Ins-30004 PROXIMITY KP series keypad
Technical Support
01273 811011 support@paxton.co.uk
Technical help is available: Monday - Friday from 07:00 - 19:00 (GMT)
Saturday from 09:00 - 13:00 (GMT)
Documentation on all Paxton products can be found on our website - http://www.paxton.co.uk/
Fitting
Paxton
K75 Screw connector option
The unit should be mounted in conjunction with
an electrical backbox to achieve the required
clearance for the connector.
If an adaptor plate (310-750) is tted, the
mountings on the backbox can also be used.
Indoor use only
Cable extensions
Readers can be extended using Belden CR9540 10-core overall screened cable to a maximum of 100 metres.

1
2 3
4 5 6
7 8 9
0 #
*
Wiring
Connection to a control
unit reader port
When using this keypad style with Net2, the software version used must be v3.21 or later.
WHITE labelled Net2 control units provide 5V at the Red terminal. The Red power wire for the reader should
therefore be directly connected to the 12V ACU terminal.
Switch2 controllers with WHITE labels are incompatible with these products. The keypads in the K and KP series,
can only be used with Switch2 controllers tted with YELLOW wiring labels.
Connection modules
Reader junction box (325-020)
This module can be used to provide a
connection point for the reader RJ45 plug.
The terminals on the module are then wired
colour for colour to the controller.
Alternatively, the reader can be wired directly
into the screw terminals of the control unit by
rst cutting off the RJ45 plug and stripping
back the wires in the cable.
Reader port module (325-030)
This module may be purchased separately to speed up
the installation and replacement of readers.
The reader port module is designed to convert the
standard reader ports on Switch2 and Net2 controllers
to accept one or two RJ45 connections. Pull off the
screw terminal block from the reader port and simply
replace it with this module.
Further information on how to purchase Installer Tools is available at:
http://paxton.info/841

Technical Help
Here is the list of topics about this product that receive the most technical support enquiries.
We list them here to help you speed up the installation and trouble shooting process.
1 - Readers/Keypads not working.
Q- Software settings - Conrm that the settings of the reader or keypad are correct.
Q- Connections - Check the wiring and integrity of the connectors. If possible, test this reader on the other port.
Q- Cable - Belden 9540 should be used to extend the reader cable (100 m maximum). Twisted pair alarm cable
Q should not be used. To conrm that an extended reader cable is not faulty, wire the reader directly to the port.
Q- Supply voltage - Conrm that the voltage is within specication. (see table)
Q- User token - Conrm that the user token used for testing is OK by presenting it to a known working reader.
Q- Interference - Conrm whether the reader works when tested 'in hand' and not mounted on the wall.
Q Ensure PROXIMITY readers are not mounted back to back and there is no interference from other RF devices.
2 - Readers / Keypads - Extending cable.
QOnly Belden CR9538 / 9540 can be used for cable extensions. CR9538 8 core up to 25 m, CR9540 10 core
Qup to 100 m (maximum). With CR9540, the two additional cores should be used to double up the power.
3 - Net2. What to do if a user has no access - Check the reader LED's when a card is shown.
Q- No LED's - the reader has no power.
Q- No change in display - try the card on a known working reader. If there is still no response, replace the card.
Q- Green LED ashing when a card is presented; check relay 1 LED to check for activity and also the lock wiring.
Q- Red LED is ashing when a card is presented; check the validity of the user at the PC.
Q Check user's access level and ensure they should have access by clicking on Current Validity.
Q Check the 'Expires end' date and conrm this has not past.
Q- Reinstate the ACU from the doors screen. Select the ACU's you wish to reinstate and then click OK.
4 - Switch2 - Adding an additional card pack.
QYou need to be in possession of the original enrolment card. Present the original enrolment card to the reader
Qand the Amber LED will ash, Green & Red LED's will be off, then present the Enrolment card from the new
Qcard pack; the reader will beep and all LED's will be lit. The additional cards will now be valid. Repeat this with
Qeach reader and with any additional card packs. Any valid enrolment card can be used to add further packs.
QThis is the same for enrolling function card packs onto a system.
5 - Switch2 - How to reset the controller.
Q1. Disconnect the power and remove the wires from the Green and Mauve terminals.
Q2. Insert a wire link between the Green and Mauve terminals.
Q3. Reconnect the power (the unit will beep 4 times).
Q4. Disconnect the power and remove the link wire, reconnect the Green and Mauve wires.
Q5. Reconnect the power (the unit will beep 3 times per second). The unit is ready to be enrolled.
Suitability
Security-sensitive doors
Mounted on metal surface
Wet environments
Readers mounted together
300mm
between
readers

Keypad bezels
Additional bezels are available in black, white, grey, blue and silver. Registered installers can order these free
of charge by logging onto the secure installer extranet: http://paxton.info/1035 or if you are not a registered
installer please call us on: 01273 811011 for more information.
Specications
Electrical
Voltage
Current
Carrier frequency
Clock and data bit period
Environment
Operating temperatures - all items
Waterproof - Fixed cable
Waterproof - K75 - Screw connection
Cable length
Dimensions
KP50 50 mm 100 mm
KP75 75 mm 143 mm
Read Range
KP50 80 mm 50 mm
KP75 100 mm 60 mm
This product is not suitable for retail sale. All warranties are invalid if this product is not installed by a competent person.
Min
8V DC 14V DC
Min
- 35 °C
IPX7
Width
Token
Max
180 mA
125 kHz
600 µs
Max
+ 66 °C
Height
Keyfob Hands Free Token
Outdoor use
Indoor use
5 metres
Depth
15 mm
16 mm
1100 mm
1500 mm
The declaration of conformity is available on request. Contact details are provided at: http://paxton.info/596