Paradox Magellan MG5050, Magellan MG5000, Spectra SP4000, Spectra SP5500, Spectra SP7000 Programming Manual

...
32 Zone Wireless Transceiver Security Systems
MG5000 V4.5 MG5050 V4.5
4 to 32 Zone Expandable Security Systems
SP4000 V4.5 SP5500 V4.5 SP6000 V4.5 SP7000 V4.5
Always Armed, Never Disarmed
Programming Guide
PARADOX.COM
For complete warranty information on this p rod uct ple ase r efer to th e Lim ited Warranty S tatement found on the website www.paradox.com/terms. Your use of the Paradox product signifies your acceptance of all warranty terms and conditions.

Limitations of Alarm Systems:

It must be understood that while your Paradox alarm system is highly advanced and secure, it does not offer any guaranteed protection against burglary, fire or other emergency (fire and emergency options are only available o n certain Paradox models). This is due to a number of re asons, includi ng b y not limited to inadequate or improp er i nst a llat ion / positioning, sensor limitations, batt ery perf orma nce, wirele ss signa l inte rru ptio n, inade qua te mai nten ance or the pote ntial fo r the system or telephone lines to be compromised or circumvented. As a result, Paradox does not represent that the alarm system will prevent personal injury or property damage, or in all cases provide adequate warn ing or prot ection.
Yo ur securit y system should th erefore be consid ered as one of man y tools availab le to reduce r isk and/or damage of burglary, fire or o ther emergencie s, such other to ols include but are not limited to insurance coverage, fire pr eventi on and extinguish devices, and sprinkler systems.
We also strongly recommend that you regularly maintain your security systems and stay aware of new and improved Paradox products and developments. TBR-21: In order to comply with TBR-21, standard f or ce di ali ng mu st be en abled .

UL AND ULC WARNINGS

This equipment has the capability of bei ng prog ra mmed w ith f eatu res not verifi ed f or use in UL installations. To stay within UL and ULC standards, the installer should use the following guidelines when configuring the system:
All components of the system should be UL listed for the intended application.
If used for “Fire” detection, the inst aller should refer to NFPA Standards #72, Chapter 2. In addition, once installation is complete, the local fire authority must be notified of the installation.
WARNING: This equipment must be installed and maint ained by qualified service personnel only
This equipment must be verified by a qualified technician once every three years.
All keypads must use an anti-tamper switch.
Do not bypass fire zones.
Maximum allowed entry delay is 45 seconds.
Maximum allowed exit delay is 60 seconds.
Minimum 4 minutes for bell cut-off time.
The following features do not comply with UL requirements: Bypass Recall and Auto Trouble Shutdown.
Do not connect the primary indicating device to a relay. The installer must use the bell output.
To comply with UL985, the auxiliary power output should not exceed 200mA.
Do not connect the zone ground terminal with UL Listed products.
The metallic enclosure must be grounded to the cold water pipe.
All outputs are Class 2 or power-limited, except for the battery terminal.The Class 2 and power-limited fire alarm circuits shall be installed using CL3, CL3R, CL3P, or substitute cable permitted by the National Electrical Code, ANSI/NFPA 70.
EOL resistor part #2011002000
For UL Installations: Universal UB1640W 16.5VAC min 40VA
All outputs are rated from 11.3Vdc to 12.7Vdc
12Vdc 4Ah rechargeable acid/lead or gel cell backup battery (YUASA model #NP7-12 recommended) for residential use. Use a 7Ah battery to comply with fire requirements.
Wheelock 46T-12 siren

Legal

© 2010 Paradox Security Systems Lt d . Al l righ ts reserved. Specifications may change without prior no t ice. O ne or mor e o f th e f o llo wing US patents may apply: 7046142, 6215399, 6111256, 6104319, 5920259, 5886632, 5721542, 528 7111, 5119069, 5077549 and RE39406. Canadian and international patents may also apply. Magellan, Spectra SP, WinLoa d and BabyWare are trademarks or regist ere d tra demarks of Para dox Se cur ity Syst ems Ltd. or its affiliates in Canada, the United States and/or other countries.
Table of Contents
System Overview .......................................................... 3
Comparison Chart ........................................................ 4
Specifications ................................................................ 5
Entering Programming Mode ........................................ 5
Data Entry & Display .................................................... 6
Important Settings and Modes ...................................... 6
System Codes .............................................................. 7
System Planning ........................................................... 8
Zone Programming ................................ .... ... ... ... .... ... . 12
Keypad Programming .................................................. 18
Partition Programming ................................................. 19
System Programming .................................................. 20
Daylight Savings Programming ............................... .... 21
Communication Programming ..................................... 22
Programmable Output Programming .......................... 29
System Report Codes ................................................. 36
Ademco Contact ID Report Codes ...............................39
Automatic Report Code List ...................... ..................40
Installer Function Keys .................................................41
Trouble Display ............................................................42
Wireless Repeater Programming (RPT1) ....................43
Wireless Keypad Programming (K32RF / K37) ...........45
Wireless Siren Programming .......................................46
LCD Keypad Labels (K32LCD) ........ ... .... ... ... ... ... .... ... ..47
User Programming .......................................................50
Hardware Connections ................................................55
Connecting to WinLoad / BabyWare ............................57
Updating Firmware Using WinLoad / BabyWare .........57
Metal Box Installation . ... ... ... ... ......................................58
Installer Quick Menu ....................................................65
Index ............................................................................ 68
Conventions
Default Settings: Options which are bold signify the default value:
e.g. Access code length:
6 digits 4 digits (4 digits is the default value)
WARNING: Important information NOTE: Suggestion or reminder

System Overview

Module Description Maximum number
K32RF, K37 32-Zone Wireless Keypad Modules 8 total Wireless K10V/H
K32 K32LCD K35 K636
ZX8 ZX8SP
RPT1 Magellan Wireless Repeater Module 2 Average = 57mA VDMP3 Plug-In Voice Dialer 1 Min. = 28mA / Max. = 28mA IP100 Internet Module 1 Min. = 90mA / Max. = 120mA RTX3 Wireless Expansion Module (Spectra SP only) 1 Min. = 61mA / Max. = 143mA RX1 Wireless Receiver (Spectra SP only) 1 Min. = 26mA / Max. = 61mA PCS200 Paradox Communicator Module 1 Min. = 80mA / Max. = 600mA

Important System Notes

Please refer to the following module compatibility exceptions to ensure proper system function:
• Wireless keypads can be used with MG/SP systems that include an RTX3 (not compatible with SP4000 systems).
• When using a K636 keypad, only partition 1 is available.
• The following modules are not compatible with SP4000 systems: K32RF, K37, K32LCD, RPT1.
• When using an SP Series panel, all wireless sections and options do not apply unless an RTX3 is used in conjunction with the panel.
• When using an SP6000 panel in conjunction with an RTX3, all K32 and K10V/H keypads must be versions 2.0 or higher.
• The K35 Fixed LCD keypad module is only compatible with MG/SP panels version 2.3 and higher.
Magellan / Spectra SP 3
10 and 32-Zone Hardwired Keypad Module 15 total including ZX8
8-Zone Expansion Module 3 Min. = 29mA / Max. = 31mA
Quick Menu (see page65)
Current
per system
and RTX3
Consumption
K10V/H: Min. = 44mA / Max. = 72mA K32: Min. = 49mA / Max. = 148mA K32LCD: Min. = 43mA / Max. = 86mA K35: Min. = 30mA / Max. = 70mA K636: Min. = 28mA / Max. = 33mA

Comparison Chart

Security Features MG5000 MG5050
StayD  Built-in transceiver  Maximum zones 32* 32* On-board zones 2 (4 with ATZ) 5 (10 with ATZ) Expansion zones (ZX8) 24 (3 x ZX8) 24 (3 x ZX8) Keypad zones 15 15 Partitions 2 2 User Codes 32 32 Remote controls 32 32 PGMs 16* (2 on-board) 16* (4 on-board) PGM +/- trigger - Alarm relay (panel relay) - ­Event buffer 256 256 Wireless keypads (K32RF and K37) 8 8 Wireless repeaters (RPT1) 2 2 Wireless sirens (SR150) 4 4 2-wire smoke detector input  GPRS/GSM communication (PCS Series)  Internet TCP/IP communication (IP100)  Plug-in voice module (VDMP3)  Personal dialing  Pager reporting  Upload/download software WinLoad WinLoad In-field firmware upgradeable 
Feature SP4000 SP5500 SP6000 SP7000
StayD   Built-in transceiver - - - ­Maximum zones 32 32* 32* 32* On-board zones 4 (8 with ATZ) 5 (10 with ATZ) 8 (16 with ATZ) 16 (32 with ATZ) Expansion zones (ZX8) 24 (3 x ZX8) 24 (3 x ZX8) 24 (3 x ZX8) 24 (2 x ZX8) Keypad zones 15 15 15 15 Partitions 2 2 2 2 User codes 32 32 3 2 32 PGMs 12 (1 on-board) 16* (2 on-board) 16* (2+2** on-board) 16* (4 on-board) PGM +/- trigger - -  Alarm relay (panel relay) - - 1** 1 Event buffer 256 256 256 256 Remote control 32 32 32 32 Wireless keypads (K32RF and K37) - 8 8 8 Wireless repeaters (RPT1) - 2 2 2 Wireless sirens (SR150) - 4 4 4 Wireless expansion (RTX3
Wireless expansion (RX1) ‡   2-wire smoke detector input - -  GPRS/GSM communication (PCS Series)   Internet TCP/IP communication (IP100)   Plug-in voice module (VDMP3)   Personal dialing   Pager reporting   Upload/download software BabyWare‡ WinLoad WinLoad WinLoad In-field firmware upgradeable   * Any of which can be wireless ** Optional *** When used with an SP4000 system, the RTX3 only allows for the use of remote controls. † When used with an SP4000 system, the RX1 only allows for the use of one-way remote controls. ‡ For compatible BabyWare version, refer to paradox.com.
)
***
 
4 Programming Guide

Specifications

MG5000 / MG5050
Power rating 16.5 VAC (50 or 60Hz) minimum 20 VA (40 VA recommended) Aux. power 600 mA typical, 700 mA maximum, fuseless shutdown at 1.1A Battery 12 VDC, 4Ah/7Ah Battery charging current 35 0 mA On-board zones MG5000: 2
MG5050: 5 Bell output 1A (fuseless shutdown at 3A) On-board PGMs MG5000: 2
MG5050: 4 (1+/- trigger)
All on-board PGMS are 100mA low-current outputs Dimensions MG5000: 14 x 10.4cm (5.5 x 4.1”)
MG5050: 19 x 10.2cm (7.5 x 4”) Operating temperature 0°C to 50°C (32°F to 122°F)
SP4000 / SP5500 / SP6000 / SP7000
Power rating 16.5Vac (50 or 60Hz) minimum 20VA (40VA recommended) Aux. power SP4000:
450mA, fuseless shutdown at 650mA
Battery 12Vdc, 4Ah/7Ah Battery charging current SP4000: Limited by 1.1A supply current
(AUX consumption - no dedicated
battery current limit circuit) On-board zones SP4000: 4
SP5500: 5 Bell output 1A (fuseless shutdown at 3A) On-board PGMs SP4000: 1
SP5500: 2 (all +/- trigger)
All on-board PGMS are 100mA low-current outputs Dimensions SP4000: 14 x 6.6cm (5.5 x 2.6”)
SP5500: 19 x 8.9cm (7.5 x 3.5”) Operating temperature 0°C to 50°C (32°F to 122°F)
SP5500 / SP6000 / SP7000:
600mA typical, 700mA maximum, fuseless shutdown at 1.1A
SP5500: 350 mA SP6000 / SP7000: 350 mA / 850 mA
SP6000: 8 SP7000: 16
SP6000: 2+(2 optional) (all +/- trigger) SP7000: 4 (all +/- trigger)
SP6000: 19 x 8.9cm (7.5 x 3.5”) SP7000: 20.3 x 10.8cm (8 x 4.25”)

Entering Programming Mode

WARNING: StayD Mode must be deactivated in order to enter programming mode. To deactivate StayD, press [OFF] + [MASTER /
USER CODE] + [OFF].
1. Press [
2. Enter your [
3. Enter the 3-digit [
4. Enter required [
Magellan / Spectra SP 5
ENTER].
INSTALLER CODE] (default: 000000) or [MAINTENANCE CODE] (no default). [ARM] and [STAY] lights flash.
To modify codes, see System Codes on page 50.
SECTION] you wish to program ([ARM] and [STAY] lights are ON).
DATA].

Data Entry & Display

K636 K10V/H
K35/K37
K32RF/K32
To access the Data Display Mode, press the [ENTER] key after entering a section and before entering any data. The four LEDs/Icon as indicated below will begin to flash indicating that you are in the Data Display Mode.
Each time the [ENTER] key is pressed, the keypad will display the next digit in the current section and will continue through all the following sections one digit at a time without changing the programmed values. Not available for sections using the Multiple Feature Select Method. Press the [
There are two methods that can be used to enter data when in programming mode: Single Digit Data Entry and Feature Select Programming methods:

Single Digit Data Entry Method

After entering programming mode, some sections will require that you enter decimal values from 000 to 255. Other sections will require that you enter hexadecimal values from 0 to F. The required data will be clearly indicated in this manual. When entering the final digit in a section, the panel will automatically save and advance to the next section. Refer to Decimal and Hexadecimal Values on page 6 to see the keys and their equivalent decimal and/or hexadecimal value.
CLEAR] key at any time to exit the Data Display Mode.

Feature Select Programming Method

After entering certain sections, eight options will be displayed where each option from [1] to [8] represents a specific feature. Press the key corresponding to the desired option. This means the option is ON. Press the key again to remove the digit, thereby, turning OFF the option. Press the [ next section.
SLEEP] key to set all eight options to OFF . When the options are set, press the [ENTER] key to save and advance to the

Important Settings and Modes

Section Description [950] Reset all programmable sections to factory default values [955] Clear bus module trouble (remove disconnected module from the bus) [960] Wireless transmitter serial number display (press any button on the assigned remote control or press the tamper switch of
the wireless module, then press [ [970] Download memory key into panel (see the Reference & Installation Manual) [975] Upload panel into the memory key (see the Reference & Installation Manual) [980] Display version number of the panel (press [ENTER] to view the next digit)

Decimal and Hexadecimal Values

Value or Action What Do I Press?
Value 0 / Replace Current
Digit with 0
Values 1 to 9 [1] TO [9] Zone 1 to 9 Keys 1 to 9
A (hex only) [0] Zone 10 Key 0(10) B (hex only) [ C (hex only) [BYP] Zone 12 BYP D (hex only) [ E (hex only) [ F (hex only)
Exit Without Saving [
Save Data (hex only) [
ENTER] to view the next digit)
What Do I See?
32-zone LED 10-zone LED
[SLEEP] Erase digit and remain in section Erase digit and remain in section
OFF] Zone 11 OFF
MEM] Zone 13 MEM
TBL] Zone 14 TBL
[]
CLEAR] Arm & Stay LED flash Arm & Stay LED flash ENTER] Advances to the next section Advances to the next section
Zone 15
[]
6 Programming Guide
System Codes
Example:
Version
01.42
Digits 1-4
Step Action Details When Viewing Keypad Version
1. Enter Viewing Mode:
- For panel version, enter section [980].
- For keypad version, enter Installer Programming, then press and hold [ARM].
The first digit is displayed (usually “0”)
Digit 1 [
ARM] is illuminated
2. Press [
ENTER] The second digit is displayed Digit 2 [SLEEP] is illuminated
3. Press [ENTER] The third digit is displayed Digit 3 [STAY] is illuminated
4. Press [
ENTER] The fourth digit is displayed Digit 4 [OFF] is illuminated
NOTE: K10V/H / K636 keypad version numbers cannot be viewed.
The Installer code is used to enter programming mode, which allows you to program
Installer Code (Default: 0000 / 000000)
Maintenance Code (No Default)
System Master Code (Default: 1234 / 123456)
everything except user codes. To change the default code, go to section [397] on page 50 and refer to section [701] option [1] on page 50. The Maintenance code is used to enter programming mode, which allows you to program everything except for user codes and communication settings (sections [395], [397], [398], [815], [816], [817], [910], [911], [970], and [975]). To set the default code, go to section [398] on page 50 and refer to section [701] option [1] on page 50. The System Master code can use any arming method and can program user codes. To change the default code, go to section [399] on page 50 and refer to section [701] option [1] on page 50.

Panel Reset

Performing a panel reset will reset all programmable sections to factory default values.
SP4000 panels:
1. Verify installer lock is disabled.
2. Remove the battery and AC power from the control panel.
3. Remove all connected wires and devices from the PG1 and zone 1 terminals.
4. Short the PG1 and zone 1 terminals with a wire.
5. Reconnect the AC and battery power to the control panel.
6. Wait for 10 seconds and remove the wire.
All other MG/SP panels:
To reset other MG/SP panels, press and hold the panel’s RESET button until the STATUS LED flashes (5 seconds). Release the RESET button and push it again within 2 seconds. Performing a manual panel reset will not clear bus module troubles.
To reset the panel to default using section programming, see secti on [950] in Important Settings and Modes on page 6.
Viewing Version Numbers
Magellan / Spectra SP 7

System Planning

Bus Module Planning

Use the following table to plan wired keypads, RTX3, RX1, ZX8 and ZX8SP modules.
Serial # Sticker Description
Bus Module 1
Bus Module 2
Bus Module 3
Bus Module 4
Bus Module 5
Bus Module 6
Bus Module 7
Path Zone*
(Entry Point)
Path Zone Path Zon e Path Zone
Bus Module 8
Bus Module 9
Bus Module 10
Bus Module 11
Bus Module 12
Bus Module 13
Bus Module 14
Bus Module 15
*Paths apply only to keypads in StayD mode.
8 Programming Guide

Wireless Keypad Planning

Serial # Sticker Description
K32RF / K37 1
K32RF / K37 2
K32RF / K37 3
K32RF / K37 4
K32RF / K37 5
Path Zone
(Entry Point)
Path Zone Path Zone Path Zone
K32RF / K37 6
K32RF / K37 7
K32RF / K37 8
NOTE: When deleting a wireless keypad (K32RF / K37) from the system, the corresponding StayD path zones will also be deleted.

Wireless Siren Planning

Serial # Sticker Description Serial # Sticker Description
Siren 1 Siren 3
Siren 2 Siren 4
Magellan / Spectra SP 9

PGM Planning

Serial # Sticker Description Serial # Sticker Description
PGM 1 PGM 9
PGM 2 PGM 10
PGM 3 PGM 11
PGM 4 PGM 12
PGM 5 PGM 13
PGM 6 PGM 14
PGM 7 PGM 15
PGM 8 PGM 16

Wireless Repeater Planning

Serial # Sticker Description Serial # Sticker Description
Repeater 1 Repeater 2

Zone Planning

Armed when... Armed when...
Serial # Sticker Zone# Zone Description Stay Sleep Full Serial # Sticker Zone# Zone Description StaySleep Full
Zone
Zone

Zone
Zone

Zone
10 Programming Guide
Zone
Armed when... Armed when...
Serial # Sticker Zone# Zone Description Stay Sleep Full Serial # Sticker Zone# Zone Description StaySleep Full
Zone
Zone
Zone
Zone
Zone
Zone
Zone




Zone
Zone
Zone
Zone
Zone
Zone
Zone




Zone
Zone
Zone
Zone
Zone
Zone



Zone
Zone
Zone
Zone
Zone
Zone



Magellan / Spectra SP 11

Zone Programming

See Quick Menus on page 65
NOTE: For keypad zone programming, see page 18.

Zone Recognition (MG Series)

When expanding zones via ZX8, up to 3 ZX8 modules can be added to the system and are identified by the ZX8 3-position jumpers +1, +9 and +17.
MG5000 No ATZ MG5000 ATZ MG5050 No ATZ MG5050 ATZ
Panel Zone 1: Panel Input 1 Zone 1: Panel Input 1A Zone 1: Panel Input 1 Zone 1: Panel Input 1A
Zone 2: Panel Input 2 Panel Zone 2: Panel Input 2A Zone 2: Panel Input 2 Zone 2: Panel Input 2A Zone 3: Input 1 Zone 3: Panel Input 1B Panel Zone 3: Panel Input 3 Zone 3: Panel Input 3A Zone 4: Input 2 Zone 4: Panel Input 2B Zone 4: Panel Input 4 Zone 4: Panel Input 4A
ZX8 Zone 5: Input 3 Zone 5: Input 1 Zone 5: Panel Input 5 Panel Zone 5: Panel Inpu t 5A
Jumper Zone 6: Input 4 Zone 6: Input 2 Zone 6: Input 1 Zone 6: Panel Input 1B
Panel + 1 Zone 7: Input 5 ZX8 Zone 7: Input 3 Zone 7: Input 2 Zone 7: Panel Input 2B
Zone 8: Input 6 Jumper Zone 8: Input 4 ZX8 Zone 8: Input 3 Zone 8: Panel Input 3B Zone 9: Input 7 Panel + 1 Zone 9: Input 5 Jumper Zone 9: Input 4 Zone 9: Panel Input 4B Zone 10: Input 8 Zone 10: Input 6 Panel + 1 Zone 10: Input 5 Zone 10: Panel Input 5B Zone 11: Input 1 Zone 11: Input 7 Zone 11: Input 6 Zone 11: Input 1 Zone 12: Input 2 Zone 12: Input 8 Zone 12: Input 7 Zone 12: Input 2
ZX8 Zone 13: Input 3 Zone 13: Input 1 Zone 13: Input 8 ZX8 Zone 13: Input 3
Jumper Zone 14: Input 4 Zone 14: Input 2 Zone 14: Input 1 Jumper Zone 14: Input 4
Panel + 9 Zone 15: Input 5 ZX8 Zone 15: Input 3 Zone 15: Input 2 Panel + 1 Zone 15: Input 5
Zone 16: Input 6 Jumper Zone 16: Input 4 ZX8 Zone 16: Input 3 Zone 16: Input 6 Zone 17: Input 7 Panel + 9 Zone 17: Input 5 Jumper Zone 17: Input 4 Zone 17: Input 7 Zone 18: Input 8 Zone 18: Input 6 Panel + 9 Zone 18: Input 5 Zone 18: Input 8 Zone 19: Input 1 Zone 19: Input 7 Zone 19: Input 6 Zone 19: Input 1 Zone 20: Input 2 Zone 20: Input 8 Zone 20: Input 7 Zone 20: Input 2
ZX8 Zone 21: Input 3 Zone 21: Input 1 Zone 21: Input 8 ZX8 Zone 21: Input 3
Jumper Zone 22: Input 4 Zone 22: Input 2 Zone 22: Input 1 Jumper Zone 22: Input 4
Panel + 17 Zone 23: Input 5 ZX8 Zone 23: Input 3 Zone 23: Input 2 Panel + 9 Zone 23: Input 5
Zone 24: Input 6 Jumper Zone 24: Input 4 ZX8 Zone 24: Input 3 Zone 24: Input 6 Zone 25: Input 7 Panel + 17 Zone 25: Input 5 Jumper Zone 25: Input 4 Zone 25: Input 7 Zone 26: Input 8 Zone 26: Input 6 Panel + 17 Zone 26: Input 5 Zone 26: Input 8 Zone 27: N/A Zone 27: Input 7 Zone 27: Input 6 Zone 27: Input 1 Zone 28: N/A Zone 28: Input 8 Zone 28: Input 7 ZX8 Zone 28: Input 2 Zone 29: N/A Zone 29: N/A Zone 29: Input 8 Jumper Zone 29: Input 3 Zone 30: N/A Zone 30: N/A Zone 30: N/A Panel + 17Zone 30: Input 4 Zone 31: N/A Zone 31: N/A Zone 31: N/A Zone 31: Input 5 Zone 32: N/A Zone 32: N/A Zone 32: N/A Zone 32: Input 6
NOTE: If a zone is already programmed and you assign a device to the same zone, a wireless zone will overwrite a keypad/hardwire zone, and a keypad zone will overwrite a hardwire zone.

Zone Recognition (SP Series)

When expanding zones via a ZX8, up to 3 ZX8 modules can be added to the system and are identified by the ZX8 3-position jumpers +1, +9 and +17.
SP4000 No ATZ SP4000 ATZ SP5500 No ATZ SP5500 ATZ
Zone 1: Panel Input 1 Zone 1: Panel Input 1A Zone 1: Panel Input 1 Zone 1: Panel Input 1A
Panel Zone 2: Panel Input 2 Zone 2: Panel Input 2A Zone 2: Panel Input 2 Zone 2: Panel Input 2A
Zone 3: Panel Input 3 Zone 3: Panel Input 3A Panel Zone 3: Panel Input 3 Zone 3: Panel Input 3A Zone 4: Panel Input 4 Panel Zone 4: Panel Input 4A Zone 4: Panel Input 4 Zone 4: Panel Input 4A Zone 5: Input 1 Zone 5: Panel Input 1B Zone 5: Panel Input 5 Panel Zone 5: Panel Input 5A Zone 6: Input 2 Zone 6: Panel Input 2B Zone 6: Input 1 Zone 6: Panel Input 1B
ZX8 Zone 7: Input 3 Zone 7: Panel Input 3B Zone 7: Input 2 Zone 7: Panel Input 2B
Jumper Zone 8: Input 4 Zone 8: Panel Input 4B ZX8 Zone 8: Input 3 Zone 8: Panel Input 3B
Panel + 1 Zone 9: Input 5 Zone 9: Input 1 Jumper Zone 9: Input 4 Zone 9: Panel Input 4B
Zone 10: Input 6 Zone 10: Input 2 Panel + 1 Zone 10: Input 5 Zone 10: Panel Input 5B Zone 11: Input 7 ZX8 Zone 11: Input 3 Zone 11: Input 6 Zone 11:Input 1 Zone 12: Input 8 Jumper Zone 12: Input 4 Zone 12: Input 7 Zone 12: Input 2 Zone 13: Input 1 Panel + 1 Zone 13: Input 5 Zone 13: Input 8 ZX8 Zone 13:Input 3 Zone 14: Input 2 Zone 14: Input 6 Zone 14: Input 1 Jumper Zone 14: Input 4
ZX8 Zone 15: Input 3 Zone 15: Input 7 Zone 15: Input 2 Panel + 1 Zone 15: Input 5
Jumper Zone 16: Input 4 Zone 16: Input 8 ZX8 Zone 16: Input 3 Zone 16: Input 6
Panel + 9 Zone 17: Input 5 Zone 17: Input 1 Jumper Zone 17: Input 4 Zone 17: Input 7
12 Programming Guide
SP4000 No ATZ SP4000 ATZ SP5500 No ATZ SP5500 ATZ
Zone 18: Input 6 Zone 18: Input 2 Panel + 9 Zone 18: Input 5 Zone 18: Input 8 Zone 19: Input 7 ZX8 Zone 19: Input 3 Zone 19: Input 6 Zone 19: Input 1 Zone 20: Input 8 Jumper Zone 20: Input 4 Zone 20: Input 7 Zone 20: Input 2 Zone 21: Input 1 Panel + 9 Zone 21: Input 5 Zone 21: Input 8 ZX8 Zone 21:Input 3 Zone 22: Input 2 Zone 22: Input 6 Zone 22: Input 1 Jumper Zone 22: Input 4
ZX8 Zone 23: Input 3 Zone 23: Input 7 Zone 23: Input 2 Panel + 9 Zone 23: Input 5
Jumper Zone 24: Input 4 Zone 24: Input 8 ZX8 Zone 24: Input 3 Zone 24: Input 6
Panel + 17 Zone 25: Input 5 Zone 25: Input 1 Jumper Zone 25: Input 4 Zone 25: Input 7
Zone 26: Input 6 Zone 26: Input 2 Panel + 17 Zone 26: Input 5 Zone 26: Input 8 Zone 27: Input 7 ZX8 Zone 27: Input 3 Zone 27: Input 6 Zone 27: Input 1 Zone 28: Input 8 Jumper Zone 28: Input 4 Zone 28: Input 7 ZX8 Zone 28: Input 2 Zone 29: N/A Panel + 17 Zone 29: Input 5 Zone 29: Input 8 Jumper Zone 29: Input 3 Zone 30: N/A Zone 30: Input 6 Zone 30: N/A Panel + 17 Zone 30:Input 4 Zone 31: N/A Zone 31: Input 7 Zone 31: N/A Zone 31: Input 5 Zone 32: N/A Zone 32: Input 8 Zone 32: N/A Zone 32: Input 6
NOTE: If a zone is already programmed and you assign a device to the same zone, a wireless zone will overwrite a keypad/hardwire zone, and a keypad zone will overwrite a hardwire zone.
SP6000 No ATZ SP6000 ATZ SP7000 No ATZ SP7000 ATZ
Zone 1: Panel Input 1 Zone 1: Panel Input 1A Zone 1: Panel Input 1 Zone 1: Panel Input 1A Zone 2: Panel Input 2 Zone 2: Panel Input 2A Zone 2: Panel Input 2 Zone 2: Panel Input 2A
Panel Zone 3: Panel Input 3 Zone 3: Panel Input 3A Zone 3: Panel Input 3 Zone 3: Panel Input 3A
Zone 4: Panel Input 4 Zone 4: Panel Input 4A Zone 4: Panel Input 4 Zone 4: Panel Input 4A Zone 5: Panel Input 5 Zone 5: Panel Input 5A Zone 5: Panel Input 5 Zone 5: Panel Input 5A Zone 6: Panel Input 6 Zone 6: Panel Input 6A Zone 6: Panel Input 6 Zone 6: Panel Input 6A Zone 7: Panel Input 7 Zone 7: Panel Input 7A Zone 7: Panel Input 7 Zone 7: Panel Input 7A Zone 8: Panel Input 8 Panel Zone 8: Panel Input 8A Panel Zone 8: Panel Input 8 Zone 8: Panel Input 8A Zone 9: Input 1 Zone 9: Panel Input 1B Zone 9: Panel Input 9 Zone 9: Panel Input 9A Zone 10: Input 2 Zone 10: Panel Input 2B Zone 10: Panel Input 10 Zone 10: Panel Input 10A
ZX8 Zone 11: Input 3 Zone 11: Panel Input 3B Zone 11: Panel Input 11 Zone 11: Panel Input 11A
Jumper Zone 12: Input 4 Zone 12: Panel Input 4B Zone 12: Panel Input 12 Zone 12: Panel Input 12A
Panel + 1 Zone 13: Input 5 Zone 13: Panel Input 5B Zone 13: Panel Input 13 Zone 13: Panel Input 13A
Zone 14: Input 6 Zone 14: Panel Input 6B Zone 14: Panel Input 14 Zone 14: Panel Input 14A Zone 15: Input 7 Zone 15: Panel Input 7B Zone 15: Panel Input 15 Zone 15: Panel Input 15A Zone 16: Input 8 Zone 16: Panel Input 8B Zone 16: Panel Input 16 Panel Zone 16: Panel Input 16A Zone 17: Input 1 Zone 17: Input 1 Zone 17: Input 1 Zone 17: Panel Input 1B Zone 18: Input 2 Zone 18: Input 2 Zone 18: Input 2 Zone 18: Panel Input 2B
ZX8 Zone 19: Input 3 ZX8 Zone 19: Input 3 ZX8 Zone 19: Input 3 Zone 19: Panel Input 3B
Jumper Zone 20: Input 4 Jumper Zone 20: Input 4 Jumper Zone 20: Input 4 Zone 20: Panel Input 4B
Panel + 9 Zone 21: Input 5 Panel + 1 Zone 21: Input 5 Panel + 1 Zone 21: Input 5 Zone 21: Panel Input 5B
Zone 22: Input 6 Zone 22: Input 6 Zone 22: Input 6 Zone 22: Panel Input 6B Zone 23: Input 7 Zone 23: Input 7 Zone 23: Input 7 Zone 23: Panel Input 7B Zone 24: Input 8 Zone 24: Input 8 Zone 24: Input 8 Zone 24: Panel Input 8B Zone 25: Input 1 Zone 25: Input 1 Zone 25: Input 1 Zone 25: Panel Input 9B Zone 26: Input 2 Zone 26: Input 2 Zone 26: Input 2 Zone 26: Panel Input 10B
ZX8 Zone 27: Input 3 ZX8 Zone 27: Input 3 ZX8 Zone 27: Input 3 Zone 27: Panel Input 11B
Jumper Zone 28: Input 4 Jumper Zone 28: Input 4 Jumper Zone 28: Input 4 Zone 28: Panel Input 12B
Panel + 17 Zone 29: Input 5 Panel + 9 Zone 29: Input 5 Panel + 9 Zone 29: Input 5 Zone 29: Panel Input 13B
Zone 30: Input 6 Zone 30: Input 6 Zone 30: Input 6 Zone 30: Panel Input 14B Zone 31: Input 7 Zone 31: Input 7 Zone 31: Input 7 Zone 31: Panel Input 15B Zone 32: Input 8 Zone 32: Input 8 Zone 32: Input 8 Zone 32: Panel Input 16B
Magellan / Spectra SP 13

Zone Definitions

[1]- N/A [2]- N/A [3]- N/A
[4] OFF = Disarm
ON = Disarm only if Stay/Sleep armed [5] = Arm only [6] = Stay arming‡ [7] = Sleep arming‡ [8] = N/A ‡ Select only one. If all are off, keyswitch will regular arm.
[1] = Auto-zone Shutdown [2] = Bypassable Zone [3] = RF Zone Supervision
[4] [5]
OFF OFF Audible Alarm
OFF ON Pulsed Alarm ON OFF Silent Alarm ON ON Report Only [6] = Intellizone [7] = Delay alarm transmission
[8] = Force Zone
[1]- Partition 1†
[2]- Partition 2† [3]- Both partitions†
When using a K636 keypad, only
partition 1 is available.
Table 2: Partition Assignment Table 3: Zone Options Table 4: Keyswitch Options
NOTE: If a zone is already programmed and you assign a device to the same zone, a wireless zone will overwrite a keypad/hardwire zone, and a keypad zone will overwrite a hardwire zone.
To program zone definitions, zone partitions and assign options:
Step Action Details 1 [
ENTER] + [INSTALLER CODE]
(default: 0000 / 000000)
2 Enter 3-digit zone you wish to program
[001] to [032] 3 Enter a 2-digit zone definition 2 digits: 01 to 32 (see Zone Definitions table on page 14) 4 Assign Partition
[1], [2] or [3] 5 Select or deselect zone options using
buttons [1] to [8]
6 To save and proceed to the next zone,
ENTER]
press [
Zone Definitions Stay Arm Sleep Arm Fully Arm Zone Definitions
00 = Zone Disabled (default) - - - 11 = Instant Fire† 01 = Entry Delay 1 Entry Delay 1 Entry Delay 1 Entry Delay 1 12 = Delayed Fire† 02 = Entry Delay 2 Entry Delay 2 Entry Delay 2 Entry Delay 2 13 = Instant Fire Silent† 03 = Entry Delay 1 (Full Arm)
Not Armed Not Armed Entry Delay 1 14 = Delayed Fire Silent† 04 = Entry Delay2 (Full Arm) Not Armed Not Armed Entry Delay 2 15 = 24Hr. Buzzer 05 = Follow Follow* Follow* Follow* 16 = 24Hr. Burglary 06 = Follow (Sleep/Full Arm)
Not Armed Follow* Follow 17 = 24Hr. Hold-up 07 = Follow (Full Arm) Not Armed Not Armed Follow 18 = 24Hr. Gas 08 = Instant Instant* Instant* Instant* 19 = 24Hr. Heat 09 = Instant (Sleep/Full Arm)
Not Armed Instant* Instant 20 = 24Hr. Water 10 = Instant (Full Arm) Not Armed Not Armed Instant 21 = 24Hr. Freeze
33 = Instant No Pre-Alarm (Stay/Sleep)
Instant Instant Not Armed 23 = Follow No Pre-Alarm 34 = Instant No Pre-Alarm (Sleep) Not Armed Instant Not Armed 24 = Instant No Pre-Alarm 35 = Entry Delay 1 (Stay/Full) / Instant Entry Delay 1 Instant Entry Delay 1 25 = Keyswitch Maintain** 36 = Entry Delay 1 (Full Arm) / Instant
Instant Instant Entry Delay 1 26 = Keyswitch Momentary** * Flex-Instant = Zone will follow the delay at section [720], (default is 15 seconds / 0 = instant zone) ** On-board hardwire control panel zones only † ZX8 inputs do not support fire zones. For 2-wire smoke installations (not supported by SP4000 / SP5500), these definitions apply to Zone 1 Input only. Section [706], option [3] must be enabled. For 4-wire smoke installations, use any panel on-board zone input. †† This alarm will follow the Panic 1 option (section [702], option [1])
NOTE: For more zone options, see sections [705] and [706] on page 1 6.
[ARM] + [STAY] = flash. [MAINTENANCE CODE] may also be used.
[ARM] + [STAY] = on (see table on page 15)
By default, all zones are assigned to partition 1. (see Partition Assignment table on page 14). Zone Options - see Zone Options table on page 14.
ON = feature activated
OFF = feature deactivated Keyswitch Options - see Keyswitch Options table on page 14.
Table 1: Zone Definitions
22 = 24hr. Panic††
14 Programming Guide

Custom Zone Definitions

Create up to four custom zone definition templates* (custom zone definition templates [033] to [036] will overwrite zone defini tions 33 to 36, refer to the Zone Definitions table on page 14). Modifications can be made according to the Permitted Zone Definitions table below.
Section Disarm Stay Arm Sleep Arm Full Arm [033] Zone Definition Template 1 _____/_____ _____/_____ _____/_____ _____/_____ [034] Zone Definition Template 2 _____/_____ _____/_____ _____/_____ _____/_____ [035] Zone Definition Template 3 _____/_____ _____/_____ _____/_____ _____/_____ * This feature is not available [036] Zone Definition Template 4 _____/_____ _____/_____ _____/_____ _____/_____
on SP4000 systems.
Zone Definitions Disarm
00 = Zone Disabled 01 = Entry Delay 1 ­02 = Entry Delay 2 ­03 = Entry Delay 1 (Full Arm) --­04 = Entry Delay2 (Full Arm) --­05 = Follow ­06 = Follow (Sleep/Full Arm) -­07 = Follow (Full Arm) --­08 = Instant ­09 = Instant (Sleep/Full Arm) -­10 = Instant (Full Arm) --­11 = Instant Fire 12 = Delayed Fire

 
Stay Arm
Section Zone*
[001] Zone 1: ___________________ ____/____ _____ [002] Zone 2: ____________________ ____/____ _____ [003] Zone 3: ____________________ ____/____ _____ [004] Zone 4: ____________________ ____/____ _____ [005] Zone 5: ____________________ ____/____ _____ [006] Zone 6: ____________________ ____/____ _____ [007] Zone 7: ____________________ ____/____ _____ [008] Zone 8: ____________________ ____/____ _____ [009] Zone 9: ____________________ ____/____ _____ [010] Zone 10: ___________________ ____/____ _____ [011] Zone 11: ___________________ ____/____ _____ [012] Zone 12: ___________________ ____/____ _____ [013] Zone 13: ___________________ ____/____ _____ [014] Zone 14: ___________________ ____/____ _____ [015] Zone 15: ___________________ ____/____ _____ [016] Zone 16: ___________________ ____/____ _____ [017] Zone 17: ___________________ ____/____ _____ [018] Zone 18: ___________________ ____/____ _____ [019] Zone 19: ___________________ ____/____ _____ [020] Zone 20: ___________________ ____/____ _____ [021] Zone 21: ___________________ ____/____ _____ [022] Zone 22: ___________________ ____/____ _____ [023] Zone 23: ___________________ ____/____ _____ [024] Zone 24: ___________________ ____/____ _____ [025] Zone 25: ___________________ ____/____ _____ [026] Zone 26: ___________________ ____/____ _____ [027] Zone 27: ___________________ ____/____ _____ [028] Zone 28: ___________________ ____/____ _____ [029] Zone 29: ___________________ ____/____ _____ [030] Zone 30: ___________________ ____/____ _____ [031] Zone 31: ___________________ ____/____ _____ [032] Zone 32: ___________________ ____/____ _____
Table 5: Permitted Zone Definition s
Sleep
Arm
 


Zone
Definition
Fully


Zone Definitions Disarm
Arm
13 = Instant Fire Silent 14 = Delayed Fire Silent 15 = 24Hr. Buzzer 16 = 24Hr. Burglary
17 = 24Hr. Hold-up
18 = 24Hr. Gas 19 = 24Hr. Heat 20 = 24Hr. Water
21 = 24Hr. Freeze 22 = 24hr. Pan ic 23 = Follow No Pre-Alarm -
24 = Instant No Pre-Alarm -
Partition Zone Options
12345678 12345678 12345678 12345678 12345678 12345678 12345678 12345678 12345678 12345678 12345678 12345678 12345678 12345678 12345678 12345678 12345678 12345678 12345678 12345678 12345678 12345678 12345678 12345678 12345678 12345678 12345678 12345678 12345678 12345678 12345678 12345678
Stay Arm
Sleep
Arm
         
 
Section
Wireless SN or press tamper/ learn. To delete, enter 000000
[061] ____/____/____/____/____/____ [062] ____/____/____/____/____/____ [063] ____/____/____/____/____/____ [064] ____/____/____/____/____/____ [065] ____/____/____/____/____/____ [066] ____/____/____/____/____/____ [067] ____/____/____/____/____/____ [068] ____/____/____/____/____/____ [069] ____/____/____/____/____/____ [070] ____/____/____/____/____/____ [071] ____/____/____/____/____/____ [072] ____/____/____/____/____/____ [073] ____/____/____/____/____/____ [074] ____/____/____/____/____/____ [075] ____/____/____/____/____/____ [076] ____/____/____/____/____/____ [077] ____/____/____/____/____/____ [078] ____/____/____/____/____/____ [079] ____/____/____/____/____/____ [080] ____/____/____/____/____/____ [081] ____/____/____/____/____/____ [082] ____/____/____/____/____/____ [083] ____/____/____/____/____/____ [084] ____/____/____/____/____/____ [085] ____/____/____/____/____/____ [086] ____/____/____/____/____/____ [087] ____/____/____/____/____/____ [088] ____/____/____/____/____/____ [089] ____/____/____/____/____/____ [090] ____/____/____/____/____/____ [091] ____/____/____/____/____/____ [092] ____/____/____/____/____/____
Refer to the Installer Quick Menu on page 65. * See Zone Recognition tables on page 12.
Fully
Arm
Magellan / Spectra SP 15

Zone Labels

[3] [4] RF Zone/Hardwired Zone Tamper Recognition Options Keypad / Bus Module Tamper Recognition Options* OFF OFF Disabled Disabled
OFF ON Trouble only Trouble only ON OFF When disarmed: Trouble only
When armed: Follow zone’s alarm type
Trouble only
ON ON When disarmed: Audible ala rm
When armed: Follow zone’s alarm type
Audible alarm
* Tamper recognition of keypad / bus module only if section [700] option [7] is enabled.
[965] Reset Zone Labels Option OFF ON [1] Reset zone labels*
* Ensure all other options are deselected. Press [
ENTER] to reset the respective set of labels to default before exiting the section.
Disabled
Section Zone Label Section Zone Label [181] 1 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__ [197] 17 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__ [182] 2 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__ [198] 18 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__ [183] 3 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__ [199] 19 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__ [184] 4 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__ [200] 20 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__ [185] 5 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__ [201] 21 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__ [186] 6 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__ [202] 22 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__ [187] 7 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__ [203] 23 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__ [188] 8 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__ [204] 24 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__ [189] 9 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__ [205] 25 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__ [190] 10 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__ [206] 26 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__ [191] 11 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__ [207] 27 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__ [192] 12 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__ [208] 28 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__ [193] 13 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__ [209] 29 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__ [194] 14 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__ [210] 30 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__ [195] 15 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__ [211] 31 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__ [196] 16 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__ [212] 32 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__
NOTE: For label character tables, see LCD Keypad Labels (K32LC D) on page 47.
Enabled

Bus Module Labels

[965] Reset Bus Module Labels Option OFF ON [5] Reset bus module labels*
Disabled
Enabled
* Ensure all other options are deselected. Enable all options you want to reset to default. Press [ENTER] to reset the respective set of report codes to default before exiting the section.
Section Bus Label Section Bus Label [781] 1 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__ [789] 9 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__ [782] 2 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__ [790] 10 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__ [783] 3 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__ [791] 11 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__ [784] 4 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__ [792] 12 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__ [785] 5 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__ [793] 13 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__ [786] 6 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__ [794] 14 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__ [787] 7 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__ [795] 15 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__ [788] 8 __/__/__/__/__/__/__/__/__/__/__/__/__/__/__/__
NOTE: For label character tables, see LCD Keypad Labels (K32LC D) on page 47.

Zone Options

[705] ATZ Options Option OFF ON [1] ATZ zone doubling [2] ATZ wiring options [3] & [4] Tamper Recognition
Disabled Series
EnabledParallel
[5] Generate tamper on bypassed zone
16 Programming Guide
No
Yes
[6] & [7] Supervision Options
[6] [7] RF Zone Supervision Options (except SP4000) Keypad / Bus Module Supervision Options
OFF OFF Disabled Disabled OFF ON Trouble only Trouble only ON OFF When disarmed: Trouble only
When armed: Follow zone’s alarm type
Trouble only
ON ON When disarmed: audible ala rm
When armed: Follow zone’s alarm type
Trouble only
[8] Generate supervision on bypassed zone
No
Yes
[706] General Zone Options Option OFF ON [1] Check-in supervision time (except SP4000)
[2] EOL resistors* [3] Zone Input 1 becomes a 2-wire smoke input (except SP5500/SP4000) [4] ZX8 ID A (Panel + 1) Input 1 [5] ZX8 ID B (Panel + 9) Input 1 [6] ZX8 ID C (Panel + 17) Input 1
24 hours Disabled Disabled Zone input Zone input Zone input
80 minutes  EnabledEnabledTamper inputTamper inputTamper input
*This option applies to all hardwired zones (panel, keypad, ZX8)

Zone Timers (MG Series)

Note that When both ATZ and EOL are enabled, zone speed should not be set below 300ms.
Section MG5000 MG5050 Data Description (Default 060) [041] Zone 1 (Z1) (Z1) ____/____/____ (000 to 255) x 10ms Hardwire Zone 1 Speed [042] Zone 2 (Z2) (Z2) ____/____/__ __ (000 to 255) x 10ms Hardwire Zone 2 Speed [043] Zone 3 (Z1 ATZ) (Z3) ____/____/____ (000 to 255) x 10ms Hardwire Zone 3 Speed [044] Zone 4 (Z2 ATZ) (Z4) ____/____/____ (000 to 255) x 10ms Hardwire Zone 4 Speed [045] Zone 5 (Z5) ____/____/____ (000 to 255) x 10ms Hardwire Zone 5 Speed [046] Zone 6 (Z1 ATZ) ____/____/____ (000 to 255) x 10ms Hardwire Zone 6 Speed [047] Zone 7 (Z2 ATZ) ____/____/____ (000 to 255) x 10ms Hardwire Zone 7 Speed [048] Zone 8 (Z3 ATZ) ____/____/____ (000 to 255) x 10ms Hardwire Zone 8 Speed [049] Zone 9 (Z4 ATZ) ____/____/____ (000 to 255) x 10ms Hardwire Zone 9 Speed [050] Zone 10 (Z5 ATZ) ____/____/____ (000 to 255) x 10ms Hardwire Zone 10 Speed [051] Zone 11 ____/____/____ (000 to 255) x 10ms Hardwire Zone 11 Speed [052] Zone 12 ____/____/____ (000 to 255) x 10ms Hardwire Zone 12 Speed [053] Zone 13 ____/____/____ (000 to 255) x 10ms Hardwire Zone 13 Speed [054] Zone 14 ____/____/____ (000 to 255) x 10ms Hardwire Zone 14 Speed [055] Zone 15 ____/____/____ (000 to 255) x 10ms Hardwire Zone 15 Speed [056] Zone 16 ____/____/____ (000 to 255) x 10ms Hardwire Zone 16 Speed

Zone Timers (SP Series)

NOTE: When both ATZ and EOL are enabled, zone speed should not be set below 300ms.
Section SP4000 SP5500 SP6000 SP7000* Data Description (Default 060) [041] Zone 1 (Z1) (Z1) (Z1) (Z1) ____/____/____ (000 to 255) x 10ms Hardwire Zone 1 Speed [042] Zone 2 (Z2) (Z2) (Z2) (Z2) ____/____/____ (000 to 255) x 10ms Hardwire Zone 2 Speed [043] Zone 3 (Z3) (Z3) (Z3) (Z3) ____/____/____ (000 to 255) x 10ms Hardwire Zone 3 Speed [044] Zone 4 (Z4) (Z4) (Z4) (Z4) ____/____/____ (000 to 255) x 10ms Hardwire Zone 4 Speed [045] Zone 5 (Z1 ATZ) (Z5) (Z5) (Z5) ____/____/____ (000 to 255) x 10ms Hardwire Zone 5 Speed [046] Zone 6 (Z2 ATZ) (Z1 ATZ) (Z6) (Z6) ____/____/____ (000 to 255) x 10ms Hardwire Zon e 6 Speed [047] Zone 7 (Z3 ATZ) (Z2 ATZ) (Z7) (Z7) ____/____/____ (000 to 255) x 10ms Hardwire Zone 7 Speed [048] Zone 8 (Z4 ATZ) (Z3 ATZ) (Z8) (Z8) ____/____/____ (000 to 255) x 10ms Hardwire Zon e 8 Speed [049] Zone 9 (Z4 ATZ) (Z1 ATZ) (Z9) ____/____/____ (000 to 255) x 10ms Hardwire Zone 9 Speed [050] Zone 10 (Z5 ATZ) (Z2 ATZ) (Z10) ____/____/____ (000 to 255) x 10ms Hardwire Zone 10 Speed [051] Zone 11 (Z3 ATZ) (Z11) ____/____/____ (000 to 255) x 10ms Hardwire Zone 11 Speed [052] Zone 12 (Z4 ATZ) (Z12) ____/____/____ (000 to 255) x 10ms Hardwire Zone 12 Speed [053] Zone 13 (Z5 ATZ) (Z13) ____/____/____ (000 to 255) x 10ms Hardwire Zone 13 Speed [054] Zone 14 (Z6 ATZ) (Z14) ____/____/____ (000 to 255) x 10ms Hardwire Zone 14 Speed [055] Zone 15 (Z7 ATZ) (Z15) ____/____/____ (000 to 255) x 10ms Hardwire Zone 15 Speed [056] Zone 16 (Z8 ATZ) (Z16) ____/____/____ (000 to 255) x 10ms Hardwire Zone 16 Speed
* SP7000: For zones 17-32 (ATZ), the zone timer is set at 0.6 seconds.
Magellan / Spectra SP 17

Zone Report Codes (Default = FF)

[966] Clear Zone Report Codes Option OFF ON [1] Clear zone report codes*
* Ensure all other options are deselected. Press [ [967] Reset Zone Report Codes
Option OFF ON [1] Reset zone report codes to default* * Ensure all other options are deselected. Press [
Section Alarm [141] Zone 1: ___/___ ___/___ ___/___ ___/___ [157] Zone 17: ___/___ ___/___ ___/___ ___/___
[142] Zone 2: ___/___ ___/___ ___/___ ___/___ [158] Zone 18: ___/___ ___/___ __ _/___ ___/___ [143] Zone 3: ___/___ ___/___ ___/___ ___/___ [159] Zone 19: ___/___ ___/___ ___/___ ___/___ [144] Zone 4: ___/___ ___/___ ___/___ ___/___ [160] Zone 20: ___/___ ___/___ __ _/___ ___/___ [145] Zone 5: ___/___ ___/___ ___/___ ___/___ [161] Zone 21: ___/___ ___/___ ___/___ ___/___ [146] Zone 6: ___/___ ___/___ ___/___ ___/___ [162] Zone 22: ___/___ ___/___ __ _/___ ___/___ [147] Zone 7: ___/___ ___/___ ___/___ ___/___ [163] Zone 23: ___/___ ___/___ ___/___ ___/___ [148] Zone 8: ___/___ ___/___ ___/___ ___/___ [164] Zone 24: ___/___ ___/___ __ _/___ ___/___ [149] Zone 9: ___/___ ___/___ ___/___ ___/___ [165] Zone 25: ___/___ ___/___ ___/___ ___/___ [150] Zone 10: ___/___ ___/___ ___/___ ___/___ [166] Zone 26: ___/___ ___/___ ___/___ ___/___ [151] Zone 11: ___/___ ___/___ ___/___ ___/___ [167] Zone 27: ___/___ ___/___ ___/___ ___/___ [152] Zone 12: ___/___ ___/___ ___/___ ___/___ [168] Zone 28: ___/___ ___/___ ___/___ ___/___ [153] Zone 13: ___/___ ___/___ ___/___ ___/___ [169] Zone 29: ___/___ ___/___ ___/___ ___/___ [154] Zone 14: ___/___ ___/___ ___/___ ___/___ [170] Zone 30: ___/___ ___/___ ___/___ ___/___ [155] Zone 15: ___/___ ___/___ ___/___ ___/___ [171] Zone 31: ___/___ ___/___ ___/___ ___/___ [156] Zone 16: ___/___ ___/___ ___/___ ___/___ [172] Zone 32: ___/___ ___/___ ___/___ ___/___
Alarm Restore
ENTER] to clear the respective set of report codes before exiting the section.
ENTER] to reset the respective set of report codes before exiting the section.
Tamper
Tamper Restore
Disabled
Disabled
Section Alarm
Enabled
Enabled
Alarm Restore
Tamper
Tamper Restore

Keypad Programming

Keypad Zone Number Assignment

Step Action Details
1 [
2 3 [

Entry Point Zone Assignment (StayD)

Step Action Details
1 [ENTER] + [INSTALLER CODE]
2 Press and hold [OFF] (3sec) [ARM] + [STAY] = on. 3 [ZONE NUMBER] K35 / K32RF / K37 / K32 / K32LCD = 2 digits: 01 to 32.
4 [

Keypad Input/Output Configuration (K636 V2.0 and higher)

Step Action Details
1 [
2 Press and hold [ENTER] (3sec) [ARM] + [STAY] = on. 3Option [1] ON = Output switches to ground following system arming (Blue wire 150mA max.).
4Option [2] ON = Output N.C. OFF = Output N.O.
NOTE: When configuring as an output, you must first clear the keypad zone (if assigned).
ENTER] + [INSTALLER CODE]
(default: 0000 / 000000) Press and hold (3sec)
ZONE NUMBER] + [ENTER] K35 / K32 / K32LCD = 2 digits: 01 to 32.
(default: 0000 / 000000)
ENTER] Press [ENTER] to save and exit.
ENTER] + [INSTALLER CODE]
(default: 0000 / 000000)
[ARM] + [STAY] = flash. [MAINTENANCE CODE] may also be used.
[ARM] + [STAY] = on.
K636 / K10V/H = 1 digit: 1 to 0 (10). To erase a keypad zone number, press [
[ARM] + [STAY] = flash.
K636 / K10V/H = 1 digit: 1 to 0(10) (maximum 10 zones). The first zone you program will be the designated entry point and will flash. Up to three more path zones can be added; these zones will light up and stay lit.
[ARM] + [STAY] = flash.
OFF = Input (Keypad zone input).
CLEAR], then [ENTER].
18 Programming Guide
[3] [4]
OFF OFF Regular
OFF ON Sleep
ON OFF Stay
[701] Keypad Options 1 Option OFF ON [3] Confidential mode
[4] To exit confidential mode [5] Confidential mode timer [7] Display entry delay on LCD keypad (K32LCD) [8] Display exit delay on LCD keypad (K32LCD)
[703] Keypad Options 2 Option OFF ON [1] [2] One-touch stay arming*
[3] One-touch sleep arming* [4] One-touch bypass programming
* These options apply to the REM3 remote control only.
[704] Keypad Options 3 Option OFF ON [5] Bell squawk when arm/disarm with a keypad
[6] Beep on exit delay [7] No exit delay beeps and no bell squawk when stay/sleep arm
Keypad Locko ut
Section Data Description [716] ____/____/____ (000 to 255) minutes Keypad lockout delay (default 000) [717] ____/____/____ (000 to 255) attempt before locking Ke ypad lockout counter (default 000)
One-touch regular arming*
Disabled Enabled
Enter a code Press a key
2 minutes
DisabledDisabled
DisabledDisabledDisabledDisabled
Disabled Enabled  DisabledDisabled
5 seconds
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled

Partition Programming

NOTE: When using a K636 keypad, only partition 1 is available. To use both partitions, use any other compatible keypad.
[700] Partitioning Option OFF ON [1] Partitioning
Partition Labels
[965] Reset Partition Labels Option OFF ON [3] Reset partition labels*
* Ensure all other options are deselected. Press [
Section Part. Label [771] 1 ___/___/___/___/___/___/___/___/___/___/___/___/___/___/___/___ Section Part. [772] 2 ___/___/___/___/___/___/___/___/___/___/___/___/___/___/___/___
NOTE: For label character tables, see LCD Keypad Labels (K32LCD) on page 47.
[741] Partition 1 Options Option OFF ON [1] Auto-arm on time
[2] Auto-arm on no movement [3]&[4] Auto-arm arming mode
ENTER] to reset the respective set of labels to default before exiting the section.
Disabled Enabled
Enabled
Disabled
Disabled Enabled
Disabled Enabled
See Table  See Table
[5] Switch to stay arming if no entry delay zone is opened [6] Follow zones become entry delay 2 when delay zone is bypassed
Magellan / Spectra SP 19
Disabled Enabled
Disabled Enabled
[742] Partition 2 Options
[3] [4]
OFF OFF Regular
OFF ON Sleep
ON OFF Stay
Option [1]
[2]
[3]&[4]
Auto-arm on time Auto-arm on no movement Auto-arm arming mode
OFF ON
Disabled Enabled
Disabled Enabled  See Table  See Table
[5] Switch to stay arming if no entry delay zone is opened [6] Follow zones become entry delay 2 when delay zone is bypassed
Disabled Enabled
Disabled Enabled

Partition Timers

Refer to the Installer Quick Menu on page 65 for alternate entry/exit and bell cut-off timer programming.
Section Data Description [745] ____/____/____ (000 to 255) seconds Partition 1 exit delay (default 060) [746] ____/____/____ (000 to 255) seconds Partition 2 exit delay (default 060) [747] ____/____/____ (000 to 255) minutes Partition 1 bell cut-off (default 004) [748] ____/____/____ (000 to 255) minutes Partition 2 bell cut-off (default 004) [749] ____/____/____ (000 to 255) x 15 minutes Partition 1 no movement (default 000) [750] ____/____/____ (000 to 255) x 15 minutes Partition 2 no movement (default 000) [761] ____/____:____/___ HH: MM Auto-arm on time Partition 1 (default 00:00) [762] ____/____:____/____ HH: MM Auto-arm on time Partition 2 (default 00:00)

System Programming

[700] General System Options Option OFF ON [2] Battery charging (350mA or 700mA)*
[3] Audible trouble warning (except AC failure) [4] Audible trouble warning on AC failure [6] Exit delay termination [7] Tamper supervision on the bus module
* Does not apply to SP4000 systems
[702] Panic Options Option OFF ON [1] Panic 1
[2] Panic 2 [3] Panic 3 [4] Panic 1: Report only or audible alarm [5] Panic 2: Report only or audible alarm [6] Panic 3: Report only or audible alarm
350mA
Disabled Enabled
Disabled Enabled
Disabled Enabled
Disabled Enabled
Disabled Enabled
Disabled Enabled
Disabled Enabled
Report only Audible
Report only Audible
Report only Audible
700mA
[703] Arming/Disarming Options Option OFF ON [5] Restrict arming on battery failure
[6] Restrict arming on tamper failure (Zone + Bus Module
+ Wireless PGM)
[7] Restrict arming on wireless supervision trouble (Wireless zones +
Wireless PGM)*
* Does not apply to SP4000 systems.
[704] Arming/Disarming Options Option OFF ON [1] Regular arming switches to force arming
[2] Stay arming switches to stay force arming [3] Sleep arming switches to sleep force arming
20 Programming Guide
Disabled Enabled
Disabled Enabled
Disabled Enabled
Enabled
DisabledDisabledDisabled
Enabled
Enabled

System Timers

Section Data Description [710] ____/____/____ (000 to 255) seconds Entry delay 1 (default 045) [711] ____/____/____ (000 to 255) seconds Entry delay 2 (default 045) [712] ____/____/____ (000 to 015) Auto zone shutdown counter (default 005) [713] ____/____/____ (000 to 255) seconds Intellizone delay (default 048) [714] ____/____/____ (000 to 255) minutes Recycle alarm delay (default 000) [715] ____/____/____ (000 to 255) Recycle alarm counter (default 000) [718] ____/____/____ (000 to 255) seconds Remote panic disarm lock delay (default 000) [719] ____/____/____ (000 to 255) days Closing delinquency delay (default 000) [720] ____/____/____ (000 to 255) seconds Flex-Instant delay (default 015) [721] ____/____/____ (000 to 255) seconds For StayD: Re-arm delay (default 005)

Daylight Savings Programming

[730] Option OFF ON [1]
Section Data Description [731] ____/____ 00 to 99 Country code
00 = Mexico, St.Johns, Bahamas, Turks and Caicos 01 = Cuba 02 = Brazil 03 = Chile 04 = Falklands 05 = Paraguay 06 = European Union, UK, and Greenland 07 = Russia and most states of the former USSR 08 = Australia- South Australia, Victoria, Australian Capital Territory, New South Wales
Daylight savings (does not apply to SP4000 systems)
Country Code List
Disabled Enabled
09 = Lord Howe Island- Tasmania 10 = Chatham 11 = Tonga 12 = Iraq and Syria 13 = Israel 14 = Lebanon, Kirgizstan 15 = Palestine 16 = Egypt 17 = Namibia 18 = USA, Canada 19 = New Zealand

Customized Daylight Saving Programming

In addition to using the default Daylight Saving Time (DST) settings in section [731], you can also set a customized DST. Set section [732] for the DST starting period and [733] for the DST ending period. Both sections recognize 5 different entries of 2 digits each. All
entries must be assigned in this respective order:
Months 01 to 12 01 = January *If the Day value is set to (00), the Day is ignored and the DST change will respect Date 01 to 31 01 = First day of the month Day** 00 to 07 00 = Default*, 01 = Sunday Hours 00 to 23 00 = Midnight Minutes 00 only 00 = 60 minutes or 1 hour
If you have modified sections [732] and [733] but want to revert to a standard DST code, change all of the settings in [732] and [733] to (00).
Daylight Savings St a rt/End Period
Section Data Description [732] __/__/__/__/__/__/__/__/__/__/ Month-date-day-hours-minutes Daylight Savings Time Starting Period [733] __/__/__/__/__/__/__/__/__/__/ Month-date-day-hours-minutes Daylight Savings Time Ending Period
only the Date value. ** If the Day setting is set to a value other than 00 (e.g. 03 - Tuesday), the DST time
change will occur on the first 'Tuesday' following the programmed Date value.
Magellan / Spectra SP 21

Communication Programming

Auto-Test Report Transmission Options
[3] [4]
OFF OFF
Transmit the test report code every time the days programmed in section [840] have elapsed at the time programmed in section [850] (default).
OFF ON
When disarmed: Transmit test report code every time the ti me programmed in section [852] has elapsed. When armed: Transmit test report code every time the time programmed in section [851] has elapsed.
ON OFF
The control panel will transmit the test report code every hour on the minute value programmed in section [850] (the last two digits). Note that the first two digits of section [850] will be ignored. E.g. If 10:25 was programmed into section [850],
the test report code would be transmitted at the 25th minute of every hour, i.e. 11:25, 12:25, etc.
ON ON
The test report code will be transmitted when any of the conditions of the second and third options listed above (options [3] = OFF and [4] = ON / options [3] = ON and [4] = OFF) are met.
The Communication Programming section is divided into sections corresponding to each installation type. Begin by programming the General Communications Options, and then program for one or more of the following specific installation types:
Landline - see page24
GSM - (PCS Series GSM) - see page 25
Network - GPRS/IP (PCS Series GPRS / IP100) - see page 26
NOTE: For increased security, it is suggested that redundant communication methods be installed.
Security Features MG5000 MG5050 SP4000 SP5500 SP6000 SP7000 GPRS Reporting (PCS Series) 
GSM Reporting and SMS (PCS Series)  IP Reporting (IP100)  E-Mail/Monitoring (IP100)  On-board Zones 2 (4 ATZ) 5 (10 ATZ) 4 (8 ATZ) 5 (10 ATZ) 8 (16 ATZ) 16 (32 ATZ) On-board PGMs 24122+24 Patented dialer  Supports VDMP3 
Software Options
[900] WinLoad / BabyWare Options Option OFF ON [1] Call back
[2] Automatic event buffer transmission
Disabled Enabled
Disabled Enabled
[910] ___/___/___/___ Panel ID NOTE: For increased communication security, change [911] ___/___/___/___ PC password
the default Panel ID and PC password.
[915] ___/___/___/___/___/___/___/___/___/___/___/___/___/___/___/___/___/___/___/___/___/
PC telephone number (landline / GSM communication only)

General Communications Options

The following sections apply to all systems that report to a monitoring station.
[801] Dialer Options Option OFF ON [1] Report system disarming
Always
[2] Report zone restore [3] & [4]
Bell cutoff
After alarm
Zone closure
[5] Contact ID Override
Disabled
CID defaults / slow
format custom
[802] Event Call Direction Options 1 Option OFF ON [1] Call tel. #1 / monitoring rcvr. #1 for arm/disarm report codes
[2] Call tel. #2 / monitoring rcvr. #2 for arm/disarm report codes [3] Call pager for arm/disarm report codes [5] Call tel. #1 / monitoring rcvr. #1 for alarm/restore report codes [6] Call tel. #2 / monitoring rcvr. #2 for alarm/restore report codes [7] Call pager for alarm/restore report codes
22 Programming Guide
Enabled
DisabledDisabled
Disabled Enabled  DisabledDisabledDisabled
Enabled
Enabled
Enabled
Enabled
Loading...
+ 50 hidden pages