Patterson-Kelley MACH C1500, MACH C2000 Installation And Owner's Manual

PATTERSON-KELLEY
MACH C1500/C2000 GAS-FIRED BOILER
LMACH- 07
C.S.A Design-Certified Complies with ANSI Z21.13/CSA 4.9 Gas-Fired Low Pressure Steam and Hot Water Boilers
ASME Code, Section IV Certified by Patterson-Kelley
C.S.A Design-Certified Complies with ANSI Z21.13/CSA 4.9 Gas-Fired Low Pressure Steam and Hot Water Boilers
Installation Date: _______________________
100 Burson Street, P.O. Box 458, East Stroudsburg, PA 18301 Telephone: (877) 728-5351, Facsimile: (570) 476-7247 www.pkboilers.com
MACH® Series Gas-Fired Boiler Table of Contents
MACH® Series Gas-Fired Boiler Table of Contents
1.0 INTRODUCTION ........................................1
2.0 SAFETY......................................................1
2.1 General..............................................................1
2.2 Training..............................................................1
2.3 Safety Features .................................................2
2.4 Safety Labels.....................................................2
2.5 Safety Precautions ............................................2
2.5.2 Burn, Fire, and Explosion Hazards..........2
2.5.3 Crush Hazards.........................................3
2.5.4 Chemical Hazards....................................4
2.5.5 Pressure Hazards ....................................4
2.5.6 Slip, Fall Hazards.....................................4
3.0 INSTALLATION..........................................5
3.1 Receiving and Storage......................................5
3.1.1 Initial Inspection .......................................5
3.1.2 Storage Prior to Installation......................5
3.2 Compliance with Codes.....................................5
3.3 Setup .................................................................5
3.3.1 Foundation and Placement......................5
3.3.2 Clearances...............................................6
3.4 Electrical Connections.......................................6
3.5 Combustion Air..................................................7
3.5.1 Air Inlet Requirements..............................7
3.6 Flue Venting.......................................................8
3.6.1 Barometric Damper..................................9
3.6.2 Flue Connection.......................................9
3.6.3 Required Clearances ...............................9
3.6.4 Vertical Vent Systems............................10
3.6.5 Vent Terminations..................................10
3.6.6. Direct Vent (Sealed Combustion) Systems
...................................................................
3.6.7 Sidewall Venting with Sealed Combustion11
3.6.8 Intake Duct Materials and Sizes: ...........12
3.6.9 Sealing the Intake Duct..........................12
3.6.10 Intake Duct Connection to Boiler .........12
3.6.11 Venting for Multiple Boilers..................12
11
3.6.12 Removing an Existing Boiler................12
3.7 Gas Piping.......................................................13
3.7.1 Gas Supply Piping by Installer...............15
3.8 Boiler Water Piping..........................................15
3.8.1 Piping Design.........................................15
3.8.2 Boiler Inlet and Outlet Connections.......16
3.8.3 Boiler Water Piping by Installer..............17
3.8.4 Flushing and Filling................................17
3.9 Burner and Ignition System.............................18
3.9.1 Inspection...............................................18
3.10 Pre-Start Check List ......................................18
3.11 Safety Checks ...............................................19
3.11.1 Test of Ignition Safety System.............19
3.11.2 Test of Low Water Cut-out...................19
3.11.3 Test of High-Limit Control....................19
3.11.4 Test of Gas Pressure Switch ...............19
3.12 Initial Adjustments .........................................20
3.12.1 Operating Temperature Controller.......20
3.12.2 Burner Setup...................................24
3.12.3 Gas Pressure Adjustment....................25
3.12.4 Air Flow Adjustments...........................25
3.12.5 Gas Valve Setup and Adjustment........25
4.0 OPERATION ............................................28
4.1 General............................................................28
4.1.1 Control Panel Front................................28
4.1.2 Tests ......................................................28
4.2 Normal Lighting and Shut-Down Procedures..28
4.2.1 Lighting Procedures...............................28
4.2.2 Normal Shut Down Procedures .............28
4.2.3 Emergency Shut-Off ..............................28
4.3 Typical Boiler Operating Conditions................29
5.0 MAINTENANCE.......................................30
5.1 Maintenance and Inspection Schedule ...........30
5.1.1 Daily.......................................................30
5.1.2 Weekly ...................................................30
5.1.3 Monthly (During Operation)....................30
MACH® Series Gas-Fired Boiler Table of Contents
5.1.4 Semi-Annually (required for boilers operated
year round) ................................................
5.1.5 Annually .................................................31
5.2 Cleaning the Burner.........................................31
5.3 After All Repairs or Maintenance.....................32
5.4 Sequence of Operation....................................32
5.5 Troubleshooting...............................................33
5.5.1 Manual Reset Service Codes ................37
5.5.2 Auto-reset Service Codes......................38
31
6.0 PARTS/TECHNICAL SUPPORT..............39
6.1 Schematic Diagrams ........................................39
6.2 Wiring Diagrams..............................................40
WARNING! It is essential to read, understand, and follow the
recommendations of this manual before installing, operating, or servicing this equipment. Failure to do so could result in fire or explosion and serious injury, death, and/or property damage.
The same features which permit this boiler to achieve high-efficiency performance make it unlike most other boilers of this general size, so it is important to understand how this boiler operates.
WARNING Do not store or use gasoline or other flammable
vapors or liquids in the vicinity of this or any other appliance.
6.2.1a Terminal Block Assignments – High
Voltage Circuit (TB2).................................
6.2.1b Terminal Block Assignments – Low Voltage
Circuit (TB1) ..............................................
6.2.2 Wiring Diagram for Series C-1500/C-200042
6.3 Boiler Parts List ...............................................43
6.3.1 Main Assembly.......................................43
6.3.2 Control Panel.........................................44
6.3.3 C1500/C2000 Heat Engine....................45
6.3.4 C1500/C2000 Gas Train........................46
40
41
7.0 LIMITED WARRANTY .............................47
8.0 APPENDIX ...............................................50
WARNING! Chemicals, fuels, or other potentially hazardous
or toxic materials must not be stored in the same room as the boiler.
WARNING! Installation and service must be performed by a
qualified installer or service agency who has been trained on the Patterson-Kelley MACH Boiler.
What to do if you smell gas:
Do not try to light any appliance.
Do not touch any electrical switch.
Do not use any phone in your building.
Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions.
If you cannot reach your gas supplier call the fire
department.
MACH® Series Gas-Fired Boiler Installation
1.0 INTRODUCTION
The P-K MACH® C1500/C2000 fully modulating using a variable speed combustion blower, sophisticated microprocessor controls, modulating gas safety shut off / control valves and a unique aluminum alloy heat exchanger capable of operating in a fully condensing mode to provide maximum efficiency in a minimum amount of space. The high-quality materials and thoroughly tested design of the boiler should provide years of trouble­free service if the instructions in this manual are followed carefully.
This manual covers installation of P-K MACH C1500/C2000 Boilers. The model numbers may be followed by a prefix or suffix letter in some cases to indicate special features or different options.
While details may differ slightly, basic operation is the same for all models. Check the rating plate for correct fuel usage and gas pressures.
The boiler is only a part of the complete heating system. This boiler may be fully operational and yet because of poor circulation, control, or other operating characteristics, not deliver heat to the desired location. Additional equipment such as temperature sensors, pumps, flow switches, balancing valves, and check valves will be required for satisfactory operation of any system. Patterson-Kelley cannot be responsible for the design or operation of such systems and a qualified engineer or contractor must be consulted.
Gas-Fired Boilers are
2.0 SAFETY
2.1
GENERAL
The MACH C1500/C2000 gas-fired boiler must be:
Installed, operated, and serviced in accordance
with instructions contained in this manual.
Installed by qualified personnel in accordance with
designs prepared by qualified facility engineers including: structural, mechanical, electrical, and other applicable disciplines.
Operated and serviced in accordance with a
comprehensive safety program determined and established by the customer. Do not attempt to operate or service until such a program has been established.
Operated and serviced by qualified and
knowledgeable personnel in accordance with all applicable codes, laws, and regulations.
The use of the term “factory-trained personnel”
throughout this manual indicates Patterson­Kelley trained on this specific piece of equipment.
Note: Each safety device must be maintained and checked per the recommended schedule; refer to Section 5.1 of this manual.
TRAINING
2.2
It is essential
to read, understand, and follow the recommendations of this manual before installing, operating, or servicing this equipment. Failure to do so could result in fire or explosion and serious injury, death, and/or property damage.
Proper training is the best protection against accidents. Operating and service personnel must be thoroughly familiar with the basic construction of the P-K MACH C1500/C2000
boiler, the use and locations of the controls, the operation of the boiler, adjustment of its various mechanisms, and all applicable safety precautions. If any of the provisions of this manual are not fully and completely understood, contact the Patterson-Kelley Sales Department toll-free at (877) 728-5351 for assistance.
Page 1
MACH® Series Gas-Fired Boiler Installation
2.3 SAFETY FEATURES
It is the responsibility of the customer to maintain the safety features, such as but not limited to: guards, safety labels, safety controls, interlocks, lockout devices, in place and operable.
SAFETY LABELS
2.4
The following words are used in this manual to de­note the degree of seriousness of the individual hazards.
DANGER – Used to indicate an imminently hazardous situation which, if not avoided, will result in death or serious injury. This signal word is to be limited to the most extreme conditions.
WARNING – Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION – Used to indicate a potentially hazardous situation which, if not avoided, may result in minor or moderate injury.
2.5.1 Electrical Hazards
Shock hazard! Properly lockout/tagout the
electrical service and all other energy sources before working on or near the boiler.
Shock hazard! Do not spray water directly on
this boiler or on any electrical components.
2.5.2 Burn, Fire, and Explosion Hazards
NOTICE/NOTE - NOTICE is the preferred signal word to address practices not related to personal injury. The safety alert symbol is not used with this signal word.
The safety labels shown below are affixed to your boiler. Although the labels are of high quality, they may become dislodged or unreadable over time. Contact Patterson-Kelley toll-free at (877) 728-5351 for replacement labels.
SAFETY PRECAUTIONS
2.5
Provide a suitable location for the boiler, away from normal personnel traffic, with adequate working space, adequate clearances, proper ventilation and lighting, with a structure sufficiently strong and rigid to support the weight of the boiler, all piping, and accessories.
NOTE
When opening leak test valves, always follow instructions in operation and safety manual.
c
1998 HCS, Inc. 800-748-0241
Burn, fire, and explosion hazards! Installation
must be in strict conformance to all applicable codes and standards including NFPA 54, ANSI Z223.1 and CSA B.149. Install all required vent lines for gas devices. Refer to Section 3.7.1.
Hazard from incorrect fuels! Possible fire,
explosion, overheating, and damage. Do not use any fuels except the design fuels for the unit.
Overfire hazards! High pressure in gas supply
could result in overfiring of this or other devices supplied from the same source.
Reorder No. 8032-01NHPK
Page 2
Fire and explosion hazards! Close the main gas
shutoff before servicing boiler.
MACH® Series Gas-Fired Boiler Installation
Fire and explosion hazards! Do not store or use
gasoline or other flammable vapors or liquids in the vicinity of this or any other gas fired appliance.
Burn hazard! Possible hot surfaces. Do not touch
gas vent during firing operation. Use only factory recommended vent components.
Burn hazard! Pipes, vents, and boiler components
could be hot. Do not touch piping or stack surfaces during operation or immediately after shutdown of the boiler.
Burn hazard! Hot fluids. Use caution when
servicing or draining boiler.
Fire and explosion hazards! Use caution when
servicing burner. Propane (LPG) is heavier than air and may linger in the combustion chamber, vent lines, or elsewhere.
Gas leak hazard! Make sure the burner is installed
correctly and blower/transition is securely fastened following any maintenance performed on them. These connections may leak gas if assembled incorrectly.
Gas leak hazard! All threaded gas connections
must be made using a pipe compound that is resistant to liquefied petroleum gas. Do not use Teflon tape on threaded gas piping.
Gas leak hazard! Check entire gas train for leaks
after installation. If there is a smell of gas, shut down the boiler and obtain immediate assistance from trained service personnel and/or your local fire department.
Overfire and underfire hazards! Possible fire,
explosion, overheating, and component failure. Do not attempt to adjust firing rate of the boiler. The firing rate must be adjusted only by factory trained personnel.
2.5.3 Crush Hazards
General Warning
Lifting hazards! Use properly rated lifting
equipment to lift and position the boiler. The load is unbalanced. Test balance before lifting 3 ft. above the floor. Do not allow personnel beneath the lifted load. Refer to approximate weights in the table below:
Boiler Size Weight in Pounds
C1500 1200 C2000 1400
Bump hazard from overhead ductwork and
piping. Install components with adequate vertical clearance.
Overfire hazard! Possible fire and explosion from
excess gas pressure. Make sure that gas inlet pressure does not exceed 14 inches W.C.
Overfire hazard! Possible fire and explosion.
Possible malfunction of regulators and/or gas safety shut off / control valves. Maintain all gas train components in good condition. Do not alter wiring connections. Annual inspection by factory­trained personnel for proper set-up and operation is recommended.
Page 3
MACH® Series Gas-Fired Boiler Installation
2.5.4 Chemical Hazards
General Warning
Chemical hazards from cleaning products. Use
caution when cleaning the system. The use of professional assistance is recommended. Use safe procedures for the disposal of all cleaning solutions.
Combustion Condensate – a pH of approximately
3 to 5 can be expected. Use PVC or CPVC piping. Collection and disposal must be in accordance with all applicable regulations.
2.5.5 Pressure Hazards
2.5.6 Slip, Fall Hazards
General Warning
Tripping hazard! Do not install piping on floor
surfaces. Maintain clear path around boiler.
Slip and fall hazard! Use drip pan to catch water
while draining the boiler. Maintain dry floor surfaces.
Slip and fall hazard! Do not locate intake or
exhaust terminations directly above a walkway; dripping of condensation can cause icing of the walking surface.
Fall hazard! Do not stand on any part of the
boiler.
Catch hazard! Do not wear rings, jewelry, long
hair, loose clothing while working on the boiler.
Pressure hazard! Hot fluids. Install isolation
valves on boiler water inlet and outlet. Make sure isolation valves are closed before servicing boiler.
Pressure hazard! Hot fluids. Annually test safety
relief valve for proper operation. Do not operate boiler with faulty relief valve.
Page 4
MACH® Series Gas-Fired Boiler Installation
3.0 INSTALLATION
WARNING!
Installation and service must be performed by a qualified installer, service agency, or gas supplier.
RECEIVING AND STORAGE
3.1
3.1.1 Initial Inspection
Upon receiving the boiler, inspect it for signs of shipping damage. Since some damage may be hidden, unpack the boiler, open the front and side doors and inspect the internals of the boiler.
Verify that the total number of pieces shown on the packing slip agrees with those actually received.
Important: Note any damage, suspected potential damage, or shortage of materials on the freight bill and immediately notify the carrier. File all claims for shortage or damage with the carrier. Claims for hidden damages must be filed with your carrier within 7 days. The boiler carton is equipped with a “Tip (N) Tell”. If "Tip (N) Tell” arrow point is blue, or if the “Tip (N) Tell” is missing, it is likely that the package has been on its side or tipped over in transit.
3.1.2 Storage Prior to Installation
If the boiler is not installed immediately, it must be stored in a location adequately protected from the weather, preferably indoors. If this is not possible, then it should remain in the shipping container and be covered by a tarpaulin or other waterproof covering.
Note: controls and other equipment that are damaged or fail due to weather exposure are not covered by warranty.
COMPLIANCE WITH CODES
3.2
The P-K MACH C1500/C2000 Boiler with standard components and options complies with American National Standard/CSA Standard ANSI Z21.13/CSA
4.9, latest edition, Gas-Fired Low Pressure Steam and Hot Water Boilers.
The heat exchanger is constructed and stamped in accordance with ASME Boiler and Pressure Vessel Code, Section IV for 100 psig maximum operating pressure and/or 200º F maximum temperature.
Installation of the boiler must comply with the requirements of all national, state and local codes established by the authorities having jurisdiction. Authorities having jurisdiction should be consulted before installations are made.
Within the US, and in the absence of such local requirements, this boiler should be installed using the National Fuel Gas Code, ANSI Z223.1/NFPA 54, latest edition.
In Canada, the equipment shall be installed in accordance with the current Installation Code for Gas Burning Appliances and Equipment, CAN/CSA­B149, latest edition and applicable Provincial Regulations for the class, which should be carefully followed in all cases.
Where required by local codes, the installation must conform to American Society of Mechanical Engineers Safety Code for Controls and Safety Devices for Automatically Fired Boilers (ASME CSD-1).
In the Commonwealth of Massachusetts see the Supplement for Massachusetts.
SETUP
3.3
3.3.1 Foundation and Placement
Provide a firm, level foundation, preferably of concrete.
WARNING! The wheels provided with this boiler are for positioning purposes only. When positioning this boiler, maintain positive control of it at all times. Do not attempt to move the boiler on surfaces that are not level. Failure to heed this warning could result in personal injury or death.
Lifting the front of the boiler slightly will allow the boiler to be rolled off the shipping skid onto the concrete foundation. Once in position, the wheel
Page 5
MACH® Series Gas-Fired Boiler Installation
bolts may be removed allowing the wheels to recess up into the boiler. The base will sit flat on the provided foundation. If the boiler is to be pulled out for maintenance, the wheels may be left attached.
The boiler must be level to function properly. To assist in leveling the boiler, the four (4) adjustable leg bolts (1/2"- 13 NC) must be installed. The adjustable legs are also necessary to prevent distortion of the cabinet, (twisting, etc.) in addition to leveling. Additionally there are three holes in the front and rear of the base that may be used for seismic anchoring. Note: The boiler may be installed on a combustible floor; however, the boiler must never be installed on carpeting.
3.3.2 Clearances
If the boiler is to be installed near combustible surfaces, the minimum clearances shown in the pictures and table below must be maintained.
Failure to provide for the service access clearances, even with non-combustible surfaces, may cause future problems servicing the boiler.
Maintain a clearance from the vent to combustible surfaces of 18” or as specified in the vent manufacturer’s listed installation instructions.
The boiler must be installed in a space large in comparison to the boiler as described in the National Fuel Gas Code, ANSI Z223.1, latest edition.
C
A
B
Minimum Clearances from Adjacent Walls, Ceiling, and Obstructions (shown above &below)
D
Combustible Surfaces
Minimum Clearances
Recommended Service
Clearances
D
D
Dimensions (inches) Type of Surface
A B C† D
18 18 18 18
12*
30
12 18**
† "C" Space required for pipes, ducts, etc. in this area above the boiler.
* Clearance depends upon exhaust vent configuration. ** Service access is required on left side of boiler to
facilitate boiler maintenance. Minimum 2” clearance is required on right side. Do not
put pipes, ducts, vents, etc in this space. Electrical conduit must be installed vertically so that the side doors can be opened.
CAUTION! Bumping hazard from overhead ducts! Install all
components with adequate vertical clearances.
ELECTRICAL CONNECTIONS
3.4
The boiler is wired for 120 volts, single phase, 60 hertz. The total operating amperage is indicated on the rating nameplate. Each C1500/C2000 boiler
Page 6
MACH® Series Gas-Fired Boiler Installation
requires less than 15 amps. Before starting the boiler, check to ensure that the proper electrical service is connected to the boiler.
An external electrical disconnect (not supplied with the boiler) is required. The boiler electrical service must be installed and grounded in accordance with local codes or in the absence of such requirements, in the U.S. with National Electrical Codes, ANSI/NFPA No. 70 latest edition or, in Canada, to the Canadian Electrical Code, Part I, CSA C22.1, latest edition. Conduit must be installed vertically so that the side doors can be opened.
Note: A dedicated earth ground (green wire) and neutral is required to avoid nuisance shutdowns. Do not ground through the conduit. It is also important that proper polarity be maintained.
Note: Refer to electrical wiring section for terminal block assignments (Section 6.1).
120 Volt Junction Box
Low Voltage Junction Box
Customer Connections for the Boiler
Viewed from Front of Boiler.
COMBUSTION AIR
3.5
Note: Additional information is contained in the venting supplement “MACH-07VG”.
Combustion air must be free from dust, lint, etc. The presence of such materials in the air supplied to the burner could cause nuisance "Low Air" shutdowns or premature burner failure. The boiler should not be operated during construction while the possibility of drywall dust, demolition dust, etc. exists.
The combustion air supply must be completely free of chemical fumes which may be corrosive when burned in the boiler. Common chemicals which must be avoided are fluorocarbons and other halogenated
compounds, most commonly present as refrigerants or solvents, such as freon, trichlorethylene, perchlorethylene, chlorine, etc. These chemicals, when burned, form acids which quickly attack the boiler and the boiler stack. The result is improper combustion and premature boiler failure.
Provisions for combustion and ventilation air must be in accordance with Section 9.3, Air for Combustion and Ventilation, of the National Fuel Gas Code, ANSI Z223.1, latest edition, or applicable provisions of the local building codes. In Canada, combustion air openings shall comply with CSA B.149 Installation Code.
3.5.1 Air Inlet Requirements
Caution. The boiler room should not be at a negative
pressure. Particular care should be taken when exhaust fans, compressors, air-handling units or other equipment may rob air from the boiler.
Combustion air may be supplied from within the building or from outdoors. The minimum required volume of the mechanical room and connected spaces is 50 cu. Ft. per 1000 Btu/hr (4.8 m
3
/kW). If this volume is not available, air must be taken from outdoors.
When air is supplied from inside the building, the total required volume shall be the sum of the required volume for all the appliances located in the mechanical room. Adjacent rooms furnished with fixed openings communicating directly with the mechanical room are considered part of the required volume.
Openings used to connect indoor spaces to obtain the required minimum volume shall be sized as follows:
When rooms are on the same floor, each opening
shall have an area equal to 1 square inch for each 1000 Btu/hr (2200 mm
2
/ kW) of installed appliance input capacity, but not less than 100 square
inches. One opening should be less than
12 inches above the floor and the other less than 12 inches below the ceiling. The minimum dimension of air openings shall be 3 inches.
Page 7
MACH® Series Gas-Fired Boiler Installation
When rooms are on different floors, each opening
shall have an area equal to 2 square inches for each 1000 Btu/hr (4400 mm
2
/ kW) of installed
appliance input capacity.
When combustion air is supplied from outside the building, the boiler room shall be provided with one or two openings to ensure adequate combustion air and proper ventilation.
When using one permanent opening, the opening shall commence within 12 inches of the ceiling and shall communicate directly with the outdoors or through a vertical or horizontal duct that communicates to the outdoors.
Minimum free area of the opening is;
1 square inch for each 3000 Btu/hr (700 mm
2
/
kW) of installed appliance input capacity, and
not less than the sum of the areas of all vent
connectors in the room.
When using two permanent openings, one opening shall be less than 12 inches above the floor and the other less than 12 inches below the ceiling, preferably on opposite walls. The openings shall communicate directly, or by way of ducts, with free outdoor air. Minimum net free area of the openings shall be calculated in accordance with the following:
When air is taken directly from outside the
building, each opening (minimum of two, as outlined above), 1 square inch for each 4,000 Btu per hour of total boiler input is required.
When air is taken from the outdoors through a
vertical duct, 1 square inch per 4,000 Btu per hour of total boiler input is required.
When air is taken from the outdoors through a
horizontal duct , 1 square inch per 2,000 Btu per hour of total boiler input is required.
NOTE:
1. The required size of openings for combustion,
ventilation and dilution air shall be based on the net free area of the opening.
2. Screens shall be not smaller than ¼”.
3. Motorized louvers shall be interlocked with the
appliance so that they are proven open prior to main burner ignition and operation.
FLUE VENTING
3.6
Note: Additional information is contained in the venting supplement “MACH-07VG”.
Caution! All boiler venting systems should be designed by
a qualified professional engineer experienced in venting system design. The information contained herein should be used as a guide only and is not intended to be used in lieu of qualified technical expertise.
This boiler is Category IV (condensing – positive pressure) as it is defined in ANSI Z21.13/CSA 4.9, latest edition. This boiler is not certified for use with Type "B" vent.
The vent material must be :
AL29-4C Stainless Steel Vent Systems listed and labeled to UL1738 Venting
Systems for Gas-Burning Appliances, Categories II, III, and IV
316L Stainless Steel where certified and warranted by the vent manufacturer for venting of Category IV appliances
Vent installations shall be in accordance with Part 12, Venting of Equipment, of the National Fuel Gas Code, ANSI Z223.1 or Part 8, Venting Systems and Air Supply for Appliances of the Natural Gas and Propane Installation Code CAN/CSA-B149 current revision, or applicable provisions of the local building codes.
The vent must be sized in accordance with the ASHRAE Systems and Equipment
handbook, Chapter 30 or according to the vent manufacturer’s recommendations. When using manufactured vent systems; consult your vent supplier for correct sizing and structural support requirements.
Page 8
MACH® Series Gas-Fired Boiler Installation
Vent design calculations should be based on a maximum of 0.44" W.C. combined frictional resistance across the air inlet duct and the stack, with a stack temperature of 185° F (gross) and a CO
level of
2
9.2% on natural gas. Consult your local vent manufacturer for proper sizing.
3.6.1 Barometric Damper
WARNING!
Do not use a barometric damper with this boiler. (This is a positive pressure system;
combustion gas may leak into the room.)
3.6.2 Flue Connection
Note: Additional information is contained in the venting supplement “MACH-07VG”.
The outlet of the boiler is a metric female pipe with a gasket. It requires a male adapter that is 9.79” OD as the mating piece. This adapter should be obtained from the venting manufacturer and will be specific for this boiler. The connection from the boiler to the stack should be as direct as possible and any horizontal breaching should have an upward slope at least 1/4 inch per linear foot.
This boiler should not be connected into any portion of another mechanical draft system without consulting your venting manufacturer. This boiler shall not be connected to any part of a vent system serving a Category I appliance, nor shall a Category I appliance be connected to any part of the vent system serving this appliance.
Note: If the vent is erected vertically directly from the boiler outlet, make sure that the weight of the vent is not supported by the boiler vent collar. The
collar is not designed to support the weight of the vent. Structural support and spacing from
combustible surfaces must be in accordance with the vent manufacturer's requirements.
3.6.3 Required Clearances
Provide clearances between combustion air intake, exhaust vent, roof and wall surfaces, doors and window, and snow line as shown in the following diagrams. All dimensions should take into account the snow line for the installation area.
WARNING! Do not locate intake or exhaust terminations
directly above a walkway; dripping of conden­sation can cause icing of the walking surface.
Page 9
MACH® Series Gas-Fired Boiler Installation
3.6.4 Vertical Vent Systems
The following termination clearance requirements are for conventional, non-direct vent installations.
The vent system shall terminate at least 3 ft above a forced air inlet within 10 feet horizontally.
The vent system shall terminate at least 4 ft below, 4 ft horizontally from or 1 ft above any door, operable window or gravity inlet into any building. The bottom of the vent terminal shall be at least 12 in. above grade or highest expected snow line (if applicable).
The boiler vent connection is vertical and may be reduced. The stack size may be a nominal ten (10”), eight (8”), or six (6”), so long as the combined air and stack pressure resistance of 0.44” total is not exceeded. When using 10” or 8” stack, a sealed air inlet duct may also be used. When using 6” stack, the only allowable configuration is vertical without offsets (elbows, tees, etc.) which results in 0.44” or less of resistance and without a sealed air inlet.
Combustion Air
Inlet of *another*
appliance
10' min*.
3' min.
Boiler Flue Gas Outlet
Typical through the roof venting.
3.6.5 Vent Terminations
Vent Supports
4' min above
snow line
No rain cap
required,
or Tee.
Vertical Vent Termination Details
The vent should extend at least four (4) feet above the roof, or at least two (2) feet above the highest part of any structure within ten (10) feet of the vent.
To prevent the possible re-circulation of flue gases, the vent designer must take into consideration such things as prevailing winds, eddy zones, building configurations, etc. Patterson-Kelley Co. can not be responsible for the effects such adverse conditions may have on the operation of the boilers. Dimensions listed above or those illustrated are minimum, and may or may not be sufficient for conditions at a specific job site.
A tee must be of approved design and adequate capacity. The installation of a bird screen on the vent termination is recommended. A rain cap is not
recommended for the vent.
Page 10
MACH® Series Gas-Fired Boiler Installation
3.6.6. Direct Vent (Sealed Combustion) Systems
The vent terminal shall be located at least 12 in. from any air opening into a building. The bottom of the vent terminal shall be at least 12 in. above grade. Both the vent and air intake terminals must be at least 12 in. above the highest expected snow line.
Through the wall terminations shall not terminate over public walkways. Maintain a minimum clearance of 4 ft (1.22 m) horizontally from any electric of gas meter, regulator or relief equipment.
3.6.7 Sidewall Venting with Sealed Combustion
The MACH C1500/C2000 Boilers are certified for direct sidewall venting with a sidewall air inlet only.
Both the air inlet and the exhaust vent must on the same wall of the building and must
terminate
utilize the same type of termination fitting with the same orientation. Allowable termination fittings are: 90° elbows, tees, or straight vents.
Do not install this boiler with sidewall vent and room air inlet!
The air inlet and vent must be sized so that the total pressure loss for the combined inlet and vent ducts does not exceed 0.44” w.c.. For example, if the inlet air duct loss is 0.2” w.c., the vent duct loss cannot exceed 0.24 “w.c.. The vent should be sized using a gross vent temperature of 185°F, a CO2 level of 9.2% and the residual vent pressure loss as indicated above. The air inlet duct should be sized as indicated in paragraph 3.6.8.
Typical Sidewall venting.
Vent Installation Details
This Installation must conform to the vent manufacturer's instructions in all respects including joining, clearances, fastening, fire-stopping, and other matters.
Vent Manufacturers Wall Penetration Kit
3’ min.
Page 11
12" min.
Sidewall Penetration Detail
MACH® Series Gas-Fired Boiler Installation
3.6.8 Intake Duct Materials and Sizes:
Material: PVC, CPVC, single wall galvanized steel, or other suitable materials.
The intake duct must be sized for a pressure drop as indicated in paragraph 3.6.7 and for the SCFM as specified below.
Boiler Size Required SCFM
1500 350 2000 467
The installation of a bird screen on the intake termination is recommended. Ensure that the screen does not become blocked with snow, ice, etc.
3.6.9 Sealing the Intake Duct
Proper sealing of the intake ductwork is necessary to prevent infiltration of air from conditioned space. Joints in PVC or CPVC must be cemented. For galvanized duct, wrap each joint and seam with adhesive aluminum tape.
3.6.10 Intake Duct Connection to Boiler
Connect the air supply duct to the 10” OD collar on the top of the boiler. Fasten the duct to the collar with sheet metal screws at 90º angles. Seal the joint.
3.6.11 Venting for Multiple Boilers
The venting instructions in this manual apply to a
single boiler. Venting systems for multiple boilers must be
designed by qualified professionals and verified by the stack manufacturer. The venting system must prevent backflow of exhaust gas through idle boilers which are not operating.
3.6.12 Removing an Existing Boiler
(from a common venting system) When an existing boiler is removed from a common
venting system, the common venting system is likely to be too large for proper venting of the appliances remaining connected to it.
At the time of removal of an existing boiler, while the other appliances remaining connected to the common venting system are not in operation, the following steps should be followed with each appliance remaining connected to the common venting system placed in operation:
1. Seal any unused openings in the common venting system.
2. Visually inspect the venting system for proper size and horizontal pitch and determine that there is no blockage or restriction, leakage, corrosion or other deficiency which could cause an unsafe condition.
3. Insofar as is practical, close all building doors and windows and all doors between the space in which the appliances remaining connected to the common venting system are located and other spaces of the building. Turn on clothes dryers and any appliances not connected to the common venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a summer exhaust fan. Close fireplace dampers.
4. Place the appliance being inspected in operation. Follow the lighting instructions. Adjust the thermostat so that the appliance will operate continuously.
5. Test for spillage at the draft hood relief opening after 5 minutes of main burner operation. Use the flame of a match or candle or smoke from a cigarette, cigar or pipe.
6. After it has been determined that each appliance remaining connected to the common venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas-burning appliance to their previous conditions of use.
Any improper operation of the common venting system should be corrected so the installation conforms with the National Fuel Gas Code, ANSI Z223.1 and CSA B149 Installation Code. When resizing any portion of the common venting system, the common vent system should be resized to approach the minimum size as determined using the appropriate tables.
Page 12
Loading...
+ 35 hidden pages