before fitting adapter to cold water inlet of heater. It is imperative that no heat be applied to the cold water inlet, as it contains a non metallic dip tube.
NOTICE
The Peerless®Partner®IDWH must be installed on a closed type hydronic system. Failure to provide such a system will result in premature failure of the outer tank and annulment of warranty.
NOTICE
DANGER
Failure to install automatic mixing valve where recommended will result in severe personal injury or death.
INSTALLATION - PIPING
9
Figure 3.1: Peerless®Partner®Recommended Installation: Domestic Water Piping
Figure 3.2: Peerless®Partner®Recommended Installation: Domestic Water Piping with Recirculation
3. INSTALLATION – PIPING DRAWINGS
1. Shut-off valve
2. Recirculation Circulator
3. Flow Check Valve
4. T&P relief valve
5. Unions
6. Backflow preventer or pressure reducing valve(*)
9. Drain valve
10. Thermal expansion tank (potable)
11. Recirculation dip tube
13. Thermostatic mixing valve (*) (*) Optional devices may be required by local codes.
INSTALLATION - PIPING DRAWINGS
5
12" min.
Heat Trap
Loop
(Optional)
1
9
Heat Trap
(Optional)
1
5
12" min.
Loop
9
10
6
10
Cold Water
1
1
6
12" min.
Heat Trap
Loop
(Optional)
13
H
M
1
Recirculating
Loop
C
1
Heat Trap
(Optional)
5
2
12" min.
Loop
4
3
4
5
11
Inlet
Cold Water
Inlet
Loading...
+ 24 hidden pages