PARADOX PRT3 c последовательным и параллельным портами DIGIPLEX-CBUS-EP00-eng.pdf

Page 1
APR-PRT3 Printer Module:
C-Bus Programming Instructions
We hope this product performs to your complete satisfaction. Should you have any
questions or comments, please visit www.paradox.com and send us your comments.
Page 2
Table of Contents
Technical Specifications ................................................................................................................................................1
Installation .....................................................................................................................................................................2
Programming Sections .......... ... ....................................... ... ... .... ... ... ... .... ... ....................................................................2
Serial Port Setup ........................................................................................................................................................... 3
Virtual PGM Programming .............................................................................................................................................3
C-Bus Entry Options ......................................................................................................................................................8
PGM Activation Event ......................................................................... .... ... ... ...............................................................22
PGM Deactivation Option ............................................................................................................................................22
PGM Deactivation Event .................................... ... .... ... ... ... ... .... ... ... ... .... ... ..................................................................22
PGM Programming Table ............................................................................................................................................22

Technical Specifications

Parallel Port: Minimum 80 column printer Serial Port: 1 start bit, 8 data bit, no parity and 1 stop bit (8N1) Input Voltage: 9 -16 Vdc Current Consumption: 60mA maximum Serial Port Baud Rates: 2400, 9600, 19200 or 57600 bps Event Buffer: 2048 events Compatibility: EVO48 / EVO96 / EVO192 control panels
DGP-848 control panel (V4.11 and up) DGP-NE96 control panel (V1.60 and up)
Introduction
The APR-PRT3 Printer Module can be used as an interface between C-Bus and your Digiplex system. When in home automation mode, the Printer Module can receive and send commands to and from the C-Bus PC interface and the Digiplex control panel, linking your building automation capabilities with your security system.
The Printer Module features 30 virtual PGMs for use with its building automation interface capabilities. These PGMs are not related to any physical output on the module, but operate in the same manner and are programmed in the same way as traditional PGMs. A virtual PGM can be used to trigger a response within C-Bus based on an event that has occurred within the Digiplex system. For example, when a user uses the Digiplex system to disarm an area, this event could activate a virtual PGM on the Printer Module and trigger a response within C­Bus, such as turning on a specific light on the premises. See “Virtual PGM Programming ” on page 4.
Up to 30 C-Bus entries can be associated with the Pri nter Module’s virtual PGMs. C-Bus entries allow you to set the commands that will be sent on the C-Bus in relation to events that occur within the Digiplex system. When the state of a virtual PGM on the Printer Module changes, a message is sent by the C-Bus entry that is associated with that virtual PGM. See “C-Bus Entry Options” on page 8.
The Printer Module also features 16 onboard virtual inputs. These inputs are not related to any physical input on the mod ule, but operate in the same manner and are programmed in the same way as a traditional zone input. A virtual input can be programmed to trigger a response from the Digiplex control panel based on an event that has occurred within C-Bus. Using virtual inp ut s to trigger event s within th e Digiplex control panel involves associating the Printer Module’s virtual input to a zone or a keyswitc h on the control p anel. See “V irtual Input Options” on page 15.
In order for C-Bus and the Digiplex control panel to communicate in such a way, the Printer Module’s serial port must be set to communicate using the Clipsal C-Bus Protocol.
For a complete list of the Printer Module’s event reporting features, see the Printer Module V1.0 (APR-PRT3) Instructions.
The APR-PRT3 Printer Module is compatible with C-Bus interface firmware V4.00.00 and higher. C-Bus lighting units must be configured with firmware V1.1 and higher.
If the Printer Module fails to connect to the C-Bus PC interface, a trouble will be generated.
1
Page 3

Installation

The Printer Module is connected to the control panel’s combus. Connect the four terminals labeled red , black, green, and yel low of the module to the corresponding terminals on the control panel as shown in Figure 2 on page 21. See the EVO or DGP-848 Reference & Installation Manual for the maximum allowable installation dist an ce from the control panel.
The C-Bus PC Interface must be connected to the Printer Module’s serial port using a null modem cable only.

Overview

The following provides of an overview of how the Printer Module communicates with C-Bus.
Figure 1: C-Bus Overview
• C-Bus entries are associated with Printer Module’s virtual PGMs.
• Printer Module sends messages to C-Bus PC interface based on
• Messages from C-Bus PC interface can be used to open/close virtual inputs on the Printer Module.
virtual PGM events and C-Bus Entry programming.

Programming Sections

The following describes the programming sections which must be set in order for the Printer Mod ule to act as an interface between a Digiplex control panel and a C-Bus PC interface.
To access the Printer Module’s programming mode:
1. Press and hold the [0] key.
2. Enter the [
3. Enter section [953] (DGP-848) / [4003] (EVO).
4. Enter the Printer Module’s 8-digit [
5. Enter the 3-digit [
6. Enter the required data. The Printer Module can also be programmed using the WinLoad Security Software (V2.62 or higher) or using the control p a nel’ s Mo dule
Broadcast feature. Refer to the EVO or DGP-848 Reference & Installation Manual for more details. Please note that th e seri al numb er can be located on the Printer Module’s PC board.
INSTALLER CODE].
SERIAL NUMBER].
SECTION] you want to program.
2
Page 4

Serial Port Setup

The following lists the serial port programming options wh ich must be set in order for the Printer Module to commun icat e with C-Bus.
Section [016] - Option [1]
Enable Serial Port
When this option is ON (enabled), you can connect the C-Bus PC interface directly to the Printer Module’s serial port (9 pins) through the use of a null modem cable. Set option [4] to ON when using the Printer Module as an interface between a C-Bus PC interface and the Digiplex system.
Section [016] - Options [2] & [3]
Baud Settings
When a C-Bus PC interface is connected to the Printer Module, the serial port baud rate is automatically set to 9600 bau d. Any other baud rate will be overridden.
Section [016] - Option [4]
Serial Port Usage
This option allows you to set the Printer Module’s serial port usage to either Event Re porting or Home Automation. Set option [4] to ON to set the Printer Module to Home Automation.
Section [016] - Options [5] & [6]
Home Automation Options
This option allows you to select the home automation protocol for the Printe r Module. Set option [5] to ON and option [6] to OFF to select the Clipsal C-Bus Protocol.
For more information on the ASCII Protocol, see the ASCII Protocol Programming Instructions on our website at paradox.com.
Sections [070] to [072]
C-Bus Applications
These sections allow you to enable which C-Bus application(s) the Printer Module can use to send and receive commands. Note that the Printer Module supports communication with the following three C-Bus applications:
Section Application Hexadecimal Value
[070] __ /__ [071] __ /__
[072] __ /__ C-Bus Security Application $DO
Refer to the appropriate C-Bus documentation for further informatio n on C-Bus ap plication s.
C-Bus lighting Application
C-Bus Air-conditioning
Application
$38
$AC
3
Page 5

Virtual PGM Programming

The Printer Module supports up to 30 virtual PGMs which are not related to any physical output on the module, but operate in the sa me manner and are programmed in the same way as traditional PGMs. The tables below of fer an example of the virtual PGM prog ramming sections which must be set for virtual PGM 1.
Section [100] : Virtual PGM Options
Option OFF ON
[1] and [2] Virtual PGM Deactivation
[3] Virtual PGM Base Time Selection U Seconds N Minutes [4] Virtual PGM Resend
Section Data Description Default
[101] __/__/__ (000 to 255) x Base Time Virtual PGM 1 Timer 005
Virtual PGM Activation [102] __/__/__ [103] __/__/__ [104] __/__/__ [105] __/__/__
Virtual PGM Deactivation [106] __/__/__ [107] __/__/__ [108] __/__/__ [109] __/__/__
U Message
not resent
Event Group Feature Group Start # End #
Section Section Section Section
N Message
resent
The following describes the programming sections and options specific to the Printer Module’ s virtual PGMs. Use the programming t ables to document specific settings for all programmed virtual PGMs.
Refer to the table below for a list of the programming sections for all virtual PGMs.
Virtual
PGM
1 [100] - [109] 2 [110] - [119] 3 [120] - [129] 4 [130] - [139] 5 [140] - [149] 6 [150] - [159]
Section
Virtual
PGM
7 8
9 10 11 12
Section
[160] - [169] [170] - [179] [180] - [189] [190] - [199] [200] - [209] [210] - [219]
Virtual
PGM
13 14 15 16 17 18
Section
[220] - [229] [230] - [239] [240] - [249] [250] - [259] [260] - [269] [270] - [279]
Virtual
PGM
19 20 21 22 23 24
Section
[280] - [289] 25 [340] - [349] [290] - [299] 26 [350] - [359] [300] - [309] 27 [360] - [369] [310] - [319] 28 [370] - [379] [320] - [329] 29 [380] - [389] [330] - [339] 30 [390] - [399]
Virtual
PGM
Section
For more informat ion on PGM programming, see “Appendix 1: Programming PGMs” on page 22.
Section [100] - Options [1] and [2]
Virtual PGM Deactivation Option
When the Virtual PGM Activation Event occurs (see “Virtual PGM Activation Event” on p age7), this option determines when the virtual PGM will return to its normal st ate (d eactiva te ). Dependi ng on the programmed value, the virtual PGM can stay activated indefinitely. It can also deactivate following a virtual deactivation event (see “Virtual PGM Deactivation Event” on page7) and/or after the virtual PGM timer has elapsed (see “Virtual PGM T imers” on page5).
4
Page 6
U = default setting
Section Virtual PGM [1] OFF / [2] OFF [1] ON / [2] OFF [1] OFF / [2] ON [1] ON / [2] ON
[100] 1 N no deactivation U deactivation event N virtual PGM timer N deactivation event or virtual PGM timer [110] 2 N no deactivation U deactivation event N virtual PGM timer N deactivation event or virtual PGM timer [120] 3 N no deactivation U deactivation event N virtual PGM timer N deactivation event or virtual PGM timer [130] 4 N no deactivation U deactivation event N virtual PGM timer N deactivation event or virtual PGM timer [140] 5 N no deactivation U deactivation event N virtual PGM timer N deactivation event or virtual PGM timer [150] 6 N no deactivation U deactivation event N virtual PGM timer N deactivation event or virtual PGM timer [160] 7 N no deactivation U deactivation event N virtual PGM timer N deactivation event or virtual PGM timer [170] 8 N no deactivation U deactivation event N virtual PGM timer N deactivation event or virtual PGM timer [180] 9 N no deactivation U [190] 10 N no deactivation U deactivation event N virtual PGM timer N deactivation event or virtual PGM timer [200] 11 N no de activation U deactivation event N virtual PGM timer N deactivation event or virtual PGM timer [210] 12 N no deactivation U deactivation event N virtual PGM timer N deactivation event or virtual PGM timer [220] 13 N no deactivation U deactivation event N virtual PGM timer N deactivation event or virtual PGM timer [230] 14 N no deactivation U deactivation event N virtual PGM timer N deactivation event or virtual PGM timer [240] 15 N no deactivation U deactivation event N virtual PGM timer N deactivation event or virtual PGM timer [250] 16 N no deactivation U deactivation event N virtual PGM timer N deactivation event or virtual PGM timer [260] 17 N no deactivation U deactivation event N virtual PGM timer N deactivation event or virtual PGM timer [270] 18 N no deactivation U deactivation event N virtual PGM timer N deactivation event or virtual PGM timer [280] 19 N no deactivation U deactivation event [290] 20 N no deactivation U deactivation event N virtual PGM timer N deactivation event or virtual PGM timer [300] 21 N no deactivation U deactivation event N virtual PGM timer N deactivation event or virtual PGM timer [310] 22 N no deactivation U deactivation event N virtual PGM timer N deactivation event or virtual PGM timer [320] 23 N no deactivation U deactivation event N virtual PGM timer N deactivation event or virtual PGM timer [330] 24 N no deactivation U deactivation event N virtual PGM timer N deactivation event or virtual PGM timer [340] 25 N no deactivation U deactivation event N virtual PGM timer N deactivation event or virtual PGM timer [350] 26 N no deactivation U deactivation event N virtual PGM timer N deactivation event or virtual PGM timer [360] 27 N no deactivation U deactivation event N virtual PGM timer N deactivation event or virtual PGM timer [370] 28 N no deactivation U deactivation event N virtual PGM timer N deactivation event or virtual PGM timer [380] 29 N no deactivation U deactivation event N [390] 30 N no deactivation U deactivation event N virtual PGM timer N deactivation event or virtual PGM timer
deactivation event N virtual PGM timer N deactivation event or virtual PGM timer
N virtual PGM timer N deactivation event or virtual PGM timer
virtual PGM timer N deactivation event or virtual PGM timer
Section [101]
Virtual PGM Timers
If the virtual PGM is set to follow its Virtual PGM Timer (see “Virtual PGM Deactivation Option” on page4), the entered value represents the amount of time that the virtual PGM will remain activated. To program the Virtual PGM Timer, enter a 3-digit value from 000 to 255. Depending on the Virtual PGM Base Time (see “Virtual PGM Base Time Selection” on page 6), the Virtual PGM Timer will either be in seconds or minutes.
Section Virtual PGM Data Section Virtual PGM Data
[101] 1 __/__/__ (000 to 255) x Base time [251] 16 __/__/__ (000 to 255) x Base time [111] 2 __/__/__ (000 to 255) x Base time [261] 17 __/__/__ (000 to 255) x Base time [121] 3 __/__/__ (000 to 255) x Base time [271] 18 __/__/__ (000 to 255) x Base time [131] 4 __/__/__ (000 to 255) x Base time [281] 19 __/__/__ (000 to 255) x Base time [141] 5 __/__/__ (000 to 255) x Base time [291] 20 __/__/__ (000 to 255) x Base time [151] 6 __/__/__ (000 to 255) x Base time [301] 21 __/__/__ (000 to 255) x Base time [161] 7 __/__/__ (000 to 255) x Base time [311] 22 __/__/__ (000 to 255) x Base time [171] 8 __/__/__ (000 to 255) x Base time [321] 23 __/__/__ (000 to 255) x Base time [181] 9 __/__/__ (000 to 255) x Base time [331] 24 __/__/__ (000 to 255) x Base time [191] 10 __/__/__ (000 to 255) x Base time [341] 25 __/__/__ (000 to 255) x Base time [201] 11 __/__/__ (000 to 255) x Base time [351] 26 __/__/__ (000 to 255) x Base time
5
Page 7
[211] 12 __/__/__ (000 to 255) x Base time [361] 27 __/__/__ (000 to 255) x Base time [221] 13 __/__/__ (000 to 255) x Base time [371] 28 __/__/__ (000 to 255) x Base time [231] 14 __/__/__ (000 to 255) x Base time [381] 29 __/__/__ (000 to 255) x Base time [241] 15 __/__/__ (000 to 255) x Base time [391] 30 __/__/__ (000 to 255) x Base time
Section [100] - Option [3]
Virtual PGM Base Time Selection
If option [3] is OFF, the value programmed for the Virtual PGM Timer will be in secon ds. If option [3] is ON, the Virtual PGM Timer will be in minutes. U = default setting
Section
[100] 1 U seconds N minutes [250] 16 U seconds N minutes [110] 2 U seconds N minutes [260] 17 U seconds N minutes [120] 3 U seconds N minutes [270] 18 U seconds N minutes [130] 4 U seconds N minutes [280] 19 U seconds N minutes [140] 5 U seconds N minutes [290] 20 U seconds N minutes [150] 6 U seconds N minutes [300] 21 U seconds N minutes [160] 7 U seconds N minutes [310] 22 U seconds N minutes [170] 8 U seconds N minutes [320] 23 [180] 9 U seconds N minutes [330] 24 U seconds N minutes [190] 10 U seconds N minutes [340] 25 U seconds N minutes [200] 11 U seconds N minutes [350] 26 U seconds N minutes [210] 12 U seconds N minutes [360] 27 U seconds N minutes [220] 13 U seconds N minutes [370] 28 U seconds N minutes [230] 14 U seconds N minutes [380] 29 U seconds N minutes [240] 15 U seconds N minutes [390] 30 U seconds N minutes
Virtual
PGM
[3] OFF [3] ON Section
Virtual
PGM
[3] OFF [3] ON
U seconds N minutes
Section [100] - Option [4]
Virtual PGM Resend Option
If option [4] is ON and a Virtual PGM’s activation event reo ccurs while the virtual PGM is ON, the message sent by the C-Bus entry that is associated with that virtual PGM will be resent. If option [4] is ON and a Virtual PGM’s deactivation event reoccurs while the virtual PGM is OFF, the message sent by the C-Bus entry that is associated with that virtual PGM will be resent.
U = default setting
Section
[100] 1 U message not resent N message resent [250] 16 U message not resent N message resent [110] 2 U message not resent N message resent [260] 17 U message not resent N message resent [120] 3 U message not resent N message resent [270] 18 U message not resent N message resent [130] 4 U message not resent N message resent [280] 19 U message not resent N message resent [140] 5 U message not resent N message resent [290] 20 U message not resent N message resent [150] 6 U message not resent N message resent [300] 21 U message not resent N message resent [160] 7 U message not resent N message resent [310] 22 U message not resent N message resent [170] 8 U message not resent N message resent [320] 23 [180] 9 U message not resent N message resent [330] 24 U message not resent N message resent [190] 10 U message not resent N message resent [340] 25 U message not resent N message resent [200] 11 U message not resent N message resent [350] 26 U message not resent N message resent [210] 12 U message not resent N message resent [360] 27 U message not resent N message resent [220] 13 U message not resent N message resent [370] 28 U message not resent N message resent [230] 14 U message not resent N message resent [380] 29 U message not resent N message resent [240] 15 U message not resent N message resent [390] 30 U message not resent N message resent
Virtual
PGM
[4] OFF [4] ON Section
Virtual
PGM
[4] OFF [4] ON
U message not resent N message resent
6
Page 8
Sections [102] to [105]
Virtual PGM Activation Event
The Virtual PGM Activation Event determines which event will activate the Printer Module’s virtual PGM output(s). The Event Group specifies the event, the Feature Group identifies the source, and the Start # and End # set the range within the Feature Group. Note that Event Groups [064] to [067] may be selected when programming virtual PGMs (see “Appendix 1: Programming PGMs” on page 22).
Event Group Feature Group Start # End #
Section Section Section Section
Virtual PGM1 Virtual PGM2 Virtual PGM3 Virtual PGM4 Virtual PGM5 Virtual PGM6 Virtual PGM7 Virtual PGM8 Virtual PGM9 Virtual PGM10 Virtual PGM11 Virtual PGM12 Virtual PGM13 Virtual PGM14 Virtual PGM15 Virtual PGM16 Virtual PGM17 Virtual PGM18 Virtual PGM19 Virtual PGM20 Virtual PGM21 Virtual PGM22 Virtual PGM23 Virtual PGM24 Virtual PGM25 Virtual PGM26 Virtual PGM27 Virtual PGM28 Virtual PGM29 Virtual PGM30
[102] __/__/__ [103] __/__/__ [104] __/__/__ [105] __/__/__ [112] __/__/__ [113] __/__/__ [114] __/__/__ [115] __/__/__ [122] __/__/__ [123] __/__/__ [124] __/__/__ [125] __/__/__ [132] __/__/__ [133] __/__/__ [134] __/__/__ [135] __/__/__ [142] __/__/__ [143] __/__/__ [144] __/__/__ [145] __/__/__ [152] __/__/__ [153] __/__/__ [154] __/__/__ [155] __/__/__ [162] __/__/__ [163] __/__/__ [164] __/__/__ [165] __/__/__ [172] __/__/__ [173] __/__/__ [174] __/__/__ [175] __/__/__ [182] __/__/__ [183] __/__/__ [184] __/__/__ [185] __/__/__ [192] __/__/__ [193] __/__/__ [194] __/__/__ [195] __/__/__ [202] __/__/__ [203] __/__/__ [204] __/__/__ [205] __/__/__ [212] __/__/__ [213] __/__/__ [214] __/__/__ [215] __/__/__ [222] __/__/__ [223] __/__/__ [224] __/__/__ [225] __/__/__ [232] __/__/__ [233] __/__/__ [234] __/__/__ [235] __/__/__ [242] __/__/__ [243] __/__/__ [244] __/__/__ [245] __/__/__ [252] __/__/__ [253] __/__/__ [254] __/__/__ [255] __/__/__ [262] __/__/__ [263] __/__/__ [264] __/__/__ [265] __/__/__ [272] __/__/__ [273] __/__/__ [274] __/__/__ [275] __/__/__ [282] __/__/__ [283] __/__/__ [284] __/__/__ [285] __/__/__ [292] __/__/__ [293] __/__/__ [294] __/__/__ [295] __/__/__ [302] __/__/__ [303] __/__/__ [304] __/__/__ [305] __/__/__ [312] __/__/__ [313] __/__/__ [314] __/__/__ [315] __/__/__ [322] __/__/__ [323] __/__/__ [324] __/__/__ [325] __/__/__ [332] __/__/__ [333] __/__/__ [334] __/__/__ [335] __/__/__ [342] __/__/__ [343] __/__/__ [344] __/__/__ [345] __/__/__ [352] __/__/__ [353] __/__/__ [354] __/__/__ [355] __/__/__ [362] __/__/__ [363] __/__/__ [364] __/__/__ [365] __/__/__ [372] __/__/__ [373] __/__/__ [374] __/__/__ [375] __/__/__ [382] __/__/__ [383] __/__/__ [384] __/__/__ [385] __/__/__ [392] __/__/__ [393] __/__/__ [394] __/__/__ [395] __/__/__
Sections [106] to [109]
Virtual PGM Deactivation Event
If the Virtual PGM Deactivation Option is set to follow the Virtual PGM Deactivation Event (see “Virtual PGM Deactivation Option” on page 4), the virtual PGM will return to its normal state when the event programmed occurs (see t able below). The Event Group specifies the event, the Feature Group identifies the source, and the Start # and End # set the range within the Feature Group.
Enter the sections that correspond to the Event Group, Feature Group, Start # and End # of the PGM.
Event Group Feature Group Start # End #
Section Section Section Section
Virtual PGM1 Virtual PGM2
[106] __/__/__ [107] __/__/__ [108] __/__/__ [109] __/__/__ [116] __/__/__ [117] __/__/__ [118] __/__/__ [119] __/__/__
7
Page 9
Virtual PGM3 Virtual PGM4 Virtual PGM5 Virtual PGM6 Virtual PGM7 Virtual PGM8 Virtual PGM9 Virtual PGM10 Virtual PGM11 Virtual PGM12 Virtual PGM13 Virtual PGM14 Virtual PGM15 Virtual PGM16 Virtual PGM17 Virtual PGM18 Virtual PGM19 Virtual PGM20 Virtual PGM21 Virtual PGM22 Virtual PGM23 Virtual PGM24 Virtual PGM25 Virtual PGM26 Virtual PGM27 Virtual PGM28 Virtual PGM29 Virtual PGM30
[126] __/__/__ [127] __/__/__ [128] __/__/__ [129] __/__/__ [136] __/__/__ [137] __/__/__ [138] __/__/__ [139] __/__/__ [146] __/__/__ [147] __/__/__ [148] __/__/__ [149] __/__/__ [156] __/__/__ [157] __/__/__ [158] __/__/__ [159] __/__/__ [166] __/__/__ [167] __/__/__ [168] __/__/__ [169] __/__/__ [176] __/__/__ [177] __/__/__ [178] __/__/__ [179] __/__/__ [186] __/__/__ [187] __/__/__ [188] __/__/__ [189] __/__/__ [196] __/__/__ [197] __/__/__ [198] __/__/__ [199] __/__/__ [206] __/__/__ [207] __/__/__ [208] __/__/__ [209] __/__/__ [216] __/__/__ [217] __/__/__ [218] __/__/__ [219] __/__/__ [226] __/__/__ [227] __/__/__ [228] __/__/__ [229] __/__/__ [236] __/__/__ [237] __/__/__ [238] __/__/__ [239] __/__/__ [246] __/__/__ [247] __/__/__ [248] __/__/__ [249] __/__/__ [256] __/__/__ [257] __/__/__ [258] __/__/__ [259] __/__/__ [266] __/__/__ [267] __/__/__ [268] __/__/__ [269] __/__/__ [276] __/__/__ [277] __/__/__ [278] __/__/__ [279] __/__/__ [286] __/__/__ [287] __/__/__ [288] __/__/__ [289] __/__/__ [296] __/__/__ [297] __/__/__ [298] __/__/__ [299] __/__/__ [306] __/__/__ [307] __/__/__ [308] __/__/__ [309] __/__/__ [316] __/__/__ [317] __/__/__ [318] __/__/__ [319] __/__/__ [326] __/__/__ [327] __/__/__ [328] __/__/__ [329] __/__/__ [336] __/__/__ [337] __/__/__ [338] __/__/__ [339] __/__/__ [346] __/__/__ [347] __/__/__ [348] __/__/__ [349] __/__/__ [356] __/__/__ [357] __/__/__ [358] __/__/__ [359] __/__/__ [366] __/__/__ [367] __/__/__ [368] __/__/__ [369] __/__/__ [376] __/__/__ [377] __/__/__ [378] __/__/__ [379] __/__/__ [386] __/__/__ [387] __/__/__ [388] __/__/__ [389] __/__/__ [396] __/__/__ [397] __/__/__ [398] __/__/__ [399] __/__/__

C-Bus Entry Options

C-Bus entries allow you to set the commands that will be sent on the C-Bus in relation to events that occur wi thin the Digiplex system. When the state of a virtual PGM on the Printer Module changes, a message is sent by the C-Bus entry that is associated with that virtual PGM. Up to 30 C-Bus entries can be associated with the Printer Module’s virtual PGMs. Multiple C-Bus entries can be associated with a single virtual PGM.
The tables below offer an example of th e C-Bu s entry pr ogramming sections which must be set for C-Bu s entry 1.
Section [400] : C-Bus Entry Options
Option OFF ON
[1] Application Selection U Lighting N Air Conditioning
[2] and [3] ON Command
[4] and [5] OFF Command
* Not used with air-conditioning
8
Page 10
Section Data Description Default
[401] __/__/__ (001 to 030)
[402] __/__/__ (000 to 255)
Virtual PGM Association
ON Group Address Variable
000
000
[403] __/__/__ (000 to 015)
[404] __/__/__ (000 to 255) ON Ramp Final Level 000*
[405] __/__/__ (000 to 255)
[406] __/__/__ (000 to 015) OFF Ramp Period 000*
[407] __/__/__ (000 to 255) OFF Ramp Final Level 000*
ON Ramp Period
OFF Group Address Variable
000*
000
*Not used with air-conditioning (values ignored if selected) Refer to the table below for a list of the programming sections for all virtual PGMs.
C-Bus
Entry
1 [400] - [407] 7 [460] - [467] 13 [520] - [527] 19 [580] - [587] 25 [640] - [647] 2 [410] - [417] 8 [470] - [477] 14 [530] - [537] 20 [590] - [597] 26 [650] - [657] 3 [420] - [427] 9 [480] - [487] 15 [540] - [547] 21 [600] - [607] 27 [660] - [667] 4 [430] - [437] 10 [490] - [497] 16 [550] - [557] 22 [610] - [617] 28 [670] - [677] 5 [440] - [447] 11 [500] - [507] 17 [560] - [567] 23 [620] - [627] 29 [680] - [687] 6 [450] - [457] 12 [510] - [517] 18 [570] - [577] 24 [630] - [637] 30 [690] - [697]
Section
C-Bus
Entry
Section
C-Bus
Entry
Section
C-Bus
Entry
Section
C-Bus
Entry
Section
The following describes the programming sections and options specific to the C-Bus entries. Use the progra mming t ables to docum ent specific settings for all programmed C-Bus entries.
Section [400] - Option [1]
Application Selection
When option [1] is OFF, C-Bus entries are associated with lighting application. When option [1] is ON, C-Bus entries are associated with air-conditioning application.
= default setting
U
Section
C-Bus
Entry
[1] OFF [1] ON Section
C-Bus
Entry
[1] OFF [1] ON
[400] 1 U lighting N air-conditioning [550] 16 U lighting N air-conditioning [410] 2 U lighting N air-conditioning [560] 17 U lighting N air-conditioning [420] 3 U lighting N air-conditioning [570] 18 U lighting N air-conditioning [430] 4 U lighting N air-conditioning [580] 19 U lighting N air-conditioning [440] 5 U lighting N air-conditioning [590] 20 U lighting N air-conditioning [450] 6 U lighting N air-conditioning [600] 21 U lighting N air-conditioning [460] 7 U lighting N air-conditioning [610] 22 U lighting N air-conditioning [470] 8 U lighting N air-conditioning [620] 23
U lighting N air-conditioning [480] 9 U lighting N air-conditioning [630] 24 U lighting N air-conditioning [490] 10 U lighting N air-conditioning [640] 25 U lighting N air-conditioning [500] 11 U lighting N air-conditioning [650] 26 U lighting N air-conditioning [510] 12 U lighting N air-conditioning [660] 27 U lighting N air-conditioning [520] 13 U lighting N air-conditioning [670] 28 U lighting N air-conditioning [530] 14 U lighting N air-conditioning [680] 29 U lighting N air-conditioning [540] 15 U lighting N air-conditioning [690] 30 U lighting N air-conditioning
9
Page 11
Section [400] - Options [2] and [3]
ON Commands
This option allows you to choose the type of command that will be sent through the C-Bus entry af ter the st ate of it s associated virtual PGM changes from OFF to ON. The types of commands include ON, OFF or ramp.
= default setting
U
Section C-Bus Entry [2] OFF / [3] OFF [2] ON / [3] OFF [2] OFF / [3] ON [2] ON / [3] ON*
[400] 1 U none N on N off N ramp [410] 2 U none N on N off N ramp [420] 3 U none N on N off N ramp [430] 4 U none N on N off N ramp [440] 5 U none N on N off N ramp [450] 6 U none N on N off N ramp [460] 7 U none N on N off N ramp [470] 8 U none N on N off N ramp [480] 9 U none N on N off N ramp [490] 10 U none N on N [500] 11 U none N on N off N ramp [510] 12 U none N on N off N ramp [520] 13 U none N on N off N ramp [530] 14 U none N on N off N ramp [540] 15 U none N on N off N ramp [550] 16 U none N on N off N ramp [560] 17 U none N on N off N ramp [570] 18 U none N on N off N ramp [580] 19 U none N on N off N ramp [590] 20 U none N on N off [600] 21 U none N on N off N ramp [610] 22 U none N on N off N ramp [620] 23 U none N on N off N ramp [630] 24 U none N on N off N ramp [640] 25 U none N on N off N ramp [650] 26 U none N on N off N ramp [660] 27 U none N on N off N ramp [670] 28 U none N on N off N ramp [680] 29 U none N on N off N ramp [690] 30 U none N on N off N
* Not used with air conditioning
off N ramp
N ramp
ramp
10
Page 12
Section [400] - Options [4] and [5]
OFF Commands
This option allows you to choose the type of command that will be sent through the C-Bus entry af ter the st ate of it s associated virtual PGM changes from ON to OFF. The types of commands include ON, OFF or ramp.
= default setting
U
Section C-Bus Entry [4] OFF / [5] OFF [4] ON / [5] OFF [4] OFF / [5] ON [4] ON / [5] ON*
[400] 1 U none N on N off N ramp [410] 2 U none N on N off N ramp [420] 3 U none N on N off N ramp [430] 4 U none N on N off N ramp [440] 5 U none N on N off N ramp [450] 6 U none N on N off N ramp [460] 7 U none N on N off N ramp [470] 8 U none N on N off N ramp [480] 9 U none N on N off N ramp [490] 10 U none N on N [500] 11 U none N on N off N ramp [510] 12 U none N on N off N ramp [520] 13 U none N on N off N ramp [530] 14 U none N on N off N ramp [540] 15 U none N on N off N ramp [550] 16 U none N on N off N ramp [560] 17 U none N on N off N ramp [570] 18 U none N on N off N ramp [580] 19 U none N on N off N ramp [590] 20 U none N on N off [600] 21 U none N on N off N ramp [610] 22 U none N on N off N ramp [620] 23 U none N on N off N ramp [630] 24 U none N on N off N ramp [640] 25 U none N on N off N ramp [650] 26 U none N on N off N ramp [660] 27 U none N on N off N ramp [670] 28 U none N on N off N ramp [680] 29 U none N on N off N ramp [690] 30 U none N on N off N
* Not used with air conditioning
off N ramp
N ramp
ramp
Section [401]
Virtual PGM Association
The Virtual PGM Association section allows you to associate a C-Bus entry (or entries) with one of the Printer Module’ s virtual PGMs. Enter
001-030 to individually assign each C-Bus entry to a virtual PGM. Multiple C-Bus entries can be associated with the same virtual PGM.
Section C-Bus Entry Associated PGM Section C-Bus Entry Associated PGM
[401] 1 [551] 16 [411] 2 [561] 17
11
.
Page 13
[421] 3 [571] 18 [431] 4 [581] 19 [441] 5 [591] 20 [451] 6 [601] 21 [461] 7 [611] 22 [471] 8 [621] 23 [481] 9 [631] 24 [491] 10 [641] 25 [501] 11 [651] 26 [511] 12 [661] 27 [521] 13 [671] 28 [531] 14 [681] 29 [541] 15 [691] 30
Section [402]
ON Group Address Variable
The ON Group Address Variable section allows you to assign which C-Bus group will receive the programmed ON command (see “ON Commands” on page 10). Enter 000-255 to assign each C-Bus entry to a group address.
For further information on Group Address Variables, refer to the appropriate C-Bus documentation.
Section C-Bus Entry
[402] 1 [552] 16 [412] 2 [562] 17 [422] 3 [572] 18 [432] 4 [582] 19 [442] 5 [592] 20 [452] 6 [602] 21 [462] 7 [612] 22 [472] 8 [622] 23 [482] 9 [632] 24 [492] 10 [642] 25 [502] 11 [652] 26 [512] 12 [662] 27 [522] 13 [672] 28 [532] 14 [682] 29 [542] 15 [692] 30
ON Ramp Period *Not used with air conditioning
The ON Ramp Period section allows you to assign a ramp time value when an ON Ramp command has been set (see “ON Commands” on page 10). The following table list s the Ramp Period prog rammed value s and their corresp ondin g real-time values.
Ramp Period Programmed
Value
000 Instant 004 20s 008 90s 012 7min 001 4s 005 30s 009 2min 013 10min 002 8s 006 40s 010 3min 014 15min 003 12s 007 60s 011 5min 015 17min
Real-Time
Value
Ramp Period Programmed
ON Group Address
Value
Variable
Real-Time
Value
Section C-Bus Entry
Ramp Period Programmed
Value
Real-Time
Value
Ramp Period Programmed
ON Group Address
Section [403]*
Value
Variable
Real-Time
Value
12
Page 14
Enter 000-015 to assign each C-Bus entry an ON Ramp Period.
Section C-Bus Entry ON Ramp Period Section C-Bus Entry ON Ramp Period
[403] 1 [553] 16 [413] 2 [563] 17 [423] 3 [573] 18 [433] 4 [583] 19 [443] 5 [593] 20 [453] 6 [603] 21 [463] 7 [613] 22 [473] 8 [623] 23 [483] 9 [633] 24 [493] 10 [643] 25 [503] 11 [653] 26 [513] 12 [663] 27 [523] 13 [673] 28 [533] 14 [683] 29 [543] 15 [693] 30
Section [404]*
ON Ramp Final Level * Not used with air conditioning
The ON Ramp Final Level section allows you to assign a final level of light intensity when an ON Ramp command has been set (see “ON Commands” on page 10). Enter 000-255 to assign each C-Bus entry an ON Ramp Fin al Level.
For further information on lighting intensity levels associated with th e ON Ramp command, re fe r to the appro priate C-Bu s documentation.
Section C-Bus Entry
[404] 1 [554] 16 [414] 2 [564] 17 [424] 3 [574] 18 [434] 4 [584] 19 [444] 5 [594] 20 [454] 6 [604] 21 [464] 7 [614] 22 [474] 8 [624] 23 [484] 9 [634] 24 [494] 10 [644] 25 [504] 11 [654] 26 [514] 12 [664] 27 [524] 13 [674] 28 [534] 14 [684] 29 [544] 15 [694] 30
ON Ramp Final
Level
Section C-Bus Entry
ON Ramp Final
Level
Section [405]
OFF Group Address Variable
The OFF Group Address V ariable section allows you to assi gn which C-Bus gro up will rece ive the pro grammed OFF command (see “OFF Commands” on page 11). Enter 000-255 to assign each C-Bus entry to a group address.
For further information on Group Address Variables, refer to the appropriate C-Bus documentation.
13
Page 15
Section C-Bus Entry
[405] 1 [555] 16 [415] 2 [565] 17 [425] 3 [575] 18 [435] 4 [585] 19 [445] 5 [595] 20 [455] 6 [605] 21 [465] 7 [615] 22 [475] 8 [625] 23 [485] 9 [635] 24 [495] 10 [645] 25 [505] 11 [655] 26 [515] 12 [665] 27 [525] 13 [675] 28 [535] 14 [685] 29 [545] 15 [695] 30
OFF Ramp Period * Not used with air conditioning
The OFF Ramp Period section allows you to assign a ramp time value when an OFF Ramp command has been set (see “OFF Commands” on page 11). Enter 000-015 to assign each C-Bus entry an OFF Ramp Period.
OFF Group
Address Variable
Section C-Bus Entry
OFF Group
Address Variable
Section [406]*
Section C-Bus Entry OFF Ramp Period Section C-Bus Entry OFF Ramp Period
[406] 1 [556] 16 [416] 2 [566] 17 [426] 3 [576] 18 [436] 4 [586] 19 [446] 5 [596] 20 [456] 6 [606] 21 [466] 7 [616] 22 [476] 8 [626] 23 [486] 9 [636] 24 [496] 10 [646] 25 [506] 11 [656] 26 [516] 12 [666] 27 [526] 13 [676] 28 [536] 14 [686] 29 [546] 15 [696] 30
Section [407]*
OFF Ramp Final Level * Not used with air conditioning
The OFF Ramp Final Level section allows you to assign a final level of light intensity when an OFF Ramp comma nd has been set (see “OFF Commands” on page 11). Enter 000-255 to assign each C-Bus entry an OFF Ramp Final Level.
For further information on lighting intensity levels associated with th e OFF Ramp command , refer to the appropriate C-Bus documentation.
14
Page 16
Section C-Bus Entry
OFF Ramp Final
Level
Section C-Bus Entry
OFF Ramp Final
Level
[407] 1 [557] 16 [417] 2 [567] 17 [427] 3 [577] 18 [437] 4 [587] 19 [447] 5 [597] 20 [457] 6 [607] 21 [467] 7 [617] 22 [477] 8 [627] 23 [487] 9 [637] 24 [497] 10 [647] 25 [507] 11 [657] 26 [517] 12 [667] 27 [527] 13 [677] 28 [537] 14 [687] 29 [547] 15 [697] 30

Virtual Input Options

The Print er M o dule features 16 v i r t ua l i np u ts. The virtual inputs’ open/close state can change based on an event that has occurred within C-Bus. The following describes the programming sections and options specific to the Printer Module’s virtual inputs. Virtual inputs must be programmed with the appropriate C-Bus application, group address variable and type of command which will cause the virtual input to react (open/close).
The tables below offer an example of th e virtua l input pr ogramming sections which must be set for virtual input 1.
Section [700] : Virtual Input Options
Option OFF ON
[1] Enabling Virtual Input U Disabled N Enabled [2] C-Bus Application Selection U Lighting N Air-conditioning
[3] and [4] Virtual Input Close
[5]
Section Data Description Default
[701] __/__/__ (000 to 255) x Base Time Virtual Input 1 Timer 005
[702] __/__/__ (000 to 255)
[703] __/__/__ (000 to 002)
[704] __/__/__ (000 to 255)
[705] __/__/__ (000 to 002)
Virtual Input Base Time
Selection
U Seconds N Minutes
Virtual Input 1 Open Group Address Variable
Virtual Input 1 Open Command
Virtual Input 1 Close Group Address Variable
Virtual Input 1 Close Command
000
000*
000
000*
[706] __/__/__ (000 to 255) Ramp Threshold 000*
15
Page 17
*Ramp command not used with air conditioning Refer to the table below for a list of the programming sections for all virtual input s.
Virtual
Input
1 [700] - [706] 5 [740] - [746] 9 [780] - [786] 13 [820] - [826] 2 [710] - [716] 6 [750] - [756] 10 [790] - [796] 14 [830] - [836] 3 [720] - [726] 7 [760] - [766] 11 [800] - [806] 15 [840] - [846] 4 [730] - [736] 8 [770] - [776] 12 [810] - [816] 16 [850] - [856]
Section
Virtual
Input
Section
Virtual
Input
Section
Virtual
Input
Section
The following describes the programming sections and options specific to the Printer Module’ s virtual input s. Use the programming t ables to document specific settings for all programmed virtual inputs.
Section [700] - Option [1]
Enabling Virtual Input Option
Each virtual input must be individually enabled. Set option [1] to ON to enable the virtual input.
U = default setting
Section
Virtual
Input
[1] OFF [1] ON Section
Virtual
Input
[1] OFF [1] ON
[700] 1 U disabled N enabled [780] 9 U disabled N enabled [710] 2 U disabled N enabled [790] 10 U disabled N enabled [720] 3 U disabled N enabled [800] 11 U disabled N enabled [730] 4 U disabled N enabled [810] 12 U disabled N enabled [740] 5 U disabled N enabled [820] 13 U disabled N enabled [750] 6 U disabled N enabled [830] 14 U disabled N enabled [760] 7 U disabled N enabled [840] 15 U disabled N enabled [770] 8 U disabled N enabled [850] 16
U disabled N enabled
Section [700] - Option [2]
C-Bus Application Selection
Each virtual input must be programmed to use a specific C-Bus application to monitor C-Bus activity. If option [2] is OFF, lighting application is used. If option [2] is ON, air-conditioning application is used.
U = default setting
Section
Virtual
Input
[2] OFF [2] ON Section
Virtual
Input
[2] OFF [2] ON
[700] 1 U lighting N air-conditioning [780] 9 U lighti ng N air-conditioning [710] 2 U lighting N air-conditioning [790] 10 U lighting N air-conditioning [720] 3 U lighting N air-conditioning [800] 11 U lighting N air-conditioning [730] 4 U lighting N air-conditioning [810] 12 U lighting N air-conditioning [740] 5 U lighting N air-conditioning [820] 13 U lighting N air-conditioning [750] 6 U lighting N air-conditioning [830] 14 U lighting N air-conditioning [760] 7 U lighting N air-conditioning [840] 15 U lighting N air-conditioning [770] 8 U lighting N air-conditioning [850] 16
U lighting N air-conditioning
16
Page 18
Section [700] - Options [3] and [4]
Virtual Input Close Option
The virtual input can be closed by either receiving a virtual input close command, after a timer elapses or either. This option determines how the virtual input will close.
U = default setting
Section Virtual Input [3] OFF / [4] OFF [3] ON / [4] OFF [3] OFF / [4] ON
[700] 1 U close command N virtual input timer N close command or virtual input timer [710] 2 U close command N virtual input timer N close command or virtual input timer [720] 3 U close command N virtual input timer N close command or virtual input timer [730] 4 U close command N virtual input timer N close command or virtual input timer [740] 5 U close command N virtual input timer N close command or virtual input timer [750] 6 U close command N virtual input timer N close command or virtual input timer [760] 7 U close command N virtual input timer N close command or virtual input timer [770] 8 U close command N virtual input timer N close command or virtual input timer [780] 9 U close command N virtual input timer N close command or virtual input timer [790] 10 U close command N virtual input timer N close command or virtua l input timer [800] 11 U close command N virtual input timer N close command or virtual input timer [810] 12 U close command N virtual input timer N close command or virtua l input timer [820] 13 [830] 14 U close command N virtual input timer N close command or virtua l input timer [840] 15 U close command N virtual input timer N close command or virtua l input timer [850] 16 U close command N virtual input timer N close command or virtua l input timer
U close command N virtual input timer N close command or virtual input timer
Section [701]
Virtual Input Timers
If the virtual input is set to follow its Virtua l Input Timer, the entered value represe nt s the amount of ti me th at th e virtual input wi ll remain open. To program the Virtual Input Timer, enter a 3-digit value from 000 to 255. Depending on the V irtual Input Base T ime (see “Virtual Input Base Time Selection” on page17), the Virtual Input Timer will either be in seconds or minutes.
Section Virtual Input Timer Data Section Virtual Input Timer Data
[701] 1 __/__/__ (000 to 255) x Base time [781] 9 __/__/__ (000 to 255) x Base time [711] 2 __ /__ /__ (000 to 255) x Base time [791] 10 __/__/__ (000 to 255) x Base time [721] 3 __/__/__ (000 to 255) x Base time [801] 11 __/__/__ (000 to 255) x Base time [731] 4 __/__/__ (000 to 255) x Base time [811] 12 __/__/__ (000 to 255) x Base time [741] 5 __/__/__ (000 to 255) x Base time [821] 13 __/__/__ (000 to 255) x Base time [751] 6 __/__/__ (000 to 255) x Base time [831] 14 __/__/__ (000 to 255) x Base time [761] 7 __/__/__ (000 to 255) x Base time [841] 15 __/__/__ (000 to 255) x Base time [771] 8 __/__/__ (000 to 255) x Base time [851] 16 __/__/__ (000 to 255) x Base time
Section [700] - Option [5]
Virtual Input Base Time Selection
If option [5] is OFF, the value programmed for the Virtual Input Timer will be in seconds. If op tion [5] is ON, the Virtual Input Timer will be in minutes. The following table lists the base time sections and their respecti ve virtual inputs.
17
Page 19
U = default setting
Section
[700] 1 U seconds N minutes [780] 9 U seconds N minutes [710] 2 U seconds N minutes [790] 10 U seconds N minutes [720] 3 U seconds N minutes [800] 11 U seconds N minutes [730] 4 U seconds N minutes [810] 12 U seconds N minutes [740] 5 U seconds N minutes [820] 13 U seconds N minutes [750] 6 U [760] 7 U seconds N minutes [840] 15 U seconds N minutes [770] 8 U seconds N minutes [850] 16 U seconds N minutes
Virtual Input Open Group Address Variable
The Virtual Input Open Group Address Variable section allows you to set which C-Bus group will cause a virtual input on the Printer Module to open. Enter 000-255 to assign which group address variable will trigger a virtual input to open.
For further information on Group Address Variables, refer to the appropriate C-Bus documentation.
Virtual
Input
[5] OFF [5] ON Section
seconds N minutes [830] 14 U seconds N minutes
Virtual
Input
[5] OFF [5] ON
Section [702]
Section Virtual Input
[702] 1 [782] 9 [712] 2 [792] 10 [722] 3 [802] 11 [732] 4 [812] 12 [742] 5 [822] 13 [752] 6 [832] 14 [762] 7 [842] 15 [772] 8 [852] 16
Virtual Input Open Command
The Virtual Input Open Command section sets the state of a virtual input to open wh en an ON, OFF or Ramp command occurs within C­Bus. The open command is based on the Open Group Addre ss Variable and on the C-Bus application selected above. Enter 000 to set the virtual input to open in response to an ON command, 001 to set the virtual input to open in response to an OFF command or 002 to set the virtual input to open in response to a Ramp command.
Section
[703] 1 U 000 N 001 N 002 [783] 9 U 000 N 001 N 002 [713] 2 U 000 N 001 N 002 [793] 10 U 000 N 001 N 002 [723] 3 U 000 N 001 N 002 [803] 11 U 000 N 001 N 002 [733] 4 U 000 N 001 N 002 [813] 12 U 000 N 001 N 002 [743] 5 U 000 N 001 N 002 [823] 13 U 000 N 001 N 002 [753] 6 U 000 N 001 N 002 [833] 14 U 000 [763] 7 U 000 N 001 N 002 [843] 15 U 000 N 001 N 002 [773] 8 U 000 N 001 N 002 [853] 16 U 000 N 001 N 002
* Not used with air conditioning
Virtual
Input
ON OFF Ramp* Section
Open Group
Address Variable
Section Virtual Input
Virtual
Input
ON OFF Ramp*
Open Group
Address Variable
Section [703]
U = default setting
N 001 N 002
18
Page 20
Section [704]
Virtual Input Close Group Address Variable
The Virtual Input Open Group Address Variable section allows you to set which C-Bus group will cause a virtual input on the Printer Module to close. Enter 000-255 to assign which group address variable will trigger a virtual input to close.
For further information on Group Address Variables, refer to the appropriate C-Bus documentation.
Section Virtual Input
[704] 1 [784] 9 [714] 2 [794] 10 [724] 3 [804] 11 [734] 4 [814] 12 [744] 5 [824] 13 [754] 6 [834] 14 [764] 7 [844] 15 [774] 8 [854] 16
Virtual Input Close Command
The Virtual Input Close Command section sets the state of a virtual input to close when an ON , OFF or Ramp command occurs withi n C­Bus. The close command is based on the Close Group Address Variable and on the C-Bus application selected above. Enter 000 to set the virtual input to close in response to an ON command, 001 to set the virtual input to close in response to an OFF command or 002 to set the virtual input to close in response to a Ramp command.
Section
[705] 1 U 000 N 001 N 002 [785] 9 U 000 N 001 N 002 [715] 2 U 000 N 001 N 002 [795] 10 U 000 N 001 N 002 [725] 3 U 000 N 001 N 002 [805] 11 U 000 N 001 N 002 [735] 4 U 000 N 001 N 002 [815] 12 U 000 N 001 N 002 [745] 5 U 000 N 001 N 002 [825] 13 U 000 N 001 N 002 [755] 6 U 000 N 001 N 002 [835] 14 U 000 [765] 7 U 000 N 001 N 002 [845] 15 U 000 N 001 N 002 [775] 8 U 000 N 001 N 002 [855] 16 U 000 N 001 N 002
* Not used with air conditioning
Virtual
Input
ON OFF Ramp* Section
Close Group
Address Variable
Section Virtual Input
Virtual
Input
ON OFF Ramp*
Close Group
Address Variable
Section [705]
U = default setting
N 001 N 002
Section [706]*
Ramp Threshold * Not used with air conditioning
The Ramp Threshold section allows you to set a threshold level to Ramp commands occurring within C-Bus. To open a virtu al input, the Ramp’s Final Level must be greater or equal to the threshold value. To close a virtual input, the Ramp’s Final level must be lower th an the threshold value. Enter 000-255 to set the virtual input’ s threshold level.
Section Virtual Input Ramp Threshold Section Virtual Input Ramp Threshold
[706] 1 [786] 9 [716] 2 [796] 10 [726] 3 [806] 11 [736] 4 [816] 12 [746] 5 [826] 13 [756] 6 [836] 14 [766] 7 [846] 15 [776] 8 [856] 16
19
Page 21
Section [900]
Security Report
Security reports are messages sent between the APR-PRT3 and the C-Bu s. Messages that are rece iv ed by the C-Bus can be used to trigger automated events.
Section Data Description Default
[900] __/__/__ (001 to 008)† Partition affected by security application 001
Section
901
Report Options OFF ON
[1] Global Security report* N = Disable U = Enable [2]
System Armed / Disarmed
N = Disable U = Enable
[3] Entry / Exit delay N = Disable U = Enable [4] Zone in alarm / Zone in alarm restore (zones 01 to 80)‡ N = Disable U = Enable [5] Fire Alarm / Fire Alarm Restore N = Disable U = Enable [6] Silent Alarm Report / Silent Alarm Restore N = Disable U = Enable [7] Panic Alarm N = Disable U = Enable [8] Future use N = N/A U =N/A
* If Global Security report is disabled, all options in sections [901] and [902] will also be disabled.
Section
902
Report Options OFF ON
[1] Low Battery / Low Battery Restored (zones 01 to 80)‡ N = Disable U = Enable [2] AC Failure / AC Failure restore N = Disable U = Enable [3] Ready to arm / Not ready to arm N = Disable U = Enable [4] Zone open / Zone ok (zones 01 to 80)‡ N = Disable U = Enable [5] Zone tamper / Zone tamper restore (zones 01 to 80)‡ N = Disable U = Enable [6] Zone Bypassed (zones 01 to 80)‡ N = Disable U = Enable [7] User Code entered on Keypad N = Disable U = Enable [8] TLM T rouble/TLM Trouble Restore N
= Disable U = Enable
Section
903
Messages from C-Bus OFF ON
[1] Arm system* N = Forbid U = Allow [2] Raise alarm** N = Forbid U = Allow [3] C-Bus tamper / C-Bus tamper restore*** N = Forbid U = Allow [4] Future use N = N/A U =N/A [5] Future use N = N/A U =N/A [6] Future use N = N/A U =N/A [7] Future use N = N/A U =N/A [8] Future use N = N/A U =N/A
EVO96 allows 8 partitions, Digiplex 848 allow 4 partitions.
Due to C-Bus limitation, only zones 01 from zones 80 can be reported, C-Bus Network will ignore all others.
*
Must enable One-touch regular arming option in the control panel.
**
Alarm will be raised as a Panic Alarm to chosen partitions.
***
Tamper from C-Bus will be reported as a Printer tamper.
20
Page 22
Figure 2: .APR-PRT3 Connection
Remove AC power and battery before adding a module to the sytem. Refer to the Digiplex DGP-848 or DGP-NE96 Reference and Installation Manual for the maximum
allowable installation distance from the control panel.
Printer cable length must not exceed 25ft.
For information on using the printer Module as an interface with home automation modules, see the ASCII Protocol programming instructions or C-BUS Programming instructions.
1. Green “RX” LED: Flashes when the Printer Module is receiving data through the serial port only.
2. Red “TX” LED: Flashes when the Printer Module is transmitting data through the serial port only.
3. 25-Pin Parallel Port: Connect the Printer Module’s 25-pin parallel port to any dot matrix printer. Note: The dot matrix printer must support a minimum of 80 columns.
4. 9-Pin Serial Port: Connect the Printer Module’s 9-Pin serial port to a dot matrix printer. Note: The dot matrix printer must support a minimum of 80 columns.
5. 9-pin Serial Port: Connect the Printer Module’s 9-pin serial port to a home automation module.
6. 9-pin Serial Port: Connect C-Bus to the Printer Module using a null modem cable.
7. 9-pin Serial Port: Connect either the Printer Module’s USB or 9-pin serial port to a computer’s COM port to view the control panel’s events on the computer’s monitor. The events display on the monitor can then be printed through the printer connected to the computer.
21
Page 23

Appendix 1: Programming PGMS

A PGM is a programmable output that toggles to its opposite st ate (i .e. a no rmally open PGM will close) when a specific e vent occ urs in the system. For example, a PGM can be used to reset smoke detectors, activate strobe lights, open/close garage doors and much more.

PGM Activation Event

The PGM Activation Event determines which event from what source will activate the PGM. The Event Group specifies the event, the Feature Group identifies the source, and the Start # and End # sets the range within the Feature Group (see PGM Programming Table below).
For example, the APR-PRT3 can activate Virtual PGM1 when the a rea is armed by User Access Codes 256 to 26 0. Therefore: Event Group section [102] = 010 “Arming with User Code” Feature Group section [103] = 001 “User Codes 256 to 511” Start # section [104] = 000 (representing user code 256) End # section [105] = 004 (representing user code 260)
Enter the sections that correspond to the Event Group, Feature Group, Start # and End # of the desired PGM and enter the data as required.

PGM Deactivation Option

Once the PGMs are activated, they can deactivate when another event occurs or after a period of time. The PGM D eactivati on Option determines which method is used, the PGM Deactivation Event or the PGM Timer. Enter the section that corresponds to the desired PGM and enable or disable the option.

PGM Deactivation Event

When the PGM Deactivation Option (see above) is disabled, the PGM Deactivation Event determines which event from what source will return the PGM to its original state. T he Event Grou p specifies the event, the Feature Grou p identifies the source, and the Start # and End # determine the range within the Feature Group. The complete PGM Programming Table appears below.
For example, the APR-PRT3 can deactivate Virtual PGM1 when zone 3 opens. Therefore: Event Group section [106] = 001 “Zone is Open” Feature Group section [107] = 000 “Zone Numbers” Start # section [108] = 003 End # section [109] = 003
Enter the sections that correspond to the Event Group, Feature Group, Start # and End # of the desired PGM and enter the data as required.

PGM Programming Table

Event Group Featu re Group Start # End #
PGM Activation
Event
PGM Deactivation
Event
Event
Group
000 Zone is OK 001 Zone is Open 001 to 096 001 to 096 002 Zone is Tampered 001 to 096 001 to 096 003 Zone is in Fire Loop Trouble 001 to 096 001 to 096
PGM __/__/__ __/__/__ __/__/__ __/__/__
PGM __/__/__ __/__/__ __/__/__ __/__/__
Event Feature Group Feature Start # End #
001 to 096 001 to 096
000
255 = any Zone #
Zone Numbers
22
Page 24
Event
Group
004 Non-reportable Event
005
006 User/Card Access on door
007 Bypass Programming Access
008 TX Delay Zone Alarm
009 Arming with Master
010 Arming with User Code
011 Arming with Keyswitch
User Code entered on Keypad
Event Feature Group Feature Start # End #
TLM Trouble (see NOTE 3 on
page 28)
Smoke detector reset 001 001
Arm with no entry delay 002 002
Arm in Stay mode 003 003
Arm in Away mode 004 004
Full arm when in Stay mode 005 005
000
255 Any non-reportable event Not Used Not Used 000 User Codes 000 to 255 000 to 255 000 to 255 001 User Codes 256 to 511 000 to 255 000 to 255 002 User Codes 512 to 767 000 to 255 000 to 255 003 User Codes 768 to 999 000 to 231 000 to 231 255 Any User Code Not Used Not Used 000 Door Numbers 001 to 032 001 to 032 255 Any door number Not Used Not Used 000 One-touch Bypass Programming 000 000 000 User Codes 001 to 255 001 to 255 001 to 255 001 User Codes 256 to 511 000 to 255 000 to 255 002 User Codes 512 to 767 000 to 255 000 to 255 003 User Codes 768 to 999 000 to 231 000 to 231 255 Any User Code Not Used Not Used 000 Zone Numbers 001 to 096 001 to 096 255 Any zone number Not Used Not Used 000 User Codes 001 to 255 001 to 255 001 to 255 001 User Codes 256 to 511 000 to 255 000 to 255 002 User Codes 512 to 767 000 to 255 000 to 255 003 User Codes 768 to 999 000 to 231 000 to 231 255 Any User Code Not Used Not Used 000 User Codes 001 to 255 001 to 255 001 to 255 001 User Codes 256 to 511 000 to 255 000 to 255 002 User Codes 512 to 767 000 to 255 000 to 255 003 User Codes 768 to 999 000 to 231 000 to 231 255 Any User Code Not Used Not Used 000 Keyswitch numbers 001 to 032 001 to 032 255 Any keyswitch number Not Used Not Used
Voice mo dule access 006 006
Remote control access 007 007
PC Fail to communicate 008 008
Midnight 009 009
NEware User Login 010 010
NEware User Logout 011 011
User Initiated Callup 012 012
Force Answer 013 013
Force Hangup 014 014
000 000
23
Page 25
Event
Group
012 Special Arming
013 Disarm with Master
014 Disarm with User Code
015 Disarm with Keyswitch
016
017
018
019 Alarm Cancelled with Master
020
021
Disarm after alarm with Master
Disarm after alarm with User Code
Disarm after alarm with Keyswitch
Alarm Cancelled with User Code
Alarm Cancelled with Keyswitch
Event Feature Group Feature Start # End #
Auto Arming 000 000
Arming by WinLoad 001 001
Late to Close 002 002
000
255 Any special arming event Not Used Not Used 000 User Codes 001 to 255 001 to 255 001 to 255 001 User Codes 256 to 511 000 to 255 000 to 255 002 User Codes 512 to 767 000 to 255 000 to 255 003 User Codes 768 to 999 000 to 231 000 to 231 255 Any User Code Not Used Not Used 000 User Codes 001 to 255 001 to 255 001 to 255 001 User Codes 256 to 511 000 to 255 000 to 255 002 User Codes 512 to 767 000 to 255 000 to 255 003 User Codes 768 to 999 000 to 231 000 to 231 255 Any User Code Not Used Not Used 000 Keyswitch numbers 001 to 032 001 to 032 255 Any keyswitch Not Used Not Used 000 User Codes 001 to 255 001 to 255 001 to 255 001 User Codes 256 to 511 000 to 255 000 to 255 002 User Codes 512 to 767 000 to 255 000 to 255 003 User Codes 768 to 999 000 to 231 000 to 231 255 Any User Code Not Used Not Used 000 User Codes 001 to 255 001 to 255 001 to 255 001 User Codes 256 to 511 000 to 255 000 to 255 002 User Codes 512 to 767 000 to 255 000 to 255 003 User Codes 768 to 999 000 to 231 000 to 231 255 Any User Code Not Used Not Used 000 Keyswitch numbers 001 to 032 001 to 032 255 Any keyswitch Not Used Not Used 000 User Codes 001 to 255 001 to 255 001 to 255 001 User Codes 256 to 511 000 to 255 000 to 255 002 User Codes 512 to 767 000 to 255 000 to 255 003 User Codes 768 to 999 000 to 231 000 to 231 255 Any User Code Not Used Not Used 000 User Codes 001 to 255 001 to 255 001 to 255 001 User Codes 256 to 511 000 to 255 000 to 255 002 User Codes 512 to 767 000 to 255 000 to 255 003 User Codes 768 to 999 000 to 231 000 to 231 255 Any User Code Not Used Not Used 000 Keyswitch numbers 001 to 032 001 to 032 255 Any keyswitch Not Used Not Used
No Movement Arming 003 003
Partial Arming 004 004
One-touch Arming 005 005
Future Use 006 006 Future Use 007 007
(InTouch) Voice Module Arming 008 008
24
Page 26
Event
Group
022 Special Disarm Events
023 Zone Bypassed 024 Zone in Alarm 001 to 096 001 to 096 025 Fire Alarm 001 to 096 001 to 096 026 Zone Alarm Restore 001 to 096 001 to 096 027 Fire Alarm Restore 001 to 096 001 to 096
028 Early to Disarm by User
029 Late to Disarm by User
030 Special Alarm
031 Duress Alarm by User
032 Zone Shutdown 033 Zone Tamper 001 to 096 001 to 096 034 Zone Tamper Restore 001 to 096 001 to 096 035 Special Tamper 000 Keypad Lockout 000 000
Event Feature Group Feature Start # End #
Auto Arm Cancelled 000 000
One-touch Stay/Instant Disarm 001 001
Disarming with WinLoad 002 002
Disarming with WinLoad after
alarm
000
255 Any special disarm event Not Used Not Used
000
255 = any zone #
000 User Codes 001 to 255 001 to 255 001 to 255 001 User Codes 256 to 511 000 to 255 000 to 255 002 User Codes 512 to 767 000 to 255 000 to 255 003 User Codes 768 to 999 000 to 231 000 to 231 255 Any User Code Not Used Not Used 000 User Codes 001 to 255 001 to 255 001 to 255 001 User Codes 256 to 511 000 to 255 000 to 255 002 User Codes 512 to 767 000 to 255 000 to 255 003 User Codes 768 to 999 000 to 231 000 to 231 255 Any User Code Not Used Not Used
000
255 Any special alarm event Not Used Not Used 000 User Codes 001 to 255 001 to 255 001 to 255 001 User Codes 256 to 511 001 to 255 001 to 255 002 User Codes 512 to 767 001 to 255 001 to 255 003 User Codes 768 to 999 001 to 231 001 to 231 255 Any User Code Not Used Not Used
000
255 = any zone #
WinLoad cancelled alarm 004 004
Future Use 005 005 Future Use 006 006 Future Use 007 007
(InTouch) Voice Module
Disarming
Zone Numbers
Emergency Panic (Keys 1 & 3) 000 000
Medical Panic (Keys 4 & 6) 001 001
Fire Panic (Keys 7 & 9) 002 002
Recent Closing 003 003
Police Code 004 004
Global Shutdown 005 005
Zone Numbers
003 003
008 008
001 to 096 001 to 096
001 to 096 001 to 096
25
Page 27
Event
Group
036 Trouble Event
037 Trouble Restore
038 Module Trouble
039 Module Trouble Restore
040 041 Low Battery on Zone
042 Zone Supervision Trouble 001 to 096 001 to 096 043
044
Fail to Communicate on telephone Number
Low Battery on Zone Restored
Zone Supervision Trouble Restored
Event Feature Group Feature Start # End #
TLM Trouble (see NOTE 2 on
page 28)
AC Failure 001 001
Battery Failure 002 002
000
255 Any trouble event Not Used Not Used
000
255 Any trouble restore event Not Used Not Used
000
255 Any module trouble Not Used Not Used
000
255 Any module trouble restore event Not Used Not Used 000 Telephone Number 001 to 004 001 to 004 255 Any telephone number Not Used Not Used
000
255 = any Zone #
Auxiliary Current Limit 003 003
Bell Current Limit 004 004
Bell Absent 005 005
Clock Trouble 006 006
Global Fire Loop 007 007
TLM Trouble 000 000
AC Failure 001 001
Battery Failure 002 002
Auxiliary Current Limit 003 003
Bell Current Limit 004 004
Bell Absent 005 005
Clock Trouble 006 006
Global Fire Loop 007 007
Combus Fault 000 000
Module Tamper 001 001
ROM/RAM error 002 002
TLM Trouble 003 003
Fail to Communicate 004 004
Printer Fault 005 005
AC Failure 006 006
Battery Failure 007 007
Auxiliary Failure 008 008
Combus Fault 000 000
Module Tamper 001 001
ROM/RAM error 002 002
TLM Trouble 003 003
Fail to Communicate 004 004
Printer Fault 005 005
AC Failure 006 006
Battery Failure 007 007
Auxiliary Failure 008 008
Zone Numbers
000 000
001 to 096 001 to 096
001 to 096 001 to 096
001 to 096 001 to 096
26
Page 28
Event
Group
Event Feature Group Feature Start # End #
Power up after total power down 000 000
Software reset (Watchdog) 001 001
Test Report 002 002
Future Use 003 003
WinLoad In (connected) 004 004
045 Special Events
000
WinLoad Out (disconnected) 005 005
Installer in programming 006 006
Installer out of programming 007 0 07
255 Any special event Not Used Not Used 000 User Codes 001 to 255 001 to 255 001 to 255 001 User Codes 256 to 511 000 to 255 000 to 255
046 Early to Arm by User
002 User Codes 512 to 767 000 to 255 000 to 255 003 User Codes 768 to 999 000 to 231 000 to 231 255 Any User Code Not Used Not Used 000 User Codes 001 to 255 001 to 255 001 to 255 001 User Codes 256 to 511 000 to 255 000 to 255
047 Late to Arm by User
002 User Codes 512 to 767 000 to 255 000 to 255 003 User Codes 768 to 999 000 to 231 000 to 231 255 Any User Code Not Used Not Used
048 Utility Key
049 Request for Exit
000 255
Utility Key 001 to 064
Any Utility Key
†*
†*
001 to 064 001 to 064
Not Used Not Used
001 to 032 001 to 032
050 Access Denied 001 to 032 001 to 032 051 Door Left Open Alarm 001 to 032 001 to 032 052 Door Forced Alarm 001 to 032 001 to 032
000
255 = any Door
Number
Door Numbers
053 Door Left Open Restore 001 to 032 001 to 032 054 Door Forced Open Restore 001 to 032 001 to 032
055 Intellizone Triggered
056 057 058
059
060 - 061
Zone Excluded on Force Arming
Zone Went Back to Arm Status New Module Assigned on
Combus Module Manually Removed
From Combus Future Use
255 = Any Module
000 Zone Numbers 001 to 096 001 to 096 255 Any zone number Not Used Not Used
000
255 = Any Zone
000
Zone Numbers 001 to 096 001 to 096 Zone Numbers 001 to 096 001 to 096
Module Address 001 to 254 001 to 254
Module Address 001 to 254 001 to 254
Future Use Future Use Future Use Future Use
000 User Codes 001 to 255 001 to 255 001 to 255 001 User Codes 256 to 511 000 to 255 000 to 255
062 Access Granted to User
002 User Codes 512 to 767 000 to 255 000 to 255 003 User Codes 768 to 999 000 to 231 000 to 231 255 Any User Code Not Used Not Used 000 User Codes 001 to 255 001 to 255 001 to 255 001 User Codes 256 to 511 000 to 255 000 to 255
063 Access Denied to User
002 User Codes 512 to 767 000 to 255 000 to 255 003 User Codes 768 to 999 000 to 231 000 to 231 255 Any User Code Not Used Not Used
†: see page 28
: see page 28
*
27
Page 29
Event
Group
Event Feature Group Feature Start # End #
Armed 000 000
Force Armed 001 001
Stay Armed 002 002
064 Status 1
See Note 1
on page 28
Instant Armed 0 03 003
Strobe Alarm 004 004
Silent Alarm 005 005
Audible Alarm 006 006
Fire Alarm 007 007
Ready 000 000
Exit Delay 001 001
Entry Delay 002 002
System in Trouble 003 003
Alarm in Memory 004 004
065 Status 2
See Note 1
on page 28
Zones Bypassed 005 005
Bypass, Master , Installer
Programming
006 006
Keypad Lockout 007 007
Intellizone Delay Engaged (see
Note 4 on page 28)
000 000
Fire Delay Engaged 001 001
Auto Arm 002 002
066 Status 3
See Note 1
on page 28
Arming with Voice Module (set
until Exit Delay finishes)
003 003
Tamper 004 004 Zone Low Battery 005 005 Fire Loop Trouble 006 006
Zone Supervision Trouble 007 007
067 Future Use Future Use Future Use Future Use Future Use
NOTE 1:000 = Occurs in all areas enabled in the system (refer to the appropriate control panel Programming Guide). 001 = Area 1003 = Area 3 005 = Area 5 (EVO96 only)007 = Area 7 (EVO96 only) 002 = Area 2004 = Area 4 006 = Area 6 (EVO96 only)008 = Area 8 (EVO96 only) 255 = Occurs in at least one area enabled in the system.
NOTE 2:This TLM trouble event can only be used with EVO96 control panels that have one dialler. NOTE 3:This TLM trouble event can only be used with DGP-848 control panels or EVO96 control panels that have one dialer. NOTE 4:This event cannot be used for a module’s PGM programming.
:If a Keyswitch Input is used, the input must be defined as “Generates a Utility Key Event on Open” or “Generates a Utility Key Event on
*
Open and Close”. If a remote control is used, the remote control button must be defined as a Utility Key button.
:Actions that Activate a Utility Key Event:
Actions
Utility Key Event
Keypad Utility Keys
Utility Key Event 1 [1] & [2] KS** Input 1 opens KS** Input 1 opens Utility Key Event 2 [4] & [5] KS** Input 2 opens KS** Input 1 closes Utility Key Event 3 [7] & [8] KS** Input 3 opens KS** Input 2 opens Utility Key Event 4 [CLEAR] & [0] or [*] & [0] KS** Input 4 opens KS** Input 2 closes
Keyswitch Inputs
(definition = [3])
Keyswitch Inputs
(definition = [4])
Remote Control
Utility Key 1 RC button Utility Key 2 RC button Utility Key 3 RC button Utility Key 4 RC button
‡ ‡ ‡ ‡
28
Page 30
Actions
Utility Key Event
Keypad Utility Keys
Utility Key Event 5 [2] & [3] KS** Input 5 opens KS** Input 3 opens
Keyswitch Inputs
(definition = [3])
Keyswitch Inputs
(definition = [4])
Remote Control
Utility Key 5 RC button Utility Key Event 6 [5] & [6] KS** Input 6 opens KS** In put 3 closes N/A Utility Key Event 7 [8] & [9] KS** Input 7 opens KS** Input 4 opens N/A Utility Key Event 8 [0] & [ENTER] or [0] & [#] KS** Input 8 opens KS** Input 4 closes N/A Utility Key Event 9 N/A KS** Input 9 opens KS** Input 5 opens N/A
Utility Key Event 10 N/A KS** Input 10 opens KS** In put 5 closes N/A Utility Key Event 11 N/A KS** Input 11 opens KS** Input 6 opens N/A Utility Key Event 12 N/A KS** Input 12 opens KS** In put 6 closes N/A Utility Key Event 13 N/A KS** Input 13 opens KS** Input 7 opens N/A Utility Key Event 14 N/A KS** Input 14 opens KS** In put 7 closes N/A Utility Key Event 15 N/A KS** Input 15 opens KS** Input 8 opens N/A Utility Key Event 16 N/A KS** Input 16 opens KS** In put 8 closes N/A Utility Key Event 17 N/A KS** Input 17 opens KS** Input 9 opens N/A Utility Key Event 18 N/A KS** Input 18 opens KS** In put 9 closes N/A
iN/AiiN/A Utility Key Event 31 N/A KS** Input 31 opens KS** Input 16 opens N/A Utility Key Event 32 N/A KS** Input 32 opens KS** Input 16 closes N/A Utility Key Event 33 N/A N/A KS** Input 17 opens N/A Utility Key Event 34 N/A N/A KS** Input 17 closes N/A
i N/A N/A i N/A Utility Key Event 63 N/A N/A KS** Input 32 opens N/A Utility Key Event 64 N/A N/A KS** Input 32 closes N/A
** Keyswitch
Refer to the Magellan™ Reference and Installation Manual for remote control button programming instructions.
Warranty Paradox Security Systems Ltd. (“Seller”) warrants its products to be free from defects in materials and workmanship under normal use for a period of one year. Except as specifically stated herein, all express or implied warranties whatsoever, statutory or otherwise, including without limitation, any implied warranty of merchantability and fitness for a particular purpose, are expressly excluded. Because Seller d oe s no t install or connect the products and because the products may be used in conjunction with products not manufactured by Seller, Seller cannot guarantee the performance of the security system and sh all no t b e responsible for circumstances resulting from the product’s inab ility to o perate. Seller obligation and liability under this warranty is expressly limited to repairing or replacing, at Seller's option, any product not meeting the specifications. Returns must include proof of purchase and be within the warranty period. In no event shall the Seller be liable to the buyer or any other person for any loss or damages whether direct or indirect or consequential or i nci de ntal, including without limitation, any damages for l ost pr of i t s stolen goods, or claims by any other party, caused by defective goods or otherwise arisi n g fr o m the i mpr ope r, incorrect or otherwise faulty installation or use of the merchandise sold.
Notwithstanding the preceding paragraph, the Seller’s maximum liability will be strictly limited to the purchase price of the defective product. Your use of this p rodu ct sig nifies your a ccep t a nce of this wa rr an ty. BEWARE: Dealers, installers and/or others selling the product are not authorized to modify this warranty or make additional warranties that are binding on the Seller.
© 2003-2007 Paradox Security Systems Lt d. All rights reserved. Specificati ons ma y ch ang e wi th ou t pr i or n oti ce . On e o r m ore o f the following US patents may apply: 6215399, 6111256, 5751803, 5721542, 5287111, 5119069 , 5 07 754 9, 5920259, 5886632. Canadian and international patents may also apply.
Digiplex is a trademark or registered trademar k of Paradox Security Syste ms Ltd. or its af filiates in Canada, the United St ates and/or other countries. Windows® is a registered trademark of Microsoft corporation. Procomm™ is a trademark of Datasto rm Technologies Inc.. Telix© - Copyright© 1986-1996 by DeltaComm Development & ELSA. HyperTerminal® is a registered trademark of Hilgraeve Inc.. C-Bus is a trademark of Clipsal Integrated Systems Pty Ltd..
For technical support in Canada or the U.S., call 1-800-791-1919, Monday to Friday from 8:00 a.m.
to 8:00 p.m. EST. For techni cal sup port outsi de Canada an d the U .S ., call 00-1-450-491-7444,
Monday to Friday from 8:00 a.m. to 8:00 p.m. EST. Please feel free to visit our website at
www.parado x.com.
Printed in Canada 04/2007 paradox.com CBUS-EP00
29
Loading...