Paradox Spectra 1725, Spectra 1728EX, Spectra 1755, Spectra 1725EX, Spectra 1755EX Programming Manual

...
PROGRAMMING GUIDE
SPECTRA CONTROL PANELS V1.2
1725, 1725EX, 1728 AND 1728EX 1755, 1755EX, 1758, AND 1758EX
Spectra Series
TABLE OF CONTENTS
HOW DO I PROGRAM THE SYSTEM? ......................................................................................................4
Single Digit Data Entry Method (Hexadecimal and decimal) ........................................................................................4
Multiple Feature Select Programming Method .............................................................................................................4
Data Display Mode (LED Keypads Only) ......................................................................................................................5
Paradox Memory Key ...................................................................................................................................................5
ZONE PROGRAMMING ................................................................................................................................. 6
What is an Expansion Input? ........................................................................................................................................6
How Do I Program the Zones? .....................................................................................................................................7
SYSTEM TIMERS ...........................................................................................................................................8
HOW DO I SET THE PROGRAMMABLE OUTPUTS? .............................................................................9
SYSTEM OPTIONS .......................................................................................................................................12
General Options ..........................................................................................................................................................12
Arming/Disarming Options ..........................................................................................................................................12
Zone Options ..............................................................................................................................................................13
Partition 1 Options ......................................................................................................................................................13
Partition 2 Options ......................................................................................................................................................14
Dialer Options .............................................................................................................................................................14
Event Call Direction ....................................................................................................................................................14
COMMUNICATION SETTINGS .................................................................................................................15
REPORT CODES ........................................................................................................................................... 16
Arming Report Codes .................................................................................................................................................16
Disarming Report Codes ............................................................................................................................................16
Alarm Report Codes ...................................................................................................................................................17
Tamper Report Codes ................................................................................................................................................17
System Trouble Report Codes ...................................................................................................................................17
Programmable - Ademco Contact ID Report Code List ..............................................................................................18
All Codes - Ademco Contact ID Report Code List ......................................................................................................19
SYSTEM SETTINGS ....................................................................................................................................20
USER CODE OPTIONS ................................................................................................................................ 21
LIBERATOR WIRELESS BUS MODULE (SPC-319) ............................................................................. 22
Wireless Transmitter Assignment (Liberator Only) .....................................................................................................22
Wireless Module Options (Liberator Only) ..................................................................................................................22
PGM Programming (Liberator Only) ...........................................................................................................................23
Serial Number Display ................................................................................................................................................23
Signal Strength Display ..............................................................................................................................................24
Liberator Module (SPC-319) Reset ............................................................................................................................24
ZONE EXPANSION MODULES (SPC-ZX4/8) ......................................................................................... 25
PGM Timer (Zone Module SPC-ZX8 Only) ................................................................................................................25
Options .......................................................................................................................................................................25
Zone Assignment ........................................................................................................................................................25
PGM Programming (Zone Module SPC-ZX8 Only) ....................................................................................................26
Reset Zone Expansion Module ...................................................................................................................................26
REMOTE CONTROL PROGRAMMING ....................................................................................................27
User Assignment ........................................................................................................................................................27
2
Programming Guide
Button Programming ..................................................................................................................................................27
Remote Control Assignment (Liberator Only) .............................................................................................................28
Remote Control Assignment (1755, 1755EX, 1758 and 1758EX Panels Only) .........................................................28
Reprogram ALL Modules ...........................................................................................................................................28
Paradox Memory Key .................................................................................................................................................28
USER OPERATION .......................................................................................................................................29
Trouble Display ..........................................................................................................................................................29
Partitioning .................................................................................................................................................................30
Programming Access Codes ......................................................................................................................................30
Disarming & Deactivating an Alarm ............................................................................................................................31
Regular Arming ..........................................................................................................................................................31
Stay Arming ................................................................................................................................................................31
Instant Arming ............................................................................................................................................................32
Force Arming ..............................................................................................................................................................32
Manual Bypass Programming ....................................................................................................................................32
Bypass Recall Feature ...............................................................................................................................................33
One-Touch Arming .....................................................................................................................................................33
Keyswitch Arming .......................................................................................................................................................33
Panic Alarms ..............................................................................................................................................................33
Auto-Arming ...............................................................................................................................................................34
Alarm Memory Display ...............................................................................................................................................34
Programming Chime Zones .......................................................................................................................................34
Keypad Muting ...........................................................................................................................................................34
Quick Function Keys ..................................................................................................................................................34
HARDWARE CONNECTIONS ....................................................................................................................35
Single Zone Inputs .....................................................................................................................................................35
Double Zone Inputs (with ATZ option only) ................................................................................................................35
Connecting a Keyswitch .............................................................................................................................................36
Connecting Fire Circuits .............................................................................................................................................36
PGM Connections ......................................................................................................................................................36
Connecting A Liberator Wireless Bus Module (SPC-319) ..........................................................................................37
Connecting A Zone Expansion Module (SPC-ZX8) ....................................................................................................37
Spectra 1725, 1725EX, 1728 and 1728EX PCB Layout ............................................................................................38
Spectra 1755, 1755EX, 1758 and 1758EX PCB Layout ............................................................................................39
Connecting Speakers to the Bell Output (Siren Driver Option Only) ..........................................................................39
Spectra Series
4
Programming Guide
HOW DO I PROGRAM THE SYSTEM?
The SpectraTM series control panels can be programmed using the WinLoad Software or by using any keypad connected to the Spectra control panel. For information on the WinLoad Software, please refer to the Spectra Installation & Reference Manual. To program the Spectra control panel using a keypad, you must enter the Programming Mode as shown below. Once a control panel has been programmed, you can use the Paradox Memory Key to copy the contents from the programmed control panel to one or more control panels (see page5).
Default Installer Code: 000000 (see section [281] on page20) Default System Master Code: 123456 (see section [301] on page21)
To enter Programming Mode:
STEP 1: Press [ENTER] STEP 2: Enter your [INSTALLER CODE] STEP 3: Enter 3 digits of [SECTION] you wish to program STEP 4: Enter required [DATA]
SINGLE DIGIT DATA ENTRY METHOD (Hexadecimal and Decimal)
Single Digit Data Entry is used in all sections except those specified in Multiple Feature Select Programming Method. After entering the programming mode as described in the shaded box above, some sections will require that you enter Decimal values from 000 to 255. Other sections will require that you enter Hexadecimal values from 0 to F. The required data will be clearly indicated in this manual. When entering the final digit in a section, the control panel will automatically save and advance to the next section. With the exception of sections 001 to 016, where after entering the first two digits, the control panel will switch to Multiple Feature Select Programming.
Table 1: Decimal and Hexadecimal Programming Table
Value or Action What Do I
Press?
10-Zone LED 16-Zone LED LCD
What Do I See?
Values 1 to 9 [1] to [9] [1] to [9] [1] to [9] [1] to [9]
A (hexa only) [0] [0 (10)] [10] A B (hexa only) [STAY] [STAY] [11] B C (hexa only) [BYP] [BYP] [12] C D (hexa only) [MEM] [MEM] [13] D E (hexa only) [TBL] / [TRBL] [TBL] [14] E F (hexa only) [PG] / [FNC1] [PG] [15] F
Erase Current Digit [FORCE] Displays next digit or next section
Exit Without Saving [CLEAR] [ENTER] flashes [ARM1] & [STAY1] flash “SECTION [ ]”
Save Data (hexa only) [ENTER] Advances to the next section
MULTIPLE FEATURE SELECT PROGRAMMING METHOD
Sections: [001] to [016], [127] to [138], [302] to [348], [610], [650] to [651] After entering the programming mode as described in the shaded box above, each option from [1] to [8] will represent a specific feature or option. Press the key corresponding to the desired option and the corresponding light will illuminate or the option number will appear in the LCD display. This means the option is on. Press the key again to extinguish the corresponding light or remove the digit from the LCD display, thereby, turning off the option. Please note that pressing the [FORCE] key will set all 8 options to “off”. Press the keys as many times as you need until all 8 options in the current section are set. When the options are set, press the [ENTER] key to save and advance to the next section.
Spectra Series
DATA DISPLAY MODE (LED Keypads Only)
In the Data Display Mode you can view the programmed contents of each section one digit at a time. After entering the desired 3-digit section (see step 3 of the “To Enter Programming Mode” box on the previous page), press the [ENTER] key to access the Data Display Mode. This mode will not function with sections using the Multiple Feature Select Programming Method (see previous page).
PARADOX MEMORY KEY
Copy the programmed contents of one Spectra control panel into the Paradox Memory Key. Then copy the contents of the Paradox Memory Key into as many Spectra control panels as you need. Each control panel is programmed in less than 3 seconds.
If you use the Memory Key to download to a Spectra 1755, 1755EX, 1758, or 1758EX, you will have to reassign the remote controls (see page28).
Download to DESTINATION Control Panel
1)Remove AC and battery power from the control panel.
2)Insert the Memory Key onto the serial connector labeled “KEY” on the Spectra control panel to which you wish to download the contents of the memory key to.
3) Reapply AC and battery power.
4)Enter installer programming mode, enter section [900], then press [ENTER] to acknowledge.
5)When the keypad emits a “confirmation beep”, remove the Memory Key.
Copy to Memory Key from SOURCE Control Panel
1)Remove AC and battery power from the control panel.
2)Insert Memory Key onto the serial connector labeled “KEY” on the Spectra control panel from which you wish to copy. Make sure the write protect jumper of the Memory Key is on.
3)Reapply AC and battery power.
4)Enter installer programming mode, enter section [902], then press [ENTER] to acknowledge.
5)When the keypad emits a “confirmation beep”, remove the Memory Key. Remove the Memory Key’s jumper if you do not wish to accidentally overwrite its contents.
6
Programming Guide
ZONE PROGRAMMING
When programming zones please note that the Spectra control panels’ zone assignment is dependent on where the detection devices in the system are connected (see Table 2 below).
Table 2: Zone Recognition Table
Device connected to
which input?
1725EX 1725 1755EX 1755
NO ATZ WITH ATZ NO ATZ WITH ATZ
Control Panel Input 1 = Zone 1 Zone 1 & 4 Zone 1 Zone 1 & 6 Control Panel Input 2 = Zone 2 Zone 2 & 5 Zone 2 Zone 2 & 7 Control Panel Input 3 = Zone 3 Zone 3 & 6 Zone 3 Zone 3 & 8 Control Panel Input 4 = N/A N/A Zone 4 Zone 4 & 9 Control Panel Input 5 = N/A N/A Zone 5 Zone 5 & 10
Keypad Zone 1 = Zone 4 Zone 7 Zone 6 Zone 11 Keypad Zone 2 = Zone 5 Zone 8 Zone 7 Zone 12
Expansion Input 1 = Zone 6 Zone 9 Zone 8 Zone 13 Expansion Input 2 = Zone 7 Zone 10 Zone 9 Zone 14 Expansion Input 3 = Zone 8 Zone 11 Zone 10 Zone 15 Expansion Input 4 = Zone 9 Zone 12 Zone 11 Zone 16 Expansion Input 5 = Zone 10 Zone 13 Zone 12 N/A Expansion Input 6 = Zone 11 Zone 14 Zone 13 N/A Expansion Input 7 = Zone 12 Zone 15 Zone 14 N/A Expansion Input 8 = Zone 13 Zone 16 Zone 15 N/A
WHAT IS AN EXPANSION INPUT?
1728EX 1728 1758EX 1758
There are a total of eight expansion inputs available. Each hardwired input on a Zone Expansion Module or wireless transmitter used by the LiberatorTM Wireless Bus Module can be assigned to an expansion input. The expansion inputs can be used in any combination. For example, you can assign four wireless transmitters as well as 4 hardwire inputs to the expansion inputs. Regardless of how many expansion modules are being used, the control panel cannot support more than eight expansion inputs. The expansion module inputs are assigned as follows:
SPC-319 Liberator Wireless Bus Module
Wireless transmitters assigned to sections [601] to [608] of the control panel represent expansion inputs 1 to 8 respectively. Refer to Wireless Transmitter Assignment on page22.
SPC-ZX4 and SPC-ZX8 Zone Expansion Module
Detection devices connected to input terminals Z1 to Z4 of the SPC-ZX4 module or Z1 to Z8 of the SPC-ZX8 module, represent expansion inputs 1 to 8 respectively. Please note that the module’s inputs must be enabled in section [651] of the control panel. Refer to Zone Assignment on page25.
Do not assign devices from different modules to the same expansion input. For example, do not assign a wireless transmitter to section [601], then connect a detection device to input Z1 of the SPC-ZX8 and enable option [1] in section [651].
Spectra Series
HOW DO I PROGRAM THE ZONES?
STEP 1: Press the [ENTER] key STEP 2: Enter the [INSTALLER CODE] (Default: 000000) STEP 3: Enter 3-digit [SECTION] STEP 4: Enter one digit from the Zone Definition table STEP 5: Enter one digit from the Partition Assignment table STEP 6: Select one or more options from the Zone Options table STEP 7: Press the [ENTER] key
Section # Description Zone Definition Partition Assignment Zone Options
First Digit Second Digit Feature Select
[001]= Zone 1:____________________ ____ ____ 1 2 3 4 5 6 7 8 [002]= Zone 2:____________________ ____ ____ 1 2 3 4 5 6 7 8 [003] = Zone 3:____________________ ____ ____ 1 2 3 4 5 6 7 8 [004] = Zone 4:____________________ ____ ____ 1 2 3 4 5 6 7 8 [005] = Zone 5:____________________ ____ ____ 1 2 3 4 5 6 7 8 [006] = Zone 6:____________________ ____ ____ 1 2 3 4 5 6 7 8 [007] = Zone 7:____________________ ____ ____ 1 2 3 4 5 6 7 8 [008] = Zone 8:____________________ ____ ____ 1 2 3 4 5 6 7 8 [009] = Zone 9:____________________ ____ ____ 1 2 3 4 5 6 7 8 [010] = Zone 10:____________________ ____ ____ 1 2 3 4 5 6 7 8 [011] = Zone 11:____________________ ____ ____ 1 2 3 4 5 6 7 8 [012] = Zone 12:____________________ ____ ____ 1 2 3 4 5 6 7 8 [013] = Zone 13:____________________ ____ ____ 1 2 3 4 5 6 7 8 [014] = Zone 14:____________________ ____ ____ 1 2 3 4 5 6 7 8 [015] = Zone 15:____________________ ____ ____ 1 2 3 4 5 6 7 8 [016] = Zone 16:____________________ ____ ____ 1 2 3 4 5 6 7 8
Default = Empty Default = 1 Default = 1 & 2 on
8
Programming Guide
SYSTEM TIMERS
Section # Decimal Value (000-255) Description Default Value
[050] ___/___/___ x10 msec. ZONE SPEED (ZONE 1) 600 msec. [051] ___/___/___ x10 msec. ZONE SPEED (ZONE 2) 600 msec. [052] ___/___/___ x10 msec. ZONE SPEED (ZONE 3) 600 msec. [053] ___/___/___ x10 msec. ZONE SPEED (ZONE 4) 600 msec. [054] ___/___/___ x10 msec. ZONE SPEED (ZONE 5) 600 msec. [055] ___/___/___ X10 msec. ZONE SPEED (ZONE 6) 600 msec. [056] ___/___/___ X10 msec. ZONE SPEED (ZONE 7) 600 msec. [057] ___/___/___ X10 msec. ZONE SPEED (ZONE 8) 600 msec. [058] ___/___/___ X10 msec. ZONE SPEED (ZONE 9) 600 msec. [059] ___/___/___ x10 msec. ZONE SPEED (ZONE 10) 600 msec. [060] ___/___/___ x10 msec. ZONE SPEED (ZONE 11) 600 msec. [061] ___/___/___ x10 msec. ZONE SPEED (ZONE 12) 600 msec. [062] ___/___/___ x10 msec. ZONE SPEED (ZONE 13) 600 msec. [063] ___/___/___ x10 msec. ZONE SPEED (ZONE 14) 600 msec. [064] ___/___/___ x10 msec. ZONE SPEED (ZONE 15) 600 msec. [065] ___/___/___ x10 msec. ZONE SPEED (ZONE 16) 600 msec.
NOTE: If ATZ is enabled (section [132], key [5]), do not set the Zone Speed to less than 50msec. as this may cause false alarms.
[066] ___/___/___ seconds (000 = follow stop event) PGM1 TIMER 5 sec. [067] ___/___/___ seconds (000 = follow stop event) PGM2 TIMER (1755/EX & 1758/EX ONLY) 5 sec. [068] ___/___/___ seconds (000 = follow stop event) GLOBAL PGM TIMER (SEE PAGE 23 & 26) 5 sec. [069] ___/___/___ seconds ENTRY DELAY 1 45 sec. [070] ___/___/___ seconds ENTRY DELAY 2 45 sec. [071] ___/___/___ seconds EXIT DELAY 1 30 sec. [072] ___/___/___ seconds EXIT DELAY 2 30 sec. [073] ___/___/___ minutes (000 = no bell on alarm) BELL CUT-OFF TIME - PARTITION 1 4 min. [074] ___/___/___ minutes (000 = no bell on alarm) BELL CUT-OFF TIME - PARTITION 2 4 min. [075] ___/___/___ x15 minutes (000 = disabled) NO MOVEMENT TIME - PARTITION 1 Disabled [076] ___/___/___ x15 minutes (000 = disabled) NO MOVEMENT TIME - PARTITION 2 Disabled [077] ___/___/___ seconds (min.= 10 sec.) ANS. MACHINE OVERRIDE DELAY Disabled [078] ___/___/___ (000 = no answer; max. = 15 rings) NUMBER OF RINGS 8 rings [079] ___/___/___ x2 sec. (min.= 32 sec.) TLM FAIL TIMER 32 sec. [080] ___/___/___ seconds DELAY ALARM TRANSMISSION Disabled [081] ___/___/___ (000 = 16; max. 16) MAXIMUM DIALING ATTEMPTS 8 attempts [082] ___/___/___ seconds DELAY BETWEEN ATTEMPTS 20 sec. [083] ___/___/___ seconds PAGER DELAY 5 sec. [084] ___/___/___ seconds (min. 10 sec.) INTELLIZONE DELAY 48 sec. [085] ___/___/___ seconds RECENT CLOSING DELAY No delay [086] ___/___/___ minutes POWER FAILURE REPORT DELAY 15 min. [087] ___/___/___ days (000 = disabled) AUTO TEST REPORT Disabled [088] ___/___/___ (001-127 = +1 to +127 sec.) CLOCK ADJUST Disabled
(128-255 = -1 to -127 sec.)
[089] ___/___/___ (000 = Disabled; max. = 15) AUTO ZONE SHUTDOWN COUNTER 5 [090] ___/___/___ minutes (000 = disabled) RECYCLE ALARM DELAY Disabled [091] ___/___/___ (000 = disabled) RECYCLE ALARM COUNTER Disabled
[110] ___/___:___/___Hrs (00-23) & Min. (00-59) AUTO TEST REPORT (TIME OF DAY) Disabled [111] ___/___:___/___Hrs (00-23) & Min. (00-59) AUTO-ARM TIME - PARTITION 1 Disabled [112] ___/___:___/___Hrs (00-23) & Min. (00-59) AUTO-ARM TIME - PARTITION 2 Disabled
Spectra Series
HOW DO I SET THE PROGRAMMABLE OUTPUTS?
Example: section [120] = 05 03 02: this means PGM1 will activate whenever partition 2 is Stay Armed.
Section # Event Group # Sub-Group # Partition #
[120] = PGM1 Start Event ___/___ ___/___ ___/___ [121] = PGM1 Stop Event ___/___ ___/___ ___/___
Can be used as another Start Event if section [066] is programmed with a value other than 000.
[122] = PGM2 Start Event ___/___ ___/___ ___/___ [123] = PGM2 Stop Event ___/___ ___/___ ___/___
Can be used as another Start Event if section [067] is programmed with a value other than 000.
[124] = Global PGM Start Event___/___ ___/___ ___/___ [125] = Global PGM Stop Event___/___ ___/___ ___/___
Used to activate PGMs on expansion modules and LCD keypads (see page22 and page25)
Event Group # Sub-Group #
00 = Zone OK 01-16 = Zones 1 to 16
99 = Any Zone
01 = Zone Open 01-16 = Zones 1 to 16
99 = Any Zone
02 = Partition Status 00 = System not ready (Partition 1 only)
01 = System ready (Partition 1 only) 02 = Steady Alarm in Partition 03 = Pulsed Alarm in Partition 04 = Pulsed or Steady Alarm in Partition 05 = Alarm in Partition Restored 06 = Bell Squawk Activated (Partition 1 only) 07 = Bell Squawk Deactivated (Partition 1 only) 99 = Any Sub-Group
03 = Global Disarm with User Code 01-48 = User Code Numbers 001 to 048
99 = Any User Code
04 = Special Global Disarm 00 = Disarm with WinLoad Software
01 = Disarm with Keyswitch 99 = Any Sub-Group
05 = Non-Reportable Events 00 = Telephone Line Trouble (Partition 1 only)
01 = [PG] or [FNC1] key was pressed (Partition 1 only) 02 = Instant Arming 03 = Stay Arming 04 = Force Arming 05 = Fast Exit (Force & Regular Only) 06 = PC Fail to Communicate (Partition 1 only) 07 = Midnight (Partition 1 only) 08 = Ground start (Partition 1 only) 99 = Any Sub-Group (Partition 1 only, except 02 to 05)
01 = Partition 1 02 = Partition 2 99 = Any Partition
Sub-Groups proceeded by (Partition 1 only) cannot be assigned to activate in partition 2.
10
Programming Guide
Event Group # Sub-Group #
06 = Arm/Disarm with Remote Control 01-08 = Remote Controls 1 to 8
99 = Any Remote Control
07 = Button Pressed on Remote (see
button option “B” on page27)
08 = Button Pressed on Remote (see
button option “C” on page27)
09 = Button Pressed on Remote (see
button option “D” on page27)
10 = Bypass Programming 01-48 = User Code Numbers 001 to 048
11 = User Activated PGM 01-48 = User Code Numbers 001 to 048
12 = Zone with Delay Transmission
Option Enabled is Breached
13 = Arm with User Code 01-48 = User Code Numbers 001 to 048
14 = Special Arm 00 = Auto Arming (timed/no movement)
15 = Disarm with User Code 01-48 = User Code Numbers 001 to 048
16 = Disarm After Alarm w/ User Code 01-48 = User Code Numbers 001 to 048
17 = Cancel Alarm with User Code 01-48 = User Code Numbers 001 to 048
18 = Special Disarm 00 = Cancel Auto Arm (timed/no movement)
19 = Zone Bypassed on Arming 01-16 = Zones 1 to 16
20 = Zone in Alarm 01-16 = Zones 1 to 16
21 = Fire Alarm 03 = Zone 3
22 = Zone Alarm Restore 01-16 = Zones 1 to 16
23 = Fire Alarm Restore 03 = Zone 3
01-08 = Remote Controls 1 to 8 99 = Any Remote Control
01-08 = Remote Controls 1 to 8 99 = Any Remote Control
01-08 = Remote Controls 1 to 8 99 = Any Remote Control
99 = Any User Code
99 = Any User Code 01-16 = Zones 1 to 16
99 = Any Zone
99 = Any User Code
01 = Late to Close (auto arming failed) 02 = No Movement Auto Arming 03 = Partial Arming (stay, force, instant, bypass) 04 = One-Touch Arming 05 = Arm with WinLoad Software 06 = Arm with Keyswitch 99 = Any Sub-Group
99 = Any User Code
99 = Any User Code
99 = Any User Code
01 = Disarm with WinLoad Software 02 = Disarm with Keyswitch 03 = Reserved for Future Use 04 = Disarm after alarm with WinLoad Software 05 = Disarm after alarm with Keyswitch 06 = Cancel Alarm with WinLoad Software 07 = Cancel Alarm with Keyswitch 99 = Any Sub-Group
99 = Any Zone
99 = Any Zone
99 = Any Zone
99 = Any Zone
99 = Any Zone
Spectra Series
11
Event Group # Sub-Group #
24 = Special Alarm 00 = Emergency Panic
01 = Auxiliary Panic 02 = Fire Panic 03 = Recent Closing 04 = Auto Zone Shutdown 05 = Duress Alarm 99 = Any Sub-Group
25 = Auto Zone Shutdown 01-16 = Zones 1 to 16
99 = Any Zone
26 = Zone Tamper 01-16 = Zones 1 to 16
99 = Any Zone
27 = Zone Tamper Restore 01-16 = Zones 1 to 16
99 = Any Zone
28 = System Trouble 01 = AC Loss: only after Power Failure Delay has elapsed
(Partition 1 only) 02 = Battery Failure (Partition 1 only) 03 = Auxiliary current overload (Partition 1 only) 04 = Bell current overload (Partition 1 only) 05 = Bell disconnected (Partition 1 only) 06 = Timer Loss (Partition 1 only) 07 = Fire Loop Trouble (Partition 1 only) 08 = Wireless Transmitter Low Battery (Partition 1 only) 09 = Module Fault (Partition 1 only) 10 = Printer Fault (Partition 1 only) 11 = Fail to Communicate (Partition 1 only) 99 = Any Sub-Group (Partition 1 only)
29 = System Trouble Restore 00 = TLM restore (Partition 1 only)
01 = AC Loss restore (Partition 1 only) 02 = Battery Failure restore (Partition 1 only) 03 = Auxiliary current overload restore (Partition 1 only) 04 = Bell current overload restore (Partition 1 only) 05 = Bell disconnected restore (Partition 1 only) 06 = Timer Programmed (Partition 1 only) 07 = Fire Loop Trouble restore (Partition 1 only) 08 = Wireless Transmitter Low Battery restore (Partition 1 only) 09 = Module Fault restore (Partition 1 only) 10 = Printer Fault restore (Partition 1 only) 11 = Fail to Communicate restore (Partition 1 only) 99 = Any Trouble Restore (Partition 1 only)
30 = Special Reporting 00 = System Power Up (Partition 1 only)
01 = Test Report (Partition 1 only) 02 = WinLoad Software Access (Partition 1 only) 03 = WinLoad Software Access finish (Partition 1 only) 04 = Installer enters programming mode (Partition 1 only) 05 = Installer exits programming mode (Partition 1 only) 99 = Any Sub-Group (Partition 1 only)
31 = Wireless Transmitter Supervi-
sion Loss
32 = Wireless Transmitter Supervi-
sion Loss Restore
01-16 = Zones 1 to 16 99 = Any Zone
01-16 = Zones 1 to 16 99 = Any Zone
Loading...
+ 29 hidden pages