Patterson-Kelley MOD-04 User Manual

MOD-04
PATTERSON-KELLEY
THERMIFIC®
MODU-FIRE® GAS-FIRED BOILER
Installation and Owner's Manual
C.S.A Design-Certified Complies with ANSI Z21.13/CSA 4.9 Gas-Fired Low Pressure Steam and Hot Water Boilers
ASME Code, Section IV Certified by Patterson-Kelley
C.S.A Design-Certified Complies with ANSI Z21.13/CSA 4.9 Gas-Fired Low Pressure Steam and Hot Water Boilers
100 Burson Street, P.O. Box 458, East Stroudsburg, PA 18301 Telephone: (877) 728-5351, Facsimile: (570) 476-7247 www.pkboilers.com
Modu-Fire® Gas-Fired Boiler Table of Contents
1.0 INTRODUCTION........................................1
2.0 SAFETY......................................................1
2.1 General.......................................................1
2.2 Training....................................................... 1
2.3 Safety Features ..........................................1
2.4 Safety Labels..............................................2
2.5 Safety Precautions...................................... 2
2.5.1 Electrical Hazards.................................2
2.5.2 Burn, Fire, and Explosion Hazards.......2
2.5.3 Crush Hazards......................................3
2.5.4 Chemical Hazards................................3
2.5.5 Pressure Hazards.................................4
2.5.6 Slip, Fall Hazards ................................. 4
3.0 INSTALLATION..........................................5
3.1 Receiving and Storage ............................... 5
3.1.1 Initial Inspection....................................5
3.1.2 Storage Prior to Installation.................. 5
3.2 Compliance with Codes.............................. 5
3.3 Setup...........................................................5
3.3.1 Foundation............................................5
3.3.2 Placement............................................. 5
3.3.3 Clearances ...........................................6
3.4 Electrical Connections................................6
3.5 Combustion Air ...........................................7
3.6 Flue Venting................................................ 7
3.6.1 Vent Elbows.......................................... 8
3.6.2 Barometric Damper .............................. 8
3.6.3 Automatic Vent Damper .......................8
3.6.4 Flue Connection ................................... 8
3.6.5 Vent Termination..................................8
3.6.6 Removing an Existing Boiler ................9
3.7 Gas Piping .................................................. 9
3.7.1 Gas Supply Piping by Installer ...........11
3.7.2 Gas Bleeds and Vents by Installer.....11
3.8 Boiler Water Piping................................... 11
3.8.1 Piping Design......................................11
3.8.2 Boiler Inlet and Outlet Connections....12
3.8.3 Boiler Water Piping by Installer...........12
3.8.4 Flushing and Filling.............................13
3.8.5 Water Quality ......................................13
3.9 Burner and Ignition System.......................13
3.9.1 Inspection............................................13
3.10 Pre-Start Check List................................13
3.11 Safety Checks.........................................14
3.11.1 Test of Ignition Safety System..........14
3.11.2 Test of Low Water Cut-off.................14
3.11.3 Test of Limit Controls........................14
3.11.4 Test of Low Gas Pressure Switch.....15
3.11.5 Test of High Gas Pressure Switch....15
3.12 Initial Adjustments...................................15
3.12.1A – Configuring the Local Controller...15
3.12.1B Optional Remote Control................20
3.12.2 Air Flow Adjustments........................20
3.12.3 Gas Pressure Adjustment.................21
4.0 OPERATION ............................................22
4.1 General......................................................22
4.1.1 Control Panel Front.............................22
4.2 Lighting and Shut-Down Procedures ........22
4.2.1 Lighting Procedures............................22
4.2.2 Normal Shut Down Procedures ..........23
4.2.3 Emergency Shut Off............................23
4.3 Typical Boiler Operating Conditions..........23
5.0 MAINTENANCE ......................................24
5.1 Maintenance and Inspection Schedule.....24
5.1.1 Daily....................................................24
5.1.2 Weekly ................................................24
5.1.3 Monthly (During Operation).................24
5.1.4 Semi-Annually.....................................24
5.1.5 Annually ..............................................25
5.2 Cleaning the Burner ..................................25
Modu-Fire® Gas-Fired Boiler Table of Contents
5.3 Removing the Exchanger ......................... 26
5.4 After All Repairs or Maintenance..............26
5.5 Sequence of Operation..............................27
5.5.1 Standard Modulating ..........................27
5.5.2 IRI Modulating .................................... 28
5.6 Troubleshooting........................................ 29
6.0 PARTS/TECHNICAL SUPPORT..............31
6.1 Schematic Diagrams..................................31
Standard Unit - Local Control - Logic Diagram32 Standard Unit - Remote Control - Logic
Diagram..................................................33
Standard Unit - Local & Remote Control -
Logic Diagram........................................34
Standard Unit - Local & Remote Control w
Options - Logic Diagram........................35
!
WARNING
Improper use may result in fire or injury.
Read instructions/safety manual before installing,
c
1998 HCS, Inc. 800-748-0241
operating or servicing boiler.
Reorder No. 6020-V2WHPK
WARNING!
IRI Unit - Local Control - Logic Diagram.......36
IRI Unit - Remote Control - Logic Diagram...37 IRI Unit - Local & Remote Control - Logic
Diagram..................................................38
IRI Unit - Local & Remote Control w Options -
Logic Diagram ........................................39
Standard Unit – Panel Layout.......................40
IRI Unit – Panel Layout.................................41
6.2 Boiler Parts List.........................................42
6.2.1 Main Assembly....................................42
6.2.2 Control Panel......................................43
6.2.3 Gas Trains...........................................45
6.2.4 Cabinet................................................49
7.0 LIMITED WARRANTY.............................50
WARNING!
It is essential to read, understand, and follow the recommendations of this manual before installing, operating, or servicing this equipment. Failure to do so could result in fire or explosion and serious in­jury, death, and/or property damage.
The same features which permit this boiler to achieve high-efficiency performance make it unlike most other boilers of this general size, so it is im­portant to understand how this boiler operates.
Do not store or use gasoline or other flammable vapors or liquids in the vicinity of this or any other appliance.
Installation and service must be performed by a qualified installer, service agency, or gas supplier.
What to do if you smell gas:
Do not try to light any appliance.
Do not touch any electrical switch.
Do not use any phone in your building. Imme-
diately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions.
If you cannot reach your gas supplier call the
fire department.
Modu-Fire® Gas-Fired Boiler Introduction/Safety
1.0 INTRODUCTION
The P-K MODU-FIRE lutionary advance; Patterson-Kelley now combines full-modulation burner control with our time-tested modular hot water boiler design. The result is “modular full-modulation”- Modu-Fire! This new hybrid boiler combines the best of our earlier de­signs with a new generation of burner and control technology. You will achieve even higher part-load efficiencies – but without the complexity you might expect in this type of high performance boiler. High performance made simple and dependable for years of trouble-free operation.
This manual covers installation of the P-K MODU-
®
FIRE
Boiler Series 1000, 1500, and 2000. The model numbers may be followed by a prefix or suf­fix letter in some cases to indicate special features or different options. While details may differ slightly, basic operation is the same for all models. Boilers are built to operate with natural gas or pro­pane. Check the rating plate for the correct gas type and flow rate.
The boiler is only a part of the complete heating system. This boiler may be fully operational and yet because of poor circulation, controls, or other oper­ating characteristics, not deliver heat to the desired location. Additional equipment such as temperature sensors, pumps, flow switches, balancing valves and check valves will be required for satisfactory opera­tion of any system. Patterson-Kelley cannot be re­sponsible for the design or operation of such sys­tems and a qualified engineer or contractor must be consulted.
®
Gas Fired Boiler is a revo-
2.0 SAFETY
2.1
GENERAL
The MODU-FIRE® gas-fired boiler must be:
Installed in accordance with designs prepared
by qualified facility engineers including: struc­tural, mechanical, electrical, and other applica­ble disciplines.
Operated and serviced in accordance with a
comprehensive safety program determined and established by the customer. Do not attempt to operate or service until such a program has been established.
Operated and serviced by qualified, factory-
trained personnel in accordance with all appli­cable codes, laws, and regulations.
The use of the term “factory-trained personnel”
throughout this manual indicates Patterson­Kelley trained on this specific piece of equip­ment.
2.2
TRAINING
!
WARNING
Improper use may result in fire or injury.
Read instructions/safety manual before installing,
c
1998 HCS, Inc. 800-748-0241
operating or servicing boiler.
Reorder No. 6020-V2WHPK
It is essential to read, understand, and follow the recommendations of this manual before installing, operating, or servicing this equipment. Failure to do so could result in serious injury, death, and/or prop­erty damage.
Proper training is the best protection against acci­dents. Operating and service personnel must be thoroughly familiar with the basic construction of the MODU-FIRE
®
boiler, the use and locations of the controls, the operation of the boiler, adjustment of its various mechanisms, and all applicable safety precautions. If any of the provisions of this manual are not fully and completely understood, contact the Patterson-Kelley Sales Department.
2.3
SAFETY FEATURES
It is the responsibility of the customer to maintain the safety features of this machine, such as: guards, safety labels, safety controls, interlocks, lockout devices, etc., in place and operable.
1
Modu-Fire® Gas-Fired Boiler Safety
SAFETY LABELS
2.4
NOTE
Make sure this union is tight before closing cabinet cover after servicing boiler.
c
1998 HCS, Inc. 800-748-0241
Reorder No. 8032-02NHAK
Shock hazard! Properly lockout/tagout the elec-
trical service and all other energy sources before working on or near the machine.
Shock hazard! Boiler is not rated for wash-
down service.
NOTE
When opening leak test valves, always follow instructions in operation and safety manual.
c
1998 HCS, Inc. 800-748-0241
c
1998 HCS, Inc. 800-748-0241
C 1998 HCS, Inc. 800-748-0241
Improper use may result in fire or injury.
Read instructions/safety manual before installing, operating or servicing boiler.
Reorder No. 8032-01NHPK
!
WARNING
Reorder No. 6020-V2WHPK
!
WARNING
Electrical hazard.
Follow lockout/tagout procedure when servicing this boiler.
Reorder No. 5025-V1WHPK
The safety labels shown above are affixed to your boiler. Although the labels are of high quality, they may become dislodged or unreadable over time. Contact Patterson-Kelley for replacement labels.
2.5
SAFETY PRECAUTIONS
Provide a suitable location for the boiler, away from normal personnel traffic, with adequate working space, adequate clearances, proper ventilation and lighting, with a structure sufficiently strong and rigid to support the weight of the boiler, all piping, and accessories.
2.5.1 Electrical Hazards
!
WARNING
Electrical hazard.
Follow lockout/tagout procedure when servicing this boiler.
C 1998 HCS, Inc. 800-748-0241
Reorder No. 5025-V1WHPK
2.5.2 Burn, Fire, and Explosion Hazards
General Warning
c
1998 HCS, Inc. 800-748-0241
!
Improper use may result in fire or injury.
Read instructions/safety manual before installing, operating or servicing boiler.
Hot Surface
WARNING
Reorder No. 6020-V2WHPK
NOTE
Make sure this union is tight before closing cabinet cover after servicing boiler.
c
1998 HCS, Inc. 800-748-0241
Reorder No. 8032-02NHAK
NOTE
When opening leak test valves, always follow instructions in operation and safety manual.
c
1998 HCS, Inc. 800-748-0241
Burn, fire, and explosion hazards! Installation
must be in strict conformance to all applicable codes and standards including NFPA 54, ANSI Z223.1 and CAN/CGA B.149. Install all re­quired ventlines for gas devices. Refer to Sec­tion 3.7.2.
Hazard from incorrect fuels! Possible fire, ex-
plosion, overheating, and damage. Do not use any fuels except the design fuel for the unit.
Overfire hazards! High pressure in gas or pro-
pane supply could result in overfiring of other devices supplied from the same source.
Fire and explosion hazards! Close the main gas
shutoff before servicing boiler.
Reorder No. 8032-01NHPK
2
Modu-Fire® Gas-Fired Boiler Safety
Fire and explosion hazards! Do not store or use
gasoline or other flammable vapors or liquids in the vicinity of this or any other gas fired appli­ance.
Burn hazard! Possible hot surfaces. Do not
touch gas vent during firing operation. Use only factory recommended vent components.
Burn hazard! Hot fluids. Use caution when
servicing or draining boiler.
Fire and explosion hazards! Use caution when
servicing burner. Propane (LPG) is heavier than air and may linger in the combustion chamber, vent lines, or elsewhere.
Gas leak hazard! Make sure all connections to
main burner are tight when reassembling the burner. These connections cannot be tested af­ter the burner is assembled.
Gas leak hazard! All threaded gas connections
must be made using a pipe compound that is re­sistant to liquefied petroleum. Do not use Tef­lon tape on threaded gas piping.
Gas leak hazard! Check entire gas train for
leaks after installation. If there is a smell of gas, shut down the boiler and obtain immediate as­sistance from factory-trained personnel and/or your local fire department.
2.5.3 Crush Hazards
General Warning
Lifting hazards! Use properly rated lifting
equipment to lift and position the boiler. The load is unbalanced. Test balance before lifting 3 ft. above the floor. Do not allow personnel be­neath the lifted load. Refer to approximate weights in the table below:
Boiler Size Weight in Pounds 1,000,000 Btu 595 1,500,000 Btu 990 2,000,000 Btu 1,025
Bump hazard from overhead piping. Install pip-
ing with adequate vertical clearance.
2.5.4 Chemical Hazards
Overfire hazard! Possible fire and explosion
from excess gas pressure. Make sure that gas inlet pressure does not exceed 14 inches w.c. to the regulator.
Overfire hazard! Possible fire and explosion.
Possible malfunction of regulators and/or mo­torized gas valves. Maintain all gas train com­ponents in good condition. Do not alter wiring connections. Annual inspection by factory­trained personnel for proper set-up and opera­tion is recommended.
Environmental hazard! The motorized gas
valves may contain hydraulic oil. Use safe pro­cedures for the disposal of all lubricants.
Chemical hazards from cleaning products. Use
caution when cleaning the system. The use of professional assistance is recommended. Use safe procedures for the disposal of all cleaning solutions.
General Warning
Overfire and underfire hazards! Possible fire,
explosion, overheating, and component failure. Do not attempt to adjust firing rate of the boiler. The firing rate must be adjusted only by fac­tory-trained personnel.
3
Modu-Fire® Gas-Fired Boiler Safety
2.5.5 Pressure Hazards
!
WARNING
Improper use may result in fire or injury.
Read instructions/safety manual before installing,
c
1998 HCS, Inc. 800-748-0241
operating or servicing boiler.
Pressure hazard! Hot fluids. Install isolation
valves on boiler water inlet and outlet. Make sure isolation valves are closed before servicing boiler.
Pressure hazard! Hot fluids. Annually test
safety relief valve for proper operation. Do not operate boiler with faulty relief valve.
2.5.6 Slip, Fall Hazards
!
WARNING
Improper use may result in fire or injury.
Read instructions/safety manual before installing,
c
1998 HCS, Inc. 800-748-0241
operating or servicing boiler.
Tripping hazard! Do not install piping on floor
surfaces. Maintain clear path around boiler.
Slip and fall hazard! Use drip pan to catch wa-
ter while draining the boiler. Maintain dry floor surfaces.
Slip and fall hazard! Do not locate intake or
exhaust terminations directly above a walkway; dripping of condensation can cause icing of the walking surface.
4
Modu-Fire® Gas-Fired Boiler Installation
3.0 INSTALLATION
RECEIVING AND STORAGE
3.1
3.1.1 Initial Inspection
Upon receiving the boiler, inspect it for signs of ship­ping damage. Pay particular attention to the control panel on the top of the boiler and the components mounted on the back, which may show damage from mishandling.
The exterior cabinet must be reasonably air-tight for the burner to operate correctly. Leaks caused by dents in the sheet metal or panels out of position may cause the limit controls to show Low Air. Check to be sure that the mixer core in the top burner is centered and has not moved in shipment; (see Section 5.2, "Clean­ing the Burner" for proper location). Verify that the total number of pieces shown on the packing slip agrees with those actually received.
Important: Note any damage or shortage on the freight bill and immediately notify the carrier. File all claims for shortage or damage with the carrier
3.1.2 Storage Prior to Installation
If the boiler is not installed immediately, it must be stored in a location adequately protected from the weather, preferably indoors. If this is not possible, then it should remain in the shipping container and be covered by a tarpaulin or other waterproof covering.
Note: Controls and other equipment that are damaged or fail due to weather exposure are not covered by warranty.
.
temperature. Other codes or approvals which apply will be labeled on the boiler.
Installation of the boiler must conform to all the re­quirements of all national, state and local codes estab­lished by the authorities having jurisdiction or, in the absence of such requirements, in the U.S. to the Na­tional Fuel Gas Code, ANSI Z223.1/NFPA 54, latest edition. In Canada, the equipment shall be installed in accordance with the current Installation Code for Gas Burning Appliances and Equipment, CAN/CGA­B.149, and applicable Provincial Regulations for the class, which should be carefully followed in all cases. Authorities having jurisdiction should be consulted before installations are made.
Where required by local codes, the installation must conform to American Society of Mechanical Engi­neers Safety Code for Controls and Safety Devices for Automatically Fired Boilers (ASME CSD-1).
In the Commonwealth of Massachusetts (a) this unit must be installed by a licensed pipe fitter / plumber, (b) field installed gas cocks must be "T" handle type, and (c) piping of condensate shall conform with the State Plumbing Code.
3.3
SETUP
3.3.1 Foundation
Provide a firm, level foundation, preferably of con­crete.
Note: The boiler may be installed on a combustible floor; however, the boiler must never be installed on carpeting.
COMPLIANCE WITH CODES
3.2
The P-K MODU-FIRE® Boiler with standard compo­nents and many options complies with American Na­tional Standard/CSA Standard ANSI Z21.13/CSA 4.9, latest edition, Gas-Fired Low Pressure Steam and Hot Water Boilers. The heat exchanger is constructed and stamped in accordance with ASME Boiler and Pres­sure Vessel Code, Section IV for 160 psig maximum
3.3.2 Placement
The boiler must be level to function properly. To as­sist in leveling the boiler, the four (4) leg bolts (1/2"­NC) holding the boiler to the shipping skid must be reinstalled in the threaded legs on the bottom. The adjustable legs are also necessary to provide adequate floor clearance and prevent distortion on the cabinet, (twisting, etc.) in addition to leveling.
operating pressure and/or 250º F maximum operating
5
Modu-Fire® Gas-Fired Boiler Installation
DD
Adjustable Legs for Leveling and Floor Clearance
3.3.3 Clearances
If the boiler is to be installed near combustible sur­faces, the minimum clearances shown in the table be­low must be maintained.
Failure to provide for the service access clearances, even with non-combustible surfaces, may cause future problems servicing the boiler.
The boiler must be installed in a space large in com­parison to the boiler as described in Section 6.3 of the National Fuel Gas Code, ANSI Z223.1, latest edition.
Minimum Clearances from Adjacent Walls, Ceiling, and
Type of Surface
Combustible Surfaces 30 24 30 24 Non-combustible Sur-
faces
† "C" dimension includes clearance to remove the burner. Do not put pipes, ducts, etc. in this area above the boiler.
* CSA minimum. Actual clearance depends upon stacking requirements.
Obstructions
Dimensions (inches)
A B C† D
30 24* 30 24**
** Service access need be only on one side of a boiler
No pipes, ducts, etc. in this area.
C
or row of boilers. Boilers may be installed immedi­ately adjacent to each other. However, P-K recom­mends this clearance between each boiler when there is insufficient access at the rear to allow for service and adjustment.
In Canada: The boilers are approved for installation with zero clearance to combustible surfaces, but 24
Front of
Boiler
AB
Back of
Boiler
inch service clearances are recommended.
3.4
ELECTRICAL CONNECTIONS
All field wiring connections for power and control are in the rear service panel on the back of the boiler. Low voltage and high voltage terminal strips are indi­cated on the wiring diagram. The boiler power circuit
6
Modu-Fire® Gas-Fired Boiler Installation
is wired for 120 volts, single phase, 60 hertz. The total operating amperage is indicated on the rating name­plate. The 1000 series require less than 9 amps; the 1500 and 2000 series less than 12 amps. Before start­ing the boiler, check to ensure that the proper voltage and amperage are connected to the boiler.
An external electrical disconnect (not supplied with the boiler) with adequate overload protection is re­quired. The boiler must be grounded in accordance with local codes or in the absence of such require­ments, in the U.S. with National Electrical Codes, ANSI/NFPA No. 70 latest edition and in Canada, wire according to the current Canadian Electrical Code.
Note: A dedicated earth ground (green wire) is re­quired to avoid nuisance shutdowns. Do not ground through the conduit. It is also important that proper polarity be maintained.
3.5
COMBUSTION AIR
Combustion air must be free from dust, lint, etc. The presence of such materials in the air supplied to the burner could cause nuisance "Low Air" shutdowns or premature burner failure. The boiler should not be operated during construction while the possibility of drywall dust, demolition dust, etc. exists.
Provisions for combustion and ventilation air must be in accordance with Section 5.3, Air for Combustion and Ventilation, of the National Fuel Gas Code, ANSI Z223.1, latest edition, or applicable provisions of the local building codes. In Canada, combustion air open­ings shall comply with CSA 4.9. The formula is "1 sq. in. per 1,000 Btu/hr of gas input not less than 100 sq. in." The location shall be "neither more than 18," nor less than 6" above the floor level."
The boiler room shall be provided with two openings to ensure adequate combustion air and proper ventila­tion. One opening should be 6 to 12 inches above the floor and the other 6 to 12 inches below the ceiling, preferably on opposite walls. The size of each open­ing is determined by whether air is taken from inside or outside the building. In Canada, ventilation air openings shall be at least 10% of the cross sectional area required for combustion air, but not less than 10 square inches. It is to be located at the highest practi­cal point communicating with outdoors.
If air is taken directly from outside the building, each opening should have a net free area of 1 square inch for each 4,000 Btu per hour of total boiler input. For instance, 300 square inches (2-1/12 square feet) are required for 1,200,000 Btu per hour input.
When air is taken from the outdoors through a vertical duct, 1 square inch per 4,000 Btu per hour is required. If a horizontal duct is used, 1 square inch per 2,000 Btu per hour is required, i.e., 600 square inches for 1,200,000 Btu per hour input.
If air is taken from another interior space, each open­ing should have a net free area of 1 square inch for each 1,000 Btu per hour of boiler input (1,200 square inches for a 1,200,000 Btu per hour.)
WARNING! Under no circumstances shall the boiler room ever be
under a negative pressure. Particular care should be taken when exhaust fans, compressors, air-handling units or other equipment may rob air from the boiler.
The combustion air supply must be completely free of chemical fumes which may be corrosive when burned in the boiler. Common chemicals which must be avoided are fluorocarbons and other halogenated com­pounds, most commonly present as refrigerants or sol­vents, such as freon, trichlorethylene, perchlorethyl­ene, chlorine, etc. These chemicals, when burned, form acids which quickly attack the boiler tubes, tube sheets, flue collectors and the boiler stack. The result is improper combustion and premature boiler failure.
3.6 FLUE VENTING
This boiler requires a special vent system. Vent instal­lations shall be in accordance with Part 7, Venting of Equipment, of the National Fuel Gas Code, ANSI Z223.1, CSA B149 code or applicable provisions of the local building codes.
This boiler is Category II as it is defined in ANSI Z21.13/CSA 4.9 latest edition. The vent material must be listed Category II Vent pipe (316L or AL-29 4C Stainless). Under no circumstances shall a Category I material (e.g. B-vent) be used.
7
Modu-Fire® Gas-Fired Boiler Installation
WARNING! This boiler should not be installed with an automatic
damper on the flue. Damper failure could create an explosion hazard.
In Canada, the boiler is certified for installation with a “Power Venter” by the Canadian Gas Association when installed with the “listed accessories.” Consult your local distributor for information on proper selec­tion.
The venting system and the horizontal portions of the venting system shall be supported to prevent sagging.
Consult your local vent supplier for correct vent sizing and structural support requirements. Vent diameter is dictated by the length and height of horizontal and ver­tical portions of the vent installation and the materials of construction. It is not necessarily the same size as the boiler connection. Correct sizing should be based on High fire input at a nominal -.04" w.c. draft pres­sure at the boiler outlet with a gross stack temp of 325º F and CO
ratings at 7.5%.
2
3.6.1 Vent Elbows
Pitch toward
boiler 1/4" per
foot minimum.
6' min.
tee. The condensate drain must be routed to a sewer drain trap or pump in accordance with local codes. Refer to diagram under Vent Elbows.
3.6.2 Barometric Damper
This boiler is certified for operation without a baro­metric damper. P-K does not recommend the use of one.
3.6.3 Automatic Vent Damper
WARNING! This equipment, as manufactured, MUST NOT be
used with an automatic vent damper.
3.6.4 Flue Connection
The connection from the boiler to the vent should be as direct as possible and the upward slope of any hori­zontal breaching should be at least 1/4 inch per linear foot. This boiler should not be connected into any por­tion of a mechanical draft system operating under positive pressure. Provisions must be made for sup­ports to prevent contact of the vent with combustible surfaces.
Note: Make sure that the weight of the vent is not supported by the boiler vent collar. The collar is not
designed to support the weight of the vent. Structural support and spacing from combustible surfaces must be in accordance with the vent manufacturer's re­quirements.
Boot Tee /135º Tee
Trap Loop 3" min.
3.6.5 Vent Termination
The minimum vent height above the flue outlet must be five (5) feet and the vent should extend at least three (3) feet above the roof / snowline, or at least two (2) feet above the highest part of any structure within
Condensate Line
To sewer trap or
condensate drain.
ten (10) feet of the vent.
The first turn from horizontal to vertical should be made with a 135° boot tee. A tee cover with a conden­sate drain shall be provided at the bottom of the boot
8
Modu-Fire® Gas-Fired Boiler Installation
(
)
4. Place the appliance being inspected in operation. Follow the lighting instructions. Adjust the ther­mostat so that the appliance will operate continu­ously.
5. Test for spillage at the draft hood relief opening
Correct Listed
Termination
Incorrect
Termination
too restrictive
Vent Termination
The vent must be provided with a weather cap of ap­proved design and adequate capacity.
3.6.6 Removing an Existing Boiler
(from a common venting system) When an existing boiler is removed from a common
venting system, the common venting system is likely to be too large for proper venting of the appliances remaining connected to it.
At the time of removal of an existing boiler, while the other appliances remaining connected to the common venting system are not in operation, the following steps should be followed with each appliance remain­ing connected to the common venting system placed in operation:
after 5 minutes of main burner operation. Use the flame of a match or candle or smoke from a ciga­rette, cigar or pipe.
6. After it has been determined that each appliance remaining connected to the common venting sys­tem properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers, and any other gas-burning appliance to their previous conditions of use.
Any improper operation of the common venting sys­tem should be corrected so the installation conforms with the National Fuel Gas Code, ANSI Z223.1. When resizing any portion of the common venting sys­tem, the common venting system should be resized to approach the minimum size as determined using the appropriate tables in Part II in the National Fuel Gas Code, ANSI Z223.1.
3.7
GAS PIPING
Before making the gas hook-up, make sure the boiler is being supplied with the type of fuel shown on the boiler nameplate.
1. Seal any unused openings in the common venting system.
2. Visually inspect the venting system for proper size and horizontal pitch and determine that there is no blockage or restriction, leakage, corrosion or other deficiency which could cause an unsafe condition.
3. Insofar as is practical, close all building doors and windows and all doors between the space in which the appliances remaining connected to the com­mon venting system are located and other spaces of the building. Turn on clothes dryers and any appliances not connected to the common venting
The boiler shall be installed such that the gas ignition system components are protected from water (drip­ping, spraying, rain, etc.) during appliance operation and service (circulator replacement, control replace­ment, etc.)
The gas train components are designed to handle a maximum inlet pressure of 14 inches water column (1/2 psig.). If the available gas pressure exceeds 14 inch w.c., a suitable additional intermediate gas pres­sure regulator of the "lock up" type must be provided to reduce the pressure to less than 14 inch w.c.
system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a summer ex­haust fan. Close fireplace dampers.
9
Modu-Fire® Gas-Fired Boiler Installation
Remote Gas
Shutoff (not
supplied)
Drip Leg
Gas Meter (not supplied)
By Installer
Union
Shutoff (on
boiler)
Gas Piping
Note: Install a sediment trap (drip leg) and a union connection ahead of the primary manual shutoff valve
Pipe Capacity for Natural Gas
Nominal
Iron
Pipe
Size
(Inches)
Internal
Diameter
(Inches)
Equivalent Pipe Length Maximum Capacity in Cubic Feet of Natural Gas per Hour
90º Ell
(Feet)
Tee
(Feet)
on the boiler. Gas piping should be installed in accor­dance with National Fuel Gas Code, ANSI Z223.1, latest edition, and any other local codes which may apply; in Canada see CAN/CGA-B 149.
Note: See chart below for required pipe size, based on overall length of pipe from meter plus equivalent length of all fittings. Approximate sizing may be based on 1 cubic foot of natural gas per 1,000 Btu per hour input, i.e., 900,000 Btu per hour requires about 900 cubic feet per hour. (See Typical Boiler Operating Conditions, Section 4.3, for more information.)
WARNING! All threaded connections must be made using a pipe
compound that is resistant to the action of liquefied petroleum gases. Do not use Teflon tape on gas line threads.
Pressure Drop of 0.5 inch Water Column/Equivalent Length of
Pipe (in feet)
20
40
60
80
100
150
200 1-1/4 1.380 3.45 6.9 950 1-1/2 1.610 4.02 8.04 1,460 990 810
2 2.067 5.17 10.3 2,750 1,900 1,520 1,300 1,150 950 800
2-1/2 2.469 6.16 12.3 4,350 3,000 2,400 2,050 1,850 1,500 1,280
3 3.068 7.67 15.3 7,700 5,300 4,300 3,700 3,250 2,650 2,280 4 4.026 10.1 20.2 15,800 10,900 8,800 7,500 6,700 5,500 4,600
10
Modu-Fire® Gas-Fired Boiler Installation
3.7.1 Gas Supply Piping by Installer
The boiler and all gas piping connections should be pressure-tested and must be checked for leaks be­fore being placed into service. Test with com­pressed air or inert gas if possible.
The boiler must be disconnected at the boiler man­ual shut-off valve (located at the end of the supplied gas train) from the gas supply piping system during any pressure testing of the system at pressures in excess of 1/2 psig (14 inch w.c.).
During any pressure testing of the gas supply piping system at pressures equal to or less than 1/2 psig (14 inch w.c.), the boiler should be isolated from the gas supply piping system by closing the manual shut­off.
Some leak test solutions, including soap and water, may cause corrosion. These solutions should be rinsed-off with water after testing.
3.7.2 Gas Bleeds and Vents by Installer
If your unit is equipped with a diaphragm gas valve, the bleed vents on the diaphragm gas valves have been factory-piped to terminate at the burner, as re­quired by ANSI Z21.13. This feature provides com­bustion of any gas which leaks past a ruptured dia­phragm during operation. Gas vents to outdoor air must be provided for the main pressure regulator. The pilot regulator is equipped with a vent limiting device and does not require external venting!
When installing per ASME CSD-1, discon-
nect factory piped bleed vents and vent the diaphragm gas valves to outdoor air (field piping.)
If a N.O. (normally open) vent valve is provided, it must be vented independently of any other bleeds and vents. Discharge of vent lines should be pro­tected by an insect screen.
The air gas ratio control valve is equipped with a “reference chamber vent filter” which does not re­quire any additional venting. This connection is labeled COMBUSTION / ATMOSPHERE.
If local conditions require venting to outdoors, the vent line connection must be piped by the installer
in accordance with the National Fuel Gas Code (NFPA 54), ANSI Z223.1, which states:
“In the case of vents leading outdoors, means shall be employed to prevent water from entering this piping and also to prevent blockage of vents by in­sects and foreign matter.”
The National Fuel Gas Code Handbook goes on to say that “Insects, insect nests, ice, or freezing rain
can block outdoor vents....”
The pilot regulator is equipped with a vent limiting device and does not require external venting!
Gas Vents by Installer
Note: Provide a drip leg in all vent/bleed lines. All vent lines should be pitched up at all times to prevent building a trap into the vent line.
“Vent limiters” are NOT to be installed on this boiler.
The air gas ratio control valve is equipped with a “reference chamber vent filter” which does not re­quire any additional venting.
3.8
BOILER WATER PIPING
3.8.1 Piping Design
Water Flow in System
Ideal operation of the P-K MODU-FIRE® Boiler would consist of a 20º F temperature differential across the heat exchanger at High fire. Insufficient flow may result in excessive short cycling of the boiler and eventual damage or premature failure of the equipment.
Minimum Return Water Temperature should be greater than 130º F to avoid problems of condensa­tion on the outside of the heat exchanger or in the flue passages.
Proper flow rates and return water temperature may be achieved through a combination of primary and secondary flow loops. Multiple zones and pumps may result in different flow rates at different times.
11
Modu-Fire® Gas-Fired Boiler Installation
Consideration must be given to all possible condi­tions and their consequences.
Piping With Refrigeration Machines
When used with a refrigeration system, the boiler shall be installed so that chilled medium is piped in parallel with the boiler. Valves should be installed to prevent chilled water from entering the boiler when the system is operated in the cooling mode.
Piping With Air Handling Units
The boiler piping system of a hot water heating boiler connected to heating coils located in air han­dling units, where they may be exposed to refriger­ated air circulation, must be equipped with flow control valves or other automatic means to prevent gravity circulation of the boiler water during the cooling cycle.
3.8.2 Boiler Inlet and Outlet Connections
Relief Valve
Drain
Union
Outlet (to
system)
Note: Pipe unions and isolating valves must be installed in both water connections for ease of service.
The bottom connection to the boiler is the INLET and must be used for the return from the system.
The top connection to the boiler is the OUTLET and must be connected as the supply to the system.
Piping must be installed such that no piping stresses are transmitted to the boiler. The boiler should not be used as a pipe anchor.
3.8.3 Boiler Water Piping by Installer
Strainer
To avoid possible contamination of the boiler with dirt, rust or sediment from the system, a strainer near the boiler inlet is strongly recommended. Even new systems may contain sufficient foreign material to eventually reduce the performance of the heat exchanger. Adequate circulation of good clean wa­ter is essential to maximum efficiency and long life of the boiler.
Relief Valve and Piping
Isolating
Valve
Isolating
Valve
Inlet (from
Boiler Drain
Strainer
Boiler Inlet and Outlet Connections
system)
Isolating Valve
Make water connections as the application warrants, or at a minimum, as shown, but always in compli­ance with the local requirements.
Each boiler is supplied with a pressure-relief valve sized in accordance with ASME requirements. The relief valve should be piped to a suitable floor drain. Reducing couplings or other restrictions are not permitted in the discharge line.
Low Water Cut-off
The boiler is furnished with a flow-switch-type low water cut-off as required by Section IV ASME Code; no field piping is required. If the flow switch does not sense water flow, the boiler will shut down and a red indicator will be illuminated on the control panel. This flow switch only proves that flow is present. It does not prove adequate flow as required by this boiler.
Installation of an external low water cutoff or man­ual reset low-water switch may be required by cer­tain codes or in certain installations. Consult your local code for details.
12
Modu-Fire® Gas-Fired Boiler Installation
WARNING! Never install a valve that can isolate the low water
cutoff from the boiler.
Drain Valve and Piping
The boiler is not provided with external drain con­nections. A drain valve should be installed near the inlet (system return) connection to the boiler and piped to a suitable floor drain. The boiler can be completely drained through the bottom header by removing the flush plug in the bottom end plate.
This plug may also be used to flush accumulated sediment from the bottom of the boiler.
3.8.4 Flushing and Filling
Flushing the System
Before filling the boiler, flush the system to remove the debris. Clean and flush old piping thoroughly before installing the boiler as recommended by your water conditioning or chemical treatment supplier.
Under no circumstances should the hydronic system be flushed while the boiler is attached to the system since the debris or corrosion products could accu­mulate in the boiler and plug the boiler heat ex­changer.
If the piping system attached to this unit will be chemically cleaned, the boiler must be disconnected from the system and a bypass installed so that the chemical cleaning solution does not circulate through the boiler.
Filling
To be sure that the boiler is not air-bound, open the pressure-relief valve located at the rear of the boiler. Leave the relief valve open until a steady flow of water is observed. Close the valve and finish filling the system.
treated make-up water can cause premature failure due to buildup of scale. Such failure is not covered by warranty.
Scale can also reduce efficiency. For example, a scale thickness of 1/16" will result in a 12.5% loss of efficiency.
The water quality should be within the guidelines established by the American Boiler Manufacturers Association, as follows:
Total solids: 2,500 ppm
Total alkalinity: 500 ppm
Total hardness: 150 ppm
The amount of oils, fats, grease, and other organic matter should be limited to 10 ppm.
Consult your water conditioning or chemical treat­ment supplier for analysis and recommendations.
If antifreeze is to be used in the system, the cus­tomer should perform a hazard analysis to determine the use and disposal of the antifreeze.
3.9
BURNER AND IGNITION SYSTEM
3.9.1 Inspection
Inspect the burners to be sure nothing was damaged or knocked loose during shipment. Make sure that the mixer core in the top of the burner is centered in the burner head; (see burner photo in section on "Cleaning the Burner" Section 5.2). Inspect the pi­lot line, main gas train and ignition electrode to be sure they were not damaged during shipment or in­stallation. Check to see that the pilot is securely attached and that it is properly positioned to ignite the main burner.
3.10
PRE-START CHECK LIST
3.8.5 Water Quality
The boiler is designed to operate in a closed-loop system. As such, the system should be tight and not
Before attempting to start the boiler, make sure the following items have been completed.
1. Flue gas from the boiler is properly vented.
require make-up water. A high percentage of un-
13
Modu-Fire® Gas-Fired Boiler Installation
2. Gas connection has been made, pressure tested for leakage, and the line purged of air. Make sure all required bleeds and vents have been in­stalled.
3. Water connections are complete, and the boiler and system have been filled and purged of air.
4. The boiler must be connected to a 120 volt / 60 Hz power source with proper polarity and dedi­cated machinery ground. Provide a disconnect having adequate overload protection.
5. Combustion air openings are not obstructed in any way and have adequate capacity. (See Sec­tion 3.5)
6. The boiler is placed the proper distance from any combustible walls or substances, in accor­dance with Section 3.3.3.
7. Relief valves have been properly piped to floor drains.
SAFETY CHECKS
3.11
The following checks of safety systems must be made before putting the boiler into normal opera­tion.
Before firing the boiler refer to Sections 4.1 and 4.2 for information on the use of the controls, lighting, and shut-down procedures.
WARNING! Never attempt to operate a boiler that has failed to
pass all the safety checks described below.
WARNING! After checking controls by manual adjustment, make
sure they are always reset to their proper settings.
3.11.1 Test of Ignition Safety System
Test the ignition system safety shutoff as follows:
1. Close the gas cock which is downstream from the two safety shut off valves (in the vertical line).
2. With the main gas cock (inlet manual gas valve) open and the pilot gas cock open, the burner should be cycled on. After all the safety limits on gas pressure, water flow and temperature are satisfied, the blower will run and pre-purge the boiler.
3. When air flow is established, the ignition trans­former and pilot will operate. Both functions will be indicated by separate indicator lights on the flame safeguard.
4. If a satisfactory pilot is established, the spark will terminate and the pilot will remain on, alone, for 10 seconds.
5. After 10 seconds, the "Main” light on the flame safeguard will go on; gas will not flow since the downstream cock is closed. The "Pilot" will remain on, along with the "Main Gas", for an­other 10 - 15 seconds and then go out. Since the gas cock is closed, at this point there will be no main flame signal and the flame safeguard pro­grammer will assume a “Flame Failure” and go to a "lockout" mode. Lockout will require man­ual reset of the flame safeguard.
After completing this test, turn off the boiler and reopen the downstream gas cock.
3.11.2 Test of Low Water Cut-off
The boiler is furnished with a flow-switch-type low water cutoff in the outlet nozzle. Test as follows:
Operation of the switch can be checked by first turn­ing the boiler off and then turning the system pump off, stopping water flow in the system. After turn­ing off the pump, turn the boiler back on. It should not operate, and a red indicator for "Low Water" or "Water Flow" should be illuminated. Do not shut the pump off while the boiler is operating.
Perform appropriate tests on any external probe-type low water cutoff.
3.11.3 Test of Limit Controls
Fire the boiler and test the high limit control as fol­lows:
With the main burner operating, turn down the tem­perature setting on the "high-limit" thermostat until
14
Loading...
+ 37 hidden pages