Serial Port Setup ........................................................................................................................................................... 3
Parallel Port: Minimum 80 column printer
Serial Port:1 start bit, 8 data bit, no parity and 1 stop bit (8N1)
Input Voltage:9 -16 Vdc
Current Consumption:60mA maximum
Serial Port Baud Rates: 2400, 9600, 19200 or 57600 bps
Event Buffer:2048 events
Compatibility:EVO48 / EVO96 / EVO192 control panels
DGP-848 control panel (V4.11 and up)
DGP-NE96 control panel (V1.60 and up)
Introduction
The APR-PRT3 Printer Module can be used as an interface between C-Bus and your Digiplex system. When in home automation mode,
the Printer Module can receive and send commands to and from the C-Bus PC interface and the Digiplex control panel, linking your
building automation capabilities with your security system.
The Printer Module features 30 virtual PGMs for use with its building automation interface capabilities. These PGMs are not related to any
physical output on the module, but operate in the same manner and are programmed in the same way as traditional PGMs. A virtual PGM
can be used to trigger a response within C-Bus based on an event that has occurred within the Digiplex system. For example, when a user
uses the Digiplex system to disarm an area, this event could activate a virtual PGM on the Printer Module and trigger a response within CBus, such as turning on a specific light on the premises. See “Virtual PGM Programming ” on page 4.
Up to 30 C-Bus entries can be associated with the Pri nter Module’s virtual PGMs. C-Bus entries allow you to set the commands that will be
sent on the C-Bus in relation to events that occur within the Digiplex system. When the state of a virtual PGM on the Printer Module
changes, a message is sent by the C-Bus entry that is associated with that virtual PGM. See “C-Bus Entry Options” on page 8.
The Printer Module also features 16 onboard virtual inputs. These inputs are not related to any physical input on the mod ule, but operate in
the same manner and are programmed in the same way as a traditional zone input. A virtual input can be programmed to trigger a response
from the Digiplex control panel based on an event that has occurred within C-Bus. Using virtual inp ut s to trigger event s within th e Digiplex
control panel involves associating the Printer Module’s virtual input to a zone or a keyswitc h on the control p anel. See “V irtual Input Options”
on page 15.
In order for C-Bus and the Digiplex control panel to communicate in such a way, the Printer Module’s serial port must be set to
communicate using the Clipsal C-Bus Protocol.
For a complete list of the Printer Module’s event reporting features, see the Printer Module V1.0 (APR-PRT3) Instructions.
The APR-PRT3 Printer Module is compatible with C-Bus interface firmware V4.00.00 and higher. C-Bus lighting units must be
configured with firmware V1.1 and higher.
If the Printer Module fails to connect to the C-Bus PC interface, a trouble will be generated.
1
Page 3
Installation
The Printer Module is connected to the control panel’s combus. Connect the four terminals labeled red , black, green, and yel low of the
module to the corresponding terminals on the control panel as shown in Figure 2 on page 21. See the EVO or DGP-848 Reference & Installation Manual for the maximum allowable installation dist an ce from the control panel.
The C-Bus PC Interface must be connected to the Printer Module’s serial port using a null modem cable only.
Overview
The following provides of an overview of how the Printer Module communicates with C-Bus.
Figure 1: C-Bus Overview
• C-Bus entries are associated with
Printer Module’s virtual PGMs.
• Printer Module sends messages to
C-Bus PC interface based on
• Messages from C-Bus PC
interface can be used to
open/close virtual inputs on
the Printer Module.
virtual PGM events and C-Bus
Entry programming.
Programming Sections
The following describes the programming sections which must be set in order for the Printer Mod ule to act as an interface between a
Digiplex control panel and a C-Bus PC interface.
To access the Printer Module’s programming mode:
1.Press and hold the [0] key.
2.Enter the [
3.Enter section [953] (DGP-848) / [4003] (EVO).
4.Enter the Printer Module’s 8-digit [
5.Enter the 3-digit [
6.Enter the required data.
The Printer Module can also be programmed using the WinLoad Security Software (V2.62 or higher) or using the control p a nel’ s Mo dule
Broadcast feature. Refer to the EVO or DGP-848 Reference & Installation Manual for more details. Please note that th e seri al numb er can
be located on the Printer Module’s PC board.
INSTALLERCODE].
SERIALNUMBER].
SECTION] you want to program.
2
Page 4
Serial Port Setup
The following lists the serial port programming options wh ich must be set in order for the Printer Module to commun icat e with C-Bus.
Section [016] - Option [1]
Enable Serial Port
When this option is ON (enabled), you can connect the C-Bus PC interface directly to the Printer Module’s serial port (9 pins) through the
use of a null modem cable. Set option [4] to ON when using the Printer Module as an interface between a C-Bus PC interface and the
Digiplex system.
Section [016] - Options [2] & [3]
Baud Settings
When a C-Bus PC interface is connected to the Printer Module, the serial port baud rate is automatically set to 9600 bau d. Any other baud
rate will be overridden.
Section [016] - Option [4]
Serial Port Usage
This option allows you to set the Printer Module’s serial port usage to either Event Re porting or Home Automation. Set option [4] to ON to
set the Printer Module to Home Automation.
Section [016] - Options [5] & [6]
Home Automation Options
This option allows you to select the home automation protocol for the Printe r Module. Set
option [5] to ON and option [6] to OFF to select the Clipsal C-Bus Protocol.
For more information on the ASCII Protocol, see the ASCII Protocol Programming
Instructions on our website at paradox.com.
Sections [070] to [072]
C-Bus Applications
These sections allow you to enable which C-Bus application(s) the Printer Module can use to send and receive commands. Note that the
Printer Module supports communication with the following three C-Bus applications:
Section ApplicationHexadecimal Value
[070]__ /__
[071]__ /__
[072]__ /__C-Bus Security Application$DO
Refer to the appropriate C-Bus documentation for further informatio n on C-Bus ap plication s.
C-Bus lighting Application
C-Bus Air-conditioning
Application
$38
$AC
3
Page 5
Virtual PGM Programming
The Printer Module supports up to 30 virtual PGMs which are not related to any physical output on the module, but operate in the sa me
manner and are programmed in the same way as traditional PGMs. The tables below of fer an example of the virtual PGM prog ramming
sections which must be set for virtual PGM 1.
Section [100] : Virtual PGM Options
OptionOFFON
[1] and [2]Virtual PGM Deactivation
[3]Virtual PGM Base Time SelectionU SecondsN Minutes
[4]Virtual PGM Resend
SectionDataDescriptionDefault
[101]__/__/__ (000 to 255) x Base TimeVirtual PGM 1 Timer005
The following describes the programming sections and options specific to the Printer Module’ s virtual PGMs. Use the programming t ables to
document specific settings for all programmed virtual PGMs.
Refer to the table below for a list of the programming sections for all virtual PGMs.
For more informat ion on PGM programming, see “Appendix 1: Programming PGMs” on page 22.
Section [100] - Options [1] and [2]
Virtual PGM Deactivation Option
When the Virtual PGM Activation Event occurs (see “Virtual PGM Activation Event” on p age7), this
option determines when the virtual PGM will return to its normal st ate (d eactiva te ). Dependi ng on the
programmed value, the virtual PGM can stay activated indefinitely. It can also deactivate following a
virtual deactivation event (see “Virtual PGM Deactivation Event” on page7) and/or after the virtual PGM
timer has elapsed (see “Virtual PGM T imers” on page5).
4
Page 6
U = default setting
Section Virtual PGM [1] OFF / [2] OFF[1] ON / [2] OFF[1] OFF / [2] ON[1] ON / [2] ON
[100]1N no deactivation U deactivation event N virtual PGM timer N deactivation event or virtual PGM timer
[110]2N no deactivation U deactivation event N virtual PGM timer N deactivation event or virtual PGM timer
[120]3N no deactivation U deactivation event N virtual PGM timer N deactivation event or virtual PGM timer
[130]4N no deactivation U deactivation event N virtual PGM timer N deactivation event or virtual PGM timer
[140]5N no deactivation U deactivation event N virtual PGM timer N deactivation event or virtual PGM timer
[150]6N no deactivation U deactivation event N virtual PGM timer N deactivation event or virtual PGM timer
[160]7N no deactivation U deactivation event N virtual PGM timer N deactivation event or virtual PGM timer
[170]8N no deactivation U deactivation event N virtual PGM timer N deactivation event or virtual PGM timer
[180]9N no deactivation U
[190]10N no deactivation U deactivation event N virtual PGM timer N deactivation event or virtual PGM timer
[200]11N no de activation U deactivation event N virtual PGM timer N deactivation event or virtual PGM timer
[210]12N no deactivation U deactivation event N virtual PGM timer N deactivation event or virtual PGM timer
[220]13N no deactivation U deactivation event N virtual PGM timer N deactivation event or virtual PGM timer
[230]14N no deactivation U deactivation event N virtual PGM timer N deactivation event or virtual PGM timer
[240]15N no deactivation U deactivation event N virtual PGM timer N deactivation event or virtual PGM timer
[250]16N no deactivation U deactivation event N virtual PGM timer N deactivation event or virtual PGM timer
[260]17N no deactivation U deactivation event N virtual PGM timer N deactivation event or virtual PGM timer
[270]18N no deactivation U deactivation event N virtual PGM timer N deactivation event or virtual PGM timer
[280]19N no deactivation U deactivation event
[290]20N no deactivation U deactivation event N virtual PGM timer N deactivation event or virtual PGM timer
[300]21N no deactivation U deactivation event N virtual PGM timer N deactivation event or virtual PGM timer
[310]22N no deactivation U deactivation event N virtual PGM timer N deactivation event or virtual PGM timer
[320]23N no deactivation U deactivation event N virtual PGM timer N deactivation event or virtual PGM timer
[330]24N no deactivation U deactivation event N virtual PGM timer N deactivation event or virtual PGM timer
[340]25N no deactivation U deactivation event N virtual PGM timer N deactivation event or virtual PGM timer
[350]26N no deactivation U deactivation event N virtual PGM timer N deactivation event or virtual PGM timer
[360]27N no deactivation U deactivation event N virtual PGM timer N deactivation event or virtual PGM timer
[370]28N no deactivation U deactivation event N virtual PGM timer N deactivation event or virtual PGM timer
[380]29N no deactivation U deactivation event N
[390]30N no deactivation U deactivation event N virtual PGM timer N deactivation event or virtual PGM timer
deactivation event N virtual PGM timer N deactivation event or virtual PGM timer
N virtual PGM timer N deactivation event or virtual PGM timer
virtual PGM timer N deactivation event or virtual PGM timer
Section [101]
Virtual PGM Timers
If the virtual PGM is set to follow its Virtual PGM Timer (see “Virtual PGM Deactivation Option” on page4), the entered value represents the
amount of time that the virtual PGM will remain activated. To program the Virtual PGM Timer, enter a 3-digit value from 000 to 255.
Depending on the Virtual PGM Base Time (see “Virtual PGM Base Time Selection” on page 6), the Virtual PGM Timer will either be in
seconds or minutes.
SectionVirtual PGMDataSectionVirtual PGMData
[101]1__/__/__ (000 to 255) x Base time[251]16__/__/__ (000 to 255) x Base time
[111]2__/__/__ (000 to 255) x Base time[261]17__/__/__ (000 to 255) x Base time
[121]3__/__/__ (000 to 255) x Base time[271]18__/__/__ (000 to 255) x Base time
[131]4__/__/__ (000 to 255) x Base time[281]19__/__/__ (000 to 255) x Base time
[141]5__/__/__ (000 to 255) x Base time[291]20__/__/__ (000 to 255) x Base time
[151]6__/__/__ (000 to 255) x Base time[301]21__/__/__ (000 to 255) x Base time
[161]7__/__/__ (000 to 255) x Base time[311]22__/__/__ (000 to 255) x Base time
[171]8__/__/__ (000 to 255) x Base time[321]23__/__/__ (000 to 255) x Base time
[181]9__/__/__ (000 to 255) x Base time[331]24__/__/__ (000 to 255) x Base time
[191]10__/__/__ (000 to 255) x Base time[341]25__/__/__ (000 to 255) x Base time
[201]11__/__/__ (000 to 255) x Base time[351]26__/__/__ (000 to 255) x Base time
5
Page 7
[211]12__/__/__ (000 to 255) x Base time[361]27__/__/__ (000 to 255) x Base time
[221]13__/__/__ (000 to 255) x Base time[371]28__/__/__ (000 to 255) x Base time
[231]14__/__/__ (000 to 255) x Base time[381]29__/__/__ (000 to 255) x Base time
[241]15__/__/__ (000 to 255) x Base time[391]30__/__/__ (000 to 255) x Base time
Section [100] - Option [3]
Virtual PGM Base Time Selection
If option [3] is OFF, the value programmed for the Virtual PGM Timer will be in secon ds. If option [3] is ON, the Virtual PGM Timer will be in
minutes. U = default setting
If option [4] is ON and a Virtual PGM’s activation event reo ccurs while the virtual PGM is ON, the message sent by the C-Bus entry that is
associated with that virtual PGM will be resent. If option [4] is ON and a Virtual PGM’s deactivation event reoccurs while the virtual PGM is
OFF, the message sent by the C-Bus entry that is associated with that virtual PGM will be resent.
U = default setting
Section
[100]1U message not resent N message resent[250]16U message not resentN message resent
[110]2U message not resent N message resent[260]17U message not resentN message resent
[120]3U message not resent N message resent[270]18U message not resentN message resent
[130]4U message not resent N message resent[280]19U message not resentN message resent
[140]5U message not resent N message resent[290]20U message not resentN message resent
[150]6U message not resent N message resent[300]21U message not resentN message resent
[160]7U message not resent N message resent[310]22U message not resentN message resent
[170]8U message not resent N message resent[320]23
[180]9U message not resent N message resent[330]24U message not resentN message resent
[190]10U message not resent N message resent[340]25U message not resentN message resent
[200]11U message not resent N message resent[350]26U message not resentN message resent
[210]12U message not resent N message resent[360]27U message not resentN message resent
[220]13U message not resent N message resent[370]28U message not resentN message resent
[230]14U message not resent N message resent[380]29U message not resentN message resent
[240]15U message not resent N message resent[390]30U message not resentN message resent
Virtual
PGM
[4] OFF[4] ONSection
Virtual
PGM
[4] OFF[4] ON
U message not resentN message resent
6
Page 8
Sections [102] to [105]
Virtual PGM Activation Event
The Virtual PGM Activation Event determines which event will activate the Printer Module’s virtual PGM output(s). The Event Group
specifies the event, the Feature Group identifies the source, and the Start # and End # set the range within the Feature Group.
Note that Event Groups [064] to [067] may be selected when programming virtual PGMs (see “Appendix 1: Programming PGMs” on
page 22).
If the Virtual PGM Deactivation Option is set to follow the Virtual PGM Deactivation Event (see “Virtual PGM Deactivation Option” on
page 4), the virtual PGM will return to its normal state when the event programmed occurs (see t able below). The Event Group specifies the
event, the Feature Group identifies the source, and the Start # and End # set the range within the Feature Group.
Enter the sections that correspond to the Event Group, Feature Group, Start # and End # of the PGM.
C-Bus entries allow you to set the commands that will be sent on the C-Bus in relation to events that occur wi thin the Digiplex system. When
the state of a virtual PGM on the Printer Module changes, a message is sent by the C-Bus entry that is associated with that virtual PGM. Up
to 30 C-Bus entries can be associated with the Printer Module’s virtual PGMs. Multiple C-Bus entries can be associated with a single virtual
PGM.
The tables below offer an example of th e C-Bu s entry pr ogramming sections which must be set for C-Bu s entry 1.
Section [400] : C-Bus Entry Options
OptionOFFON
[1]Application SelectionU LightingN Air Conditioning
[2] and [3]ON Command
[4] and [5]OFF Command
* Not used with air-conditioning
8
Page 10
SectionDataDescriptionDefault
[401]__/__/__ (001 to 030)
[402]__/__/__ (000 to 255)
Virtual PGM
Association
ON Group Address
Variable
000
000
[403]__/__/__ (000 to 015)
[404]__/__/__ (000 to 255)ON Ramp Final Level000*
[405]__/__/__ (000 to 255)
[406]__/__/__ (000 to 015)OFF Ramp Period000*
[407]__/__/__ (000 to 255)OFF Ramp Final Level000*
↓ON Ramp Period
OFF Group Address
Variable
000*
000
*Not used with air-conditioning (values ignored if selected)
Refer to the table below for a list of the programming sections for all virtual PGMs.
The following describes the programming sections and options specific to the C-Bus entries. Use the progra mming t ables to docum ent
specific settings for all programmed C-Bus entries.
Section [400] - Option [1]
Application Selection
When option [1] is OFF, C-Bus entries are associated with lighting application. When option [1] is ON, C-Bus entries are associated with
air-conditioning application.
This option allows you to choose the type of command that will be sent through the C-Bus entry af ter the st ate of it s associated virtual PGM
changes from OFF to ON. The types of commands include ON, OFF or ramp.
= default setting
U
SectionC-Bus Entry[2] OFF / [3] OFF[2] ON / [3] OFF[2] OFF / [3] ON[2] ON / [3] ON*
This option allows you to choose the type of command that will be sent through the C-Bus entry af ter the st ate of it s associated virtual PGM
changes from ON to OFF. The types of commands include ON, OFF or ramp.
= default setting
U
SectionC-Bus Entry[4] OFF / [5] OFF[4] ON / [5] OFF[4] OFF / [5] ON[4] ON / [5] ON*
The ON Group Address Variable section allows you to assign which C-Bus group will receive the programmed ON command (see “ON
Commands” on page 10). Enter 000-255 to assign each C-Bus entry to a group address.
For further information on Group Address Variables, refer to the appropriate C-Bus documentation.
The ON Ramp Period section allows you to assign a ramp time value when an ON Ramp command has been set (see “ON Commands” on
page 10). The following table list s the Ramp Period prog rammed value s and their corresp ondin g real-time values.
ON Ramp Final Level * Not used with air conditioning
The ON Ramp Final Level section allows you to assign a final level of light intensity when an ON Ramp command has been set (see “ON
Commands” on page 10). Enter 000-255 to assign each C-Bus entry an ON Ramp Fin al Level.
For further information on lighting intensity levels associated with th e ON Ramp command, re fe r to the appro priate C-Bu s
documentation.
The OFF Group Address V ariable section allows you to assi gn which C-Bus gro up will rece ive the pro grammed OFF command (see “OFF
Commands” on page 11). Enter 000-255 to assign each C-Bus entry to a group address.
For further information on Group Address Variables, refer to the appropriate C-Bus documentation.
The OFF Ramp Period section allows you to assign a ramp time value when an OFF Ramp command has been set (see “OFF Commands”
on page 11). Enter 000-015 to assign each C-Bus entry an OFF Ramp Period.
OFF Group
Address Variable
SectionC-Bus Entry
OFF Group
Address Variable
Section [406]*
SectionC-Bus EntryOFF Ramp PeriodSectionC-Bus EntryOFF Ramp Period
OFF Ramp Final Level * Not used with air conditioning
The OFF Ramp Final Level section allows you to assign a final level of light intensity when an OFF Ramp comma nd has been set (see “OFF
Commands” on page 11). Enter 000-255 to assign each C-Bus entry an OFF Ramp Final Level.
For further information on lighting intensity levels associated with th e OFF Ramp command , refer to the appropriate C-Bus
documentation.
The Print er M o dule features 16 v i r t ua l i np u ts. The virtual inputs’ open/close state can change based on an event that has occurred within
C-Bus. The following describes the programming sections and options specific to the Printer Module’s virtual inputs. Virtual inputs must be
programmed with the appropriate C-Bus application, group address variable and type of command which will cause the virtual input to
react (open/close).
The tables below offer an example of th e virtua l input pr ogramming sections which must be set for virtual input 1.
The following describes the programming sections and options specific to the Printer Module’ s virtual input s. Use the programming t ables to
document specific settings for all programmed virtual inputs.
Section [700] - Option [1]
Enabling Virtual Input Option
Each virtual input must be individually enabled. Set option [1] to ON to enable the virtual input.
Each virtual input must be programmed to use a specific C-Bus application to monitor C-Bus activity. If option [2] is OFF, lighting
application is used. If option [2] is ON, air-conditioning application is used.
The virtual input can be closed by either receiving a virtual input close command, after a timer
elapses or either. This option determines how the virtual input will close.
U = default setting
SectionVirtual Input[3] OFF / [4] OFF[3] ON / [4] OFF[3] OFF / [4] ON
[700]1U close commandN virtual input timerN close command or virtual input timer
[710]2U close commandN virtual input timerN close command or virtual input timer
[720]3U close commandN virtual input timerN close command or virtual input timer
[730]4U close commandN virtual input timerN close command or virtual input timer
[740]5U close commandN virtual input timerN close command or virtual input timer
[750]6U close commandN virtual input timerN close command or virtual input timer
[760]7U close commandN virtual input timerN close command or virtual input timer
[770]8U close commandN virtual input timerN close command or virtual input timer
[780]9U close commandN virtual input timerN close command or virtual input timer
[790]10U close commandN virtual input timerN close command or virtua l input timer
[800]11U close commandN virtual input timerN close command or virtual input timer
[810]12U close commandN virtual input timerN close command or virtua l input timer
[820]13
[830]14U close commandN virtual input timerN close command or virtua l input timer
[840]15U close commandN virtual input timerN close command or virtua l input timer
[850]16U close commandN virtual input timerN close command or virtua l input timer
U close commandN virtual input timerN close command or virtual input timer
Section [701]
Virtual Input Timers
If the virtual input is set to follow its Virtua l Input Timer, the entered value represe nt s the amount of ti me th at th e virtual input wi ll remain
open. To program the Virtual Input Timer, enter a 3-digit value from 000 to 255. Depending on the V irtual Input Base T ime (see “Virtual Input
Base Time Selection” on page17), the Virtual Input Timer will either be in seconds or minutes.
SectionVirtual InputTimer DataSectionVirtual InputTimer Data
[701]1__/__/__ (000 to 255) x Base time[781]9__/__/__ (000 to 255) x Base time
[711]2__ /__ /__ (000 to 255) x Base time[791]10__/__/__ (000 to 255) x Base time
[721]3__/__/__ (000 to 255) x Base time[801]11__/__/__ (000 to 255) x Base time
[731]4__/__/__ (000 to 255) x Base time[811]12__/__/__ (000 to 255) x Base time
[741]5__/__/__ (000 to 255) x Base time[821]13__/__/__ (000 to 255) x Base time
[751]6__/__/__ (000 to 255) x Base time[831]14__/__/__ (000 to 255) x Base time
[761]7__/__/__ (000 to 255) x Base time[841]15__/__/__ (000 to 255) x Base time
[771]8__/__/__ (000 to 255) x Base time[851]16__/__/__ (000 to 255) x Base time
Section [700] - Option [5]
Virtual Input Base Time Selection
If option [5] is OFF, the value programmed for the Virtual Input Timer will be in seconds. If op tion [5] is ON, the Virtual Input Timer will be in
minutes. The following table lists the base time sections and their respecti ve virtual inputs.
The Virtual Input Open Group Address Variable section allows you to set which C-Bus group will cause a virtual input on the Printer Module
to open. Enter 000-255 to assign which group address variable will trigger a virtual input to open.
For further information on Group Address Variables, refer to the appropriate C-Bus documentation.
The Virtual Input Open Command section sets the state of a virtual input to open wh en an ON, OFF or Ramp command occurs within CBus. The open command is based on the Open Group Addre ss Variable and on the C-Bus application selected above. Enter 000 to set the
virtual input to open in response to an ON command, 001 to set the virtual input to open in response to an OFF command or 002 to set the
virtual input to open in response to a Ramp command.
The Virtual Input Open Group Address Variable section allows you to set which C-Bus group will cause a virtual input on the Printer Module
to close. Enter 000-255 to assign which group address variable will trigger a virtual input to close.
For further information on Group Address Variables, refer to the appropriate C-Bus documentation.
The Virtual Input Close Command section sets the state of a virtual input to close when an ON , OFF or Ramp command occurs withi n CBus. The close command is based on the Close Group Address Variable and on the C-Bus application selected above. Enter 000 to set the
virtual input to close in response to an ON command, 001 to set the virtual input to close in response to an OFF command or 002 to set the
virtual input to close in response to a Ramp command.
The Ramp Threshold section allows you to set a threshold level to Ramp commands occurring within C-Bus. To open a virtu al input, the
Ramp’s Final Level must be greater or equal to the threshold value. To close a virtual input, the Ramp’s Final level must be lower th an the
threshold value. Enter 000-255 to set the virtual input’ s threshold level.
Security reports are messages sent between the APR-PRT3 and the C-Bu s. Messages that are rece iv ed by the C-Bus can be used to
trigger automated events.
SectionDataDescriptionDefault
[900]__/__/__ (001 to 008)† Partition affected by security application001
Section
901
Report OptionsOFFON
[1]Global Security report* N = DisableU = Enable
[2]
System Armed / Disarmed
N = DisableU = Enable
[3]Entry / Exit delay N = DisableU = Enable
[4]Zone in alarm / Zone in alarm restore (zones 01 to 80)‡N = DisableU = Enable
[5]Fire Alarm / Fire Alarm Restore N = DisableU = Enable
[6]Silent Alarm Report / Silent Alarm Restore N = DisableU = Enable
[7]Panic Alarm N = DisableU = Enable
[8]Future use N = N/AU =N/A
* If Global Security report is disabled, all options in sections [901] and [902] will also be disabled.
Section
902
Report OptionsOFFON
[1]Low Battery / Low Battery Restored (zones 01 to 80)‡ N = DisableU = Enable
[2]AC Failure / AC Failure restore N = DisableU = Enable
[3]Ready to arm / Not ready to arm N = DisableU = Enable
[4]Zone open / Zone ok (zones 01 to 80)‡ N = DisableU = Enable
[5]Zone tamper / Zone tamper restore (zones 01 to 80)‡ N = DisableU = Enable
[6]Zone Bypassed (zones 01 to 80)‡ N = DisableU = Enable
[7]User Code entered on Keypad N = DisableU = Enable
[8]TLM T rouble/TLM Trouble Restore N
= DisableU = Enable
Section
903
Messages from C-BusOFFON
[1]Arm system*N = ForbidU = Allow
[2]Raise alarm** N = ForbidU = Allow
[3]C-Bus tamper / C-Bus tamper restore*** N = ForbidU = Allow
[4]Future use N = N/AU =N/A
[5]Future use N = N/AU =N/A
[6]Future use N = N/AU =N/A
[7]Future use N = N/AU =N/A
[8]Future use N = N/AU =N/A
‡ Due to C-Bus limitation, only zones 01 from zones 80 can be reported, C-Bus Network will ignore all others.
*
Must enable One-touch regular arming option in the control panel.
**
Alarm will be raised as a Panic Alarm to chosen partitions.
***
Tamper from C-Bus will be reported as a Printer tamper.
20
Page 22
Figure 2: .APR-PRT3 Connection
Remove AC power and battery before adding a module to the sytem.
Refer to the Digiplex DGP-848 or DGP-NE96 Reference and Installation Manual for the maximum
allowable installation distance from the control panel.
Printer cable length must not exceed 25ft.
For information on using the printer Module as an interface with home automation modules, see the ASCII Protocol programming instructions or C-BUS Programming instructions.
1.Green “RX” LED: Flashes when the Printer Module is receiving data through the serial port only.
2.Red “TX” LED: Flashes when the Printer Module is transmitting data through the serial port only.
3.25-Pin Parallel Port: Connect the Printer Module’s 25-pin parallel port to any dot matrix printer.
Note: The dot matrix printer must support a minimum of 80 columns.
4.9-Pin Serial Port: Connect the Printer Module’s 9-Pin serial port to a dot matrix printer.
Note: The dot matrix printer must support a minimum of 80 columns.
5.9-pin Serial Port: Connect the Printer Module’s 9-pin serial port to a home automation module.
6.9-pin Serial Port: Connect C-Bus to the Printer Module using a null modem cable.
7.9-pin Serial Port: Connect either the Printer Module’s USB or 9-pin serial port to a computer’s COM port to view the control panel’s
events on the computer’s monitor. The events display on the monitor can then be printed through the printer connected to the
computer.
21
Page 23
Appendix 1: Programming PGMS
A PGM is a programmable output that toggles to its opposite st ate (i .e. a no rmally open PGM will close) when a specific e vent occ urs in the
system. For example, a PGM can be used to reset smoke detectors, activate strobe lights, open/close garage doors and much more.
PGM Activation Event
The PGM Activation Event determines which event from what source will activate the PGM. The Event Group specifies the event, the
Feature Group identifies the source, and the Start # and End # sets the range within the Feature Group (see PGM Programming Table
below).
For example, the APR-PRT3 can activate Virtual PGM1 when the a rea is armed by User Access Codes 256 to 26 0. Therefore:
Event Group section [102] = 010 “Arming with User Code”
Feature Group section [103] = 001 “User Codes 256 to 511”
Start # section [104] = 000 (representing user code 256)
End # section [105] = 004 (representing user code 260)
Enter the sections that correspond to the Event Group, Feature Group, Start # and End # of the desired PGM and enter the data as required.
PGM Deactivation Option
Once the PGMs are activated, they can deactivate when another event occurs or after a period of time. The PGM D eactivati on Option
determines which method is used, the PGM Deactivation Event or the PGM Timer. Enter the section that corresponds to the desired PGM
and enable or disable the option.
PGM Deactivation Event
When the PGM Deactivation Option (see above) is disabled, the PGM Deactivation Event determines which event from what source will
return the PGM to its original state. T he Event Grou p specifies the event, the Feature Grou p identifies the source, and the Start # and End #
determine the range within the Feature Group. The complete PGM Programming Table appears below.
For example, the APR-PRT3 can deactivate Virtual PGM1 when zone 3 opens. Therefore:
Event Group section [106] = 001 “Zone is Open”
Feature Group section [107] = 000 “Zone Numbers”
Start # section [108] = 003
End # section [109] = 003
Enter the sections that correspond to the Event Group, Feature Group, Start # and End # of the desired PGM and enter the data as required.
PGM Programming Table
Event GroupFeatu re Group Start #End #
PGM Activation
Event
PGM Deactivation
Event
Event
Group
000Zone is OK
001Zone is Open001 to 096001 to 096
002Zone is Tampered001 to 096001 to 096
003Zone is in Fire Loop Trouble001 to 096001 to 096
PGM__/__/____/__/____/__/____/__/__
PGM__/__/____/__/____/__/____/__/__
EventFeature GroupFeatureStart #End #
001 to 096001 to 096
000
255 = any Zone #
Zone Numbers
22
Page 24
Event
Group
004Non-reportable Event
005
006User/Card Access on door
007Bypass Programming Access
008TX Delay Zone Alarm
009Arming with Master
010Arming with User Code
011Arming with Keyswitch
User Code entered on
Keypad
EventFeature GroupFeatureStart #End #
TLM Trouble (see NOTE 3 on
page 28)
Smoke detector reset001001
Arm with no entry delay002002
Arm in Stay mode003003
Arm in Away mode004004
Full arm when in Stay mode005005
000
255Any non-reportable eventNot UsedNot Used
000User Codes 000 to 255000 to 255000 to 255
001User Codes 256 to 511000 to 255000 to 255
002User Codes 512 to 767000 to 255000 to 255
003User Codes 768 to 999000 to 231000 to 231
255Any User CodeNot UsedNot Used
000Door Numbers001 to 032001 to 032
255Any door numberNot UsedNot Used
000One-touch Bypass Programming000000
000User Codes 001 to 255001 to 255001 to 255
001User Codes 256 to 511000 to 255000 to 255
002User Codes 512 to 767000 to 255000 to 255
003User Codes 768 to 999000 to 231000 to 231
255Any User CodeNot UsedNot Used
000Zone Numbers001 to 096001 to 096
255Any zone numberNot UsedNot Used
000User Codes 001 to 255001 to 255001 to 255
001User Codes 256 to 511000 to 255000 to 255
002User Codes 512 to 767000 to 255000 to 255
003User Codes 768 to 999000 to 231000 to 231
255Any User CodeNot UsedNot Used
000User Codes 001 to 255001 to 255001 to 255
001User Codes 256 to 511000 to 255000 to 255
002User Codes 512 to 767000 to 255000 to 255
003User Codes 768 to 999000 to 231000 to 231
255Any User CodeNot UsedNot Used
000Keyswitch numbers001 to 032001 to 032
255Any keyswitch numberNot UsedNot Used
Voice mo dule access006006
Remote control access007007
PC Fail to communicate008008
Midnight009009
NEware User Login010010
NEware User Logout011011
User Initiated Callup012012
Force Answer013013
Force Hangup014014
000000
23
Page 25
Event
Group
012Special Arming
013Disarm with Master
014Disarm with User Code
015Disarm with Keyswitch
016
017
018
019Alarm Cancelled with Master
020
021
Disarm after alarm with
Master
Disarm after alarm with User
Code
Disarm after alarm with
Keyswitch
Alarm Cancelled with User
Code
Alarm Cancelled with
Keyswitch
EventFeature GroupFeatureStart #End #
Auto Arming000000
Arming by WinLoad001001
Late to Close002002
000
255Any special arming eventNot UsedNot Used
000User Codes 001 to 255001 to 255001 to 255
001User Codes 256 to 511000 to 255000 to 255
002User Codes 512 to 767000 to 255000 to 255
003User Codes 768 to 999000 to 231000 to 231
255Any User CodeNot UsedNot Used
000User Codes 001 to 255001 to 255001 to 255
001User Codes 256 to 511000 to 255000 to 255
002User Codes 512 to 767000 to 255000 to 255
003User Codes 768 to 999000 to 231000 to 231
255Any User CodeNot UsedNot Used
000Keyswitch numbers001 to 032001 to 032
255Any keyswitchNot UsedNot Used
000User Codes 001 to 255001 to 255001 to 255
001User Codes 256 to 511000 to 255000 to 255
002User Codes 512 to 767000 to 255000 to 255
003User Codes 768 to 999000 to 231000 to 231
255Any User CodeNot UsedNot Used
000User Codes 001 to 255001 to 255001 to 255
001User Codes 256 to 511000 to 255000 to 255
002User Codes 512 to 767000 to 255000 to 255
003User Codes 768 to 999000 to 231000 to 231
255Any User CodeNot UsedNot Used
000Keyswitch numbers001 to 032001 to 032
255Any keyswitchNot UsedNot Used
000User Codes 001 to 255001 to 255001 to 255
001User Codes 256 to 511000 to 255000 to 255
002User Codes 512 to 767000 to 255000 to 255
003User Codes 768 to 999000 to 231000 to 231
255Any User CodeNot UsedNot Used
000User Codes 001 to 255001 to 255001 to 255
001User Codes 256 to 511000 to 255000 to 255
002User Codes 512 to 767000 to 255000 to 255
003User Codes 768 to 999000 to 231000 to 231
255Any User CodeNot UsedNot Used
000Keyswitch numbers001 to 032001 to 032
255Any keyswitchNot UsedNot Used
No Movement Arming003003
Partial Arming004004
One-touch Arming005005
Future Use006006
Future Use007007
(InTouch) Voice Module Arming008008
24
Page 26
Event
Group
022Special Disarm Events
023Zone Bypassed
024Zone in Alarm001 to 096001 to 096
025Fire Alarm001 to 096001 to 096
026Zone Alarm Restore001 to 096001 to 096
027Fire Alarm Restore001 to 096001 to 096
028Early to Disarm by User
029Late to Disarm by User
030Special Alarm
031Duress Alarm by User
032Zone Shutdown
033Zone Tamper001 to 096001 to 096
034Zone Tamper Restore001 to 096001 to 096
035Special Tamper000Keypad Lockout000000
EventFeature GroupFeatureStart #End #
Auto Arm Cancelled000000
One-touch Stay/Instant Disarm001001
Disarming with WinLoad002002
Disarming with WinLoad after
alarm
000
255Any special disarm eventNot UsedNot Used
000
255 = any zone #
000User Codes 001 to 255001 to 255001 to 255
001User Codes 256 to 511000 to 255000 to 255
002User Codes 512 to 767000 to 255000 to 255
003User Codes 768 to 999000 to 231000 to 231
255Any User CodeNot UsedNot Used
000User Codes 001 to 255001 to 255001 to 255
001User Codes 256 to 511000 to 255000 to 255
002User Codes 512 to 767000 to 255000 to 255
003User Codes 768 to 999000 to 231000 to 231
255Any User CodeNot UsedNot Used
000
255Any special alarm eventNot UsedNot Used
000User Codes 001 to 255001 to 255001 to 255
001User Codes 256 to 511001 to 255001 to 255
002User Codes 512 to 767001 to 255001 to 255
003User Codes 768 to 999001 to 231001 to 231
255Any User CodeNot UsedNot Used
042Zone Supervision Trouble001 to 096001 to 096
043
044
Fail to Communicate on
telephone Number
Low Battery on Zone
Restored
Zone Supervision Trouble
Restored
EventFeature GroupFeatureStart #End #
TLM Trouble (see NOTE 2 on
page 28)
AC Failure001001
Battery Failure002002
000
255Any trouble eventNot UsedNot Used
000
255Any trouble restore eventNot UsedNot Used
000
255Any module troubleNot UsedNot Used
000
255Any module trouble restore eventNot UsedNot Used
000Telephone Number001 to 004001 to 004
255Any telephone numberNot UsedNot Used
000
255 = any Zone #
Auxiliary Current Limit003003
Bell Current Limit004004
Bell Absent005005
Clock Trouble006006
Global Fire Loop007007
TLM Trouble000000
AC Failure001001
Battery Failure002002
Auxiliary Current Limit003003
Bell Current Limit004004
Bell Absent005005
Clock Trouble006006
Global Fire Loop007007
Combus Fault000000
Module Tamper001001
ROM/RAM error002002
TLM Trouble003003
Fail to Communicate004004
Printer Fault005005
AC Failure006006
Battery Failure007007
Auxiliary Failure008008
Combus Fault000000
Module Tamper001001
ROM/RAM error002002
TLM Trouble003003
Fail to Communicate004004
Printer Fault005005
AC Failure006006
Battery Failure007007
Auxiliary Failure008008
Zone Numbers
000000
001 to 096001 to 096
001 to 096001 to 096
001 to 096001 to 096
26
Page 28
Event
Group
EventFeature GroupFeatureStart #End #
Power up after total power down000000
Software reset (Watchdog)001001
Test Report002002
Future Use003003
WinLoad In (connected)004004
045Special Events
000
WinLoad Out (disconnected)005005
Installer in programming006006
Installer out of programming0070 07
255Any special eventNot UsedNot Used
000User Codes 001 to 255001 to 255001 to 255
001User Codes 256 to 511000 to 255000 to 255
046Early to Arm by User
002User Codes 512 to 767000 to 255000 to 255
003User Codes 768 to 999000 to 231000 to 231
255Any User CodeNot UsedNot Used
000User Codes 001 to 255001 to 255001 to 255
001User Codes 256 to 511000 to 255000 to 255
047Late to Arm by User
002User Codes 512 to 767000 to 255000 to 255
003User Codes 768 to 999000 to 231000 to 231
255Any User CodeNot UsedNot Used
048Utility Key
049Request for Exit
000
255
Utility Key 001 to 064
Any Utility Key
†*
†*
001 to 064001 to 064
Not UsedNot Used
001 to 032001 to 032
050Access Denied001 to 032001 to 032
051Door Left Open Alarm001 to 032001 to 032
052Door Forced Alarm001 to 032001 to 032
000
255 = any Door
Number
Door Numbers
053Door Left Open Restore001 to 032001 to 032
054Door Forced Open Restore001 to 032001 to 032
055Intellizone Triggered
056
057
058
059
060 - 061
Zone Excluded on Force
Arming
Zone Went Back to Arm Status
New Module Assigned on
Combus
Module Manually Removed
From Combus
Future Use
255 = Any Module
000 Zone Numbers001 to 096001 to 096
255Any zone numberNot UsedNot Used
000
255 = Any Zone
000
Zone Numbers001 to 096001 to 096
Zone Numbers001 to 096001 to 096
Module Address001 to 254001 to 254
Module Address001 to 254001 to 254
Future UseFuture UseFuture UseFuture Use
000User Codes 001 to 255001 to 255001 to 255
001User Codes 256 to 511000 to 255000 to 255
062Access Granted to User
002User Codes 512 to 767000 to 255000 to 255
003User Codes 768 to 999000 to 231000 to 231
255Any User CodeNot UsedNot Used
000User Codes 001 to 255001 to 255001 to 255
001User Codes 256 to 511000 to 255000 to 255
063Access Denied to User
002User Codes 512 to 767000 to 255000 to 255
003User Codes 768 to 999000 to 231000 to 231
255Any User CodeNot UsedNot Used
†: see page 28
: see page 28
*
27
Page 29
Event
Group
EventFeature GroupFeatureStart #End #
Armed000000
Force Armed001001
Stay Armed002002
064Status 1
See Note 1
on page 28
Instant Armed0 03003
Strobe Alarm004004
Silent Alarm005005
Audible Alarm006006
Fire Alarm007007
Ready000000
Exit Delay001001
Entry Delay002002
System in Trouble003003
Alarm in Memory004004
065Status 2
See Note 1
on page 28
Zones Bypassed005005
Bypass, Master , Installer
Programming
006006
Keypad Lockout007007
Intellizone Delay Engaged (see
Note 4 on page 28)
000000
Fire Delay Engaged001001
Auto Arm002002
066Status 3
See Note 1
on page 28
Arming with Voice Module (set
until Exit Delay finishes)
003003
Tamper004004
Zone Low Battery005005
Fire Loop Trouble006006
Zone Supervision Trouble007007
067Future UseFuture UseFuture UseFuture UseFuture Use
NOTE 1:000 = Occurs in all areas enabled in the system (refer to the appropriate control panel Programming Guide).
001 = Area 1003 = Area 3 005 = Area 5 (EVO96 only)007 = Area 7 (EVO96 only)
002 = Area 2004 = Area 4 006 = Area 6 (EVO96 only)008 = Area 8 (EVO96 only)
255 = Occurs in at least one area enabled in the system.
NOTE 2:This TLM trouble event can only be used with EVO96 control panels that have one dialler.
NOTE 3:This TLM trouble event can only be used with DGP-848 control panels or EVO96 control panels that have one dialer.
NOTE 4:This event cannot be used for a module’s PGM programming.
:If a Keyswitch Input is used, the input must be defined as “Generates a Utility Key Event on Open” or “Generates a Utility Key Event on
*
Open and Close”. If a remote control is used, the remote control button must be defined as a Utility Key button.
Refer to the Magellan™ Reference and Installation Manual for remote control button programming instructions.
Warranty
Paradox Security Systems Ltd. (“Seller”) warrants its products to be free from defects in materials and workmanship under normal use for a period of one year. Except as specifically stated herein, all express or
implied warranties whatsoever, statutory or otherwise, including without limitation, any implied warranty of merchantability and fitness for a particular purpose, are expressly excluded. Because Seller d oe s no t
install or connect the products and because the products may be used in conjunction with products not manufactured by Seller, Seller cannot guarantee the performance of the security system and sh all no t b e
responsible for circumstances resulting from the product’s inab ility to o perate. Seller obligation and liability under this warranty is expressly limited to repairing or replacing, at Seller's option, any product not
meeting the specifications. Returns must include proof of purchase and be within the warranty period. In no event shall the Seller be liable to the buyer or any other person for any loss or damages whether direct
or indirect or consequential or i nci de ntal, including without limitation, any damages for l ost pr of i t s stolen goods, or claims by any other party, caused by defective goods or otherwise arisi n g fr o m the i mpr ope r,
incorrect or otherwise faulty installation or use of the merchandise sold.
Notwithstanding the preceding paragraph, the Seller’s maximum liability will be strictly limited to the purchase price of the defective product. Your use of this p rodu ct sig nifies your a ccep t a nce of this wa rr an ty.
BEWARE: Dealers, installers and/or others selling the product are not authorized to modify this warranty or make additional warranties that are binding on the Seller.