Paxton PROXIMITY metal reader User Manual

16/03/2011
Ins-30049 PROXIMITY metal reader
Technical Support
01273 811011 support@paxton.co.uk
Technical help is available: Monday - Friday from 07:00 - 19:00 (GMT)
Saturday from 09:00 - 13:00 (GMT)
Documentation on all Paxton products can be found on our website - http://www.paxton.co.uk/
Suitability
Security-sensitive doors
Wet environments
Paxton
Mounted on metal surface
Readers mounted together
Cable extensions
Readers can be extended using Belden CR9540 10-core overall screened cable to a maximum of 100 metres.
Wiring
Connection to a control
unit reader port
Connection modules
Reader junction box (325-020)
This module can be used to provide a connection point for the reader RJ45 plug. The terminals on the module are then wired colour for colour to the controller.
Alternatively, the reader can be wired directly into the screw terminals of the control unit by
rst cutting off the RJ45 plug and stripping back
the wires in the cable.
Further information on how to purchase Installer Tools is available at:
http://paxton.info/841
Reader port module (325-030)
This module may be purchased separately to speed up the installation and replacement of readers.
The reader port module is designed to convert the standard reader ports on Switch2 and Net2 controllers to accept one or two RJ45 connections. Pull off the screw terminal block from the reader port and simply replace it with this module.
Technical Help
Here is the list of topics about this product that receive the most technical support enquiries.
We list them here to help you speed up the installation and trouble shooting process.
1 - Readers/Keypads not working.
Q- Software settings - Conrm that the settings of the reader or keypad are correct. Q- Connections - Check the wiring and integrity of the connectors. If possible, test this reader on the other port. Q- Cable - Belden 9540 should be used to extend the reader cable (100 m maximum). Twisted pair alarm cable Q should not be used. To conrm that an extended reader cable is not faulty, wire the reader directly to the port. Q- Supply voltage - Conrm that the voltage is within specication. (see table) Q- User token - Conrm that the user token used for testing is OK by presenting it to a known working reader. Q- Interference - Conrm whether the reader works when tested 'in hand' and not mounted on the wall. Q Ensure PROXIMITY readers are not mounted back to back and there is no interference from other RF devices.
2 - Readers / Keypads - Extending cable.
QOnly Belden CR9538 / 9540 can be used for cable extensions. CR9538 8 core up to 25 m, CR9540 10 core Qup to 100 m (maximum). With CR9540, the two additional cores should be used to double up the power.
3 - Net2. What to do if a user has no access - Check the reader LED's when a card is shown.
Q- No LED's - the reader has no power. Q- No change in display - try the card on a known working reader. If there is still no response, replace the card. Q- Green LED ashing when a card is presented; check relay 1 LED to check for activity and also the lock wiring. Q- Red LED is ashing when a card is presented; check the validity of the user at the PC. Q Check user's access level and ensure they should have access by clicking on Current Validity. Q Check the 'Valid Until' date and conrm this has not expired. Q- Reinstate the ACU from the doors screen. Select the ACU's you wish to reinstate and then click OK.
4 - Switch2 - Adding an additional card pack.
QYou need to be in possession of the original enrolment card. Present the original enrolment card to the reader Qand the Amber LED will ash, Green & Red LED's will be off, then present the Enrolment card from the new Qcard pack; the reader will beep and all LED's will be lit. The additional cards will now be valid. Repeat this with Qeach reader and with any additional card packs. Any valid enrolment card can be used to add further packs. QThis is the same for enrolling function card packs onto a system.
5 - Switch2 - How to reset the controller.
Q1. Disconnect the power and remove the wires from the Green and Mauve terminals. Q2. Insert a wire link between the Green and Mauve terminals. Q3. Reconnect the power (the unit will beep 4 times). Q4. Disconnect the power and remove the link wire, reconnect the Green and Mauve wires. Q5. Reconnect the power (the unit will beep 3 times per second). The unit is ready to be enrolled.
Specications
Electrical
Voltage
Current
Carrier frequency
Clock and data bit period
Environment
Operating temperatures - all items
Waterproof
Cable length
Dimensions
Read Range
Min
10V DC 14V DC
Min
- 35 °C
Width
76 mm 76 mm
Token
50 mm 40 mm
This product is not suitable for retail sale. All warranties are invalid if this product is not installed by a competent person.
Max
110 mA
Max
+ 66 °C
IPX7
Height
Keyfob
The declaration of conformity is available on request. Contact details are provided at: http://paxton.info/596
125 kHz
600 µs
5 metres
Depth
27 mm
Watchprox
10 mm