Patterson-Kelley DVSCM-02 User Manual

DVSCM-02
DIRECT VENT/ SEALED COMBUSTION
DIRECT VENT/
PATTERSON-KELLEY
DIRECT VENT/SEALED COMBUSTION GAS-FIRED BOILER
Supplement to the standard Installation and Owner's Manual (TBIG - Latest Edition)
®
C.S.A Design-Certified Complies with ANSI Z21.13/CSA 4.9 Gas-Fired Low Pressure Steam and Hot Water Boilers
ASME Code, Section IV Certified by Patterson-Kelley
SEALED COMBUSTION
DIRECT VENT/ SEALED COMBUSTION
DIRECT VENT/ SEALED COMBUSTION
DIRECT VENT/ SEALED COMBUSTION
C.S.A Design-Certified Complies with ANSI Z21.13/CSA 4.9 Gas-Fired Low Pressure Steam and Hot Water Boilers
Installation Date:
100 Burson Street, P.O. Box 458, East Stroudsburg, PA 18301 Telephone: (877) 728-5351, Facsimile: (570) 476-7247 www.pkboilers.com
Patterson-Kelley
P.O. Box 458, 100 Burson Street East Stroudsburg, PA 18301 Telephone: (570) 421-7500, Facsimile: (570) 476-7247
_______________________
DIRECT VENT/ SEALED COMBUSTION
DIRECT VENT/ SEALED COMBUSTION
DIRECT VENT/ SEALED COMBUSTION
DIRECT VENT/
Thermific® Gas-Fired Boiler Table of Contents
1.0 INTRODUCTION..................................1
1.1 Code Compliance................................1
1.1.1 Direct Vent/Sealed Combustion
System..............................................1
1.1.2 Fresh Air System...........................1
1.2 Basic Inlet/Vent Configurations ...........1
1.3 Purpose and Scope of this Manual......2
2.0 SAFETY ...............................................2
3.0 INSTALLATION....................................3
3.1 Components Provided......................... 3
3.2 Combustion Air Inlet System ...............3
3.2.1 System Design - Pressure Drop....3
3.2.2 Inlet Duct.......................................3
3.2.3 Air Inlet Termination......................3
3.2.4 Inlet Duct Assembly at the Boiler... 4
3.2.5 Inlet Damper and Auxiliary Control
Panel (optional).................................5
3.3 Exhaust Venting System .....................5
3.3.1 System Design - Materials, Length,
Size, and Construction ......................5
3.3.2 Flue Gas Outlet Duct.....................5
3.3.3 Exhaust Vent Connection at the
Boiler.................................................6
3.3.4 Flue Gas Termination....................6
3.4.5 Equivalent Length of Fittings .........7
3.4 Clearances .......................................... 7
3.4.1 Sidewall Installations.....................7
3.4.2 Rooftop Installations......................8
3.4.3 Minimum Clearance for Boiler
Connections ......................................8
4.0 OPERATION ........................................9
4.1 Sequence of Operation .......................9
4.2 Combustion Operating Conditions.......9
4.2.1 Combustion Air Requirement,
SCFM............................................10
5.0 MAINTENANCE .................................10
6.0 WIRING DIAGRAMS..........................11
6.1 On-Off Series 700, 1000, 1200......... 11
6.1a On-Off IRI Series 700, 1000, 1200 .13
6.1b Lo-Hi Lo ..........................................15
6.1c Lo-Hi-Lo IRI .................................... 17
6.1d On-Off Series 1500, 1700, 2000 ..... 19
6.1e On-Off IRI Series 1500, 1700, 2000 21
6.2 Auxiliary Control Panel...................... 23
6.2.1 On-Off Auxiliary Control Panel.... 23
!
WARNING
Improper use may result in fire or injury.
Read instructions/safety manual before installing,
c
1998 HCS, Inc. 800-748-0241
WARNING!
essential
It is recommendations of this manual before installing, operating, or servicing this equipment. Failure to do so could result in fire or explosion and serious injury, death, and/or property damage.
to read, understand, and follow the
operating or servicing boiler.
Reorder No. 6020-V2WHPK
The same features which permit this boiler to achieve high-efficiency performance make it unlike most other boilers of this general size, so it is important to understand how this boiler operates. Do not store or use gasoline or other flammable vapors or liquids in the vicinity of this or any other appliance.
WARNING!
Installation and service must be performed by a qualified installer, service agency, or gas supplier.
What to do if you smell gas:
Do not try to light any appliance.
Do not touch any electrical switch.
Do not use any phone in your building. Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions.
If you cannot reach your gas supplier call the fire department.
Thermific® Gas-Fired Boiler Introduction
1.0 INTRODUCTION
Direct vent (ANSI Z21.13) is a closed system method of ducting the combustion air directly from the outside of the building into the inlet compartment of the burner, and a sealed exhaust vent from the combustion chamber to the outdoors.
The direct vent/sealed combustion option is available on the Thermific® boilers on Series 700, 1000, 1200, 1500, 1700, and 2000.
Advantages are:
Savings in energy costs due to the elimination of using conditioned air (heated and/or cooled building air) from going back up the stack.
Isolation of the burner from pressure changes in the building which can cause erratic combustion performance.
Combustion air is taken from the outside which is generally more clean than indoor air. Halide contaminants within a building, such as chlorides, can cause excessive corrosion in the burner, heat exchanger and venting system.
1.1.2 Fresh Air System
(ducted combustion air system)
In some instances compliance with ANSI Z21.13
may
not be required, in which case a "fresh air system" may be used. Consultation with qualified professionals is required to determine whether a "fresh air system" is suitable for any particular application and in compliance with all applicable codes and regulations.
All flue gas outlet (exhaust vent) material for a fresh air system must be certified for use with a Category I Appliance. (Standard B-vent isapproved.) The exhaust vent may be run horizontally or vertically. Proper vent sizing by the vent manufacturer's recommendation must be followed.
1.2 B
ASIC INLET/VENTCONFIGURATIONS
Four basic configurations are allowable for the combustion air inlet and flue gas exhaust vent, as follows; installation details are provided in Section 3.
Eliminates the need for two large combustion air/ventilation air openings into the mechanical space.
1.1 C
ODECOMPLIANCE
1.1.1 Direct Vent/Sealed Combustion System
(complying with ANSI Z21.13)
All flue gas outlet (exhaust vent) material must comply with UL-1738. (Standard B-vent
is not
approved.) Proper vent sizing by the vent manufacturer's recommendation must be followed. The exhaust vent may be run horizontally or vertically. The maximum allowable length of the exhaust vent for horizontal installations, including the boot tee/135º (not a standard tee) and the termination is
equivalent feet.
Refer to Section 3.4.5 for equivalent
100
lengths.
Exhaust Vent
Roof
Sidewall
Air Inlet
1. Combustion air inlet duct through the sidewall and the flue gas exhaust through the roof. This is the preferred method.
Page 1
Thermific® Gas-Fired Boiler Introduction/Safety
Sidewall
Exhaust Vent
Air Inlet
2. Both the combustion air inlet and flue gas exhaust through the sidewall.
Air Inlet
Exhaust Vent
Air Inlet
Exhaust Vent
Roof
Sidewall
4. The combustion air inlet from the roof and the flue gas exhaust through the sidewall.
1.3 P
URPOSE AND SCOPE OF THIS MANUAL
This manual is a supplement and companion to the Thermific Installation and Owner's Manual. "TBIG." Both documents must be used together.
Roof
3. The combustion air inlet from the roof and the flue gas exhaust through the roof.
This companion document describes those safety, installation, adjustment, and maintenance procedures which differ from the standard model. Information that applies to both models is found in the "TBIG" latest edition.
2.0 SAFETY
Refer to the manual for the standard Thermific® Gas­Fired Boiler for safety information applicable to this equipment. Safety information applicable only to the direct vent option appears below.
Danger!
Acceptable Venting Methods:
The only acceptable venting methods are the four configurations shown in Section 1.2. Do not attempt to use any other method of obtaining combustion air or venting flue gases.
Page 2
Thermific® Gas-Fired Boiler Installation
Do not manifold two (2) or more units into a common sidewall vent system without provisions for additional forced draft.
3.0 INSTALLATION
3.1 C
OMPONENTS PROVIDED
The direct vent/sealed combustion option is shipped with the following items shipped loose for field installation:
Custom 6 inch diameter to 12 inch diameter transition duct with extension, for attachment to the combustion air inlet on the boiler.
A 12" inlet damper assembly with actuator and limit switch mounted to the damper shaft.
Auxiliary Control Panel to operate the inlet damper assembly.
The inlet damper assembly and control panel will prevent the flow of cold air through the boiler during the off cycle and prevent freeze up and "off cycle" losses. The use of these two items is optional.
3.2 C
OMBUSTION AIRINLETSYSTEM
Note:
silicone sealant, or equivalent, must be used on each circumferential and horizontal joint before joining together. At least 24 hours must be allowed for cure of this sealant and proper bond. Cure time can be reduced through the application of heat (See instructions provided with the sealant). After the cure period, each joint must be wrapped with an aluminum tape which is faced on the contact side with an adhesive.
3.2.2.2 PVC Duct
Proper sealing of the tubing is necessary to prevent flow of combustion air from conditioned space.
The installation must follow the vent manufacturer's instructions in all respects including proper joining and sealing of the tubing and fittings. Clearances to combustible materials and installation of firestops must conform to applicable codes.
3.2.3 Air Inlet Termination
Centering Support Plate
Outside Plate
Cover Plate Fastener
Sealant
Recommended Termination (refer to text).
3.2.1 System Design - Pressure Drop
The air inlet duct system shall be designed for a maximum pressure drop of 0.05" W.C. taking into account the equivalent length of all fittings. Refer to Section 3.4.5 for equivalent length of fittings.
3.2.2 Inlet Duct
Materials shall be single wall galvanized duct (minimum thickness 26 gauge) or PVC duct tubing (0.187 inch wall thickness) only.
3.2.2.1 Single Wall Galvanized Duct
No substitutions.
Proper sealing of the tubing is necessary to prevent flow of combustion air from conditioned space. If single wall galvanized tubing is used, GE RTV 102
Page 3
Sealant
12" Min.
Field Provided Inlet Screen
The boiler combustion air inlet duct must be fitted with a termination device meeting the requirements of ANSI Z21.13. There are four recommended sidewall terminations:
Double wall B vent 90 degree elbow, or
Two double wall B vent 45 degree elbows, or
Schedule 40 PVC 90 degree elbow, or
Properly engineered intake louver screen.
Thermific® Gas-Fired Boiler Installation
Whichever material is used, the termination must point down and must be backed by a metal plate secured to the wall.
Important:
The chosen inlet termination must be included in the calculation of the maximum allowable equivalent length. See Section 3.4.5 for equivalent lengths.
Correct rain cap, unrestricted.
Typical incorrect rain cap.
If the combustion air inlet duct is routed through the roof, the termination must be either the same type as described for a sidewall installation or a rain cap. The rain cap must be unrestrictive type similar to the illustration below.
3.2.4 Inlet Duct Assembly at the Boiler
Damper
Transition
Round
Duct
Damper Housing
(Sidewall installation shown.)
The boiler is equipped with a special collar attached to the air inlet opening on the back of the unit (at the blower housing on Series 700, 1000, and 1200; at the back of the cabinet on Series 1500, 1700 and 2000.). A separate box of accessories is sent with the boiler.
1. Attach the 6 inch diameter end of the custom transition duct and the extension to the collar using a minimum of 4 sheet metal screws spaced approximately at 90 degree intervals. This joint must then be wrapped with an aluminum tape backed on the contact side with an adhesive. Do not use "duct tape."
Roof
Transition Duct
(Roof installation shown.)
Round
Damper
o
90 Elbow
Damper Housing
Page 4
Important:
do not insulate the transition duct or
extension.
Refer to Section 3.2 for instructions for installing and wiring the auxiliary control panel; it is required if the optional inlet damper is used.
3.2.4.1 Sealing PVC Duct Tubing to the Inlet Duct
Apply a 3/4" wide x 1/8" thick gasket to the outside surface edge of the entire circumference of the transition duct (or extension). A closed cell foam rubber gasket with pressure sensitive adhesive works very well. Insert 3/4" of the transition duct into the PVC duct tubing so that the gasket lines up with the edge of the PVC tubing. Lay an approximate 3/8" wide bead of GE RTV-102 silicone sealant, or equivalent, along the gap between the gasket and inside wall of the tubing. Allow the silicone sealant to cure for 24 hours. The cure time can be shortened
Thermific® Gas-Fired Boiler Installation
with the application of heat. Refer to the manufacturer's instructions. Wrap the joint with aluminum tape which is backed with an adhesive on the contact side.
3.2.5 Inlet Damper and Auxiliary Control Panel (optional)
Note:
The inlet damper assembly and control panel will prevent the flow of cold air through the boiler during the off cycle and prevent freeze up. These two items
optional
are
in all installations.
Refer to Section 4.1 for a description of the control sequence applicable to the inlet damper.
The damper must be field installed into a section of horizontal or vertical inlet ductwork. Orient the damper such that the arrow points towards the boiler.
3.2.5.1 Field Wiring to Auxiliary Control Panel
The auxiliary control panel controls the inlet damper (if used). The auxiliary control panel does not have to be mounted on or near the boiler; it can be remotely mounted.
Use 16GA MTW Wire for all field wiring. See Section 6 for the logic and wiring diagrams of this auxiliary control panel and the sealed combustion boilers.
There are five (5) field run wires between the boiler and its auxiliary control panel; three (3) for main power supply and two (2) wires for boiler interconnect.
1. The main power supply (G/H/N) must come from the same boiler that the damper is connected to.
2. Remove the blue jumper wire in the terminal block on the boiler when wiring.
There are also five (5) field run wires between the auxiliary control panel and the inlet damper assembly; three (3) to the damper actuator and two (2) to the limit switch.
1. Terminals for the damper actuator:
DO = Damper Open (CW) DC = Damper Closed (CCW) DN = Neutral/Common
2. Terminals for the limit (end) switch
SI = N.O. (Normally Open) S2 = Common
3.3 E
XHAUST VENTINGSYSTEM
3.3.1 System Design - Materials, Length, Size, and Construction
The flue gas outlet (exhaust vent) must be designed to comply with UL 1738 and ULC-636. (Refer to Section 1.1.2 for situations where alternate compliance may be permitted.) The exhaust vent can be run horizontally or vertically.
The vent must be sized according to the vent manufacture's recommendations. Consult the vent supplier for correct sizing and structural support requirements. Vent diameter is dictated by the length and height of horizontal and vertical portions of the vent installation and materials of construction. Design calculations should be based on a negative 0.03 W.C. with a stack temperature of 325º F (gross) and a CO
2
level of 7.6%; (these values are to be used for vent sizing calculations.) The
maximum
allowable length of the vent duct, including the boot tee/135º tee (not a standard tee) and the termination is 100 equivalent feet. See Section 3.4.5 for the equivalent length of the fittings.
3.3.2 Flue Gas Outlet Duct
The installation must follow the vent manufacturer's instructions in all respects including proper joining and sealing of the tubing and fittings, clearances to combustible materials and installation of firestops.
Page 5
Thermific® Gas-Fired Boiler Installation
3.3.3 Exhaust Vent Connection at the Boiler
Pitch toward boiler 1/4" per foot min.
6' Min.
Boot Tee/
o
135 Tee
Trap Loop
3" Min.
Condensate Drain
To s ewe r t rap or condensate pump.
At the outlet of the boiler, an adjustable or fixed length (minimum 2 feet for clearance from inlet duct; maximum 3 feet for proper lift) section may be utilized. This section must be secured to the outlet collar by a minimum of 4 sheet metal screws spaced at approximately 90 degree intervals.
from the outlet of the boot tee/ 135º tee to the inlet of the elbow. In addition, for sidewall venting, it is
important
to provide a downward pitch of at least 1/4
very
inch per foot of run from the termination at the wall toward the boiler for proper drainage of the condensate and for buoyancy assist of the flue gas. Furthermore,
do not
locate sidewall terminations over area of pedestrian or vehicular traffic due to potential condensate drippage and ice build-up. See Section 3.4 Clearances for more information.
When joining the double wall tubing and fittings, it is important to orient the male end of the section toward the boiler. The female end is positioned away from the boiler towards the vent terminal. Follow the vent manufacturer's instructions for proper installation.
3.3.4 Flue Gas Termination
Centering Support Plate
Sealant
Outside Plate
Cover Plate Fastener
Sealant
Recommended termination (refer to text).
Even though the unit is classified as a Category I boiler (Non-pressurized-non condensing), there are certain abnormal conditions which may cause condensation in the flue vent. Therefore, it is recommended that a tee cover with a drain be provided at the bottom of the boot tee/135º tee. For proper disposal of the condensate, corrosion resistant tubing or plastic tubing should be connected to the drain nipple. Before connecting the tubing to the tee cover nipple, the trap loop must be primed by pouring a small quantity of water into the drain line. The condensate drain line can be routed to a sewer drain trap or pump. Consult the vent manufacturer's instructions for proper installation of drain line.
In transitioning from horizontal to vertical, a double wall boot tee/135º tee must be installed (not a standard tee). If the flue gas exhaust is to be routed through the sidewall, a minimum vertical rise of 6 feet is required
Page 6
12" Min.
The exhaust vent termination must be a P-K recommended device. There are four approved sidewall terminations:
90º elbow pointing down, or
Two 45º elbows pointing down, or
45º elbow pointing down, or
Standard tee pointing up/down.
Important:
The equivalent length of the chosen termination must be included in the calculation of the maximum allowable equivalent length. See Section
3.4.5 for equivalent lengths.
Loading...
+ 18 hidden pages