ZONE PROGRAMMING ................................................................................................................................. 6
What is an Expansion Input? ........................................................................................................................................6
How Do I Program the Zones? .....................................................................................................................................7
SYSTEM TIMERS ...........................................................................................................................................8
HOW DO I SET THE PROGRAMMABLE OUTPUTS? .............................................................................9
SYSTEM OPTIONS .......................................................................................................................................12
General Options ..........................................................................................................................................................12
Zone Options ..............................................................................................................................................................13
Event Call Direction ....................................................................................................................................................14
COMMUNICATION SETTINGS .................................................................................................................15
System Trouble Report Codes ...................................................................................................................................17
Programmable - Ademco Contact ID Report Code List ..............................................................................................18
All Codes - Ademco Contact ID Report Code List ......................................................................................................19
SYSTEM SETTINGS ....................................................................................................................................20
USER CODE OPTIONS ................................................................................................................................ 21
LIBERATOR WIRELESS BUS MODULE (SPC-319) ............................................................................. 22
Serial Number Display ................................................................................................................................................23
Signal Strength Display ..............................................................................................................................................24
Zone Assignment ........................................................................................................................................................25
Reset Zone Expansion Module ...................................................................................................................................26
REMOTE CONTROL PROGRAMMING ....................................................................................................27
User Assignment ........................................................................................................................................................27
Remote Control Assignment (Liberator Only) .............................................................................................................28
Remote Control Assignment (1755, 1755EX, 1758 and 1758EX Panels Only) .........................................................28
Reprogram ALL Modules ...........................................................................................................................................28
USER OPERATION .......................................................................................................................................29
Force Arming ..............................................................................................................................................................32
Programming Chime Zones .......................................................................................................................................34
Quick Function Keys ..................................................................................................................................................34
Single Zone Inputs .....................................................................................................................................................35
Double Zone Inputs (with ATZ option only) ................................................................................................................35
Connecting a Keyswitch .............................................................................................................................................36
Connecting Fire Circuits .............................................................................................................................................36
Connecting A Liberator Wireless Bus Module (SPC-319) ..........................................................................................37
Connecting A Zone Expansion Module (SPC-ZX8) ....................................................................................................37
Spectra 1725, 1725EX, 1728 and 1728EX PCB Layout ............................................................................................38
Spectra 1755, 1755EX, 1758 and 1758EX PCB Layout ............................................................................................39
Connecting Speakers to the Bell Output (Siren Driver Option Only) ..........................................................................39
Spectra Series
3
4
Programming Guide
HOW DO I PROGRAM THE SYSTEM?
The SpectraTM series control panels can be programmed using the WinLoad Software or by using any keypad connected to
the Spectra control panel. For information on the WinLoad Software, please refer to the Spectra Installation & ReferenceManual. To program the Spectra control panel using a keypad, you must enter the Programming Mode as shown below.
Once a control panel has been programmed, you can use the Paradox Memory Key to copy the contents from the
programmed control panel to one or more control panels (see page5).
Default Installer Code: 000000 (see section [281] on page20)
Default System Master Code: 123456 (see section [301] on page21)
To enter Programming Mode:
STEP 1: Press [ENTER]
STEP 2: Enter your [INSTALLERCODE]
STEP 3: Enter 3 digits of [SECTION] you wish to program
STEP 4: Enter required [DATA]
SINGLE DIGIT DATA ENTRY METHOD (Hexadecimal and Decimal)
Single Digit Data Entry is used in all sections except those specified in Multiple Feature Select ProgrammingMethod. After
entering the programming mode as described in the shaded box above, some sections will require that you enter Decimal
values from 000 to 255. Other sections will require that you enter Hexadecimal values from 0 to F. The required data will be
clearly indicated in this manual. When entering the final digit in a section, the control panel will automatically save and
advance to the next section. With the exception of sections 001 to 016, where after entering the first two digits, the control
panel will switch to Multiple Feature Select Programming.
Table 1: Decimal and Hexadecimal Programming Table
Value or ActionWhat Do I
Press?
10-Zone LED16-Zone LEDLCD
What Do I See?
Values 1 to 9[1] to [9][1] to [9][1] to [9][1] to [9]
A (hexa only)[0][0 (10)][10]A
B (hexa only)[STAY][STAY][11]B
C (hexa only)[BYP][BYP][12]C
D (hexa only)[MEM][MEM][13]D
E (hexa only)[TBL] / [TRBL][TBL][14]E
F (hexa only)[PG] / [FNC1][PG][15]F
Erase Current Digit[FORCE]Displays next digit or next section
Save Data (hexa only)[ENTER]Advances to the next section
MULTIPLE FEATURE SELECT PROGRAMMING METHOD
Sections: [001] to [016], [127] to [138], [302] to [348], [610], [650] to [651]
After entering the programming mode as described in the shaded box above, each option from [1] to [8] will represent a
specific feature or option. Press the key corresponding to the desired option and the corresponding light will illuminate or the
option number will appear in the LCD display. This means the option is on. Press the key again to extinguish the
corresponding light or remove the digit from the LCD display, thereby, turning off the option. Please note that pressing the
[FORCE] key will set all 8 options to “off”. Press the keys as many times as you need until all 8 options in the current section
are set. When the options are set, press the [ENTER] key to save and advance to the next section.
Spectra Series
5
DATA DISPLAY MODE (LED Keypads Only)
In the Data Display Mode you can view the programmed contents of each section one digit at a time. After entering the
desired 3-digit section (see step 3 of the “To Enter Programming Mode” box on the previous page), press the [ENTER] key to
access the Data Display Mode. This mode will not function with sections using the MultipleFeature Select ProgrammingMethod (see previous page).
PARADOX MEMORY KEY
Copy the programmed contents of one Spectra control panel into the Paradox Memory Key. Then copy the contents of the Paradox
Memory Key into as many Spectra control panels as you need. Each control panel is programmed in less than 3 seconds.
If you use the Memory Key to download to a Spectra 1755, 1755EX, 1758, or 1758EX, you will have to
reassign the remote controls (see page28).
Download to DESTINATION Control Panel
1)Remove AC and battery power from the control panel.
2)Insert the Memory Key onto the serial connector labeled “KEY” on the Spectra control panel to
which you wish to download the contents of the memory key to.
3) Reapply AC and battery power.
4)Enter installer programming mode, enter section [900], then press [ENTER] to acknowledge.
5)When the keypad emits a “confirmation beep”, remove the Memory Key.
Copy to Memory Key from SOURCE Control Panel
1)Remove AC and battery power from the control panel.
2)Insert Memory Key onto the serial connector labeled “KEY” on the Spectra control panel from which
you wish to copy. Make sure the write protect jumper of the Memory Key is on.
3)Reapply AC and battery power.
4)Enter installer programming mode, enter section [902], then press [ENTER] to acknowledge.
5)When the keypad emits a “confirmation beep”, remove the Memory Key. Remove the Memory Key’s jumper if you do not wish to accidentally overwrite its contents.
6
Programming Guide
ZONE PROGRAMMING
When programming zones please note that the Spectra control panels’ zone assignment is dependent on where
the detection devices in the system are connected (see Table 2 below).
Table 2: Zone Recognition Table
Device connected to
which input?
1725EX 1725
1755EX 1755
NO ATZ WITH ATZNO ATZ WITH ATZ
Control Panel Input 1 = Zone 1 Zone 1 & 4Zone 1 Zone 1 & 6
Control Panel Input 2 =Zone 2 Zone 2 & 5Zone 2 Zone 2 & 7
Control Panel Input 3 =Zone 3 Zone 3 & 6Zone 3 Zone 3 & 8
Control Panel Input 4 =N/A N/AZone 4 Zone 4 & 9
Control Panel Input 5 =N/A N/AZone 5 Zone 5 & 10
Keypad Zone 1 = Zone 4 Zone 7Zone 6 Zone 11
Keypad Zone 2 = Zone 5 Zone 8Zone 7 Zone 12
Expansion Input 1 = Zone 6 Zone 9Zone 8 Zone 13
Expansion Input 2 = Zone 7 Zone 10Zone 9 Zone 14
Expansion Input 3 = Zone 8 Zone 11Zone 10 Zone 15
Expansion Input 4 = Zone 9 Zone 12Zone 11 Zone 16
Expansion Input 5 = Zone 10 Zone 13Zone 12 N/A
Expansion Input 6 = Zone 11 Zone 14Zone 13 N/A
Expansion Input 7 = Zone 12 Zone 15Zone 14 N/A
Expansion Input 8 = Zone 13 Zone 16Zone 15 N/A
WHAT IS AN EXPANSION INPUT?
1728EX 1728
1758EX 1758
There are a total of eight expansion inputs available. Each hardwired input on a Zone Expansion Module or wireless
transmitter used by the LiberatorTM Wireless Bus Module can be assigned to an expansion input. The expansion inputs can
be used in any combination. For example, you can assign four wireless transmitters as well as 4 hardwire inputs to the
expansion inputs. Regardless of how many expansion modules are being used, the control panel cannot support morethan eight expansion inputs. The expansion module inputs are assigned as follows:
SPC-319 Liberator Wireless Bus Module
Wireless transmitters assigned to sections [601] to [608] of the control panel represent expansion inputs 1 to 8 respectively.
Refer to Wireless Transmitter Assignment on page22.
SPC-ZX4 and SPC-ZX8 Zone Expansion Module
Detection devices connected to input terminals Z1 to Z4 of the SPC-ZX4 module or Z1 to Z8 of the SPC-ZX8 module,
represent expansion inputs 1 to 8 respectively. Please note that the module’s inputs must be enabled in section [651] of the
control panel. Refer to Zone Assignment on page25.
Do not assign devices from different modules to the same expansion input. For example, do not assign a
wireless transmitter to section [601], then connect a detection device to input Z1 of the SPC-ZX8 and enable
option [1] in section [651].
Spectra Series
7
HOW DO I PROGRAM THE ZONES?
STEP 1: Press the [ENTER] key
STEP 2: Enter the [INSTALLERCODE] (Default: 000000)
STEP 3: Enter 3-digit [SECTION]
STEP 4: Enter one digit from the Zone Definition table
STEP 5: Enter one digit from the Partition Assignment table
STEP 6: Select one or more options from the Zone Options table
STEP 7: Press the [ENTER] key
Section #Description Zone Definition Partition Assignment Zone Options
Sub-Groups proceeded by
(Partition 1 only) cannot be
assigned to activate in partition 2.
10
Programming Guide
Event Group #Sub-Group #
06 = Arm/Disarm with Remote Control01-08 = Remote Controls 1 to 8
99 = Any Remote Control
07 = Button Pressed on Remote (see
button option “B” on page27)
08 = Button Pressed on Remote (see
button option “C” on page27)
09 = Button Pressed on Remote (see
button option “D” on page27)
10 = Bypass Programming01-48 = User Code Numbers 001 to 048
11 = User Activated PGM01-48 = User Code Numbers 001 to 048
12 = Zone with Delay Transmission
Option Enabled is Breached
13 = Arm with User Code01-48 = User Code Numbers 001 to 048
14 = Special Arm00 = Auto Arming (timed/no movement)
15 = Disarm with User Code01-48 = User Code Numbers 001 to 048
16 = Disarm After Alarm w/ User Code01-48 = User Code Numbers 001 to 048
17 = Cancel Alarm with User Code01-48 = User Code Numbers 001 to 048
18 = Special Disarm00 = Cancel Auto Arm (timed/no movement)
19 = Zone Bypassed on Arming01-16 = Zones 1 to 16
20 = Zone in Alarm01-16 = Zones 1 to 16
21 = Fire Alarm03 = Zone 3
22 = Zone Alarm Restore01-16 = Zones 1 to 16
23 = Fire Alarm Restore03 = Zone 3
01-08 = Remote Controls 1 to 8
99 = Any Remote Control
01-08 = Remote Controls 1 to 8
99 = Any Remote Control
01-08 = Remote Controls 1 to 8
99 = Any Remote Control
99 = Any User Code
99 = Any User Code
01-16 = Zones 1 to 16
99 = Any Zone
99 = Any User Code
01 = Late to Close (auto arming failed)
02 = No Movement Auto Arming
03 = Partial Arming (stay, force, instant, bypass)
04 = One-Touch Arming
05 = Arm with WinLoad Software
06 = Arm with Keyswitch
99 = Any Sub-Group
99 = Any User Code
99 = Any User Code
99 = Any User Code
01 = Disarm with WinLoad Software
02 = Disarm with Keyswitch
03 = Reserved for Future Use
04 = Disarm after alarm with WinLoad Software
05 = Disarm after alarm with Keyswitch
06 = Cancel Alarm with WinLoad Software
07 = Cancel Alarm with Keyswitch
99 = Any Sub-Group
99 = Any Zone
99 = Any Zone
99 = Any Zone
99 = Any Zone
99 = Any Zone
Spectra Series
11
Event Group #Sub-Group #
24 = Special Alarm00 = Emergency Panic
01 = Auxiliary Panic
02 = Fire Panic
03 = Recent Closing
04 = Auto Zone Shutdown
05 = Duress Alarm
99 = Any Sub-Group
25 = Auto Zone Shutdown01-16 = Zones 1 to 16
99 = Any Zone
26 = Zone Tamper01-16 = Zones 1 to 16
99 = Any Zone
27 = Zone Tamper Restore01-16 = Zones 1 to 16
99 = Any Zone
28 = System Trouble01 = AC Loss: only after Power Failure Delay has elapsed
[1]Partitioning l Disabled l Enabled
[2]Access Code Length l 6-digits l 4-digits
[3]Keypad Audible Trouble Warning l Disabled l Enabled
[4]Lock System Master Code l Disabled l Enabled
[5]Battery Charge Current l 350mA l 700mA
[6]User Code 048 is a Duress Code l Disabled l Enabled
[7]Alarm Relay follows (1755/EX & 1758/EX only) l Bell Output l Global PGM
[8]Normal State of PGM1 l Normally Closed (N.C.) l Normally Open
SECTION [128]: General Options
OptionOFFON
[1]Panic 1: Keys [1] & [3] l Disabled l Enabled
[2]Panic 2: Keys [4] & [6] l Disabled l Enabled
[3]Panic 3: Keys [7] & [9] l Disabled l Enabled
[4]Panic 1: Silent or Audible l Silent l Audible
[5]Panic 2: Silent or Audible l Silent l Audible
[6]Panic 3: Silent or Fire l Silent l Fire
[7]Keypad 1 Tamper Supervision l Disabled l Enabled
[8]Keypad 2 Tamper Supervision l Disabled l Enabled
SECTION [129]: General Options
OptionOFFON
[1]PGM2 Output Activation Option* l Steady l Pulse (flash)
[2]PGM2 Pulse Once Every 30sec. If System Armed* l Disabled l Enabled
[3]PGM2 Pulse On Arm, Twice On Disarm* l Disabled l Enabled
[4]SPC-ZX4/8 Zone Expansion Module Supervision l Disabled l Enabled
[5]SPC-319 Wireless Module Supervision l Disabled l Enabled
[6]SPC-319 Wireless Module Low Battery Super. l Disabled l Enabled
[7]Siren Driver* on Bell Output l Disabled l Enabled
[8]Normal State of PGM2 l Normally Closed (N.C.) l Normally Open
*1755, 1755EX, 1758 and 1758EX only
SECTION [130]: Arming/Disarming Options
OptionOFFON
[1]One-Touch Regular Arming l Disabled l Enabled
[2]One-Touch Stay Arming l Disabled l Enabled
[3]One-Touch Force Arming l Disabled l Enabled
[4]One-Touch Bypass Programming l Disabled l Enabled
[5]Restrict Arming on Battery Failure l Disabled l Enabled
[6]Restrict Arming on Tamper Trouble l Disabled l Enabled
[7]Bell Squawk on Arm/Disarm with Keypad l Disabled l Enabled
[8]Beep on Exit Delay l Disabled l Enabled
Spectra Series
13
Bold = Default Setting
SECTION [131]: Arming/Disarming Options
OptionOFFON
[1]Report Disarming l Always l Only after alarm
[2]Regular Arming Switches to Force Arming l Disabled l Enabled
[3]Bell Squawk on Arm/Disarm with Remote Control
(must be enabled for UL installations)
[4]No Exit Delay When Arming with a Remote Control l Disabled l Enabled
[5]No Exit Delay Beeps and No Bell Squawk When
Stay Arming
[6]Restrict Arming On Wireless Transmitter
Supervision Loss
[7]Generate Supervision Loss if Detected on
Bypassed Wireless Zone
[8]Normal State of Global PGM l Normally Closed (N.C.) l Normally Open
l Disabled l Enabled
l Disabled l Enabled
l Disabled l Enabled
l Yes l No
SECTION [132]: Zone Options
OptionOFFON
[1]&[2] l see table
l see table
l see table
l see table
[3]Generate Tamper if detected on Bypassed Zone l Yes l No
[4]EOL (end-of-line) Resistors l No EOL l Use EOL Resistors
[5]ATZ Zone Doubling (optional) l Disabled l Enabled
[6]Report Zone Restore l On Bell Cut-off l On Zone Closure
[7]&[8] l see table
l see table
l see table
l see table
SECTION [133]: Partition 1 Options
OptionOFFON
[1]Auto-Arm on Time l Disabled l Enabled
[2]Auto-Arm on No Movement l Disabled l Enabled
[3]Auto Arming = Regular or Stay l Regular Arming l Stay Arming
[4]Future Use l N/A l N/A
[5]Future Use l N/A l N/A
[6]Future Use l N/A l N/A
[7]Switch to Stay Arming if no entry delay is opened l Disabled l Enabled
[8]Future Use l N/A l N/A
14
Programming Guide
Bold = Default Setting
SECTION [134]: Partition 2 Options
OptionOFFON
[1]Auto-Arm on Time l Disabled l Enabled
[2]Auto-Arm on No Movement l Disabled l Enabled
[3]Auto Arming = Regular or Stay l Regular Arming l Stay Arming
[4]Future Use l N/A l N/A
[5]Future Use l N/A l N/A
[6]Future Use l N/A l N/A
[7]Switch to Stay Arming if no entry delay is opened l Disabled l Enabled
[8]Future Use l N/A l N/A
SECTION [135]: Dialer Options
OptionOFFON
[1]
[2]
[3]Reporting l Disabled l Enabled
[4]Dialing Method l Pulse Dialing l Tone (DTMF) Dialing
[5]Pulse Ratio l 1:2 (Europe) l 1:1.5 (North America)
[6]If armed, activate bell output on Com. Failure l Disabled l Enabled
[7]Future Use l N/A l N/A
[8]Future Use l N/A l N/A
l see table
l see table
l see table
l see table
SECTION [136]: Dialer Options
OptionOFFON
[1]Call Back l Disabled l Enabled
[2]Automatic Event Buffer Transmission l Disabled l Enabled
[3]Contact I.D. Report Codes l Programmable l All Codes (automatic)
[4]Alternate Dial l Disabled l Enabled
[5]If no dial tone is present l Continue after 4 sec. l Hang-up after 16 sec.
[6]Future Use l N/A l N/A
[7]Future Use l N/A l N/A
[8]Future Use l N/A l N/A
SECTION [137]: Event Call Direction
OptionOFFON
[1]Call Telephone #1 for Arming/Disarming Report Codes l Disabled l Enabled
[2]Call Telephone #2 for Arming/Disarming Report Codes l Disabled l Enabled
[3]Call Telephone #1 for Alarm/Restore Report Codes l Disabled l Enabled
[4]Call Telephone #2 for Alarm/Restore Report Codes l Disabled l Enabled
[5]Call Telephone #1 for Tamper/Restore Report Codes l Disabled l Enabled
[6]Call Telephone #2 for Tamper/Restore Report Codes l Disabled l Enabled
[7]Future Use l N/A l N/A
[8]Future Use l N/A l N/A
Spectra Series
15
SECTION [138]: Event Call Direction
OptionOFFON
[1]Call Telephone #1 for Trouble/Restore Report Codes l Disabled l Enabled
[2]Call Telephone #2 for Trouble/Restore Report Codes l Disabled l Enabled
[3]Call Telephone #1 for Special Report Codes l Disabled l Enabled
[4]Call Telephone #2 for Special Report Codes l Disabled l Enabled
[5]Future Use l N/A l N/A
[6]Future Use l N/A l N/A
[7]Future Use l N/A l N/A
[8]Future Use l N/A l N/A
BACKUPTELEPHONENUMBER (32-DIGITS, if less than 32 press [ENTER] to accept)
[STAY] = *[MEM] = Switch from pulse to tone dialing or vice versa[FORCE] = Delete current digit
[BYP] = #[TBL] or [TRBL] = 4-second pause[PG] or [FNC1] = Inserts Blank Space
Special Keys for Telephone Numbers
16
Programming Guide
REPORT CODES
[160]
:
__ /__ Access code 1
[165]
:
__ /__ Access code 21
[170]
:
__ /__ Access code 41
[174]
:
__ /__ Access code 1
[179]
:
__ /__ Access code 21
[184]
:
__ /__ Access code 41
Each section contains report codes for up to 4 events:
Ademco Slow, Silent Knight, SESCOA, Ademco Express and Pager Formats: Enter desired 1 or 2-digit hexa-value (0-F)
Ademco “All Codes” Format: The control panel automatically generates report codes from the “All Codes - Ademco Report Code List” on page19.
Ademco “Programmable” Format: Enter desired 2-digit hexa values from the “Programmable - Ademco Report Code List” on page18. Also Note that
entering FF will set the report code to the default Ademco Report Code.
__ /__ Test Report
__ /__ PC Call Back
__ /__ PC Access
[212]: __ /__ Installer In
__ /__ Installer Out
__ /__ N/A
__ /__ N/A
[213]: __ /__ TX Supervision Loss
__ /__ N/A
__ /__ N/A
18
Programming Guide
PROGRAMMABLE - ADEMCO CONTACT ID REPORT CODE LIST
If using the Ademco Contact ID Programmable code format, enter the 2-digit hexadecimal value from the table below (Prog.
Value) into sections [160] to [213] to program the desired report codes. To enter a 0 value press the [FORCE] key.
CID#Reporting Prog.
CodeValue
MEDICAL ALARMS - 100204Low Water Level2F403Automatic O/C5D
100Medical Alarm01205Pump Activated30404Late to O/C5E
101Pendant Transmitter02206Pump Failure31405Deferred5F
102Fail to Report In03SYSTEM TROUBLES - 300 & 310406Cancel60
FIRE ALARMS - 110300System Trouble32407Remote Arm/Disarm61
200Fire Supervisory2BOPEN/CLOSE - 400628Program Mode Exit86
201Low Water Pressure2C400Open/Close5A631Exception Schedule Change 87
202Low CO22D401O/C by User5B
203Gate Valve Sensor2E402Group O/C5C
CID#Reporting Prog.
CodeValue
CID#Reporting Prog.
CodeValue
Spectra Series
19
ALL CODES - ADEMCO CONTACT ID REPORT CODE LIST
System EventDefault Contact ID Report Code
when option [3] is on in section [136]
Arming with Master Code (##)3 4A1 - Close by user
Arming with User Code (##)3 4A1 - Close by user
Arming with Keyswitch (##)3 4A9 - Keyswitch Close
Auto Arming3 4A3 - Automatic Close
Arm with PC software3 4A7 - Remote arm/disarm
Late To Close3 4A4 - Late to Close
No Movement 3 4A4 - Late to Close
Partial arming1 574 - Group bypass
Quick arming 3 408 - Quick arm
Disarm with Master Code (##)1 4A1 - Open by user
Disarm with User Code (##)1 4A1 - Open by user
Disarm with Keyswitch (##)1 4A9 - Keyswitch Open
Disarm after alarm with Master Code (##)1 4A1 - Open by user
Disarm after alarm with User Code (##)1 4A1 - Open by user
Disarm after alarm with Keyswitch (##)1 4A9 - Keyswitch Open
Auto Arming Cancellation1 4A5 - Deferred Open/Close
Disarm with PC software1 4A7 - Remote arm/disarm
Disarm after an alarm with PC software1 4A7 - Remote arm/disarm
Zone Bypassed (##)1 57A - Zone bypass
Zone alarm (##)1 13A - Burglary Alarm
Fire alarm (##)1 11A - Fire alarm
Zone alarm restore (##)3 13A - Burglary Alarm Restore
Fire alarm restore (##)3 11A - Fire alarm Restore
Panic 1 - Emergency 1 12A - Panic alarm
Panic 2 - Medical 1 1AA - Medical alarm
Panic 3 - Fire 1 115 - Pull Station
Recent closing3 4AA - Open/Close
Global zone shutdown1 574 - Group bypass
Duress alarm1 121 - Duress
Zone shutdown (##)1 57A - Zone bypass
Zone tampered (##)1 144 - Sensor tamper
Zone tamper restore (##)3 144 - Sensor tamper restore
AC Failure1 3A1 - AC loss
Battery Failure1 3A9 - Battery test failure
Auxiliary supply trouble1 3AA - System trouble
Bell output current limit1 321 - Bell 1
Bell absent1 321 - Bell 1
20
Programming Guide
System EventDefault Contact ID Report Code
when option [3] is on in section [136]
Clock lost1 626 - Time/Date inaccurate
Fire loop trouble1 373 - Fire trouble
Wireless Transmitter Low Battery1 384 - RF xmtr. low battery
Wireless Transmitter Supervision Loss1 381 - Loss of super. - RF
Module fault1 333 - Expansion module failure
Printer fault1 336 - Local printer failure
Fail to communicate with central station1 354 - Fail to communicate
TLM trouble restore3 351 - Telco 1 fault restore
AC Failure restore3 3A1 - AC loss restore
Battery Failure restore3 3A9 - Battery test restore
Auxiliary supply trouble restore3 3AA - System trouble restore
Bell output current limit restore3 321 - Bell 1 restore
Bell absent restore3 321 - Bell 1 restore
Clock programmed3 626 - Time/Date Reset
Fire loop trouble restore3 373 - Fire trouble restore
Wireless Transmitter Low Battery3 384 - RF xmtr. low battery
Wireless Transmitter Supervision Loss3 381 - Loss of super. - RF
Module fault restore3 333 - Expansion module failure restore
Printer fault restore3 336 - Local printer failure restore
Fail to communicate with central station3 354 - Fail to communicate restore
Cold Start1 3A8 - System shutdown
Test Report engaged1 6A2 - Periodic test report
PC software communication finished1 412 - Successful - download access
Installer on site1 627 - Program mode Entry
Installer programming finished1 628 - Program mode Exit
SYSTEM SETTINGS
Section #Description
[280] __/__:__/__SYSTEMREALTIMECLOCK (HH:MM)
[281] __/__/__/__/__/__INSTALLERCODEDefault: 000000
[282] __/__/__INSTALLERCODELOCK Default: 000 (147 to lock, 000 to unlock)
IMPORTANT NOTE: If the Access Code Length is changed from four digits to six digits when access codes have
already been programmed, the control panel will automatically add the last 2 digits by using the first 2 digits.
For example, if the access code is 1234 and you switch to 6 digits, the code will become 123412. Be sure to
verify the access codes after switching from 4-digit access codes to 6-digit codes. When switching from six digits to four digits, the control panel will simply remove the final two digits of the access code. For example,
123456 will become 1234.
Spectra Series
21
USER CODE OPTIONS
Section #
User Code Options (on/off)
Section #
User Code Options (on/off)
[301]__/__/__/__/__/__SYSTEMMASTERCODE (see note on preceeding page) Default: 123456
[1] on = Partition 1 Access
[2] on = Partition 2 Access
[3] on = Bypass Programming
[4] on = Stay Arming
The following options and features are only available to program when a Liberator Wireless Bus Module has
been connected to the Spectra control panel’s communication bus as shown on page 37. The Liberator Wireless
Bus Module (SPC-319) allows you to add up to eight fully programmable remote controls and up to eight Liberator
Wireless Detectors and Contact Switches (door contacts). The SPC-319 also provides one programmable 5A
relay (PGM). A second 5A programmable relay (PGM) is available as an option.
The Liberator Wireless Bus Module does not function with the Spectra 1755, 1755EX, 1758 and 1758EX
control panels. Do not connect more than one Liberator Module.
WIRELESS TRANSMITTER ASSIGNMENT (Liberator Only)
The serial number can be located on the inside of the transmitter or you can use the Serial Number Display (see page23).
Use the Liberator Wireless Motion Detectors (Model# 9002) and the Liberator Contact Switches (Model# 9020).
Avoid assigning devices from different modules to the same Expansion Input. For example, do not assign a wireless transmitter to section [601], then connect a detection device to input 1 of a hardwire module and enable option [1] in section
[651]. This would mean both devices have been assigned to the same Expansion Input.
WIRELESS MODULE OPTIONS (Liberator Only)
Bold = Default Setting
SECTION [610]: General Options
OptionOFFON
[1]Wireless Transmitter Supervision l Disabled l Enabled
[2]Supervision Timer Setting
(must be same as the transmitter’s jumper setting)
[3]PGM1 on Liberator follows Global PGM
programmed in sections [124] & [125]
[4]PGM2 on Liberator follows Global PGM
programmed in sections [124] & [125]
[5]Future Use l N/A l N/A
[6]Future Use l N/A l N/A
[7]Future Use l N/A l N/A
[8]Future Use l N/A l N/A
l Low = Every 12 hours l High = Every 12 minutes
l Disabled l Enabled
l Disabled l Enabled
Spectra Series
23
Section #Decimal Value (000-255)DescriptionDefault Value
The system will ignore sections [620] and [621] if PGM1 has been programmed to follow the Global PGM.
The system will ignore sections [622] and [623] if PGM2 has been programmed to follow the Global PGM.
Refer to options [3] and [4] in section [610] on page22.
02 = Remote Control #2 - Section [722]/[732]
03 = Remote Control #3 - Section [723]/[733]
04 = Remote Control #4 - Section [724]/[734]
05 = Remote Control #5 - Section [725]/[735]
06 = Remote Control #6 - Section [726]/[736]
07 = Remote Control #7 - Section [727]/[737]
08 = Remote Control #8 - Section [728]/[738]
99 = Any remote control
02 = Tamper Closed
99 = Tamper opened or closed
Not used; enter 00
01 = Button A
02 = Button B
03 = Button C
04 = Button D
05 = Button A & B
06 = Button C & D
07 = Button A & C
08 = Button B & D
Not used; enter 00
SERIAL NUMBER DISPLAY
[630] STEP 1: Enter section [630]
STEP 2: Press the tamper switch of the desired wireless transmitter or press any two buttons on the desired remote
control. The keypad will emit a confirmation beep.
STEP 3: On LED keypads the digits will appear one at a time by illuminating the corresponding light. To view the next
digit press the [ENTER] key. On LCD keypads the entire serial number will appear on the screen.
STEP 4: Return to STEP 2 to continue or press [CLEAR] to exit the Serial Number Display.
24
Programming Guide
SIGNAL STRENGTH DISPLAY
Enter the section (see next page) corresponding to the desired Expansion Input, then activate the transmitter by opening/
closing the zone or by pressing the tamper switch. NOTE: after entering the section, ignore the first reading as it won’t be
accurate. LED Keypad: Lights numbered from one to eight will illuminate. An average reading of 3 and up is acceptable.
LCD Keypad: One to eight characters will appear on the screen. An average reading of 3 characters and up is acceptable.
Section #Description
[631]Display Signal Strength of Expansion Input 1 - Section [601]
[632]Display Signal Strength of Expansion Input 2 - Section [602]
[633]Display Signal Strength of Expansion Input 3 - Section [603]
[634]Display Signal Strength of Expansion Input 4 - Section [604]
[635]Display Signal Strength of Expansion Input 5 - Section [605]
[636]Display Signal Strength of Expansion Input 6 - Section [606]
[637]Display Signal Strength of Expansion Input 7 - Section [607]
[638]Display Signal Strength of Expansion Input 8 - Section [608]
LIBERATOR MODULE (SPC-319) RESET
[640]PRESS [ENTER] TOCONFIRM. WILLRESETTHELIBERATORMODULE’SSECTIONS [601] TO [624] TODEFAULTVALUES.
Spectra Series
25
ZONE EXPANSION MODULES (SPC-ZX4/8)
The following options and features are only available to program when a Zone Expansion Bus Module has been
connected to the Spectra control panel’s communication bus as shown on page37. The Zone Expansion Modules
provide you with up to 4 (SPC-ZX4) or up to eight (SPC-ZX8) additional hardwired inputs and one normally open
50mA PGM output (on SPC-ZX8 only).
Do not connect more than one Zone Expansion Module.
Bold = Default Setting
SECTION [650]: Options
OptionOFFON
[1]EOL (end-of-line) Resistors for hardwire modules l No EOL l Use EOL Resistors
[2]Zone Expansion Module Tamper Recognition l Disabled l Z1 becomes tamper input
[3]PGM1 on Zone Expansion Module follows Global
PGM programmed in sections [124] & [125]
[4]Future Use l N/A l N/A
[5]Future Use l N/A l N/A
[6]Future Use l N/A l N/A
[7]Future Use l N/A l N/A
[8]Future Use l N/A l N/A
l Disabled l Enabled
SECTION [651]: Zone Assignment
OptionOFFON
[1] l Disabled l Z1 = Expan. Input 1 =
[2] l Disabled l Z2 = Expan. Input 2 =
[3] l Disabled l Z3 = Expan. Input 3 =
[4] l Disabled l Z4 = Expan. Input 4 =
[5] l Disabled l Z5 = Expan. Input 5 =
[6] l Disabled l Z6 = Expan. Input 6 =
[7] l Disabled l Z7 = Expan. Input 7 =
[8] l Disabled l Z8 = Expan. Input 8 =
WARNING!
Avoid assigning devices from different modules to the same Expansion Input. For example, do not assign a wireless transmitter to section [601], then connect a detection device to Z1 of a hardwire module and enable option [1] in section [651].
This would mean both devices have been assigned to the same Expansion Input.
PGM TIMER (Zone Module SPC-ZX8 Only)
[655]___/___/___seconds (000 = follow stop event)PGM1TIMER (HARDWIRE)5 sec. (default)
26
Programming Guide
PGM PROGRAMMING (Zone Module SPC-ZX8 Only)
The system will ignore sections [656] and [657] if PGM1 has been programmed to follow the Global PGM.
Refer to option [3] in section [650] on page25.
Please note that the User Code
assigned to the remote control
(sections [701] to [708]) must have the
same User Options enabled. For
example, if you enable the Force
Arming button option you must enable
the appropriate Force Arming user
option. Also, if you enable any of the
Panic button options, you must enable
the Panic options in the control panel.
NOTE: Use the Serial Number Display (see page23) to find out the serial number of a remote control. To delete
a remote control, enter the desired section then enter a value of 000000.
REMOTE CONTROL ASSIGNMENT (1755, 1755EX, 1758 and 1758EX Panels Only)
NOTE: If you hear rejection beep, an error has occurred or the remote control has already been assigned. To
delete a remote control, enter the desired section then press the [FORCE] key.
The Spectra system continuously monitors fourteen possible trouble conditions. When a trouble condition occurs, the [TBL]
button or [TRBL] indicator will illuminate on the LED keypads or “Trouble” will appear on the LCD keypad’s screen. Press the
[TBL] or [TRBL] button to switch to the Trouble Display. The [TBL] button or [TRBL] indicator will flash and lights corresponding
to an existing trouble condition will illuminate on the LED keypads (see below) or the appropriate trouble message will appear
on the LCD keypad. Press the [CLEAR] button to exit the Trouble Display.
Please note that the keypad can be programmed to emit a “BEEP” every 5 seconds whenever a new trouble condition has
occurred. Pressing the [TBL] or [TRBL] button will stop the “beeping”.
LED #DescriptionDetails
[1]No/Low Battery FailureThe control panel performs a dynamic battery test under load every 60 seconds. This trou-
ble indicates that the back-up battery is disconnected or that the battery should be
replaced, as it will not provide adequate back-up current in case of AC loss. This trouble
will also appear when the control panel is running on battery power and the battery voltage
has dropped to 10.5 volts or lower. This means the battery must be recharged or replaced.
[2]Wireless Transmitter
Low Battery
[3]Power FailureUpon power failure, the AC LED on all keypads will turn off. The control panel can trans-
[4]Bell or PGM2 DisconnectedThere is no bell or siren connected to the bell output terminals of the control panel or there
[5]Maximum Bell CurrentThe BELL output uses a fuseless circuit and will automatically shut down if the current
[6]Maximum Auxiliary CurrentThe auxiliary output uses a fuseless circuit to protect the power supply against current
[7]Communicator Report FailThe control panel has failed all attempts to communicate with the central monitoring station.
[8]Timer LossThe control panel’s internal clock must be re-programmed. To re-program the timer press the
[9]Tamper/Zone Wiring FailIf the Tamper Recognition options are enabled, this trouble indicates a wiring problem on
[10]Telephone Line MonitoringIf the Telephone Line Monitoring (TLM) feature is enabled (see section [135]), this trouble
[STAY]
OR [11]
[FORCE]
or [16]
[BYP] OR
[12]
[MEM] OR
[13]
Fire Loop TroubleDenotes a wiring problem on zone 3, if defined as a Fire Zone.
Keypad FaultIf the keypad is no longer communicating with the control panel, the [TBL] or [TRBL] will
Module LossA Liberator or zone module is no longer communicating with the control panel.
Wireless Transmitter
Supervision Loss
This means the battery voltage of a Liberator wireless transmitter has dropped to 6.5V or
less. Also, the yellow LED on the transmitter can flash to indicate this trouble. The battery should be replaced.
mit the report code programmed in section [205]. This report code can be delayed by
programming a Power Failure Report Delay in section [086]. The AC LED turns back on
as soon as power is restored.
is no device connected to the PGM2 terminals (1755, 1755EX, 1758 and 1758EX only). If
you are not using the BELL or PGM2 terminals, the trouble indicator will always be on. To
avoid this, connect a 1KΩ resistor across the bell or PGM2 output.
exceeds 3A with a 1725, 1725EX, 1728, or 1728EX or 2.5A with a 1755, 1755EX, 1758,
or 1758EX . After opening the short or reducing the load, the bell current is restored upon
the following alarm generation. This trouble indicator will only appear when a condition has
occured that would activate the bell output (e.g. during an alarm).
overload and automatically shuts down if the current exceeds 1.1A. After opening the
short or reducing the load, the panel will restore power to the auxiliary output.
[8] key and enter the current time using the 24-hour clock (i.e. 8:30PM = 20:30).
one or more zones or that the cover has been removed on one or more wireless transmitters. In order to provide line short recognition the zone connections must have EOL resistors. If you press the [9] key, the keypad will display which zones are in trouble.
indicates that the control panel has not detected the presence of a telephone line for 30 sec.
flash, the [FORCE] key will illuminate (the LCD keypad displays “Keypad Fault”) and the
keypad will emit four consecutive beeps at 5-second intervals. Press any key on the keypad to terminate the “beeping” sequence. When communication has been restored, the
system will revert to previous status.
One or more wireless transmitters are no longer communicating with the receiver. If you
press the [MEM] key, the keypad will display which zones are in trouble.
30
Programming Guide
PARTITIONING
The Spectra system is equipped with a partitioning feature which can divide the alarm system into two distinct areas
identified as Partition 1 and Partition 2. Partitioning can be used in installations where shared security systems are more
practical, such as an office/warehouse building. When partitioned, each zone, each User Code and some of the system's
features can be assigned to either Partition 1, Partition 2, or both partitions. If the system is not partitioned, all User Codes
and features will be recognized as belonging to partition 1.
How does a partitioned system work?
•Users can only arm/disarm partitions to which they have been
assigned.
•Only zones assigned to Partition 1 will arm/disarm when Partition 1 is
armed or disarmed.
•Only zones assigned to Partition 2 will arm/disarm when Partition 2 is
armed or disarmed.
•Zones assigned to both partitions will arm when both partitions are
armed and will disarm when at least one partition disarms.
•Some of the system’s features can be programmed separately for
each partition.
PROGRAMMING ACCESS CODES
Access Codes are personal identification numbers that allow users to enter certain programming modes, arm or disarm the
alarm system as well as activate or deactivate PGMs. The Spectra security system supports the following:
System Master Codecan arm or disarm any partition using any arming method and can create, modify or delete any User
Access Code. Only the System Master Code can modify or delete User Access Codes assigned to both partitions.
Master Code 1 is permanently assigned to partition 1 and can be used to create, modify or delete User Access Codes that
are assigned to partition 1.
Master Code 2 is permanently assigned to partition 2 (except when partitioning is disabled, Master Code 2 will be assigned
to partition 1) and can be used to create, modify or delete User Access Codes that are assigned to the same partition.
45 User Access Codes (including 1 Duress code)
How Do I Program Access Codes?
1) Press [ENTER]
2) Key in the [SYSTEMMASTERCODE] or [MASTERCODE]
3) Key in 3-digit [SECTION] (see Table below)
4) Key in new 4 or 6-digit [ACCESSCODE]
[ENTER] flashes. Return to step 3
How Do I Delete Access Codes?
1) Repeat steps 1 to 3 (see above)
2) Press the [FORCE] button once for each digit in the access code (4 or
6 times) until the keypad emits a "CONFIRMATIONBEEP"
SectionUser Codes
[001]User Code 001 = System Master Code
[002]User Code 002 = Master Code 1
[003]User Code 003 = Master Code 2
[004] to [047]User Code 004 to User Code 047
[048]User Code 048 or Duress Code
Spectra Series
31
DISARMING & DEACTIVATING AN ALARM
To disarm an already armed system or to deactivate an alarm simply key in a valid access code. Program a designated entry/exit
point, such as the front door or the garage door with an Entry Delay Timer. When these entry/exit point are opened (breached), it
will set off a timer. The system will not generate an alarm until this timer elapses, giving users enough time to enter the premises
and disarm the system. Any user can disarm the system, except users have been assigned the Arm Only Option.
How Do I Disarm the System or Deactivate an Alarm?
1) Key in your [ACCESSCODE]
The arm or alarm indication will turn off and the keypad will emit a “CON-
FIRMATIONBEEP”.
IF YOU HAVE ACCESS TO BOTH PARTITIONS:
2) Press the button corresponding to the partition you wish to Disarm or
to Disarm both partitions, press the [1] key then after the
confirmation beep press the [2] key.
REGULAR ARMING
This method, commonly used for day-to-day arming, will arm all the zones in the selected partition.
How Do I Regular Arm?
1) Green “READY” indicator must be illuminated. Unless the system is
partitioned, in which case all zones in the desired partition must be closed.
2) Key in a valid [ACCESSCODE]
IF YOU HAVE ACCESS TO BOTH PARTITIONS:
3) Press the button corresponding to the partition you wish to Arm. To
Arm both partitions, press the [1] key then after the confirmation
beep press the [2] key.
If you make a mistake, the keypad will emit a "REJECTIONBEEP". When you have correctly armed the system, the appropriate
"ARM" indication will turn on and the Exit Delay will be initiated. Please note that Regular Arming can also be activated using
Auto-Arming, a Keyswitch or using One-Touch Arming.
STAY ARMING
This method allows users to remain in the protected area while partially arming the system. For example, when going to sleep
at night, entry/exit points like doors and windows can be armed while other zones like motion detectors remain deactivated.
Please note that Fire Zones can not be bypassed.
How Do I Stay Arm?
1) All zones in the desired partition (except Stay Zones) must be closed.
2) Press the [STAY] button
3) Key in a valid [ACCESSCODE]
IF YOU HAVE ACCESS TO BOTH PARTITIONS:
4) Press the button corresponding to the partition you wish to Stay Arm.
To StayArm both partitions, press the [1] key then after the
confirmation beep press the [2] key.
If you make a mistake, the keypad will emit a "REJECTIONBEEP". When you have correctly Stay Armed the system, the appropriate
“ARM” indication will appear and the Exit Delay will be initiated. Stay Arming can also be activated using Auto-Arming, KeyswitchArming or using One-Touch Arming. Also note that the User Code must have the Stay Arming Option enabled.
32
Programming Guide
INSTANT ARMING
After Stay Armingthe system and during its Exit Delay, press and hold the [STAY] button for 3 seconds. You should hear a
"CONFIRMATIONBEEP". This will switch all armed zones to Instant zones.
If you have access to both partitions:
To Instant Arm one partition, press [STAY] + [ACCESSCODE] + [SELECTPARTITION] + [CLEAR] + press & hold [STAY]
To Instant Arm both partitions, press [STAY] + [ACCESSCODE] + [1] + [2] + press & hold [STAY]
FORCE ARMING
Force Arming allows users to rapidly arm the system, without having to wait for all zones in the system to be closed. Force Arming
is commonly used when a motion detector is protecting the area occupied by a keypad. Therefore, when arming the system, if the
motion detector is set as a Force Zone, the control panel will ignore the zone and allow users to arm the system even if the zone
is open. Any open Force Zones at the time of arming will be considered "deactivated" by the control panel. If during this period a
"deactivated" zone is closed, the control panel will revert that zone to "active" status, hence, will generate an alarm if breached.
How Do I Force Arm?
1) All zones in the desired partition (except Force Zones) must be closed.
2) Press the [FORCE] button
3) Key in a valid [ACCESSCODE]
IF YOU HAVE ACCESS TO BOTH PARTITIONS:
4) Press the button corresponding to the partition you wish to Arm. To
Arm both partitions, press the [1] key then after the confirmation beep
press the [2] key.
If you make a mistake, the keypad will emit a "REJECTIONBEEP". When correctly Force Armed, the appropriate "ARM"
indication will appear and the Exit Delay will be initiated. Please note that Force Arming can also be activated using One-Touch Force Arming. Also note that the Access Code must have the Force Arming Option enabled.
MANUAL BYPASS PROGRAMMING
Manual Bypass Programming allows users to program the alarm system to ignore ("deactivate") specified zones the next
time the system is armed. Please note that Fire Zones can not be bypassed and that Manual Bypass Programming can also
be activated using One-Touch Bypass Programming.
How do I Program Bypass Entries?
1) Press the [BYP] button.
2) Key in a valid [ACCESSCODE]*
3) Select one or more [ZONES] you wish to bypass
4) Once you have entered the desired bypass entries, press the [ENTER]
button to accept these entries.
*If you have access to both partitions, press the button corresponding to the desired
partition. The Access Code must have the Bypass Programming Option enabled.
Spectra Series
33
BYPASS RECALL FEATURE
After disarming the system, the control panel will erase the bypass entries. By using the Bypass Recall Feature, you can
reinstate the previous bypass entries saved in memory. This eliminates the need to manually program the bypass entries
every time you arm the system.
How Do I Recall Bypass Entries?
1) Press the [BYP] button.
2) Key in your [ACCESSCODE]*
3) Press the [BYP] button.
4) Press the [ENTER] button.
*If you have access to both partitions, press the button corresponding to the desired
partition. The Access Code must have the Bypass Programming Option enabled.
ONE-TOUCH ARMING
One-Touch Arming allows users to arm the system without the use of an access code, simply press and hold a button. One-
Touch Arming can be used to allow specific individuals like service personnel (i.e. cleaners, maintenance) to arm the system when
leaving the protected area, without giving them access to any other alarm system operations.
One-Touch Regular Arming
Press and hold the [ENTER] button for 3 seconds* to arm all zones in the partition.
One-Touch Force Arming
Press and hold the [FORCE] button for 3 seconds* to bypass any open Force Zones.
One-Touch Bypass Programming
Press and hold the [BYP] button for 3 seconds* to access Bypass Programming Mode.
One-Touch Stay Arming
Press and hold the [STAY] button for 3 seconds* to arm all zones not defined as Stay Zones.
Fast Exit - When the system is already Stay Armed:
To Exit and Stay Arm: Press and hold the [STAY] button for 3 seconds*. The system will switch to Exit Delay mode. At
the end of the Exit Delay period, the system will return to Stay Arming.
To Exit and Regular Arm: Press and hold the [ENTER] button for 3 seconds*. The system will switch to Exit Delay mode.
At the end of the Exit Delay period, the control panel will switch to Regular Arming.
To Exit and Force Arm: Press and hold the [FORCE] button for 3 seconds*. The system will switch to Exit Delay mode.
At the end of the Exit Delay period, the control panel will switch to Force Arming.
* If you have access to both partitions after activating a one-touch feature, press the button corresponding to the desired
partition. To select both partitions, press the [1] key then after the confirmation beep press the [2] key.
KEYSWITCH ARMING
A keyswitch can be used to arm and disarm the system. Assign the keyswitch to a specific partition and program the
keyswitch to Stay or Regular Arm the assigned partition. Also program the keyswitch to function as a Maintained or
Momentary keyswitch. To arm the system using a Maintained Keyswitch, set the keyswitch to the "on" position. To disarm the
system set the keyswitch to the "off" position. To arm the system using a Momentary Keyswitch, set the keyswitch to the "on"
position then turn it back to the "off" position. Repeating this sequence will disarm the system.
PANIC ALARMS
In case of emergency, the Spectra system provides up to three panic alarms. These panic alarms, if programmed, will
immediately generate an alarm after pressing and holding two specific buttons for two seconds, as described below.
Press and hold buttons [1] and [3] for a panic alarm.
Press and hold buttons [4] and [6] for a panic or medical alarm.
Press and hold buttons [7] and [9] for a panic or fire alarm.
34
Programming Guide
AUTO-ARMING
You can program the Spectra alarm panel to automatically arm at a specific time everyday or if no movement is detected for a
specified period of time. The user is only allowed to program the Auto Arm Timer. Please note that the control panel will enter a 60-
second Exit Delay period before arming the system. At this point, Auto-Arming can be cancelled by entering a valid access code.
ALARM MEMORY DISPLAY
A record of all alarm situations that occur will be stored in memory. After disarming the system, pressing the [MEM] button will
display which zones were in alarm during the last armed period. To exit the Alarm Memory Display, press the [CLEAR] button.
The control panel will erase the contents of the alarm memory every time the system is armed.
PROGRAMMING CHIME ZONES
This feature allows users to program which zones will be "Chime Enabled". A "Chime Enabled" zone will cause the keypad to
emit a rapid intermittent beep tone (BEEP-BEEP-BEEP-BEEP) advising the user every time it is opened. Each keypad must be
Chime Programmed separately. Keypad chimes must be re-programmed if the system suffers a total power loss.
10-Zone LED Keypad:
Press and hold any button from [1] to [10] for 3 seconds to activate or deactivate Chiming for zones 1 to 10. For example,
press and hold the [1] button to enable chiming on zone 1. If after pressing and holding a button, the keypad emits a
confirmation beep, this means the chime feature has been enabled for that zone. If the keypad emits a rejection beep, this
means the chime feature has been disabled for the corresponding zone.
16-Zone LED Keypad:
Press and hold the [9] button. Enter the 2-digit (01 to 16) zone number(s). When the corresponding LED is on, the zone is
chimed. When the corresponding LED is off, the zone is unchimed. When the desired zones are chimed, press [ENTER].
LCD Keypad:
Press and hold the [9] button. Enter the 2-digit (01 to 16) zone number(s), or use the arrow keys to scroll through the zones.
and when the appropriate zone is displayed, press the [FNC1] button. When the desired zones are chimed, press [ENTER].
KEYPAD MUTING
Press and hold the [CLEAR] button for 3 seconds to enable or disable keypad muting. When muted, the keypad will only “beep”
when a button is pressed or when the keypad emits a rejection or confirmation beep. All other “beep” functions are disabled.
QUICK FUNCTION KEYS
Installer Test Mode
[ENTER] + [INSTALLERCODE] + [TBL] or [TRBL]
The Installer Test Mode allows you to perform walk tests where the bell/siren will squawk once to indicate an open zone
and twice to indicate a closed zone. To enter this mode, press [ENTER] + [INSTALLERCODE] + [TBL] or [TRBL]. The keypad will
emit a confirmation beep. To disable this mode, press the [TBL] or [TRBL] key again. The keypad will emit a rejection beep.
Test Report
[ENTER] + [INSTALLER/MASTERCODE] + [MEM]
Sends the "Test Report" report code programmed in section [211] to the central station.
Call WinLoad Software
[ENTER] + [INSTALLER/MASTERCODE] + [BYP]
This feature is used to establish communication between the control panel and a computer using the WinLoad Software.
After entering this mode the control panel will dial the telephone number programmed in section [150].
Cancel Communication
[ENTER] + [INSTALLER/MASTERCODE] + [STAY]
Cancels all communication until the next reportable event. If the Master Code was used, only communication with
WinLoad would be cancelled.
Answer WinLoad Software
[ENTER] + [INSTALLER/MASTERCODE] + [FORCE]
Forces the control panel to pick-up an incoming telephone call.
Spectra Series
35
HARDWARE CONNECTIONS
SINGLE ZONE INPUTS
DOUBLE ZONE INPUTS (with ATZ option only)
36
Programming Guide
CONNECTING A KEYSWITCH
CONNECTING FIRE CIRCUITS
PGM CONNECTIONS
Spectra Series
37
CONNECTING A LIBERATOR WIRELESS BUS MODULE (SPC-319)
CONNECTING A ZONE EXPANSION MODULE (SPC-ZX8)
38
Programming Guide
SPECTRA 1725, 1725EX, 1728 AND 1728EX PCB LAYOUT
Spectra Series
39
SPECTRA 1755, 1755EX, 1758 AND 1758EX PCB LAYOUT
Other than the location of the parts on the board and the items that have been indicated below, connections to these control
panels are identical to those on page 38.
CONNECTING SPEAKERS TO THE BELL OUTPUT (Siren Driver Option Only)
An optional siren driver is available with the Spectra 1755, 1755EX, 1758 and 1758EX control panels. This siren driver allows
you to connect speakers directly to the “bell” output as shown in the figure below. Minimum speaker rating = 30 watts.
# of 8ΩΩ speakersConnection TypeTotal LoadAverage Current Draw*