NOTE: Read entire instruction sheet before you start installation and assembly.
WARNING
• Do not begin to install your Peerless product until you have read and understood the instructions
and warnings contained in this Installation Sheet. If you have any questions regarding any of the
instructions or warnings, for US customers please call Peerless customer care at
1-800-865-2112, for all international customers, please contact your local distributor.
• This product should only be installed by someone of good mechanical aptitude, has experience
with basic building construction, and fully understands these instructions.
• Make sure that the supporting surface will safely support the combined load of the equipment and
all attached hardware and components.
• Never exceed the Maximum Load Capacity. See page one.
• If mounting to wood wall studs, make sure that mounting screws are anchored into the center of
the studs. Use of an "edge to edge" stud fi nder is highly recommended.
• Always use an assistant or mechanical lifting equipment to safely lift and position equipment.
• Tighten screws fi rmly, but do not overtighten. Overtightening can damage the items, greatly
reducing their holding power.
• This product is intended for indoor use only. Use of this product outdoors could lead to product
failure and personal injury.
• This product was designed to be installed on the following wall construction only;
WALL CONSTRUCTION HARDWARE REQUIRED
• Wood Stud Included
• Wood Beam Included
• Solid Concrete Included
• Metal Stud Do not attach except with Peerless Metal Stud Accessory
Kit; ACC215. Contact Customer Service for Peerless
metal stud accessory kit.
• Brick Contact Qualifi ed Professional
• Other or unsure? Contact Qualifi ed Professional
Tools Needed for Assembly
• stud fi nder ("edge to edge" stud fi nder is recommended)
• phillips screwdriver
• drill
• 5/16" (8mm) bit for concrete surface
• 1/8" (3mm) bit for wood studs
• level
Table of Contents
Parts List................................................................................................................................................3
Installation to Wood Stud Wall...............................................................................................................4
Installation to Solid Concrete or Cinder Block........................................................................................5
Before you start check the parts list to insure all of the parts shown are included.
0
0
Parts List
Description
A column
B M5 X 44mm wood screw
C wall anchor
D shelf attachment clamp
E M5 X 18mm socket cap screw
F M5 X 12mm socket cap screw
G glass support bracket
H screw cover2
I M5 washer
J shelf bracket
K glass shelf
L support clip44
M 4mm allen wrench
N 2.5mm allen wrench
ACCSH100/ESHV1
Qty.
11
22
22
11
22
—1
—1
23
11
—1
11
11
ACCSH200/ESHV2
Qty.
A
2
B
C
D
E
F
G
H
I
J
L
K
M
N
3 of 27
ISSUED: 01-17-11 SHEET #: 083-9013-1
Installation to Single Wood Stud Wall
WARNING
• Installer must verify that the supporting surface will safely support the combined load of the
equipment and all attached hardware and components.
• Tighten wood screws so that wall plate is fi rmly attached, but do not overtighten. Overtightening
can damage the screws, greatly reducing their holding power.
• Never tighten in excess of 80 in. • lb (9 N.M.).
• Make sure that mounting screws are anchored into the center of the stud. The use of an "edge to
edge" stud fi nder is highly recommended.
• Hardware provided is for attachment of mount through standard thickness drywall or plaster into
wood studs. Installers are responsible to provide hardware for other types of mounting situations.
Remove end cap with bubble level from column (A). Column (A) can be mounted to a single
1
stud. Use a stud fi nder to locate the edges of the stud. Use of an edge-to-edge stud fi nder is
highly recommended. Based on their edges, draw a vertical line down the stud’s center. Place
column (A) on wall as a template. Level column and mark the center of the two mounting holes
as shown in fi gure 1.1. Make sure that the center mounting holes are on the stud center lines.
Drill two mounting holes .12" (3mm) dia. by 2" (51mm) deep. Secure column (A) with two
M5 X 44mm wood screws (B) as shown in fi gure 1.2.
Tighten fasteners then cover M5 X 44mm wood screws (B) with screw covers (H).
Skip to step 3
STUD
END CAP
A
fi g. 1.1
DRILL .12" DIA
HOLES
B
H
4 of 27
fi g. 1.2
ISSUED: 01-17-11 SHEET #: 083-9013-1
Installation To Solid Concrete or Cinder Block
WARNING
• When installing Peerless wall mounts on cinder block, verify that you have a minimum of 1-3/8"
(35 mm) of actual concrete thickness in the hole to be used for the concrete anchors. Do not drill
into mortar joints! Be sure to mount in a solid part of the block, generally 1" (25 mm) minimum
from the side of the block. Cinder block must meet ASTM C-90 specifi cations. It is suggested
that a standard electric drill on slow setting is used to drill the hole instead of a hammer drill to
avoid breaking out the back of the hole when entering a void or cavity.
• Concrete must be 2000 psi density minimum. Lighter density concrete may not hold concrete
anchor.
• Installer must verify that the supporting surface will safely support the combined load of the
equipment and all attached hardware and components.
Remove end cap with bubble level from
1
column (A) as shown in fi gure 1.1. Make sure
that column (A) is level, use it as a template
to mark two mounting holes. Drill two 5/16" (8
mm) dia. holes to a minimum depth of 2"
(51 mm). Insert anchors (C) in holes fl ush with
wall as shown. Place column (A) over anchors
and secure with two M5 X 44mm wood screws
(B).
Tighten fasteners then cover M5 X 44mm
wood screws (B) with screw covers (H) as
shown in fi gure 1.2.
WARNING
• Tighten screws so that column is
fi rmly attached, but do not overtighten.
Overtightening can damage screws, greatly
reducing their holding power.
• Never tighten in excess of 80 in. • lb (9
N.M.).
• Always attach concrete expansion anchors
directly to load-bearing concrete.
• Never attach concrete expansion anchors
to concrete covered with plaster, drywall,
or other fi nishing material. If mounting to
concrete surfaces covered with a fi nishing
surface is unavoidable, the fi nishing
surface must be counter bored as shown
below. Be sure concrete anchors do not
pull away from concrete when tightening
screws. If plaster/drywall is thicker than
5/8" (16 mm), custom fasteners must be
supplied by installer.
1
Drill holes and insert anchors (C).
2
A
B
Place column (A) over anchors (C) and secure
with screws (B). Tighten all fasteners.
END CAP
A
CONCRETE
fi g. 1.1
C
A
concrete
surface
C
C
CINDER BLOCK
column
plaster/
dry wall
CUTAWAY VIEW
INCORRECTCORRECT
concrete
column
plaster/
dry wall
concrete
5 of 27
B
H
fi g. 1.2
ISSUED: 01-17-11 SHEET #: 083-9013-1
Installing Shelf to Column
Slide shelf attachment clamp (D) into column (A) and reattach end cap onto column (A) as
2
shown in fi gure 3.1.
END CAP
D
A
fi g. 3.1
Attach support clips (L) to shelf bracket (J) and slide to desired position as shown in fi gure 4.1.
3
Securely tighten all set screws using the 2.5 mm allen wrench (N). Do not overtighten screws.
NOTE: Set screws may already be attached to support clips.
For ACCSH100 and ESHV10 models, continue to step 5. For ACCSH200 and ESHV20 models,
skip to step 6.
L
J
SET SCREW
fi g. 4.1
6 of 27
ISSUED: 01-17-11 SHEET #: 083-9013-1
ACCSH100 and ESHV10 Models
Attach shelf bracket (J) to shelf attachment clamp (D) using two M5 x 18mm screws (E) and
4
washers (I) shown in fi gure 5.1 using 4mm allen wrench (M). Adjust the level of the shelf bracket
(J) to desired height then tighten knob to secure.
D
KNOB
J
E
fi g. 5.1
I
ACCSH200 and ESHV20 Models
Attach shelf bracket (J) and glass support bracket (G) to shelf attachment clamp (D) using two
5
M5 x 18mm screws (E) and washers (I) shown in fi gure 6.1 using 4mm allen wrench (M). Adjust
the level of the shelf bracket (J) to desired height then tighten knob to secure.
Place glass shelf (K) onto shelf bracket (J) and secure with M5 x 12mm screw (F) as shown in
fi gure 6.2 using 2.5mm allen wrench (N).
NOTE: Overtightening the screws may cause damage to glass shelf (K).
KNOB
F
D
J
I
E
G
fi g. 6.1
7 of 27
fi g. 6.2
ISSUED: 01-17-11 SHEET #: 083-9013-1
K
J
Cable Management
This mount includes a cable management function, where cables can be routed along the side
6
interior of the column (A).
NOTE: For best system performance, route the power cables separately from the signal cables.
A
Peerless Industries, Inc.
2300 White Oak Circle
Aurora, IL 60502
www.peerlessconsumer.com
CABLES
8 of 27
All other brand and product names are trademarks or registered trademarks of their respective owners.