Paradox Esprit 728ULT, Esprit E65, Esprit E55 Programming Manual

4 to 32 Zone Security Systems
Esprit E55 V2.0 Esprit E65 V2.1
Always Armed, Never Disarmed
Programming Guide
PARADOX.COM

Warranty

Limitations of Alarm Systems

We strongly advise that you review and take into consideration the “Limitations of Alarm Systems” document available on our website at
http://paradox.com/Terms/
.

Warning for Connections to Non-Traditional Telephony (e.g. VoIP)

Paradox alarm equipment was designed to work effectively around traditional telephone systems. For those customers who are using a Paradox alarm panel connected to a non-traditional telephone system, such as "Voice Over Internet Protocol" (VoIP) that converts the voice signal from your telephone to a digital signal traveling over the Internet, you should be aware that your alarm system may not function as effectively as with traditional telephone systems.
For example, if your VoIP equipment has no battery back-up, during a power failure your system's ability to transmit signals to the central station may be compromised. Or, if your VoIP connection becomes disabled, your telephone line monitoring feature may al so be compromised. Other concerns would include, without limitation, Internet connection failures which may be more frequent than regular telephone line outages.
We therefore strongly recommend that you discuss these and other limitations involved with operating an alarm system on a VoIP or other non-traditional telephone system with your installation company. They should be able to offer or recommend measures to reduce the risks involved and give you a better understanding.

TBR-21: In order to comply with TBR-21, standard force dialing must be enabled.

UL AND ULC WARNINGS

This equipment has the capability of being programmed with features not verified for use in UL installations. To stay within these standards, the installer should use the following guidelines when configuring the system:
All components of the system should be UL listed for the intended application.
If used for “Fire” detection, the installer should refer to NFPA St andards #72, Chapter 2. In addition, once installation is complete, the local fire authority must be notified of the installation.
WARNING: This equipment must be installed and maintained by qualified service personnel only
This equipment must be verified by a qualified technician once every three years.
All keypads must use an anti-tamper switch.
Do not bypass fire zones.
Maximum allowed entry delay is 45 seconds.
Maximum allowed exit delay is 60 seconds.
Minimum 4 minutes for bell cut-off time.
The following features do not comply with UL requirements: Bypass Recall and Auto Trouble Shutdown.
Do not connect the primary indicating device to a relay. The installer must use the bell output.
To comply with UL985, the auxiliary power output should not exceed 200mA.
Do not connect the zone ground terminal with UL Listed products.
The metallic enclosure must be grounded to the cold water pipe.
All outputs are Class 2 or power-limited, except for the battery terminal.The Class 2 and power-limited fire alar m circuits shall be installed using CL3, CL3R, CL3P, or substitute cable permitted by the National Electrical Code, ANSI/NFPA 70.
EOL resistor part #2011002000
For UL Installations: Universal UB1640W 16.5VAC min 40VA
All outputs are rated from 11.3Vdc to 12.7Vdc
12Vdc 4Ah rechargeable acid/lead or gel cell backup battery (YUASA model #NP7-12 recommended) for residential use. Use a 7Ah battery to comply with fire requirements.
Wheelock 46T-12 siren

Patents

One or more of the following US patents may apply: 7046142, 6215399, 6111256, 6104319, 5920259, 5886632, 5721542, 5287111, 5119069, 5077549 and RE39406. Canadian and international patents may also apply.
© 2008 Paradox Security Systems Ltd. All rights reserved. Specifications may change without prior notice. Esprit, Esprit E55 and Esprit E65 are trademarks or registered trademarks of Paradox Security Systems Ltd. or its affiliates in Canada, the United States and/or other countries.
Table of Contents
System Overview ...........................................................1
Comparison Chart ..........................................................1
Entering Programming Mode .........................................2
Data Entry & Display ......................................................2
Viewing Version Numbers .............................................3
System Planning ............................................................4
Zone Programming .......................................................5
Keypad Programming ..................................................10
Partition Programming .................................................11
System Programming ..................................................12
Communication Programming ........... ... ... ....... ... ... .... ...13
Programmable Output Programming ..........................19
System Report Codes ..................... ... ... .... ... ... ............ 24
Ademco Contact ID Report Codes .............................. 26
Automatic Report Code List ........................................ 28
Installer Function Keys ................................................ 30
Trouble Display ........................................................... 30
User Programming ......................... ... ... .... ... ... ... ......... 31
Hardware Connections ................................................ 33
Connecting to WinLoad ...... ... ... .... ... ... ... .... ... ... ............ 36
Metal Box Installation .................................................. 36
Installer Quick Menu .................................................... 39
NOTE: Suggestion or reminder.
More detailed information can be found in the Refe rence & Inst allation Manual, wh ich can be download ed from our website at paradox.com.
Conventions
Default Settings:
Warning or important information. Quick Menu (see page 39)
Options which are bold signify the default value: e.g. Access code length:
N6 digits 4 digits (4 dig it s is the default value).

System Overview

Module Description Maximum
K636* K10V/H K32 K32I VDMP3 Plug-In Voice Dialer 1 Min. = 28mA / Max. = 28mA IP100 Internet Module 1 Min. = 90mA / Max. = 120mA PCS100 GSM Communicator Module 1 Min. = 400mA / Max. = 1A ZX8 & ZX8SP 8-Zone Expansion Modules 3 Min. = 29mA / Max. = 31mA
* When using a K636 keypad, only partition 1 is available. To use both partitions, use a K10V/H, K32, or K32I keypad.
K636: 10-zone, 1-partition LED keypad K10V/H: 10-zone LED keypads K32: 32-zone LED keypad K32I: 32-zone, fixed-LCD keypad

Comparison Chart

Feature Esprit E55 Esprit E65 Esprit 728ULT
StayD Maximum Zones* 32 32 8 On-board Zones 4 9 4 Keypad Zones 15 15 2 Partitions** 222 User Codes 32 32 49 PGMs 1 3 1 Event Buffer 256 256 256 Internet TCP/IP Communication (IP100) Landline (dialer) Plug-In Voice Module (VDMP3) In-Field Firmware Upgradeable Upload/Download with WinLoad Software GSM Reporting
* When used with a K636 or K10V/H keypad, only zones 1-10 can be displayed. ** When used with a K636 keypad, only partition one can be displayed.
Esprit E55 / E65 1
Current
number per system
15 total (including ZX8s)
33
33 3 3 33 33 33
- 3
via GSM only -
Consumption
K636: Min. = 15mA / Max. = 30mA K10V/H: Min. = 44mA / Max. = 72mA K32: Min. 49mA / Max. = 148mA K32I: Min. = 30mA / Max. = 70mA
-
-
-
-
-

Entering Programming Mode

To access the Data Display Mode, press the [ENTER] key after entering a section and before entering any data. The three keys / four LEDs as indicated below will begin to flash indicating that you are in the Data Display Mode.
Each time the [
ENTER] key is pressed, the keypad will display the next digit in the current section and will continue through all the
following sections one digit at a time without changing the programmed values. Not available for sections using the Multiple Feature Select Method. Press the [
CLEAR] key at any time to exit the Data Display Mode.
K636 K10V/H
K32I
K32
1. Press [ENTER].
2. Enter your [ To modify codes, see System Codes on page 31.
3. Enter 3-digit [
4. Enter required [DATA].
WARNING: StayD Mode must be deactivated in order to enter programming mode. To deactivate StayD, press [ [OFF].
INSTALLER CODE] (default: 000000) or [MAINTENANCE CODE] (no default). [ARM] and [STAY] lights flash.
SECTION] you wish to program. [ARM] and [STAY] lights are ON.

Data Entry & Display

OFF] + [CODE] +
There are two methods that can be used to enter data when in programming mode: Single Digit Data Entry and Feature Select Programming methods:

Single Digit Data Entry Method

After entering programming mode, some sections will require that you enter decimal values from 000 to 255. Other sections will require that you enter hexadecimal values from 0 to F. The required data will be clearly indicated in this manual. When entering the final digit in a section, the panel will automatically save and advance to the next section.

Feature Select Programming Method

After entering certain sections, eight options will be displayed where each option from [1] to [8] represents a specific feature. Press the key corresponding to the desired option. This means the option is ON. Press the key again to remove the digit, thereby, turning OFF the option. Press the [ next section.
CLEAR] key to set all eight options to OFF. When the options are set, press the [ENTER] key to save and advance to the

Important Settings and Modes

Section Description [950] Reset all programmable sections to factory default values [955] Clear bus module trouble (remove disconnected module from the bus) [970] Download memory key into panel (see the Reference & Installation Manual) [975] Upload panel into the memory key (see the Reference & Installation Manual) [980] Display version number of the panel (see Viewing Version Numbers on page 3)
2 Programming Guide

Decimal and Hexadecimal Values

Example:
Version 01.42.
Digits 1-4
NOTE: K10V/H / K636 keypad version numbers cannot be viewed.
Step Action Details When Viewing Keypad Version 1 Enter Viewing Mode:
-For panel version, Enter section [980].
-For keypad version, Enter Installer Programming, then press and hold [
ARM].
The first digit is displayed (usually “0”)
Digit 1 D [
ARM] is illuminated
2 Press [
ENTER] The second digit is displayed. Digit 2 D [SLEEP] is illuminated
3 Press [ENTER] The third digit is displayed. Digit 3 D [STAY] is illuminated 4 Press [
ENTER] The fourth digit is displayed. Digit 4 D [OFF] is illuminated
Value or Action What Do I Press?
Value 0 / Replace Current
SLEEP] Erase digit and remain in section Erase digit and remain in section
[
Digit with 0
Values 1 to 9 [1] to [9] Erase digit and remain in section Zone 1 to 9
A (hex only) [0] Keys 1 to 9 Zone 10 B (hex only) [ C (hex only) [ D (hex only) [ E (hex only) [ F (hex only)
Exit Without Saving [
Save Data (hex only) [
OFF] Key 0(10) Zone 11 BYP] OFF Zone 12
MEM] BYP Zone 13
TBL] MEM Zone 14
[]
CLEAR] ENTER] ARM & STAY LED flash Advances to the next section

Codes and Panel Reset

Installer Code (Default: 0000 / 000000)
Maintenance Code (No Default)
System Master Code (Default: 1234 / 123456)
Panel Reset
What Do I See?
10-zone LED 32-zone LED
TBL Zone 15
A
[]
The Installer code is used to enter programming mode, which allows you to program everything except
user codes. T o change the default code, go to section [397] on page 31 and refer to sec-
tion [701] option [1] on page 31. The Maintenance code is used to enter programming mode, which allows you to
program everything except [398], [815], [816], [817], [910], and [911]). To set the default code, go to section [398] on page 31 and refer to section [701] option [1] on page 31.
The System Master code can use any arming method and can program user codes. To change the default code, go to section [399] on page 31 and refer to section [701] option [1] on page 31.
Before powering-up the panel, connect a wire from the zone 1 input to the PGM input. Power up the panel and wait 6 seconds. Remove the wire and the panel will be reset to default.
for user codes and communication settings (sections [395], [397],
RM & STAY LED flash

Viewing Version Numbers

Esprit E55 / E65 3

System Planning

Serial # Sticker Description
Keypad 1 / ZX8
/ ZX8SP
Keypad 2 / ZX8
/ ZX8SP
Keypad 3 / ZX8
/ ZX8SP
Keypad 4 / ZX8
/ ZX8SP
Keypad 5 / ZX8
/ ZX8SP
Keypad 6 / ZX8
/ ZX8SP
Path Zone
(Entry Point)
Path Zone Path Zone Path Zone
Keypad 7 / ZX8
/ ZX8SP
Keypad 8 / ZX8
/ ZX8SP
Keypad 9 / ZX8
/ ZX8SP
Keypad 10 / ZX8
/ ZX8SP
Keypad 11 / ZX8
/ ZX8SP
Keypad 12 / ZX8
/ ZX8SP
Keypad 13 / ZX8
/ ZX8SP
Keypad 14 / ZX8
/ ZX8SP
Keypad 15 / ZX8
/ ZX8SP
NOTE: Maximum of three ZX8 or ZX8SP modules.
4 Programming Guide

Zone Programming

See Quick Menus on page 39

To program zone definitions, zone partitions and assign options:

Zone Recognition

When expanding zones via ZX8, up to 3 ZX8 modules can be added to the system and are identified by the ZX8 3-position jumpers +1, +9 and +17.
E 55 No ATZ E 55 ATZ E65 No ATZ E65 ATZ
Zone 1: Panel Input 1 Zone 1: Panel Input 1A Zone 1: Panel Input 1 Zone 1: Panel Input 1A
Panel Zone 2: Panel Input 2 Zone 2: Panel Input 2A Zone 2: Panel Input 2 Zone 2: Panel Input 2A
Zone 3: Panel Input 3 Zone 3: Panel Input 3A Zone 3: Panel Input 3 Zone 3: Panel Input 3A Zone 4: Panel Input 4 Panel Zone 4: Panel Input 4A Zone 4: Panel Input 4 Zone 4: Panel Input 4A Zone 5: Input 1 Zone 5: Panel Input 1B Panel Zone 5: Panel Input 5 Zone 5: Panel Input 5A Zone 6: Input 2 Zone 6: Panel Input 2B Zone 6: Panel Input 6 Zone 6: Panel Input 6A
ZX8 Zone 7: Input 3 Zone 7: Panel Input 3B Zone 7: Panel Input 7 Zone 7: Panel Input 7A
Jumper Zone 8: Input 4 Zone 8: Panel Input 4B Zone 8: Panel Input 8 Zone 8: Panel Input 8A
Panel + 1 Zone 9: Input 5 Zone 9: Input 1 Zone 9: Panel Input 9 Panel Zone 9: Panel Input 9A
Zone 10: Input 6 Zone 10: Input 2 Zone 10: Input 1 Zone 10: Panel Input 1B Zone 11: Input 7 ZX8 Zone 11: Input 3 Zone 11: Input 2 Zone 11: Panel Input 2B Zone 12: Input 8 Jumper Zone 12: Input 4 ZX8 Zone 12: Input 3 Zone 12: Panel Input 3B Zone 13: Input 1 Panel + 1 Zone 13: Input 5 Jumper Zone 13: Input 4 Zone 13: Panel Input 4B Zone 14: Input 2 Zone 14: Input 6 Panel + 1 Zone 14: Input 5 Zone 14: Panel Input 5B
ZX8 Zone 15: Input 3 Zone 15: Input 7 Zone 15: Input 6 Zone 15: Panel Input 6B
Jumper Zone 16: Input 4 Zone 16: Input 8 Zone 16: Input 7 Zone 16: Panel Input 7B
Panel + 9 Zone 17: Input 5 Zone 17: Input 1 Zone 17: Input 8 Zone 17: Panel Input 8B
Zone 18: Input 6 Zone 18: Input 2 Zone 18: Input 1 Zone 18: Panel Input 9B Zone 19: Input 7 ZX8 Zone 19: Input 3 Zone 19: Input 2 Zone 19: Input 1 Zone 20: Input 8 Jumper Zone 20: Input 4 ZX8 Zone 20: Input 3 Zone 20: Input 2 Zone 21: Input 1 Panel + 9 Zone 21: Input 5 Jumper Zone 21: Input 4 ZX8 Zone 21: Input 3 Zone 22: Input 2 Zone 22: Input 6 Panel + 9 Zone 22: Input 5 Jumper Zone 22: Input 4
ZX8 Zone 23: Input 3 Zone 23: Input 7 Zone 23: Input 6 Panel + 1 Zone 23: Input 5
Jumper Zone 24: Input 4 Zone 24: Input 8 Zone 24: Input 7 Zone 24: Input 6
Panel + 17 Zone 25: Input 5 Zone 25: Input 1 Zone 25: Input 8 Zone 25: Input 7
Zone 26: Input 6 Zone 26: Input 2 Zone 26: Input 1 Zone 26: Input 8 Zone 27: Input 7 ZX8 Zone 27: Input 3 Zone 27: Input 2 Zone 27: Input 1 Zone 28: Input 8 Jumper Zone 28: Input 4 ZX8 Zone 28: Input 3 Zone 28: Input 2 Zone 29: N/A Panel + 17 Zone 29: Input 5 Jumper Zone 29: Input 4 ZX8 Zone 29: Input 3 Zone 30: N/A Zone 30:Input 6 Panel + 17 Zone 30: Input 5 Jumper Zone 30: Input 4 Zone 31: N/A Zone 31: Input 7 Zone 31: Input 6 Panel + 9 Zone 31: Input 5 Zone 32: N/A Zone 32: Input 8 Zone 32: Input 7 Zone 32: Input 6
Esprit E55 / E65 5
Zone Definitions
[1]- N/A [2]- N/A [3]- N/A [4] OFF = Disarm
ON = Disarm only if Stay/Sleep
armed [5] = Arm only [6] = Stay arming‡ [7] = Sleep arming‡ [8] = N/A
‡ Select only one. If all are off, key­switch will regular arm.
[1] = Auto-zone Shutdown [2] = Bypassable Zone
[3] = N/A
[4] [5]
OFF OFF Audible Alarm
OFF ON Pulsed Alarm ON OFF Silent Alarm ON ON Report Only [6] = Intellizone [7] = Delay alarm transmission
[8] = Force Zone
[1]- Partition 1
[2]- Partition 2† [3]- Both partitions†
When using a K636 keypad, only
partition 1 is available. To use both partitions, use a K10V/H, K32, or K32I keypad.
Table 2 Partition Assignment Table 3 Zone Options Table 4 Keyswitch Options
To program zone definitions, zone partitions and assign options:
Step Action Details 1 [
ENTER] + [INSTALLER CODE]
(default: 0000 / 000000)
[ARM] + [STAY] = flash. [MAINTENANCE CODE] may also be used.
2 Enter 3-digit zone you wish to program
[
ARM] + [STAY] = on (see table on page 7)
[001] to [032]
3 Enter a 2-digit zone definition 2 digits: 01 to 32 (see Table 1 below) 4 Assign Partition
By default, all zones are assigned to partition 1. (see Table 2)
[1], [2] or [3]
5 Select or deselect zone options using
buttons [1] to [8]
See Table 3 for zone options. ON = feature activated See Table 4 for keyswitch options. OFF = feature deactivated
6 To save and proceed to the next zone,
ENTER]
press [
Table 1: Zone Definitions
Zone Definitions Stay Arm Sleep Arm Fully Arm Zone Definitions 00 = Zone Disabled (default) - - -
11 = Instant Fire† 01 = Entry Delay 1 Entry Delay 1 Entry Delay 1 Entry Delay 1 12 = Delayed Fire† 02 = Entry Delay 2 Entry Delay 2 Entry Delay 2 Entry Delay 2 13 = Instant Fire Silent† 03 = Entry Delay 1 (Full Arm)
Not Armed Not Armed Entry Delay 1 14 = Delayed Fire Silent† 04 = Entry Delay2 (Full Arm) Not Armed Not Armed Entry Delay 2 15 = 24Hr. Buzzer 05 = Follow Follow* Follow* Follow* 16 = 24Hr. Burglary 06 = Follow (Sleep/Full Arm)
Not Armed Follow* Follow 17 = 24Hr. Hold-up 07 = Follow (Full Arm) Not Armed Not Armed Follow 18 = 24Hr. Gas 08 = Instant Instant* Instant* Instant* 19 = 24Hr. Heat 09 = Instant (Sleep/Full Arm)
Not Armed Instant* Instant 20 = 24Hr. Water 10 = Instant (Full Arm) Not Armed Not Armed Instant 21 = 24Hr. Freeze
18 = 24Hr. Gas
* Flex-Instant = Zone will follow the delay at section [720], (default is 15 seconds / 0 = instant zone) 19 = 24Hr. Heat ** On-board hardwire control panel zones 1 to 4 (E55) or 1 to 9 (E65) 20 = 24Hr. Water † Only on-board zones can be defined as fire zones 21 = 24Hr. Freeze †† This alarm will follow the Panic 1 option (section [702], option [1]) 22 = 24hr. Panic††
23 = Follow No Pre-Alarm
NOTE: For more zone options, see sections [705] and [706] on page 8. 24 = Instant No Pre-Alarm
25 = Keyswitch Maintain** 26 = Keyswitch Momentary**
6 Programming Guide
Partition
Section Zone*
[001] Zone 1: __________________________ _____/_____ ________ 12345678 [002] Zone 2: __________________________ _____/_____ ________ 12345678 [003] Zone 3: __________________________ _____/_____ ________ 12345678 [004] Zone 4: __________________________ _____/_____ ________ 12345678 [005] Zone 5: __________________________ _____/_____ ________ 12345678 [006] Zone 6: __________________________ _____/_____ ________ 12345678 [007] Zone 7: __________________________ _____/_____ ________ 12345678 [008] Zone 8: __________________________ _____/_____ ________ 12345678 [009] Zone 9: __________________________ _____/_____ ________ 12345678 [010] Zone 10: _________________________ _____/_____ ________ 12345678
[011] Zone 11: _________________________ _____/_____ ________ 12345678 [012] Zone 12: _________________________ _____/_____ ________ 12345678 [013] Zone 13: _________________________ _____/_____ ________ 12345678
Zone
Definition
(For a one-partition system, use K636 keypads. For a two-partition system, use K10V/H, K32, or K32I keypads.)
Zone Options
[014] Zone 14: _________________________ _____/_____ ________ 12345678 [015] Zone 15: _________________________ _____/_____ ________ 12345678 [016] Zone 16: _________________________ _____/_____ ________ 12345678 [017] Zone 17: _________________________ _____/_____ ________ 12345678 [018] Zone 18: _________________________ _____/_____ ________ 12345678 [019] Zone 19: _________________________ _____/_____ ________ 12345678 [020] Zone 20: _________________________ _____/_____ ________ 12345678 [021] Zone 21: _________________________ _____/_____ ________ 12345678 [022] Zone 22: _________________________ _____/_____ ________ 12345678 [023] Zone 23: _________________________ _____/_____ ________ 12345678 [024] Zone 24: _________________________ _____/_____ ________ 12345678 [025] Zone 25: _________________________ _____/_____ ________ 12345678 [026] Zone 26: _________________________ _____/_____ ________ 12345678 [027] Zone 27: _________________________ _____/_____ ________ 12345678 [028] Zone 28: _________________________ _____/_____ ________ 12345678 [029] Zone 29: _________________________ _____/_____ ________ 12345678 [030] Zone 30: _________________________ _____/_____ ________ 12345678 [031] Zone 31: _________________________ _____/_____ ________ 12345678 [032] Zone 32: _________________________ _____/_____ ________ 12345678
* See Zone Recognition on page 5.
NOTE: For keypad zone programming, see page 10.
Esprit E55 / E65 7
[705] General Zone Options 1
Keypad Bus Tamper Recognition Options* Keypad / Bus Module Tamper Recognition Options*
[3] [4]
OFF OFF Disabled Disabled
OFF ON Trouble only Trouble only
ON OFF When disarmed:
TROUBLE ONLY
When armed: Follow zone’s alarm type
Trouble only
ON ON When di sa rm e d:
AUDIBLE ALARM
When armed: Follow zone’s alarm type
Audible alarm
* Tamper recognition of keypad / bus module only if section [700] option [7] is enabled.
Keypad Bus Module Supervision Options
[6] [7]
OFF OFF Disabled OFF ON Trouble only
ON OFF When disarmed:
TROUBLE ONLY
When armed: Follow zone’s alarm type
ON ON When di sa rm e d:
AUDIBLE ALARM
When armed: Follow zone’s alarm type
Option OFF ON [1] [2]
A TZ zone dou blin g A TZ wiring option s
Disabled N EnabledSeries N Parallel
[3]+[4] Tamper Recognition
[5]
Generate tamper on bypassed zone
N No Yes
[6]+[7] Supervision Options
[8] N/A N/A N/A
[706] General Zone Options 2 Option OFF ON [1] N/A N/A N/A [2]
EOL resistors
Disabled N Enabled
[3] N/A N/A N/A [4] [5] [6]
ZX8 ID (Panel + 1) Input 1 ZX8 ID (Panel + 9) Input 1 ZX8 ID (Panel + 17) Input 1
Zone input N T amper inputZone input N T amper inputZone input N T amper input

Zone Timers

Section E55 E65 Data Description (Default 060) [041] Zone 1 (Z1): (Z1): ____/____/____ (000 to 255) x 10ms Hardwi re Zone 1 Speed [042] Zone 2 (Z2): (Z2): ____/____/____ (000 to 255) x 10ms Hardwire Zone 2 Speed [043] Zone 3 (Z3): (Z3): ____/____/____ (000 to 255) x 10ms Hardwi re Zone 3 Speed [044] Zone 4 (Z4): (Z4): ____/____/____ (000 to 255) x 10ms Hardwire Zone 4 Speed [045] Zone 5 (Z1 with ATZ): (Z5): ____/____/____ (000 to 255) x 10ms Hardwire Zone 5 Speed [046] Zone 6 (Z2 with A TZ): (Z6): ____/____/____ (000 to 255) x 10ms Hardwire Zone 6 Speed [047] Zone 7 (Z3 with ATZ): ( Z7): ____/____/____ (000 to 255) x 10ms Hardwire Zone 7 Speed [048] Zone 8 (Z4 with A TZ): (Z8): ____/____/____ (000 to 255) x 10ms Hardwire Zone 8 Speed [049] Zone 9 N/A (Z9): ____/____/____ (000 to 255) x 10ms Hardwire Zone 9 Speed [050] Zone 10 N/A (Z1 with ATZ): ____/____/____ (000 to 255) x 10ms Hardwire Zone 10 Speed [051] Zone 11 N/A (Z2 with ATZ): ____/____/____ (000 to 255) x 10ms Hardwire Zone 11 S peed [052] Zone 12 N/A (Z3 with ATZ): ____/____/____ (000 to 255) x 10ms Hardwire Zone 12 Speed [053] Zone 13 N/A (Z4 with ATZ): ____/____/____ (000 to 255) x 10ms Hardwire Zone 13 Speed
8 Programming Guide
Section E55 E65 Data Description (Default 060) [054] Zone 14 N/A (Z5 with ATZ): ____/____/____ (000 to 255) x 10ms Hardwire Zone 14 Speed [055] Zone 15 N/A (Z6 with ATZ): ____/____/____ (000 to 255) x 10ms Hardwire Zone 15 Speed [056] Zone 16 N/A (Z7 with ATZ): ____/____/____ (000 to 255) x 10ms Hardwire Zone 16 Speed
NOTE: For zones 17 and 18 (ATZ on the E65,) the zone timer is set at 600ms.

Zone Report Codes (Default = FF)

[966] Clear Zone Report Codes Option OFF ON [1] * Press [
[967] Reset Zone Report Codes Option OFF ON [1]
* Press [
Clear zone report codes*
ENTER] to reset the respective set of report codes to default before exiting the section.
Reset zone report codes to default*
ENTER] to reset the respective set of report codes to default before exiting the section.
N Disabled N Enabled
N Disabled N Enabled
Alarm
Section Alarm
[141] Zone 1: ___/_ __ ___/___ ___/___ ___/___ [157] Zone 17: ___/___ ___/___ ___/___ ___/___ [142] Zone 2: ___/___ ___/___ ___/___ ___/___ [158] Zone 18: ___/___ ___/___ ___/___ ___/___ [143] Zone 3: ___/_ __ ___/___ ___/___ ___/___ [159] Zone 19: ___/___ ___/___ ___/___ ___/___ [144] Zone 4: ___/___ ___/___ ___/___ ___/___ [160] Zone 20: ___/___ ___/___ ___/___ ___/___ [145] Zone 5: ___/___ ___/___ ___/___ ___/___ [161] Zone 21: ___/___ ___/___ ___/___ ___/___ [146] Zone 6: ___/___ ___/___ ___/___ ___/___ [162] Zone 22: ___/___ ___/___ ___/___ ___/___ [147] Zone 7: ___/___ ___/___ ___/___ ___/___ [163] Zone 23: ___/___ ___/___ ___/___ ___/___ [148] Zone 8: ___/___ ___/___ ___/___ ___/___ [164] Zone 24: ___/___ ___/___ ___/___ ___/___ [149] Zone 9: ___/_ __ ___/___ ___/___ ___/___ [165] Zone 25: ___/___ ___/___ ___/___ ___/___ [150] Zone 10: ___/___ ___/___ ___/___ ___/___ [166] Zone 26: ___/___ ___/___ ___/___ ___/___ [151] Zone 11: ___/___ ___/___ ___/___ ___/___ [167] Zone 27: ___/___ ___/___ ___/___ ___/___ [152] Zone 12: ___/___ ___/___ ___/___ ___/___ [168] Zone 28: ___/___ ___/___ ___/___ ___/___ [153] Zone 13: ___/___ ___/___ ___/___ ___/___ [169] Zone 29: ___/___ ___/___ ___/___ ___/___ [154] Zone 14: ___/___ ___/___ ___/___ ___/___ [170] Zone 30: ___/___ ___/___ ___/___ ___/___ [155] Zone 15: ___/___ ___/___ ___/___ ___/___ [171] Zone 31: ___/___ ___/___ ___/___ ___/___ [156] Zone 16: ___/___ ___/___ ___/___ ___/___ [172] Zone 32: ___/___ ___/___ ___/___ ___/___
Restore Tamper
Tamper
Restore Section Alarm
Alarm
Restore Tamper
Tamper
Restore
Esprit E55 / E65 9

Keypad Programming

Keypad Zone Number Assignment

Step Action Details 1 [
2 3 [

Entry Point Zone Assignment (StayD)

Step Action Details 1 [
2 Press and hold [OFF] (3sec) [ARM] + [STAY] = on 3 [
4 [ENTER] Press [ENTER] to save and exit
ENTER] + [INSTALLER CODE]
(default: 0000 / 000000) Press and hold (3sec)
ZONE NUMBER] + [ENTER]* K32LED / K32I = 2 digits: 01 to 32
ENTER] + [INSTALLER CODE]
(default: 0000 / 000000)
ZONE NUMBER]* K32LED / K32I = 2 digits: 01 to 32
[ARM] + [STAY] = flash. [MAINTENANCE CODE] may also be used.
[ARM] + [STAY] = on
K10V/H / K636 = 1 digit: 1 to 0(10) (can only assign zones 1-10) * To erase a keypad zone number, press [CLEAR], then [ENTER].
[ARM] + [STAY] = flash.
K10V/H / K636 = 1 digit: 1 to 0(10) (can only assign zones 1-10) * The first zone you program will be the designated entry point and will flash. Up to three more path zones can be added; these zones will light up and stay lit.

Keypad Input/Output Configuration (K636 V2.0 and higher)

Step Action Details 1 [
2 Press and hold [ 3 Option [1] ON = Output switches to ground following system arming (Blue wire 150mA max.).
4 Option [2] ON = Output N.C.
NOTE: When configuring as an output, you must first clear the keypad zone (if assigned).
[701] Keypad Options Option OFF ON [3]
[4] [5]
[703] Keypad Options Option OFF ON [1]
[2] [3] [4]
ENTER] + [INSTALLER CODE]
(default: 0000 / 000000)
ARM] (3sec) [ARM] + [STAY] = on
Confidential mode To exit confidential mode Confidential mode timer
One-touch regular arming One-touch stay arming One-touch sleep arming One-touch bypass programming
[ARM] + [STAY] = flash.
OFF = Input (Keypad zone input)
OFF = Output N.O.
N Disabled N Enabled N Enter a code N Press a key N 2 minutes N 5 seconds
N Disabled N Enabled N Disabled N Enabled N Disabled N Enabled N Disabled N Enabled
10 Programming Guide
[704] Keypad Options
[3] [4]
OFF OFF Regular
OFF ON Sleep
ON OFF Stay
[3] [4]
OFF OFF Regular
OFF ON Sleep
ON OFF Stay
Option OFF ON [5] [6] [7] N o exit delay beep s a nd no bell sq uawk when stay/sleep
Keypad Locko ut
[716] ____/____/____ (000 to 255) minutes Keypad lockout delay (default 000) [717] ____/____/____ (000 to 255) attempt before locking Keypad lockout counter (default 000)
Bell squawk when arm/disarm with a keypad Beep on exit delay
arm
Data Description
N Disabled N Enabled N Disabled N Enabled N Disabled N Enabled

Partition Programming

NOTE: When using a K636 keypad, only partition 1 is available. To use both partitions, use a K10V/H, K32, or K32I keypad.
[700] Partitioning Option OFF ON [1]
[741] Partition 1 Options Bold = Default setting Option OFF ON [1] Auto-arm on time
[2] Auto-arm on no movement
Partitioning
Auto-arm arming mode
N Disabled N Enabled
Disabled N EnabledDisabled N Enabled
N See Table N See Table
[3]& [4]
[5] Switch to stay arming if no zone entry delay is opened [6] [7]& [8] N/A N/A N/A
[742] Partition 2 Options Option OFF ON [1] Auto-arm on time
[2] Auto-arm on no movement
[3]& [4]
[5] Switch to stay arming if no entry delay is opened [6]
Follow zones become entry delay 2 when delay zone is bypassed
Auto-arm arming mode
Follow zones become entry delay 2 when delay zone is bypassed
Disabled N EnabledDisabled N Enabled
Disabled N EnabledDisabled N Enabled
N See Table N See Table
Disabled N EnabledDisabled N Enabled

Partition Timers

Refer to the Installer Quick Menu on page 39 for alternate entry/exit and bell cut-off timer programming.
Section Data Description [745] ____/____/____ (000 to 255) seconds Partition 1 exit delay (default 060) [746] ____/____/____ (000 to 255) seconds Partition 2 exit delay (default 060) [747] ____/____/____ (000 to 255) minutes Partiti on 1 bell cut-off (default 004) [748] ____/____/____ (000 to 255) minutes Parti tion 2 bell cut-off (default 004)
Esprit E55 / E65 11
Section Data Description
See Quick Menus on page 39
[749] ____/____/____ (000 to 255) x 15 minutes Partition 1 no movement (default 000) [750] ____/____/____ (000 to 255) x 15 minutes Partition 2 no movement (default 000)
Section Data Description [761] ____/____:____/___ HH: MM Auto-arm on time Partition 1 (default 00:00) [762] ____/____:____/____ HH: MM Auto-arm on time Partition 2 (default 00:00)

System Programming

[700] General System Options Option OFF ON [3] [4]
[6] [7]
[702] Panic Options Option OFF ON [1]
[2] [3] [4] [5] [6]
Audible trouble warning (except AC failure) Audible trouble warning on AC failure Exit delay termination Tamper supervision on the bus module
Panic 1 Panic 2 Panic 3 Panic 1: Report only or audible alarm Panic 2: Report only or audible alarm Panic 3: Report only or audible alarm
N Disabled N Enabled N Disabled N Enabled N Disabled N Enabled N Disabled N Enabled
Disabled N EnabledDisabled N EnabledDisabled N EnabledReport only N AudibleReport only N AudibleReport only N Audible
[703] Arming/Disarming Options 1 Option OFF ON [5] [6]
[8]
[704] Arming/Disarming Options 2 Option OFF ON [1]
[2] [3]
Restrict arming on battery failure Restrict arming on tamper failure (Zone + Bus Module) Calling the VDMP3
Regular arming switches to force arming Stay arming sw itches to st ay fo rce arming Sleep arming switches to sleep force arming
Disabled N EnabledDisabled N Enabled
N Disabled Enabled
N Disabled Enabled N Disabled Enabled N Disabled Enabled

System Timers

Section Data Description [710] ____/____/____ (000 to 255) seconds Entry delay 1 (default 045) [711] ____/____/____ (000 to 255) seconds Entry delay 2 (default 045) [712] ____/____/____ (000 to 015) Auto zone shutdown counter (default 005) [713] ____/____/____ (000 to 255) seconds Intellizone delay (default 048) [714] ____/____/____ (000 to 255) minutes Recycle alarm delay (default 000) [715] ____/____/____ (000 to 255) Recycle alarm counter (default 000) [718] N/A N/A N/A [719] ____/____/____ (000 to 255) days Closing delinquency delay (default 000) [720] ____/____/____ (000 to 255) seconds For StayD: Flex-Instant delay (default 015) [721] ____/____/____ (000 to 255) seconds For StayD: Re-arm delay (default 005)
12 Programming Guide

Communication Programming

Telephone Line Monitoring (TLM) Options
[1] [2]
OFF OFF Disabled
OFF ON When disarmed: Trouble only
When armed: Trouble only
ON OFF When disarmed: Trouble only
When armed: Audible alarm
ON ON Silent alarms become Audible alarm
Auto-Test Report Transmission Options
[3] [4] Auto-Test Report Transmission Options
OFF OFF Transmit the test report code every time the days programmed in section [840] have elapsed at the time programmed in
section [850] (default).
OFF ON When disarmed: Transmit test report code every time the time programmed in section [852] has elapsed. When armed:
Transmit test report code every time the time programmed in section [851] has elapsed.
ON OFF The control panel will transmit the test report code every hour on the minute value programmed in section [850] (the last
two digits). Note that the first two digits of section [850] will be ignored. E.g. If 10:25 was programmed into section [850],
the test report code would be transmitted at the 25th minute of every hour, i.e. 11:25, 12:25, etc.
ON ON The test report code will be transmitted when any of the conditions of the second and third options listed above (options
[3] = OFF and [4] = ON / options [3] = ON and [4] = OFF) are met.
[800] Dialer Options Option OFF ON [1]+2]*
N See Table N See Table
[3]* [4]
[5]* [6]* [7]* [8]
Switch to pulse on 5th attempt Alternate dial Force dial (must be enabled to comply with TBR-21) DTMF dialing Pulse ratio Reporting
Disabled N EnabledDisabled N Enabled
N Disabled Enabled N Disabled Enabled N1:2 1:1.5
Dialer activated N Dialer deactivated
* E55 only
[801] Dialer Options Option OFF ON [1] Report system disarming
[2] Report zone restore
N Always After alarmBell cutoff N Zone closure
[3]+[4]
[5] Contact ID Override
N Disabled
N CID defaults / slow
format custom
[802] Event Call Direction Options 1 Option OFF ON [1] Call tel. #1 for arm/disarm report codes
[2] Call tel. #2 for arm/disarm report codes [3] Call pager for arm/disarm report codes [5] Call tel. #1 for alarm/restore report codes [6] Call tel. #2 for alarm/restore report codes [7]
Esprit E55 / E65 13
Call pager for alarm/restore report codes
N Disabled Enabled N Disabled Enabled Disabled N Enabled N Disabled Enabled N Disabled Enabled N Disabled Enabled
Loading...
+ 33 hidden pages