For complete warranty information on this product please refer to the Limited Warranty Statement found on the website
www.paradox.com/terms. Your use of the Paradox product signifies your acceptance of all warranty terms and conditions.
Limitations of Alarm Systems
We strongly advise that you review and take into consideration the “Limitations of Alarm Systems” document available on our website at
http://paradox.com/Terms/
.
Warning for Connections to Non-Traditional Telephony (e.g. VoIP)
Paradox alarm equipment was designed to work effectively around traditional telephone systems. For those customers who are using a
Paradox alarm panel connected to a non-traditional telephone system, such as "Voice Over Internet Protocol" (VoIP) that converts the
voice signal from your telephone to a digital signal traveling over the Internet, you should be aware that your alarm system may not
function as effectively as with traditional telephone systems.
For example, if your VoIP equipment has no battery back-up, during a power failure your system's ability to transmit signals to the central
station may be compromised. Or, if your VoIP connection becomes disabled, your telephone line monitoring feature may al so be
compromised. Other concerns would include, without limitation, Internet connection failures which may be more frequent than regular
telephone line outages.
We therefore strongly recommend that you discuss these and other limitations involved with operating an alarm system on a VoIP or
other non-traditional telephone system with your installation company. They should be able to offer or recommend measures to reduce
the risks involved and give you a better understanding.
TBR-21: In order to comply with TBR-21, standard force dialing must be enabled.
UL AND ULC WARNINGS
This equipment has the capability of being programmed with features not verified for use in UL installations. To stay within these
standards, the installer should use the following guidelines when configuring the system:
•All components of the system should be UL listed for the intended application.
•If used for “Fire” detection, the installer should refer to NFPA St andards #72, Chapter 2. In addition, once installation is complete, the
local fire authority must be notified of the installation.
•WARNING: This equipment must be installed and maintained by qualified service personnel only
•This equipment must be verified by a qualified technician once every three years.
•All keypads must use an anti-tamper switch.
•Do not bypass fire zones.
•Maximum allowed entry delay is 45 seconds.
•Maximum allowed exit delay is 60 seconds.
•Minimum 4 minutes for bell cut-off time.
•The following features do not comply with UL requirements: Bypass Recall and Auto Trouble Shutdown.
•Do not connect the primary indicating device to a relay. The installer must use the bell output.
•To comply with UL985, the auxiliary power output should not exceed 200mA.
•Do not connect the zone ground terminal with UL Listed products.
•The metallic enclosure must be grounded to the cold water pipe.
•All outputs are Class 2 or power-limited, except for the battery terminal.The Class 2 and power-limited fire alar m circuits shall be
installed using CL3, CL3R, CL3P, or substitute cable permitted by the National Electrical Code, ANSI/NFPA 70.
•EOL resistor part #2011002000
•For UL Installations: Universal UB1640W 16.5VAC min 40VA
•All outputs are rated from 11.3Vdc to 12.7Vdc
•12Vdc 4Ah rechargeable acid/lead or gel cell backup battery (YUASA model #NP7-12 recommended) for residential use. Use a 7Ah
battery to comply with fire requirements.
•Wheelock 46T-12 siren
Patents
One or more of the following US patents may apply: 7046142, 6215399, 6111256, 6104319, 5920259, 5886632, 5721542, 5287111,
5119069, 5077549 and RE39406. Canadian and international patents may also apply.
* When using a K636 keypad, only partition 1 is available. To use both partitions, use a K10V/H, K32, or K32I keypad.
K636: 10-zone, 1-partition LED keypad
K10V/H: 10-zone LED keypads
K32: 32-zone LED keypad
K32I: 32-zone, fixed-LCD keypad
Comparison Chart
FeatureEsprit E55Esprit E65Esprit 728ULT
StayD
Maximum Zones*32328
On-board Zones494
Keypad Zones15152
Partitions**222
User Codes323249
PGMs131
Event Buffer256256256
Internet TCP/IP Communication (IP100)
Landline (dialer)
Plug-In Voice Module (VDMP3)
In-Field Firmware Upgradeable
Upload/Download with WinLoad Software
GSM Reporting
* When used with a K636 or K10V/H keypad, only zones 1-10 can be displayed.
** When used with a K636 keypad, only partition one can be displayed.
Esprit E55 / E651
Current
number per system
15 total
(including ZX8s)
33
33
3
3
33
33
33
-3
via GSM only-
Consumption
K636: Min. = 15mA / Max. = 30mA
K10V/H: Min. = 44mA / Max. = 72mA
K32: Min. 49mA / Max. = 148mA
K32I: Min. = 30mA / Max. = 70mA
-
-
-
-
-
Entering Programming Mode
To access the Data Display Mode, press the [ENTER] key after entering a section and before entering any data.
The three keys / four LEDs as indicated below will begin to flash indicating that you are in the Data Display Mode.
Each time the [
ENTER] key is pressed, the keypad will display the next digit in the current section and will continue through all the
following sections one digit at a time without changing the programmed values. Not available for sections using the Multiple Feature
Select Method. Press the [
CLEAR] key at any time to exit the Data Display Mode.
K636K10V/H
K32I
K32
1. Press [ENTER].
2. Enter your [
To modify codes, see System Codes on page 31.
3. Enter 3-digit [
4. Enter required [DATA].
WARNING: StayD Mode must be deactivated in order to enter programming mode. To deactivate StayD, press [
[OFF].
INSTALLERCODE] (default: 000000) or [MAINTENANCECODE] (no default). [ARM] and [STAY] lights flash.
SECTION] you wish to program. [ARM] and [STAY] lights are ON.
Data Entry & Display
OFF] + [CODE] +
There are two methods that can be used to enter data when in programming mode: Single Digit Data Entry and Feature Select
Programming methods:
Single Digit Data Entry Method
After entering programming mode, some sections will require that you enter decimal values from 000 to 255. Other sections will require
that you enter hexadecimal values from 0 to F. The required data will be clearly indicated in this manual. When entering the final digit in a
section, the panel will automatically save and advance to the next section.
Feature Select Programming Method
After entering certain sections, eight options will be displayed where each option from [1] to [8] represents a specific feature. Press the
key corresponding to the desired option. This means the option is ON. Press the key again to remove the digit, thereby, turning OFF the
option. Press the [
next section.
CLEAR] key to set all eight options to OFF. When the options are set, press the [ENTER] key to save and advance to the
Important Settings and Modes
SectionDescription
[950]Reset all programmable sections to factory default values
[955]Clear bus module trouble (remove disconnected module from the bus)
[970]Download memory key into panel (see the Reference & Installation Manual)
[975]Upload panel into the memory key (see the Reference & Installation Manual)
[980]Display version number of the panel (see Viewing Version Numbers on page 3)
2Programming Guide
Decimal and Hexadecimal Values
Example:
Version 01.42.
Digits 1-4
NOTE: K10V/H / K636 keypad version numbers cannot be viewed.
StepActionDetailsWhen Viewing Keypad Version
1Enter Viewing Mode:
-For panel version, Enter section [980].
-For keypad version, Enter Installer Programming,
then press and hold [
ARM].
The first digit is displayed
(usually “0”)
Digit 1 D [
ARM] is illuminated
2Press [
ENTER]The second digit is displayed. Digit 2 D [SLEEP] is illuminated
3Press [ENTER]The third digit is displayed.Digit 3 D [STAY] is illuminated
4Press [
ENTER]The fourth digit is displayed.Digit 4 D [OFF] is illuminated
Value or ActionWhat Do I Press?
Value 0 / Replace Current
SLEEP]Erase digit and remain in sectionErase digit and remain in section
[
Digit with 0
Values 1 to 9[1] to [9]Erase digit and remain in sectionZone 1 to 9
A (hex only)[0]Keys 1 to 9Zone 10
B (hex only)[
C (hex only)[
D (hex only)[
E (hex only)[
F (hex only)
Exit Without Saving[
Save Data (hex only)[
OFF]Key 0(10)Zone 11
BYP]OFFZone 12
MEM]BYPZone 13
TBL] MEMZone 14
[]
CLEAR]
ENTER]ARM & STAY LED flashAdvances to the next section
Codes and Panel Reset
Installer Code (Default: 0000 / 000000)
Maintenance Code (No Default)
System Master Code (Default: 1234 / 123456)
Panel Reset
What Do I See?
10-zone LED32-zone LED
TBLZone 15
A
[]
The Installer code is used to enter programming mode, which allows you to program everything
except
user codes. T o change the default code, go to section [397] on page 31 and refer to sec-
tion [701] option [1] on page 31.
The Maintenance code is used to enter programming mode, which allows you to
program everything except
[398], [815], [816], [817], [910], and [911]). To set the default code, go to section [398] on
page 31 and refer to section [701] option [1] on page 31.
The System Master code can use any arming method and can program user codes. To change
the default code, go to section [399] on page 31 and refer to section [701] option [1] on
page 31.
Before powering-up the panel, connect a wire from the zone 1 input to the PGM input. Power up
the panel and wait 6 seconds. Remove the wire and the panel will be reset to default.
for user codes and communication settings (sections [395], [397],
RM & STAY LED flash
Viewing Version Numbers
Esprit E55 / E653
System Planning
Serial # StickerDescription
Keypad 1 / ZX8
/ ZX8SP
Keypad 2 / ZX8
/ ZX8SP
Keypad 3 / ZX8
/ ZX8SP
Keypad 4 / ZX8
/ ZX8SP
Keypad 5 / ZX8
/ ZX8SP
Keypad 6 / ZX8
/ ZX8SP
Path Zone
(Entry Point)
Path ZonePath ZonePath Zone
Keypad 7 / ZX8
/ ZX8SP
Keypad 8 / ZX8
/ ZX8SP
Keypad 9 / ZX8
/ ZX8SP
Keypad 10 / ZX8
/ ZX8SP
Keypad 11 / ZX8
/ ZX8SP
Keypad 12 / ZX8
/ ZX8SP
Keypad 13 / ZX8
/ ZX8SP
Keypad 14 / ZX8
/ ZX8SP
Keypad 15 / ZX8
/ ZX8SP
NOTE: Maximum of three ZX8 or ZX8SP modules.
4Programming Guide
Zone Programming
See Quick Menus on page 39
To program zone definitions, zone partitions and assign options:
Zone Recognition
When expanding zones via ZX8, up to 3 ZX8 modules can be added to the system and are identified by the ZX8 3-position jumpers +1,
+9 and +17.
Not ArmedInstant*Instant20 = 24Hr. Water
10 = Instant (Full Arm)Not ArmedNot ArmedInstant21 = 24Hr. Freeze
18 = 24Hr. Gas
* Flex-Instant = Zone will follow the delay at section [720], (default is 15 seconds / 0 = instant zone)19 = 24Hr. Heat
** On-board hardwire control panel zones 1 to 4 (E55) or 1 to 9 (E65)20 = 24Hr. Water
† Only on-board zones can be defined as fire zones21 = 24Hr. Freeze
†† This alarm will follow the Panic 1 option (section [702], option [1])22 = 24hr. Panic††
23 = Follow No Pre-Alarm
NOTE: For more zone options, see sections [705] and [706] on page 8.24 = Instant No Pre-Alarm
Keypad Bus Tamper Recognition Options*Keypad / Bus Module Tamper Recognition Options*
[3][4]
OFFOFF Disabled Disabled
OFFON Trouble onlyTrouble only
ONOFF When disarmed:
TROUBLEONLY
When armed: Follow zone’s alarm type
Trouble only
ONON When di sa rm e d:
AUDIBLEALARM
When armed: Follow zone’s alarm type
Audible alarm
* Tamper recognition of keypad / bus module only if section [700] option [7] is enabled.
Keypad Bus Module Supervision Options
[6][7]
OFF OFF Disabled
OFFON Trouble only
ONOFF When disarmed:
TROUBLEONLY
When armed: Follow zone’s alarm type
ONON When di sa rm e d:
AUDIBLEALARM
When armed: Follow zone’s alarm type
OptionOFFON
[1]
[2]
A TZ zone dou blin g
A TZ wiring option s
DisabledN Enabled
SeriesN Parallel
[3]+[4] Tamper Recognition
[5]
Generate tamper on bypassed zone
N No Yes
[6]+[7] Supervision Options
[8] N/AN/AN/A
[706]General Zone Options 2
OptionOFFON
[1]N/AN/AN/A
[2]
EOL resistors
DisabledN Enabled
[3]N/AN/AN/A
[4]
[5]
[6]
ZX8 ID (Panel + 1) Input 1
ZX8 ID (Panel + 9) Input 1
ZX8 ID (Panel + 17) Input 1
Zone inputN T amper input
Zone inputN T amper input
Zone inputN T amper input
Zone Timers
Section E55 E65DataDescription (Default 060)
[041] Zone 1 (Z1):(Z1):____/____/____(000 to 255) x 10msHardwi re Zone 1 Speed
[042] Zone 2 (Z2):(Z2):____/____/____(000 to 255) x 10msHardwire Zone 2 Speed
[043] Zone 3 (Z3):(Z3):____/____/____(000 to 255) x 10msHardwi re Zone 3 Speed
[044] Zone 4 (Z4):(Z4):____/____/____(000 to 255) x 10msHardwire Zone 4 Speed
[045] Zone 5(Z1 with ATZ):(Z5):____/____/____(000 to 255) x 10msHardwire Zone 5 Speed
[046] Zone 6 (Z2 with A TZ):(Z6):____/____/____(000 to 255) x 10msHardwire Zone 6 Speed
[047] Zone 7 (Z3 with ATZ):( Z7):____/____/____(000 to 255) x 10msHardwire Zone 7 Speed
[048] Zone 8 (Z4 with A TZ):(Z8):____/____/____(000 to 255) x 10msHardwire Zone 8 Speed
[049]Zone 9N/A(Z9):____/____/____(000 to 255) x 10msHardwire Zone 9 Speed
[050]Zone 10N/A(Z1 with ATZ):____/____/____(000 to 255) x 10msHardwire Zone 10 Speed
[051]Zone 11N/A(Z2 with ATZ):____/____/____(000 to 255) x 10msHardwire Zone 11 S peed
[052]Zone 12N/A(Z3 with ATZ):____/____/____(000 to 255) x 10msHardwire Zone 12 Speed
[053]Zone 13N/A(Z4 with ATZ):____/____/____(000 to 255) x 10msHardwire Zone 13 Speed
8Programming Guide
Section E55 E65DataDescription (Default 060)
[054]Zone 14N/A(Z5 with ATZ):____/____/____(000 to 255) x 10msHardwire Zone 14 Speed
[055]Zone 15N/A(Z6 with ATZ):____/____/____(000 to 255) x 10msHardwire Zone 15 Speed
[056]Zone 16N/A(Z7 with ATZ):____/____/____(000 to 255) x 10msHardwire Zone 16 Speed
NOTE: For zones 17 and 18 (ATZ on the E65,) the zone timer is set at 600ms.
Zone Report Codes (Default = FF)
[966]Clear Zone Report Codes
OptionOFFON
[1]
* Press [
[967]Reset Zone Report Codes
OptionOFFON
[1]
* Press [
Clear zone report codes*
ENTER] to reset the respective set of report codes to default before exiting the section.
Reset zone report codes to default*
ENTER] to reset the respective set of report codes to default before exiting the section.
[ARM] + [STAY] = flash. [MAINTENANCECODE] may also be used.
[ARM] + [STAY] = on
K10V/H / K636 = 1 digit: 1 to 0(10) (can only assign zones 1-10)
* To erase a keypad zone number, press [CLEAR], then [ENTER].
[ARM] + [STAY] = flash.
K10V/H / K636 = 1 digit: 1 to 0(10) (can only assign zones 1-10)
* The first zone you program will be the designated entry point and will flash. Up to three
more path zones can be added; these zones will light up and stay lit.
Keypad Input/Output Configuration (K636 V2.0 and higher)
StepActionDetails
1[
2Press and hold [
3Option [1]ON = Output switches to ground following system arming (Blue wire 150mA max.).
4Option [2]ON = Output N.C.
NOTE: When configuring as an output, you must first clear the keypad zone (if assigned).
[701]Keypad Options
OptionOFFON
[3]
[4]
[5]
[703]Keypad Options
OptionOFFON
[1]
[2]
[3]
[4]
ENTER] + [INSTALLERCODE]
(default: 0000 / 000000)
ARM] (3sec)[ARM] + [STAY] = on
Confidential mode
To exit confidential mode
Confidential mode timer
N DisabledN Enabled
N Enter a codeN Press a key
N 2 minutesN 5 seconds
N DisabledN Enabled
N DisabledN Enabled
N DisabledN Enabled
N DisabledN Enabled
10Programming Guide
[704]Keypad Options
[3][4]
OFFOFF Regular
OFFON Sleep
ONOFF Stay
[3][4]
OFFOFF Regular
OFFON Sleep
ONOFF Stay
OptionOFFON
[5]
[6]
[7]N o exit delay beep s a nd no bell sq uawk when stay/sleep
Keypad Locko ut
[716] ____/____/____(000 to 255) minutesKeypad lockout delay (default 000)
[717] ____/____/____(000 to 255) attempt before lockingKeypad lockout counter (default 000)
Bell squawk when arm/disarm with a keypad
Beep on exit delay
arm
DataDescription
N DisabledN Enabled
N DisabledN Enabled
N DisabledN Enabled
Partition Programming
NOTE: When using a K636 keypad, only partition 1 is available. To use both partitions, use a K10V/H, K32, or K32I keypad.
[700]Partitioning
OptionOFFON
[1]
[741]Partition 1 OptionsBold = Default setting
OptionOFFON
[1]Auto-arm on time
[2]Auto-arm on no movement
Partitioning
Auto-arm arming mode
N DisabledN Enabled
DisabledN Enabled
DisabledN Enabled
N See TableN See Table
[3]& [4]
[5]Switch to stay arming if no zone entry delay is opened
[6]
[7]& [8] N/AN/AN/A
[742]Partition 2 Options
OptionOFFON
[1]Auto-arm on time
[2]Auto-arm on no movement
[3]& [4]
[5]Switch to stay arming if no entry delay is opened
[6]
Follow zones become entry delay 2 when delay zone is
bypassed
Auto-arm arming mode
Follow zones become entry delay 2 when delay zone is
bypassed
DisabledN Enabled
DisabledN Enabled
DisabledN Enabled
DisabledN Enabled
N See TableN See Table
DisabledN Enabled
DisabledN Enabled
Partition Timers
Refer to the Installer Quick Menu on page 39 for alternate entry/exit and bell cut-off timer programming.
Section DataDescription
[745]____/____/____(000 to 255) secondsPartition 1 exit delay (default 060)
[746]____/____/____(000 to 255) secondsPartition 2 exit delay (default 060)
[747]____/____/____(000 to 255) minutesPartiti on 1 bell cut-off (default 004)
[748]____/____/____(000 to 255) minutesParti tion 2 bell cut-off (default 004)
Esprit E55 / E6511
Section DataDescription
See Quick Menus on page 39
[749]____/____/____(000 to 255) x 15 minutesPartition 1 no movement (default 000)
[750]____/____/____(000 to 255) x 15 minutesPartition 2 no movement (default 000)
Section DataDescription
[761]____/____:____/___HH: MMAuto-arm on time Partition 1 (default 00:00)
[762]____/____:____/____HH: MMAuto-arm on time Partition 2 (default 00:00)
System Programming
[700]General System Options
OptionOFFON
[3]
[4]
[6]
[7]
[702]Panic Options
OptionOFFON
[1]
[2]
[3]
[4]
[5]
[6]
Audible trouble warning (except AC failure)
Audible trouble warning on AC failure
Exit delay termination
Tamper supervision on the bus module
Panic 1
Panic 2
Panic 3
Panic 1: Report only or audible alarm
Panic 2: Report only or audible alarm
Panic 3: Report only or audible alarm
N DisabledN Enabled
N DisabledN Enabled
N DisabledN Enabled
N DisabledN Enabled
Restrict arming on battery failure
Restrict arming on tamper failure (Zone + Bus Module)
Calling the VDMP3
Regular arming switches to force arming
Stay arming sw itches to st ay fo rce arming
Sleep arming switches to sleep force arming
DisabledN Enabled
DisabledN Enabled
N Disabled Enabled
N Disabled Enabled
N Disabled Enabled
N Disabled Enabled
System Timers
Section DataDescription
[710] ____/____/____(000 to 255) secondsEntry delay 1 (default 045)
[711] ____/____/____(000 to 255) secondsEntry delay 2 (default 045)
[712] ____/____/____(000 to 015) Auto zone shutdown counter (default 005)
[713] ____/____/____(000 to 255) secondsIntellizone delay (default 048)
[714] ____/____/____(000 to 255) minutesRecycle alarm delay (default 000)
[715] ____/____/____(000 to 255) Recycle alarm counter (default 000)
[718] N/AN/AN/A
[719] ____/____/____(000 to 255) daysClosing delinquency delay (default 000)
[720] ____/____/____(000 to 255) secondsFor StayD: Flex-Instant delay (default 015)
[721] ____/____/____(000 to 255) secondsFor StayD: Re-arm delay (default 005)
12Programming Guide
Communication Programming
Telephone Line Monitoring (TLM) Options
[1][2]
OFFOFFDisabled
OFFONWhen disarmed: Trouble only
When armed: Trouble only
ONOFFWhen disarmed: Trouble only
When armed: Audible alarm
ONONSilent alarms become Audible alarm
Auto-Test Report Transmission Options
[3][4] Auto-Test Report Transmission Options
OFF OFF Transmit the test report code every time the days programmed in section [840] have elapsed at the time programmed in
section [850] (default).
OFFON When disarmed: Transmit test report code every time the time programmed in section [852] has elapsed. When armed:
Transmit test report code every time the time programmed in section [851] has elapsed.
ONOFF The control panel will transmit the test report code every hour on the minute value programmed in section [850] (the last
two digits). Note that the first two digits of section [850] will be ignored. E.g. If 10:25 was programmed into section [850],
the test report code would be transmitted at the 25th minute of every hour, i.e. 11:25, 12:25, etc.
ONON The test report code will be transmitted when any of the conditions of the second and third options listed above (options
[3] = OFF and [4] = ON / options [3] = ON and [4] = OFF) are met.
[800]Dialer Options
OptionOFFON
[1]+2]*
N See TableN See Table
[3]*
[4]
[5]*
[6]*
[7]*
[8]
Switch to pulse on 5th attempt
Alternate dial
Force dial (must be enabled to comply with TBR-21)
DTMF dialing
Pulse ratio
Reporting
DisabledN Enabled
DisabledN Enabled
N Disabled Enabled
N Disabled Enabled
N1:2 1:1.5
Dialer activatedN Dialer deactivated
* E55 only
[801]Dialer Options
OptionOFFON
[1]Report system disarming
[2]Report zone restore
NAlways After alarm
Bell cutoffN Zone closure
[3]+[4]
[5]Contact ID Override
N Disabled
N CID defaults / slow
format custom
[802]Event Call Direction Options 1
OptionOFFON
[1]Call tel. #1 for arm/disarm report codes
[2]Call tel. #2 for arm/disarm report codes
[3]Call pager for arm/disarm report codes
[5]Call tel. #1 for alarm/restore report codes
[6]Call tel. #2 for alarm/restore report codes
[7]
Esprit E55 / E6513
Call pager for alarm/restore report codes
N Disabled Enabled
N Disabled EnabledDisabledN Enabled
N Disabled Enabled
N Disabled Enabled
N Disabled Enabled
[803]Event Call Direction Options 2
See Quick Menus on page 39
OptionOFFON
[1]Call tel. #1 for tamper/restore report codes
[2]Call tel. #2 for tamper/restore report codes
[3]Call pager for tamper/restore report codes
[5]Call tel. #1 for trouble/restore report codes
[6]Call tel. #2 for trouble/restore report codes
[7]
[804]Event Call Direction Options 3
OptionOFFON
[1]Call tel. #1 for special report codes
[2]Call tel. #2 for special report codes
[3]Call pager for special report codes
[5]Call personal tel. # on zone alarm (burglary/fire)
[6]Call personal tel. # on panic alarms
[7]
[8]Call personal tel. # on panel power trouble
Call pager for trouble/restore report codes
Call personal tel. # on parademic alarm
N Disabled Enabled
N Disabled EnabledDisabledN Enabled
N Disabled Enabled
N Disabled EnabledDisabledN Enabled
N Disabled Enabled
N Disabled EnabledDisabledN Enabled
N Disabled Enabled
N Disabled Enabled
N Disabled Enabled
DisabledN Enabled
Communication Settings
SectionDataDescription
[810] ___/___Reporting format
TEL1 TEL2
[811]
[812]
[815]
[816]
[817]
[818]
[819]
NOTE: To erase a phone number/numeric message, press the [SLEEP] key for each digit in the respective section.
____/____/____/____Partition 1 Account number
____/____/____/____Partition 2 Account number
___/___/___/___/___/___/___/___/___/___/___/___/___/___/___/___/___/___/___/___/___/___/___/___/___/___/
Special Keys for Telephone Numbers
PressAction or Value
OFF]*
[
[BYP]#
[MEM]switch from pulse to tone dialing or vice versa
[TBL] 4-second pause
[SLEEP]deletes current digit
[] inserts blank space
Communication Timers
Section DataDescription
[830] ____/____/____(000 to 255) x 2 secondsTLM fail delay (default 016)
[831] ____/____/____(000 to 032)Maximum dialing attempts monitoring st a tion (default 008)
[832]* ____/____/____( 000 to 127) secondsDelay between dialing attempts* (default 020)
[833] ____/____/____(000 to 255) second sDelay alarm tra nsmission (default 000)
[834] ____/____/____(000 to 127) secondsPager reporting delay (default 020)
[835] ____/____/____(000 to 010) Pager reporting message repetition (default 003)
[836]* ____/____/____(000 to 127) secondsPersonal reporting delay* (default 005)
[837]* ____/____/____(000 to 010)Personal reporting message repetition* (default 003)
[838] ____/____/____(000 to 255) secondsRecent closing delay (default 000)
[839] ____/____/____(000 to 255) minutesPower failure report delay (default 015)
[840] ____/____/____(000 to 255) daysAuto test report (default 000) (see section [801] options [3]
and [4] on page page 13)
* This section applies to the Plug-In Voice Dialer when using a VDMP3.
[850] ____/____/____/____ HH: MMAuto test report time of day (default 00:00) (see section [801]
options [3] and [4] on page page 13)
[851] ____/____/____(000 to 255) x 1 minuteArmed report delay (default 005)
[852] ____/____/____(000 to 255) x 1 minuteDisarmed report delay (default 060)
[901]* ____/____/____(000 to 255) rings Number of rings* (default 008)
[902]* ____/____/____(000 to 255) secondsAnswering machine override delay* (default 030)
* This section applies to the Plug-In Voice Dialer when using a VDMP3 (E55 only).
Communication Report Codes
[966]Clear Communication Report Codes
OptionOFFON
[6]
* Press [
[967]Reset Communication Report Codes
OptionOFFON
[6]
* Press [
[879] ____/____GSM RF jam[880] __ __/____N/A
[884] ____/____Report code for GSM lost communication with panel
Clear report code for GSM lost communication with panel*
ENTER] to reset the respective set of report codes to default before exiting the section.
Reset report code for GSM lost communication with panel*
ENTER] to reset the respective set of report codes to default before exiting the section.
____/____GSM no service ____/____IP100 no service*
____/____GSM module supervision lost ____/____IP100 supervision lost*
____/____GPRS receiver fail to communicate* ____/____IP receiver fail to communicate*
____/____N/A
____/____N/A* E65 panels only
____/____N/A
N DisabledN Enabled
N DisabledN Enabled
Esprit E55 / E6515
Communication Restore Report Codes
[881] ____/____GSM RF jam[882] ____/____N/A
____/____GSM no service ____/____IP100 no service*
____/____GSM module supervision lost ____/____IP100 supervision lost*
____/____GPRS receiver fail to commu nicat e* ____/____IP receiver fail to communicate*
* E65 panels only
Refer to the Installer Quick Menu on page 40 for alternate programming of PC phone number, panel ID, and PC password.
16Programming Guide
PCS100 Programming
GSM Reporting*
[1][2]PrimaryBackup
OFFOFF
LandlineLandline
OFFON
LandlineGSM
ONOFF
GSMLandline
ONON
GSMGSM
* Options [1] and [2] are only available on the
E55 control panel. The E65 will only
communicate via GSM.
GSM No Service Trouble Feedback
[5][6]
OFFOFF
Disabled
OFFON
When disarmed: Trouble only
When armed: Trouble only
ONOFF
When disarmed: Trouble only
When armed: Audible alarm
ONON
Silent alarm becomes audible alarm
IP/GPRS No Service Trouble Feedback
[5][6]
OFFOFF
Disabled
OFFON
When disarmed: Trouble only
When armed: Trouble only
ONOFF
When disarmed: Trouble only
When armed: Audible alarm
ONON
Silent alarm becomes audible alarm
[805]GSM Options
Option
[1] & [2]
[3] & [4] Future use
[5] & [6]
[7]Future use
[8]GSM RF jamming supervision
OFFON
NDisabled Enabled
PCS100 (GSM) Settings
SectionDataDescription
[855] ___/___/___(000 to 255) x 2 secondsGSM no service timer (default 016)
[856] ___/___/___(000 to 255) SMS language (default 000)
PGMs 6 to 8 are only available when using an ZX8 or ZX8SP Hardwired Zone Expansion module.
PGMs 9 to 12 are only available when using a PGM4 4-PGM Expansion module.
If a PGM Delay is programmed, the deactivation event can be used as a second activation event (see sections
[281] to [292] on page 24).
Partition # (99 for any
partitions)
Default
Esprit E55 / E6519
Event Description
Event Group #Sub-group #
00 = Zone OK01 to 32 = Zone number
99 = Any zone number01 = Zone open
02 = Partition status00 to 01= N/A
02 = Silent alarm
03 = Buzzer alarm
04 = Steady alarm
05 = Pulsed alarm
06 = Strobe
07 = Alarm stopped
08 = Squawk ON (Partition 1 only)
09 = Squawk OFF (Partition 1 only)
10 = Ground start (Partition 1 only)
11 = Di sarm p artition
12 = Arm partition
13 = Entry delay started
14 = Exit delay started
15 = Pre-alarm delay
99 = Any partition status event
03 = Bell status (Partition 1 only)00 = Bell OFF
01 = Bell ON
02 = Bell squawk arm
03 = Bell squawk disarm
99 = Any bell status event
06 = Non-reportable event00 = Telephone line trouble
01 = WinLoad direct
02 = WinLoad through IP module
03 = WinLoad through GSM module
04 = WinLoad through modem
05 = NEware direct
06 = NEware through IP module
07 = NEware through GSM module
08 = NEware through modem
09 = IP100 direct
10 = VDMP3 direct
1 1 = Voice through GSM module
12 = Remote access
13 = SMS through GSM module
99 = Any software access
27 = Bus module event00 = A bus module was added
01 = A bus module was removed
99 = Any Bus module event
28 = StayD pass acknowledged01 to 32 = Zone number
99 = Any zone number
29 = Arming with user01 to 32 = User number
99 = Any user number
30 = Special arming00 = Auto-arming (on time/no movement)
01 = Late to close
02 = No movement arming
03 = Partial arming
04 = Quick arming
05 = Arming through WinLoad
06 = Arming with keyswitch
99 = Any special arming
31 = Disarming with user01 to 32 = User number
99 = Any user number32 = Disarming after alarm with user
33 = Alarm cancelled with user
34 = Special disarming00 = Auto-arm cancelled (on time/no movement)
01 = Disarming through WinLoad
02 = Disarming through WinLoad after alarm
03 = Alarm cancelled through WinLoad
04 = N/A
05 = Disarm with keyswitch
06 = Disarm with keyswitch after an alarm
07 = Alarm cancelled with keyswitch
99 = Any special disarming
35 = Zone bypassed01 to 32 = Zone number
99 = Any zone number36 = Zone in alarm
37 = Fire alarm
38 = Zone alarm restore
39 = Fire alarm restore
40 = Special alarm00 = Panic non-medical emergency
01 = Panic medical (this panic alarm is not UL approved)
02 = Panic fire
03 = Recent closing
04 = Global shutdown
05 = Duress alarm
06 = Keypad lockout (Partition 1 only)
99 = Any special alarm event
41 = Zone shutdown01 to 32 = Zone number
99 = Any zone number42 = Zone tampered
43 = Zone tamper restore
Esprit E55 / E6521
Event Group #Sub-group #
44 = New trouble
(Partition 1 only except sub-group 07 = both partitions)
00 = N/A
01 = AC failure
02 = Battery failure
03 = Auxiliary current overload
04 = Bell current overload
05 = Bell disconnected
06 = Clock loss
07 = Fire loop trouble
08 = Fail to communicate to monitoring station telephone #1
09 = Fail to communicate to monitoring station telephone #2
10 = Fail to communicate to pager report
11 = Fail to communicate to voice report
13 = GSM RF jamming
14 = GSM no service
15 = GSM supervision lost
16 = Fail To Communicate IP Receiver 1 (GPRS) (E65 panels only)
17 = Fail To Communicate IP Receiver 2 (GPRS) (E65 panels only)
18 = IP Module No Service (E65 panels only)
19 = IP Module Supervision Loss (E65 panels only)
20 = Fail To Communicate IP Receiver 1 (IP) (E65 panels only)
21 = Fail To Communicate IP Receiver 2 (IP) (E65 panels only)
99 = Any new trouble event
45 = Trouble restored 00 = Telephone line restored
01 = AC failure restore
02 = Battery failure restore
03 = Auxiliary current overload restore
04 = Bell current overload restore
05 = Bell disconnected restore
06 = Clock loss restore
07 = Fire loop trouble restore
08 = FTC central 1 restored
09 = FTC central 2 restored
10 = FTC pager restored
11 = FTC voice restored
13 = GSM jamming restored
14 = GSM no service restore
15 = GSM supervision lost restore
16 = Fail To Communicate restore IP Receiver 1 (GPRS) (E65 only)
17 = Fail To Communicate restore IP Receiver 2 (GPRS) (E65 only)
18 = IP Module No Service restore (E65 panels only)
19 = IP Module Supervision loss restore (E65 only)
20 = Fail To Communicate restore IP Receiver 1 (IP) (E65 only)
21 = Fail To Communicate restore IP Receiver 2 (IP) (E65 only)
99 = Any trouble restored event
46 = Bus / EBus module new trouble
(Partition 1 only)
00 = Bus / EBus module communication fault
01 = Tamper trouble
02 = Power fail
03 = Battery failure
99 = Any bus module new trouble event
00 = Bus / EBus module communication fault restore
01 = Tamper trouble restore
02 = Power fail
03 = Battery failure
99 = Any bus module trouble restored event
48 = Special(Partition 1 only)00 = System power up
01 = Reporting test
02 = Software log on
03 = Software log off
04 = Installer in programming mode
05 = Installer exited programming mode
06 = Maintenance in programming mode
07 = Maintenance exited programming mode
08 = Closing delinquency delay elapsed
99 = Any special event
22Programming Guide
Event Group #Sub-group #
49 to 56 = N/A
58 = Zone forced01 to 32 = Zone number
99 = Any zone number59 = Zone included
64 = System Status00 = Follow Arm LED status*:
1. PGM pulse fast in alarm
2. PGM pulse fast in exit delay below 10 sec.
3. PGM pulse slow in exit delay over 10 sec.
4. PGM steady ON if armed
5. PGM OFF if disarmed
* On-board PGM only: This event can be assigned to an y parti tion. If
assigned to both partitions, the PGM event will follow the priority of
the list above, with #1 being the highest priority.
Programmable Output Options
PGM 1
[261]
OptionOFFONOFFONOFFON
PGM 2
[262]
PGM 3
[263]
PGM 4-5
[264]-[265]
future use
PGM Base Time
[1]
Off=Sec, On=Min
[2]PGM State Off=N.O., On=N.C.
[3]N/AN/AN/A N/AN/A N/AN/A
Off= Partition 1, On= Partition 2
[8]N/A-------------* If options 5 or 6 are enabled, The following Programmable Output Activation/Deactivation Events do not apply: [22 0 ], [230], [ 232], and [234].
N N N
N N N
N N N
N N N
N N N
N N N
N N N
ZX8 +1ZX8 +9ZX8 +17PGM4
PGM 6
[266]
PGM 7
[267]
PGM 8
[268]
PGM 9
[269]
PGM 10
[270]
PGM 11
[271]
PGM 12
[272]
N N N N N N N
N N N N N N N
N N N N N N N
N N N N N N N
N N N N N N N
N N N N N N N
NOTE: PGM 1 (E55/E65) PGMs 2 and 3 (E65 only)
PGMs 6 to 8 are only available when using an ZX8 or ZX8SP Hardwi red Zone Expansion module.
PGMs 9 to 12 are only available when using a PGM4 4-PGM Expansion module.
PGM cannot exceed 150mA (current limit).
Esprit E55 / E6523
Programmable Output Delays & Recognition
Section Data Default = 005
[281]PGM 1: (E55/E65 onboard) ___/___/___ (000 to 255 x 1 sec./mins.)
[282]PGM 2: (E65 onboard)___/___/___ (000 to 255 x 1 sec./mins.)
[283]PGM 3: (E65 onboard)___/___/___ (000 to 255 x 1 sec./mins.)
[286]PGM 6: (ZX8 ID =+1)___/___/___ (000 to 255 x 1 sec./mins.)
[287]PGM 7: (ZX8 ID =+9)___/___/___ (000 to 255 x 1 sec./mins.)
[288]PGM 8: (ZX8 ID =+17)___/___/___ (000 to 255 x 1 sec./mins.)
[289]PGM 9: (PGM4 output 1)___/___/___ (000 to 255 x 1 sec./mins.)
[290]PGM 10: (PGM4 output 2)___/_ __/___ (000 to 255 x 1 sec./mins.)
[291]PGM 11: (PGM4 output 3)___/_ __/___ (000 to 255 x 1 sec./mins.)
[292]PGM 12: (PGM4 output 4)___/_ __/___ (000 to 255 x 1 sec./mins.)
System Report Codes
Entering Report Codes
Ademco Slow, Silent Knight, SESCOA, and Ademco Express Formats:
Enter the desired 2-digit hex value (00-FF).
Ademco “Programmable” Format:
Enter the desired 2-digit hex values from the “Ademco Report Code List - Programmable” (see page 26). Also Note that entering FF will
set the report code to the “Automatic Report Code List” (see page 28).
Ademco “All Codes” Format:
The control panel automatically generates report codes from the “Ademco Report Code List - All Codes” (see page 26).
Refer to Decimal and Hexadecimal Values on page 3.
Clear System Report Codes
[966]Clear Report Codes
OptionOFFON
[3]
[4]
[5]
* Press [
Clear arm/disarm/alarm report codes*
Clear trouble report codes*
Clear system special report codes*
ENTER] to reset the respective set of report codes to default before exiting the section.
N DisabledN Enabled
N DisabledN Enabled
N DisabledN Enabled
Reset System Report Codes
[967]Reset Report Codes
OptionOFFON
[3]
[4]
[5]
* Enable all options you want to reset to default. Press [
default before exiting the section.
____/____Bell output disconnect
____/____Timer loss
____/____N/A
[872] ____/____Fail to communicate
____/____N/A
____/____Module lost
____/____Module tamper
System Special Report Codes (Default = FF)
SectionDataDescriptionSectionDataDescription
[875] ____/____Cold start[876] ____/____Installer in
Esprit E55 / E6525
SectionDataDescriptionSectionDataDescription
____/____Test report ____/____Installer out
____/____N/A ____/____Closing Delinquency
____/____WinLoad out ____/____N/A
[878] _____ /_____Disarm with keyswitch
Disarm with keyswitch after
_____/_____
alarm
Alarm cancelled with key-
_____/_____
switch
_____/_____N/A
NOTE: For reporting code format instructions, see page 24.
NOTE: Refer to Decimal and Hexadecimal Values on page 3.
Ademco Contact ID Report Codes
CID#Reporting CodeProgramming
Value
Medical Alarms - 100151 Gas detected26327 Notification appliance chk. #44E
100 Medical alarm 01152 Refrigeration27System Peripheral Troubles - 330 and 340
101 Pendant transmitter02153 Loss of heat28
102 Fail to report in03154 Water leakage29
Fire Alarms - 110155 Foil break2A332 Polling loop sho rt51
110 Fire alarm04156 Day trouble2B333 Expansion module failure52
111 Smoke05157 Low bottled gas level2C
112 Combustion06158 High temperature2D
113 Water flow07159 Low temperature2E336 Local printer failure55
114 Heat08161 Loss of air flow2F337 Exp. module DC loss56
115 Pull station09162 Carbon monoxide detected 30
116 Duct0A
117 Flame0BFire Supervisory - 200 and 210341 Exp. module tamper59
118 Near alarm0C200 Fire supervisory32342 Exp. module AC loss5A
75451 Early open/close9A603 Periodic RF transmissionBF
sensitivity
388 Intrusion detector Low
76452 Late open/close9B604 Fire testC0
sensitivity
389 Sensor self-test failure77453 Failed to open9C605 Status report to followC1
391 Sensor watch trouble78454 Failed to close9D606 Listen-in to followC2
392 Drift compensation error79455 Auto-arm failed9E607 Walk test modeC3
393 Maintenance alert7A456 Partial arm9F608 Periodic test - system
C4
trouble present
Open/Close - 400457 Exit error (user)A0609 Video transmitter activeC5
400 Open/Close7B458 User on premisesA1611 Point test OKC6
401 Open/Close by user7C459 Recent closeA2612 Point not testedC7
402 Group open/close7D
System - 460613 Intrusion zone walk tested C8
403 Automatic open/close7E461 Wrong code entryA3614 Fire zone walk testedC9
462 Legal code entryA4615 Panic zone walk testedCA
463 Re-arm after alarmA5616 Service requestCB
Arming with User Code (##)3 4A1 - Close by user
Auto arming3 4A3 - Automatic close
Late to close3 452 - Late to close
No movement 3 452 - Late to close
Partial arming1 456 - Group bypass
Quick arming 3 4A8 - Quick arm
Arm with PC software3 4A7 - Remote arm/disarm
ming Value
Disarm with User Code (##)1 4A1 - Open by user
Disarm after alarm* with User Code (##)1 4A1 - Open by user
Cancel alarm** with User Code (##)1 4A6 - Cancel by user
Auto-arming cancellation1 464 - Deferred open/close
Disarm with PC software1 4A7 - Remote arm/disarm
Disarm after an alarm with PC software1 4A7 - Remote arm/disarm
Cancel alarm with PC software1 4A6 - Cancel by user
Cancel paramedic alarm1 4A6 - Cancel by user
Zone bypassed (##)1 57A - Zone bypass
Zone alarm (##)1 13A - Burglary alarm
Fire alarm (##)1 11A - Fire alarm
Zone alarm restore (##)3 13A - Burglary alarm restore
Fire alarm restore (##)3 11A - Fire alarm restore
Panic 1 - emergency 1 12A - Panic alarm
Panic 2 - medical 1 1AA - Medical alarm
Panic 3 - fire 1 115 - Pull station
Recent closing3 459 - Open/Close
Global zone shutdown 1 575 - Group bypass
Duress alarm1 121 - Duress
Keypad lockout1 421 - Access denied
* An armed system is or was in alarm and was disarmed by a user.
** A disarmed system is or was in alarm (e.g. 24Hr. zone) and was disarmed by a user.
28Programming Guide
System EventDefault Contact ID Report Code
Zone shutdown (##)1 57A - Zone bypass
Zone tampered (##)1 144 - Sensor tamper
Zone tamper restore (##)3 144 - Sensor tamper restore
AC failure1 3A1 - AC loss
Battery failure1 3A9 - Battery test failure
Auxiliary supply trouble1 3AA - System trouble
Bell output current limit1 321 - Bell 1
Bell absent1 321 - Bell 1
Clock lost1 626 - Time/date inaccurate
Fire loop trouble1 373 - Fire trouble
Communication fail1 354 - Communication fail
RF jamming1 344 - RF receiver jam detection
TLM trouble restore3 351 - Telco 1 fault restore
AC failure restore3 3A1 - AC loss restore
Battery failure restore3 3A9 - Battery test restore
Auxiliary supply trouble restore3 3AA - System trouble restore
Bell output current limit restore3 321 - Bell 1 restore
Bell absent restore3 321 - Bell 1 restore
Clock programmed3 625 - Time/date reset
Fire loop trouble restore3 373 - Fire trouble restore
Fail to communicate with monitoring station3 354 - Fail to communicate
RF jamming3 344 - RF receiver jam detection
Cold start1 3A8 - System shutdown
Test report engaged1 6A2 - Periodic test report
PC software communication finished1 412 - Successful - download access
Installer on site1 627 - Program mode entry
Installer programming finished1 628 - Program mode exit
Maintenance in1 627 - Program mode entry
Maintenance out1 628 - Program mode exit
Closing delinquency1 654 - System inactivity
Module AC fail1 342 - AC failure on module
Module AC fail restore3 342 - AC restored on module
Module battery fail1 338 - Battery failure on module
Module battery fail restore3 338 - Battery failure on module
RF Module low battery1 384 - RF transmitter low battery
RF Module battery restore3 384 - RF transmitter battery restore
RF Module supervision trouble1 381 - Loss of supervision - RF
RF Module supervision restore3 381 - Supervision restore - RF
RF Module supervision lost1 381 - Loss of supervision- RF
RF Module supervision restore3 381 - Loss of supervision- RF restore
RF Module tamper1 145 - Expansion module tamper
RF Module tamper restore3 145 - Expansion module tamper restore
Paramedic alarm1 1AA - Medical
Zone forced1 57A - Zone forced
Zone included3 57A - Zone included
Esprit E55 / E6529
Installer Function Keys
To access the Installer Function keys, press:
ENTER]+[INSTALLERCODE] + [MEM] = Test Report: Send the “Test Report” report code programmed in section [875] (page 25) to the
[
monitoring station.
ENTER]+[INSTALLERCODE] + [STAY] = Cancel Communication: Cancels all communication with the WinLoad software or with the
[
monitoring station until the next reportable event.
ENTER]+[INSTALLERCODE] + [SLEEP] = Answer WinLoad Software: Will force the console to answer an incoming call from the monitoring
[
station that is using the WinLoad software.
ENTER]+[INSTALLERCODE] + [BYP] = Call WinLoad Software: Will dial the PC telephone number programmed in section [915] (page 15)
[
in order to initiate communication with a computer using the WinLoad software.
ENTER]+[INSTALLERCODE] + [TBL] = Installer Test Mode: The installer test mode will allow you to perform walk tests where the siren will
[
squawk to indicate opened zones. Press the [
TBL] key again to exit.
Trouble Display
- Press the [TBL] key to view the Trouble Display. Please note that the keypad can be programmed to emit a beep every 5 seconds
whenever a new trouble condition has occurred. Press the [TBL] key to stop the beeping.
- To view the sub-menu, press the corresponding key in the main menu.
Main Menu TroubleSub-Menu Trouble Menu
[2] Power trouble[1] Low/No battery on the control panel
[2] AC failure on control panel
[3] Auxiliary overload on control panel
[8] Low power on GSM communication module
[3] Bell trouble[1] Bell disconnect on control panel
[2] Bell overload on control panel
[4] Communication trouble[1] Telephone Line Monitoring on control panel
[2] Fail to communicate on Monitoring Telephone 1 on control panel
[3] Fail to communicate on Monitoring Telephone 2 on control panel
[4] Fail to communicate on pager telephone on control panel
[5] Fail to communicate on voice telephone on control panel
[6] Fail to communicate with PC on control panel
[7] Fail to communicate with IP receiver 1 or 2 (GPRS) (E65 panels only)
[8] Fail to communicate with IP receiver 1 or 2 (IP) (E65 panels only)
[9] GSM no service (GSM network failure)
[10] IP Module No Service (network failure) (E65 panels only)
[STAY] GSM RF jamming
[OFF] IP Receiver Unregistered (I P/GPRS) (E65 panels only)
[5] Tamper and zone wiring failure[1] to [32] Zones in tamper and zone wiring failure
[6] Module tamper trouble[2] Keypad bus
[3] ZX8 bus module
[6] GSM bus module
[7] Fire loop trouble[1] to [32] Zones in fire loop trouble
[8] Timer loss
[0 (10)] or [10] Module supervision loss[2] Keypad bus (Panel reset will not clear this trouble, clear it in
section [955] on page 2.)
[3] ZX8 bus module
[7] PGM4 bus module
[8] VDMP3
[9] PCS100
[10] IP100 (E65 panels only)
Section DataDescription
[395]____/____/____(147 to lock, other to unlock)Installer Code Lock (default 000)
[397]*____/____/____/____/____/____Installer Code (default = 000000)*
[398]____/____/____/____/____/____Maintenance Code (no default)
[399]*____/____/____/____/____/____System Master Code (default = 123456)*
*4 or 6 digits according to section [701] option [1]. The control panel automatically removes the last 2 digits of the user access code if the
length is changed from 6 digits to 4 digits. However, if the user access code length is changed from 4 to 6 digits, the control panel copies
the first 2 digits and uses them for digits 5 and 6.
Maintenance Code Limited Access Table
The Maintenance Code cannot access the following sections:
[395]Installer code lock[817]Backup monitoring station telephone
[397]Installer code[910]Panel ID
[398]Maintenance code[911]PC password
[815]Monitoring station telephone number 1[970]Download memory ke y into panel
[816]Monitoring station telephone number 2[975]Upload panel into the memory key
Access code length
Lock master code
N 6 digits 4 digits
DisabledN Enabled
User Code Options
User Options
1 - Partition 1 Access5 - Force Arming (Regular/Sleep/StayArming)
When section [400] is accessed, the panel will copy the saved value of that section to all user options- [404] to [432].
NOTE: The System Master, Master 1, and Master 2 user code options cannot be modified. However, if partitioning is not
enabled, the user code options for Master 2 will match those of Master 1.
Esprit E55 / E6531
User Report Codes (Default = FF)
[966]Clear User Report Codes
OptionOFFON
[2]
* Press [
[967]Reset User Report Codes
OptionOFFON
[2]
*Press [
Clear user report codes*
ENTER] to reset the respective set of report codes to default before exiting the section.
Reset user report codes to default*
ENTER] to reset the respective set of report codes to default before exiting the section.
N DisabledN Enabled
N DisabledN Enabled
SectionArming
[471] S. Master:____/________/____[487] User 17:____/________/____
[472] Master 1:____/________/____[488] User 18:____/________/____
[473] Master 2:____/________/____[489] User 19:____/________/____
[474] User 4:____/________/____[490] User 20:____/________/____
[475] User 5:____/________/____[491] User 21:____/________/_ ___
[476] User 6:____/________/____[492] User 22:____/________/____
[477] User 7:____/________/____[493] User 23:____/________ /____
[478] User 8:____/________/____[494] User 24:____/________/____
[479] User 9:____/________/____[495] User 25:____/________ /____
[480] User 10:____/________/____[496] User 26:____/________/____
[481] User 1 1:____/________/____[497]: User 27:____/________/____
[482] User 12:____/________/____[498] User 28:____/________/____
[483] User 13:____/________/____[499] User 29:____/________/____
[484] User 14:____/________/____[500] User 30:____/________/____
[485] User 15:____/________/____[501] User 31:____/________/____
[486] User 16:____/________/____[502] User 32:____/________/____
NOTE: For reporting code format instructions, see Entering Report Codes on page 24.
Refer to Decimal and Hexadecimal Values on page 3.
Disarming/Cancel
Alarm
SectionArming
Disarming/Cancel
Alarm
32Programming Guide
Hardware Connections
NOTE: Keyswitches are connected as standard zones and will follow ATZ options programmed in
section [705] options [1] and [2] on page 8.
Single Zone Inputs
Esprit E55 / E6533
Advanced Technology Zone (ATZ) Connections
34Programming Guide
Connecting Fire Circuits
Single Fire Zone Connections Only
If the ATZ feature is enabled, do no t u s e th e e x tra
input (i.e. in the above example, input 005 cannot be
used as a zone).
PGM Power Source
AUX + terminal = E55 current consumption must not
exceed 450mA
= E65 current consumption must not
exceed 500mA
External power supply = PGM cannot exceed 150mA
exceed the power supply’s current
limit
NOTE: For PGM options, see page 23.
Partial view of control panel
Improper connection of the transformer may result
damage to the system.
Disconnect battery before replacing the fuse.
NOTE: It is recommended that the smoke detectors be connected in a daisy chain configuration.
Alarm Relay and PGM Connections
AC Power & Backup Battery Connections
Refer to transformer requirements on page 6 for Aux. Power Output.
Transformer Requirements Table
Transformer:16.5Vac transformer with minimum 20VA
DC Power
Supply rated at:
Auxiliary Supply can
provide a maximum of:
Acceptable Battery Charge
Current
Esprit E55 / E6535
rating (40VA recommended), 50-60Hz
12Vdc, 4Ah/7Ah
(E55) 450mA, fuseless shutdown at 650mA
(E65) 500mA, fuseless shutdown at 700mA
1.1A
Connecting to WinLoad
Serial Connector
Computer
containing
WinLoad
software
307 Adapter
(CONV4USB
Converter may
also be used)
4-pin
connector
cable
Standard DB-9
cable -9-pin serial
cable (USB cable
may also be used)
For the bottom left mounting hole, instead of a plastic
standoff, use double-sided tape.
Updating Firmware Using WinLoad
To update your system firmware:
1.Connect the product to your computer using a 307USB Direct Connect Interface or CONV3USB Converter.
4.Verify the product information located in the In-Field Firmware Programmer window.
5.If the firmware programmer does not automatically detect your control panel, click the Com port settings button and select the
correct Com port. Then click the Refresh Product Info button to connect with the panel.
6.To check for new updates, click the Download Firmware from the web button.
7.From the Select Firmware drop-down box, select the firmware version you wish to install.
or
If you have already downloaded the .pef file from paradox.com, click the [...] button and select the location of the .pef file.
8.Click the Update product firmware button.
9.When the download process finishes, the update is complete.
Metal Box Installation
The crosses and dotted line represent the mounting location. If you need specific dimensions, contact Paradox Distributor Support.
(8x10”) (11x11”)
36Programming Guide
Used for connecting the
IP100 Internet Module.
Also used for In-Field
Firmware upgrade
through a 307USB Direct
Connect Interface. See
Connecting to WinLoad
on page 36 for details.
DIALER and EBUS port used for voice reporting
with the
VDMP3 plug-in voice module .
Paradox Memory Key
(PMC-4, PMC5)
Status LED:
• Flash once every second = Normal
• Flashes ON 1 second and OFF 1
second = Any trouble
• Always ON = Panel is using phone line
• Fast flash 6 seconds after power up =
Installer lock enabled
Disconnect
telephone line
before servicing.
To metallic
enclosure
Ground
clamp
AWG#14 single
conductor solid
copper wire
Cold water
pipe grounding
AUX Power
For AC power connection
information, see AC Power
& Backup Battery
Connections on page 35.
40VA transformer strongly recommended. Exceeding this limit will overload the panel power supply and lead to
complete system shutdown.
The "BELL" output
will shutdown if the
current exceeds 3A.
To provide maximum
lightning protection we
strongly recommend
having separate earth
connections for the dialer
and zone ground
terminals.
Max. number of keypads = 15 keypads Max. aux. current = 650 mA
Max. distance of keypad from panel = 76m (250 feet) Max. total run of wire = 230m (750 feet)
For the keypad’s zone
configurations, refer to the
Installer Quick Menu. If
EOL is enabled: see section
[706] option [2]. Also refer to
Keypad Zone Connections
on page 33.
Connect to any
Common input.
Refer to AC Power
& Backup Battery
Connections on
page 35.
Refer to Hardware
Connections page 33.
This equipment must be installed and maintained by qualified service personnel only.
For UL and C-UL warnings, refer to the UL and C-UL Warnings section at the back of the E55 Reference & Installation Manual.
E55 PCB Layout
Refer to PGM
Connections
on page 35.
DIALER port used for GSM
reporting using the
PCS100 GSM
Communicator Module.
Esprit E55 / E6537
Used for connecting the
IP100 Internet Module.
Also used for In-Field
Firmware upgrade
through a 307USB Direct
Connect Interface. See
Connecting to WinLoad
on page 36 for details.
The VDMP3 Plug-In Voice Module
must be stacked on top of the
PCS100.
Paradox Memory Key
(PMC-4, PMC5)
Status LED:
• Flash once every second = Normal
• Flashes ON 1 second and OFF 1
second = Any trouble
• Fast flash 6 seconds after power up
= Installer lock enabled
To metallic
enclosure
Ground
clamp
AWG#14 single
conductor solid
copper wire
Cold water
pipe grounding
AUX Power
For AC power connection
information, see AC Power
& Backup Battery
Connections on page 35.
40VA transformer strongly recommended. Exceeding this limit will overload the panel power supply and lead to
complete system shutdown.
The "BELL" output
will shutdown if the
current exceeds 3A.
Max. number of keypads = 15 keypads Max. aux. current = 700 mA
Max. distance of keypad from panel = 76m (250 feet) Max. total run of wire = 230m (750 feet)
For the keypad’s zone
configurations, refer to the
Installer Quick Menu. If
EOL is enabled: see section
[706] option [2]. Also refer to
Keypad Zone Connections
on page 33.
Connect to any
Common input.
Refer to AC Power &
Backup Battery
Connections on page 35.
Refer to Hardware
Connections page 33.
This equipment must be installed and maintained by qualified service personnel only.
For UL and C-UL warnings, refer to the UL and C-UL Warnings section at the back of the E65 Reference & Installation Manual.
E65 PCB Layout
Refer to PGM
Connections
on page 35.
EBUS port used for GSM reporting
using the
PCS100 GSM
Communicator Module.
38Programming Guide
Installer Quick Menu
Zones
StepActionDetails
1
2[
+ [INSTALLERCODE] = flash. Programmed zones are lit (button or LED depending on keypad).
ZONENUMBER] 2 digits: 01 to 32
[MAINTENANCECODE] may also be used.
3[E
4[
5Assign Partition
NROLLORERASEZONE]Wireless zone = open/close cover or press learn/tamper switch. Hardwired zone =
Press [ENTER]. T o erase a programmed zone, press [SLEEP] for 3 seconds.
ZONETYPE] Refer to page 6 for the zone type (zone defi nition).
Assign the zone to one or both partitions and press [ENTER]. By default, all zones are
[1] and/or [2] + [
ENTER]
assigned to partition 1. Goes to next available zone.
Keypad Zone Number Assignment (Keypad Programming)