Patterson-Kelley Thermific Installation & Owner's Manual

PATTERSON-KELLEY
THERMIFIC®
GAS-FIRED BOILER
Installation Date: _______________________
100 Burson Street, P.O. Box 458, East Stroudsburg, PA 18301 Telephone: (877) 728-5351, Facsimile: (570) 476-7247 www.pkboilers.com
C.S.A Design-Certified Complies with ANSI Z21.13/CSA 4.9 Gas-Fired Low Pressure Steam and Hot Water Boilers
ASME Code, Section IV Certified by Patterson-Kelley
C.S.A Design-Certified Complies with ANSI Z21.13/CSA 4.9 Gas-Fired Low Pressure Steam and Hot Water Boilers
TBIG-02
INSTALLATION
OWNER’S
&
MANUAL
INSTALLATION
OWNER’S
&
MANUAL
INSTALLATION
OWNER’S
&
MANUAL
INSTALLATION
OWNER’S
&
MANUAL
INSTALLATION
OWNER’S
&
MANUAL
INSTALLATION
OWNER’S
&
MANUAL
INSTALLATION
OWNER’S
&
MANUAL
INSTALLATION
OWNER’S
&
MANUAL
Thermific® Gas-Fired Boiler Table of Contents
1.0 INTRODUCTION ................................. 1
2.0 SAFETY............................................... 1
2.1 General ......................................................1
2.2 Training......................................................1
2.3 Safety Features..........................................1
2.4 Safety Labels .............................................2
2.5 Safety Precautions.....................................2
2.5.1 Electrical Hazards .............................2
2.5.2 Burn, Fire, and Explosion Hazards ...2
2.5.3 Crush Hazards ..................................3
2.5.4 Chemical Hazards.............................3
2.5.5 Pressure Hazards .............................4
2.5.6 Slip, Fall Hazards..............................4
3.0 INSTALLATION ................................... 5
3.1 Receiving and Storage ..............................5
3.1.1 Initial Inspection ................................5
3.1.2 Storage Prior to Installation...............5
3.2 Compliance with Codes .............................5
3.3 Setup .........................................................5
3.3.1 Foundation ........................................5
3.3.2 Placement .........................................5
3.3.3 Clearances........................................6
3.4 Electrical Connections ...............................6
3.5 Combustion Air ..........................................7
3.6 Flue Venting...............................................7
3.6.1 Vent Elbows ......................................8
3.6.2 Barometric Damper...........................8
3.6.3 Barometric Damper Location ............8
3.6.4 Flue Connection................................8
3.6.5 Vent Termination...............................9
3.6.6 Removing an Existing Boiler .............9
3.7 Gas Piping .................................................9
3.7.1 Gas Supply Piping by Installer ........11
3.7.2 Gas Bleeds and Vents ....................11
3.8 Boiler Water Piping..................................11
3.8.1 Piping Design..................................11
3.8.2 Boiler Inlet and Outlet Connections 12
3.8.3 Boiler Water Piping by Installer.......12
3.8.4 Flushing and Filling.........................13
3.9 Burner and Ignition System .....................13
3.9.1 Inspection .......................................13
3.10 Pre-Start Check List...............................13
3.11 Safety Checks........................................13
3.11.1 Test of Ignition Safety System ...... 13
3.11.2 Test of Low Water Cut-off.............14
3.11.3 Test of High-Limit Control ............. 14
3.11.4 Test of Gas Pressure Switch ........14
3.12 Initial Adjustments..................................15
3.12.1 Operating Temperature Controller for Lo-Hi-Lo Thermific
®
.............................15
3.12.2 Gas Pressure Adjustment.............16
3.12.3 Air Flow Adjustments .................... 16
4.0 OPERATION ..................................... 19
4.1 General....................................................19
4.1.1 Control Panel Front.........................19
4.1.2 Tests ............................................... 19
4.2 Lighting and Shut-Down Procedures.......19
4.2.1 Lighting Procedures........................19
4.2.2 Normal Shut Down Procedures ......20
4.2.3 Emergency Shut Off .......................20
4.3 Typical Boiler Operating Conditions ........20
5.0 MAINTENANCE ................................ 21
5.1 Maintenance and Inspection Schedule.... 21
5.1.1 Daily................................................21
5.1.2 Weekly ............................................ 21
5.1.3 Monthly (During Operation) ............21
5.1.4 Semi-Annually.................................21
5.1.5 Annually .......................................... 22
Thermific® Gas-Fired Boiler Table of Contents
5.2 Cleaning the Burner.................................22
5.2.1 Semi-Annual Cleaning ....................22
5.2.2 Annual Cleaning .............................22
5.3 Removing the Exchanger ........................23
5.4 After All Repairs or Maintenance .............23
5.5 Sequence Of Operation ...........................23
5.6 Troubleshooting .......................................24
6.0 PARTS/TECHNICAL SUPPORT .......26
6.1 Wiring Diagrams ......................................27
6.1.1 On-Off .............................................28
6.1.1a On-Off IRI .....................................30
6.1.2 Lo-Hi-Lo .......................................... 32
!
WARNING
Improper use may result in fire or injury.
Read instructions/safety manual before installing,
c
1998 HCS, Inc. 800-748-0241
WARNING!
It is essential to read, understand, and follow the rec­ommendations of this manual before installing, operat­ing, or servicing this equipment. Failure to do so could result in fire or explosion and serious injury, death, and/or property damage.
The same features which permit this boiler to achieve high-efficiency performance make it unlike most other boilers of this general size, so it is important to under­stand how this boiler operates.
Do not store or use gasoline or other flammable vapors or liquids in the vicinity of this or any other appliance.
WARNING!
operating or servicing boiler.
Reorder No. 6020-V2WHPK
6.1.2a Lo-Hi-Lo IRI ..................................34
6.1.3 Water Cut-Off.................................. 36
6.2 Boiler Parts List .......................................38
6.2.1 Main Assembly ...............................38
6.2.2 Control Panel.................................. 39
6.2.3 Gas Train........................................ 40
6.2.4 Cabinet ...........................................41
7.0 LIMITED WARRANTY ....................... 42
7.1 Express Warranty .................................... 42
7.2 Warranty Disclaimer ................................ 42
What to do if you smell gas:
Do not try to light any appliance.
Do not touch any electrical switch.
Do not use any phone in your building. Immedi-
ately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions.
If you cannot reach your gas supplier call the fire
department.
Installation and service must be performed by a quali­fied installer, service agency, or gas supplier.
Thermific® Gas-Fired Boiler Introduction/Safety
1.0 INTRODUCTION
The P-K Thermific® Gas-Fired Boiler combines a ra­dial pre-mix fan-assisted burner with a compact, fin­ned-tube heat exchanger to provide maximum effi­ciency in a minimum of space. The high-quality mate­rials and thoroughly tested design of the boiler should provide years of trouble-free, hot-water service, if the instructions in this manual are followed carefully. This manual covers installation of P-K Thermific
®
Boiler Series 700, 1000, 1200, 1500, 1700, and 2000. The model numbers may be followed by a prefix or suffix letter in some cases to indicate special features or different options.
While details may differ slightly, basic operation is the same for all models. Boilers may be built to operate with natural gas or liquefied petroleum gas (propane). Check the rating plate for correct fuel usage and gas pressures.
The boiler is only a part of the complete heating sys­tem. This boiler may be fully operational and yet be­cause of poor circulation, control or other operating characteristics, not deliver heat to the desired location. Additional equipment such as temperature sensors, pumps, flow switches, balancing valves and check valves will be required for satisfactory operation of any system. Patterson-Kelley cannot be responsible for the design or operation of such systems and a qualified engineer or contractor must be consulted.
2.0 SAFETY
2.1
GENERAL
The Thermific gas-fired boiler must be:
Installed by qualified personnel in accordance with
designs prepared by qualified facility engineers in­cluding: structural, mechanical, electrical, and other applicable disciplines.
Operated and serviced by qualified, properly
trained personnel in accordance with all applicable codes, laws, and regulations.
2.2
TRAINING
!
WARNING
Improper use may result in fire or injury.
Read instructions/safety manual before installing,
c
1998 HCS, Inc. 800-748-0241
operating or servicing boiler.
Reorder No. 6020-V2WHPK
It is essential to read, understand, and follow the rec­ommendations of this manual before installing, operat­ing, or servicing this equipment. Failure to do so could result in serious injury, death, and/or property damage.
Proper training is the best protection against accidents. Operating and service personnel must be thoroughly familiar with the basic construction of the Thermific
boiler, the use and locations of the controls, the opera­tion of the boiler, adjustment of its various mecha­nisms, and all applicable safety precautions. If any of the provisions of this manual are not fully and com­pletely understood, contact the Patterson-Kelley Sales Department toll-free at (877) 728-5351 for assistance.
2.3
SAFETY FEATURES
It is the responsibility of the customer to maintain the safety features of this machine, such as: guards, safety labels, safety controls, interlocks, lockout devices, etc., in place and operable.
Operated and serviced in accordance with a com-
prehensive safety program determined and estab­lished by the customer. Do not attempt to operate or service until such a program has been estab­lished.
Page 1
Thermific® Gas-Fired Boiler Safety
2.4 SAFETY LABELS
NOTE
Make sure this union is tight before closing cabinet cover after servicing boiler.
c
1998 HCS, Inc. 800-748-0241
Reorder No. 8032-02NHAK
NOTE
When opening leak test valves, always follow instructions in operation and safety manual.
c
1998 HCS, Inc. 800-748-0241
Improper use may result in fire or injury.
Read instructions/safety manual before installing,
c
1998 HCS, Inc. 800-748-0241
C 1998 HCS, Inc. 800-748-0241
operating or servicing boiler.
The safety labels shown above are affixed to your boiler. Although the labels are of high quality, they may become dislodged or unreadable over time. Con­tact Patterson-Kelley toll-free at (877) 728-5351 for replacement labels.
2.5
SAFETY PRECAUTIONS
Reorder No. 8032-01NHPK
!
WARNING
Reorder No. 6020-V2WHPK
!
WARNING
Electrical hazard.
Follow lockout/tagout procedure when servicing this boiler.
Reorder No. 5025-V1WHPK
Shock hazard! Properly lockout/tagout the electri-
cal service and all other energy sources before working on or near the machine.
Shock hazard! Boiler is not rated for wash-down
service.
2.5.2 Burn, Fire, and Explosion Hazards
General Warning
c
1998 HCS, Inc. 800-748-0241
Improper use may result in fire or injury.
Read instructions/safety manual before installing, operating or servicing boiler.
Hot Surface
!
WARNING
Reorder No. 6020-V2WHPK
NOTE
Make sure this union is tight before closing cabinet cover after servicing boiler.
c
1998 HCS, Inc. 800-748-0241
Reorder No. 8032-02NHAK
NOTE
When opening leak test valves, always follow instructions in operation and safety manual.
c
1998 HCS, Inc. 800-748-0241
Reorder No. 8032-01NHPK
Provide a suitable location for the boiler, away from normal personnel traffic, with adequate working space, adequate clearances, proper ventilation and lighting, with a structure sufficiently strong and rigid to support the weight of the boiler, all piping, and accessories.
2.5.1 Electrical Hazards
!
WARNING
Electrical hazard.
Follow lockout/tagout procedure when servicing this boiler.
C 1998 HCS, Inc. 800-748-0241
Reorder No. 5025-V1WHPK
Page 2
Burn, fire, and explosion hazards! Installation
must be in strict conformance to all applicable codes and standards including NFPA 54, ANSI Z223.1 and CAN/CGA B.149. Install all required ventlines for gas devices. Refer to Section 3.7.2 below.
Hazard from incorrect fuels! Possible fire, explo-
sion, overheating, and damage. Do not use any fuels except the design fuel for the unit.
Overfire hazards! High pressure in gas or propane
supply could result in overfiring of other devices supplied from the same source.
Fire and explosion hazards! Close the main gas
shutoff before servicing boiler.
Thermific® Gas-Fired Boiler Safety
Fire and explosion hazards! Do not store or use
gasoline or other flammable vapors or liquids in the vicinity of this or any other gas fired appliance.
Burn hazard! Possible hot surfaces. Do not touch
gas vent during firing operation. Use only factory recommended vent components.
Burn hazard! Hot fluids. Use caution when ser-
vicing or draining boiler.
Fire and explosion hazards! Use caution when
servicing burner. Propane (LPG) is heavier than air and may linger in the combustion chamber, vent lines, or elsewhere.
Gas leak hazard! Make sure all connections to
main burner are tight when reassembling the burner. These connections cannot be tested after the burner is assembled.
Gas leak hazard! All threaded gas connections
must be made using a pipe compound that is resis­tant to liquefied petroleum. Do not use Teflon tape on threaded gas piping.
Gas leak hazard! Check entire gas train for leaks
after installation. If there is a smell of gas, shut down the boiler and obtain immediate assistance from trained service personnel and/or your local fire department.
Overfire hazard! Possible fire and explosion from
excess gas pressure. Make sure that gas inlet pres­sure does not exceed 14 inches W.C. to the regula­tor.
Overfire hazard! Possible fire and explosion.
Possible malfunction of regulators and/or motor­ized gas valves. Maintain all gas train components in good condition. Do not alter wiring connec­tions. Annual inspection by factory-trained per­sonnel for proper set-up and operation is recom­mended.
Overfire and underfire hazards! Possible fire, ex-
plosion, overheating, and component failure. Do not attempt to adjust firing rate of the boiler. The firing rate must be adjusted only by factory trained personnel.
2.5.3 Crush Hazards
General Warning
Lifting hazards! Use properly rated lifting equip-
ment to lift and position the boiler. The load is unbalanced. Test balance before lifting 3 ft. above the floor. Do not allow personnel beneath the lifted load. Refer to approximate weights in the table below:
Boiler Size Weight in Pounds 700,000 Btu 595 1,000,000 Btu 595 1,200,000 Btu 685 1,500,000 Btu 990 1,700,000 Btu 985 2,000,000 Btu 1,025
Bump hazard from overhead piping. Install piping
with adequate vertical clearance.
2.5.4 Chemical Hazards
Environmental hazard! The motorized gas valves
may contain hydraulic oil. Use safe procedures for the disposal of all lubricants.
Chemical hazards from cleaning products. Use
caution when cleaning the system. The use of pro­fessional assistance is recommended. Use safe procedures for the disposal of all cleaning solu­tions.
Page 3
Thermific® Gas-Fired Boiler Safety
2.5.5 Pressure Hazards
!
WARNING
Improper use may result in fire or injury.
Read instructions/safety manual before installing,
c
1998 HCS, Inc. 800-748-0241
operating or servicing boiler.
Pressure hazard! Hot fluids. Install isolation
valves on boiler water inlet and outlet. Make sure isolation valves are closed before servicing boiler.
Pressure hazard! Hot fluids. Annually test safety
relief valve for proper operation. Do not operate boiler with faulty relief valve.
2.5.6 Slip, Fall Hazards
!
WARNING
Improper use may result in fire or injury.
Read instructions/safety manual before installing,
c
1998 HCS, Inc. 800-748-0241
operating or servicing boiler.
Tripping hazard! Do not install piping on floor
surfaces. Maintain clear path around boiler.
Slip and fall hazard! Use drip pan to catch water
while draining the boiler. Maintain dry floor sur­faces.
Slip and fall hazard! Do not locate intake or ex-
haust terminations directly above a walkway; dripping of condensation can cause icing of the walking surface.
Page 4
Thermific® Gas-Fired Boiler Installation
3.0 INSTALLATION
RECEIVING AND STORAGE
3.1
3.1.1 Initial Inspection
Upon receiving the boiler, inspect it for signs of ship­ping damage. Pay particular attention to the control panel on the top of the boiler and the components mounted on the back, which may show damage from mishandling.
The exterior cabinet must be reasonably air-tight for the burner to operate correctly. Leaks caused by dents in the sheet metal or panels out of position may cause the limit controls to show Low Air. Check to be sure that the mixer core in the top burner is centered and has not moved in shipment; (see Section 5.2, "Clean­ing the Burner" for proper location). Verify that the total number of pieces shown on the packing slip agrees with those actually received.
Important: Note any damage or shortage on the freight bill and immediately notify the carrier. File all claims for shortage or damage with the carrier.
3.1.2 Storage Prior to Installation
If the boiler is not installed immediately, it must be stored in a location adequately protected from the weather, preferably indoors. If this is not possible, then it should remain in the shipping container and be covered by a tarpaulin or other waterproof covering.
Note: Controls and other equipment that are damaged or fail due to weather exposure are not covered by warranty.
3.2
COMPLIANCE WITH CODES
The P-K Thermific® Boiler with standard components and many options complies with American National Standard/CSA Standard ANSI Z21.13/CSA 4.9, latest edition, Gas-Fired Low Pressure Steam and Hot Water Boilers. The heat exchanger is constructed and stamped in accordance with ASME Boiler and Pres-
sure Vessel Code, Section IV for 160 psig maximum operating pressure and/or 250º F maximum operating temperature. Other codes or approvals which apply will be labeled on the boiler.
Installation of the boiler must conform to all the re­quirements of all national, state and local codes estab­lished by the authorities having jurisdiction or, in the absence of such requirements, in the U.S. to the Na­tional Fuel Gas Code, ANSI Z223.1/NFPA 54, latest edition. In Canada, the equipment shall be installed in accordance with the current Installation Code for Gas Burning Appliances and Equipment, CAN/CGA­B.149, and applicable Provincial Regulations for the class, which should be carefully followed in all cases. Authorities having jurisdiction should be consulted before installations are made.
Where required by local codes, the installation must conform to American Society of Mechanical Engi­neers Safety Code for Controls and Safety Devices for Automatically Fired Boilers (ASME CSD-1).
3.3
SETUP
3.3.1 Foundation
Provide a firm, level foundation, preferably of con­crete.
Note: The boiler may be installed on a combustible floor; however, the boiler must never be installed on carpeting.
3.3.2 Placement
The boiler must be level to function properly. To as­sist in leveling the boiler, the four (4) leg bolts (1/2"­NC) holding the boiler to the shipping skid must be reinstalled in the threaded legs on the bottom. The adjustable legs are also necessary to provide adequate floor clearance and prevent distortion on the cabinet, (twisting, etc.) in addition to leveling.
Page 5
Thermific® Gas-Fired Boiler Installation
DD
Adjustable Legs for Leveling and Floor Clearance
3.3.3 Clearances
If the boiler is to be installed near combustible sur­faces, the minimum clearances shown in the table be­low must be maintained.
Failure to provide for the service access clearances, even with non-combustible surfaces, may cause future problems servicing the boiler.
The boiler must be installed in a space large in com­parison to the boiler as described in Section 6.3 of the National Fuel Gas Code, ANSI Z223.1, latest edition.
Minimum Clearances from Adjacent Walls, Ceiling, and
Type of Surface
Dimensions (inches)
Obstructions
A B C† D
Combustible Surfaces 30 24 24 24
Non-combustible Sur-
30 24* 24 24**
faces
† "C" dimension includes clearance to remove the burner. Do not put pipes, ducts, etc. in this area above the boiler.
* CSA minimum. Actual clearance depends upon stacking requirements.
No pipes, ducts, etc. in this area.
AB
C
Page 6
** Service access need be only on one side of a boiler or row of boilers. Boilers may be installed immedi­ately adjacent to each other. However, P-K recom­mends this clearance between each boiler when there is insufficient access at the rear to allow for service and adjustment.
In Canada: The boilers are approved for installation with zero clearance to combustible surfaces, but 24 inch service clearances are recommended.
ELECTRICAL CONNECTIONS
3.4
The boiler is wired for 120 volts, single phase, 60 hertz. The total operating amperage is indicated on the rating nameplate. The 700 and 1000 series require less than 8 amps; the 1200 series less than 9 amps; the 1500, 1700, 2000 series less than 12 amps. Before
Thermific® Gas-Fired Boiler Installation
starting the boiler, check to ensure that the proper voltage and amperage is connected to the boiler.
An external electrical disconnect (not supplied with the boiler) with adequate overload protection is re­quired. The boiler must be grounded in accordance with local codes or in the absence of such require­ments, in the U.S. with National Electrical Codes, ANSI/NFPA No. 70 latest edition and in Canada, wire according to the current Canadian Electrical Code.
Note: A dedicated earth ground (green wire) is re­quired to avoid nuisance shutdowns. Do not ground through the conduit. It is also important that proper polarity be maintained.
COMBUSTION AIR
3.5
Combustion air must be free from dust, lint, etc. The presence of such materials in the air supplied to the burner could cause nuisance "Low Air" shutdowns or premature burner failure. The boiler should not be operated during construction while the possibility of drywall dust, demolition dust, etc. exists.
Provisions for combustion and ventilation air must be in accordance with Section 5.3, Air for Combustion and Ventilation, of the National Fuel Gas Code, ANSI Z223.1, latest edition, or applicable provisions of the local building codes. In Canada, combustion air open­ings shall comply with CSA 4.9. The formula is "1 sq. in. per 1,000 Btu/hr of gas input not less than 100 sq. in." The location shall be "neither more than 18," nor less than 6" above the floor level.
The boiler room shall be provided with two openings to ensure adequate combustion air and proper ventila­tion. One opening should be 6 to 12 inches above the floor and the other 6 to 12 inches below the ceiling, preferably on opposite walls. The size of each open­ing is determined by whether air is taken from inside or outside the building. In Canada, ventilation air openings shall be at least 10% of the cross sectional area required for combustion air, but not less than 10 square inches. It is to be located at the highest practi­cal point communicating with outdoors.
If air is taken directly from outside the building, each opening should have a net free area of 1 square inch for each 4,000 Btu per hour of total boiler input. For
instance, 300 square inches (2-1/12 square feet) are required for 1,200,000 Btu per hour input.
When air is taken from the outdoors through a vertical duct, 1 square inch per 4,000 Btu per hour is required. If a horizontal duct is used, 1 square inch per 2,000 Btu per hour is required, i.e., 600 square inches for 1,200,000 Btu per hour input.
If air is taken from another interior space, each open­ing should have a net free area of 1 square inch for each 1,000 Btu per hour of boiler input (1,200 square inches for a 1,200,000 Btu per hour.)
WARNING!
Under no circumstances shall the boiler room ever be under a negative pressure. Particular care should be taken when exhaust fans, compressors, air-handling units or other equipment may rob air from the boiler.
The combustion air supply must be completely free of chemical fumes which may be corrosive when burned in the boiler. Common chemicals which must be avoided are fluorocarbons and other halogenated com­pounds, most commonly present as refrigerants or sol­vents, such as freon, trichlorethylene, perchlorethyl­ene, chlorine, etc. These chemicals, when burned, form acids which quickly attack the boiler tubes, tube sheets, flue collectors and the boiler stack. The result is improper combustion and premature boiler failure.
3.6
FLUE VENTING
For boilers connected to gas vents or chimneys, vent installations shall be in accordance with Part 7, Vent­ing of Equipment, of the National Fuel Gas Code, ANSI Z223.1, or applicable provisions of the local building codes.
This boiler is certified as Category I as it is defined in ANSI Z21.13/CSA 4.9, latest edition. This boiler is suitable for use with Type "B" vent.
In Canada, the boiler is certified for installation with a "Power Venter" by the Canadian Gas Association when installed with the "listed accessories." Consult your local distributor for information on proper selec­tion.
Page 7
Thermific® Gas-Fired Boiler Installation
The venting system and the horizontal portions of the venting system shall be supported to prevent sagging.
Consult your local vent supplier for correct vent sizing and structural support requirements. Vent diameter is dictated by the length and height of horizontal and ver­tical portions of the vent installation and the materials of construction. Correct sizing should provide a slightly negative pressure (less than 0.1 inches of wa­ter column) at the boiler flue outlet with a stack tem­perature of 280º F.
3.6.1 Vent Elbows
The turn from horizontal to vertical should be made with two 45º ells or with one long radius 90º ell for best operation. Do not use "short radius" ells.
3.6.2 Barometric Damper
This boiler is certified for operation without a baro­metric damper. However, some venting installations may require a barometric damper for smooth opera­tion. A barometric damper is supplied with each boiler, and when used, should be installed according to the following guidelines.
3.6.3 Barometric Damper Location
2. The damper may be located in either side of the horizontal section of stack.
3. In a multiple boiler installation, one barometric damper must be installed with each boiler.
Be sure that the damper is mounted horizontally (never vertically). Be sure to remove all three red stops from the damper before start-up. The damper door should swing freely. Carefully follow all the instructions pro­vided with the barometric damper.
Boiler
Barometric Damper,
incorrect
( locations)
Incorrect Damper Locations
WARNING!
To avoid spillage into the boiler room of dangerous flue gas containing carbon monoxide, the opening in the damper (draft control gate) must never face against the flow of flue gas.
Boiler
Barometric Damper
Correct Damper Location
1. We recommend that the barometric damper be located immediately after the flue connector for best operation. Consult vent supplier for specific installation requirements.
Page 8
3.6.4 Flue Connection
The connection from the boiler to the vent should be as direct as possible and the upward slope of any hori­zontal breaching should be at least 1/4 inch per linear foot. This boiler should not be connected into any por­tion of a mechanical draft system operating under positive pressure. Provisions must be made for sup­ports to prevent contact of the vent with combustible surfaces.
Note: If the vent is erected directly behind the boiler, make sure that the weight of the vent is not supported by the boiler vent collar. The collar is not designed to support the weight of the vent. Structural support and spacing from combustible surfaces must be in accor­dance with the vent manufacturer's requirements.
Thermific® Gas-Fired Boiler Installation
3.6.5 Vent Termination
Correct
Listed
Te rm ination
Typical Incorrect
(too restrictive)
Vent Termination
The minimum vent height above the flue outlet must be five (5) feet and the vent should extend at least three (3) feet above the roof, or at least two (2) feet above the highest part of any structure within ten (10) feet of the vent.
The vent must be provided with a weather cap of ap­proved design and adequate capacity.
3.6.6 Removing an Existing Boiler
(from a common venting system)
When an existing boiler is removed from a common venting system, the common venting system is likely to be too large for proper venting of the appliances remaining connected to it.
system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a summer ex­haust fan. Close fireplace dampers.
4. Place the appliance being inspected in operation. Follow the lighting instructions. Adjust the ther­mostat so that the appliance will operate continu­ously.
5. Test for spillage at the draft hood relief opening after 5 minutes of main burner operation. Use the flame of a match or candle or smoke from a ciga­rette, cigar or pipe.
6. After it has been determined that each appliance remaining connected to the common venting sys­tem properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas-burning appliance to their previous conditions of use.
Any improper operation of the common venting sys­tem should be corrected so the installation conforms with the National Fuel Gas Code, ANSI Z223.1. When resizing any portion of the common venting sys­tem, the common venting system should be resized to approach the minimum size as determined using the appropriate tables in Part II in the National Fuel Gas Code, ANSI Z223.1.
At the time of removal of an existing boiler, while the other appliances remaining connected to the common venting system are not in operation, the following steps should be followed with each appliance remain­ing connected to the common venting system placed in operation:
1. Seal any unused openings in the common venting system.
2. Visually inspect the venting system for proper size and horizontal pitch and determine that there is no blockage or restriction, leakage, corrosion or other deficiency which could cause an unsafe condition.
3. Insofar as is practical, close all building doors and windows and all doors between the space in which the appliances remaining connected to the com­mon venting system are located and other spaces of the building. Turn on clothes dryers and any appliances not connected to the common venting
Page 9
3.7
GAS PIPING
Before making the gas hook-up, make sure the boiler is being supplied with the type of fuel shown on the boiler nameplate.
The boiler shall be installed such that the gas ignition system components are protected from water (drip­ping, spraying, rain, etc.) during appliance operation and service (circulator replacement, control replace­ment, etc.)
The gas pressure regulator supplied with the boiler is set during a factory fire-test to provide the proper pres­sure to the main burner, which for natural gas is based on 7 inches W.C. inlet pressure to the regulator (11 inches W.C. for propane). The gas train components are designed to handle a maximum inlet pressure of 14 inches water column (1/2 psig.). If the available gas pressure exceeds 14 inch W.C., a suitable additional
Thermific® Gas-Fired Boiler Installation
intermediate gas pressure regulator of the "lock up" type must be provided to reduce the pressure to less than 14 inch W.C.
WARNING!
All threaded connections must be made using a pipe compound that is resistant to the action of liquefied petroleum gases. Do not use Teflon tape on gas line threads.
by installer natural gas supply
remote gas shutoff (not supplied)
drip leg
meter
(not supplied)
union
shutoff (on boiler)
Gas Piping
Pipe Capacity for Natural Gas
Nominal
Iron Pipe
Size
(Inches)
Internal Diame-
ter
(Inches)
Equivalent Pipe Length Maximum Capacity in Cubic Feet of Natural Gas per Hour
90º Ell
(Feet)
Tee
(Feet)
Note: Install a sediment trap (drip leg) and a union connection ahead of the primary manual shutoff valve on the boiler. Gas piping should be installed in accor­dance with National Fuel Gas Code, ANSI Z223.1, latest edition, and any other local codes which may apply; in Canada see CAN/CGA-B 149.
Note: See chart below for required pipe size, based on overall length of pipe from meter plus equivalent length of all fittings. Approximate sizing may be based on 1 cubic foot of natural gas per 1,000 Btu per hour input, i.e., 900,000 Btu per hour requires about 900 cubic feet per hour. (See Typical Boiler Operating Conditions, Section 4.3, for more information.)
Pressure Drop of 0.5 inch Water Column/Equivalent Length of
Pipe (in feet)
20
40
60
80
100
150
200
1-1/4 1.380 3.5 6.9 950 1-1/2 1.610 4.0 8.0 1,460 990 810
2 2.067 5.2 10.3 2,750 1,900 1,520 1,300 1,150 950 950
2-1/2 2.469 6.2 12.3 4,350 3,000 2,400 2,050 1,850 1,500 1,280
3 3.068 7.7 15.3 7,700 5,300 4,300 3,700 3,250 2,650 2,280 4 4.026 10.1 20.2 15,800 15,800 8,800 7,500 6,700 5,500 4,800
Page 10
Loading...
+ 32 hidden pages