Paradox Hellas S.A CAA470A-EI02, CT-V900 User Manual

CAA470A-EI02
2-Door Expansion Module
PRINTED IN CANADA 07/2004
CA-A470-A
Instructions
780 Industriel Blvd., Saint-Eustache (Quebec) J7R 5V3 CANADA Tel.: (450) 491-7444 Fax: (450) 491-2313
www.paradox.ca
Introduction
Connected to the CT-V900 controller’s expansion bus, the 2-Door Expansion Module (CA-A470-A) supports two readers, two BCD keypads, four zone inputs, 6 outputs and two locking devices.
Specifications
CA-A470-A Specifications: Readers: connect 2 per module Keypads: connect 2 per module Inputs: 4 standard without ATZ, 1 tamper Outputs: 6 (open collector) Lock Outputs: 2 lock outputs (Form C relays)
each: 15A @ 16VDC (resistive) AC Power: 16VAC, 40VA max. Frequency: 50Hz/60Hz Aux. Current: 500mA (max.) Battery: 12VDC, 7Ah
low battery = 10.2VDC
low battery restore = 12.2VDC
low battery cut-off = 8.5VDC Communication: expansion bus (E-Bus), RS-485, Plug
and Play, 3 modules per CT-V900
o
Operating temp.: 5
C to 55oC (41oF to 133oF)
In order for new DIP switch settings to take effect, the 2-Door Expansion Module’s power must be disconnected and then reconnected.
Assign Address (1 and 2)
DIP switches 1 and 2 determine the 2-Door Expansion Module’s address in the network, regardless of the order that they are connected to the controller. Centaur recognizes the doors according to the DIP switch settings as shown in Figure 1.
Figure 1: Setting the network address
Lock State during Communication Failure
DIP switches 3 and 4 determine the state of Lock #1 and Lock #2 ONLY during a communication failure between the 2-Door Expansion Module and the controller (CT-V900­A). Normally, the lock outputs follow the Lock Control for the CT-V900-A. Therefore, the DIP switches should have the same setting as the Lock Control for the corresponding doors in Centaur.
Lock #1 = DIP switch 3 Lock #2 = DIP switch 4
OFF
= De-energized:
During a communication failure, the normal state of the lock output is De-energized. When Lock #1 or Lock #2 is activated, power is corresponding lock output to unlock the door. Activation depends on the setting of the DIP switches 5 & 6 (Access during Communication Failure).
ON
= Energized:
During a communication failure, the normal state of the lock output is Energized. When Lock #1 or Lock #2 is activated, power is corresponding lock output to unlock the door. Activation depends on the setting of the DIP switches 5 & 6 (Access during Communication Failure).
De-energized: no power in normal state; requires power to activate.
Energized: power in normal state; remove power to activate.
applied
removed
to the
from the
Access during Communication Failure (5 and 6)
DIP switches 5 and 6 determine the access to the protected doors during a communication failure.
Switch Setting During a Communication Failure:
5 = off (0) 6 = off (0)
5 = on (1) 6 = off (0)
5 = off (0) 6 = on (1)
5 = on (1) 6 = on (1)
“No Card” Access is denied to all cards and doors are locked until communication is restored.
“2 Cards” Access is granted only when 2 cards of a valid format are presented to the reader.
“All Cards” Access is granted when any card with a valid format is presented to the reader.
“Unlock Door” Doors are unlocked until communication is restored.
Activate Output on Communication Failure (7)
DIP switch 7 determines if OUT5 and OUT6 will pulse during a communication failure. When DIP switch 7 placed in the
ON position, the outputs on
the device(s) connected to the OUT5 and OUT6 terminals will pulse. For example, the LED on the reader can pulse to advise users that a communication failure has occurred.
DIP Switch (8)
For future use.
EOL Jumper
Place the EOL jumper ON if the 2-Door Expansion Module is at the beginning (Start Point) or at the end (End Point) of the E-bus Network (see Figure 2). Otherwise, place the EOL jumper OFF.
Figure 2: Setting the Jumpers
High/Low Bias Jumpers
Place the A+ and B- jumpers on LOW only if the 2-Door Expansion Module is at the beginning (Start Point) of the E-bus Network. Otherwise, place the A+ and B- jumpers on HIGH (see Figure 2 and Figure 3).
Figure 3: Setting the A+ and B- jumpers
Jumpers set to low Jumpers set to high
A+ B-
LOW
HIGH
A+ B-
LOW
HIGH
350mA/700mA Battery Charging Jumper
The 350mA/700mA Jumper allows you to select the charging current for the backup battery of the 2-Door Expansion Module. Charging the battery at 350mA takes longer, but consumes less power. Charging the battery at 700mA takes less time, but consumes more power.
Figure 4: Setting the 350mA/700mA jumper
Jumper set
as 350mA
Jumper set
as 700mA
Programming in Centaur
Using the Centaur Access Control Software, program the inputs, outputs, readers, and keypads connected to the 2­Door Expansion Module. The options are explained in the Centaur Access Control Software Reference Manual.
Centaur will identify the 2-Door Expansion Module by its address (see DIP Switches 1 to 4) and will recognize the devices as follows:
Address 1 Address 2 Address 3
Doors
Keypad/Reader 1 Door 3 Door 5 Door 7 Keypad/Reader 2 Door 4 Door 6 Door 8
Inputs
Z1 Input 17 Input 21 Input 25 Z2 Input 18 Input 22 Input 26 Z3 Input 19 Input 23 Input 27 Z4 Input 20 Input 24 Input 28
Outputs
OUT1 Output 7 Output 13 Output 19 OUT2 Output 8 Output 14 Output 20 OUT3 Output 9 Output 15 Output 21 OUT4 Output 10 Output 16 Output 22 OUT5 Output 11 Output 17 Output 23 OUT6 Output 12 Output 18 Output 24
Doors cannot be defined as Door Type Elevator (Door Properties window, General tab, Door Type: Elevator) and the module does not support Interlock Inputs (Door Properties window, Inputs and Outputs tab, Interlock Input).
Other modules in the system cannot activate the 2­Door Expansion Module’s outputs.
The 2-Door Expansion Module does not support Zone Doubling (see Figure 6).
Green “
STATUS” LED:
Flash = Module OK Slow flash = Communication failure
(see also “
COMM” LED)
Green “LOCK#1” and “LOCK #2” LEDs: ON = Relay activated.
Figure 5: CA-A470-A indicators
Green “AC” LED: ON = AC power OFF= Power failure
Green “
AUX” LED:
ON = Auxiliary power OFF= Auxiliary power failure
COMM” LED:
Red “ ON = Communication failure OFF= OK
Green “
CHECK BATT” LED:
ON = Battery verification in
progress (every minute)
BATT TRBL” LED:
Red “ ON = Battery low or disconnected
Figure 6: Connection drawing of the CA-A470-A
Green “ Long flash = Receiving card read Short flash = Receiving card read, but the system does not recognize the card’s format
READER#2 DATA” and “READER#1 DATA” LED:
Red “
TX” LED and green “RX” LED:
ON = Communication OK (may flicker) OFF = Communication failure
OFF = Not receiving card read
The reader LEDs can be used to verify the reader’s connections and programming. If no flashing occurs when a card is presented to the reader, the reader may be installed incorrectly. A short flash indicates that the reader is correctly installed, but the card is the wrong type or that the reader was incorrectly pro grammed.
Warranty
Paradox Security Systems Ltd. (“Seller”) warrants its products to be free from defects in materials and workmanship under normal use for a period of one year. Except as specifically stated herein, all express or implied warranties whatsoever, statutory or otherwise, including without limitation, any implied warranty of merchantability and fitness for a particular purpose, are expressly excluded. Because Seller does not install or connect the products and because the products may be used in conjunction with products not manufactured by Seller, Seller cannot guarantee the performance of the security system and shall not be responsible for circumstances resulting from the product’s inability to operate. Seller obligation and liability under this warranty is expressly limited to repairing or replacing, at Seller's option, any product not meeting the specifications. Returns must include proof of purchase and be within th e warrant y period. In n o event shall the Seller be liable to the buyer or any other p erson for any loss or da mages whether direct or indirect or consequential or incidental, including without limitation, any damages for lost profits stolen goods, or claims by any other party, caused by defective goods or otherwise arising from the improper, incorrect or otherwise faulty installation or use of the merchandise sold.
Notwithstanding the preceding paragraph, the Seller’s maximum liability will be strictly limited to the purchase price of the defective product. Your use of this product signifies your acceptance of this warranty.
BEWARE: Dealers, installers and/or others selling the product are not authorized to modify this warranty or make ad ditional warranties that are binding on the Seller. © 2001-2004 Paradox Security Systems Ltd. All rights reserved. Specifications may change without prior notice. One or more of the following US patents may apply: 6215399,
6111256, 5751803, 5721542, 5287111, 5119069, 5077549, 5920259, 5886632. Canadian and international patents may also apply. Centaur is a trademark or registered trademark of Paradox Security Systems Ltd. or its affiliates in Canada, the United States and/or other countries.