Software Versions 3.1 (728+, 738EX+ and 738+), 3.2 (728EX4+, 728DZ8+ and 748+) and 3.3 (728EX+)
INSTALLER CODE
Full access to programming, except user access codes (PINs). No access to arming/disarming. Use only numeric keys from [1] to [10] (key
[10] = 0). For default installer codes, refer to Table 1 below.
Press the [TBL]/[TRBL] key to view the trouble. Refer to Table 2 below.
[1]
- No Battery or Low Voltage
[2]
- Power Failure
[4]
- Bell Output Disconnected[9] - Tamper or Zone Wiring Failure
[5]
- Maximum Bell Current[10] - Telephone Line Monitoring Failure
[6]
- Maximum Auxiliary Current[11] - Fire Loop Trouble
Default Installer Codes by Control Panel
Ta ble 2:
Trouble Display
[7]
- Communicator Report Failure
[8]
- Timer Loss*
* To clear the Timer Loss trouble, refer to Key Access Programming on page 12 (the [
Press the [
CLEAR] button to clear troubles.
MEM] key).
HEXA PROGRAMMING
Addresses 000 to 043 and 300 to 527 are programmed using the Hexa Programming method. In this mode, you can enter any hexadecimal
digit from 0 - F where keys [1] to [9] represent digits 1 to 9 respectively; the other keys represe nt hexadecimal digits A to F as shown in
Figure 1 on page 1. To program using the Hexa Programming method:
1)Press [
2)The [
3)Enter the desired 3-digit [
4)The keypad will display the 2-digit data currently saved at this address as described in Figure 1 on page 1
5)Enter 2-digit [
6)Return to step 2 or press [
ENTER] + [INSTALLERCODE] (default: see Table 1 on page 1)
ENTER] key will flash indicating you are in programming mode
ADDRESS]
DATA] and do not press [ENTER], the software automatically saves the data
CLEAR] to exit programming mode
Figure 1: Hexa Digit Data Display For LED Keypads
Note: LCD keypads will display current data on the screen.
Each key in the first 2 rows of the keypad represents a specific value when the key is lit, as shown above. If the key
isn’t lit, the key represents 0. The sum of the values of the lit keys in the first row correspond to the second hexa
digit. The sum of the values of the lit keys in the second row correspond to the first hexa digit as shown in the
example below.
If the key is not lit, value = 0
Sum of the first row = second hexa digit
Sum of the second row = first hexa digit
Note: Values 10 to 15 represent hexa digits A to F respectively. See keypad to the left.
Esprit+- 1 - Programming Guide
= Second digit = 8 + 2 = 10
= First digit = 4 + 2 + 1 = 7
Therefore 2-digit data = 7A
STREAMLINED SECTION PROGRAMMING
This is an alternate method to Hexa Programmi ng. The addresses (000 - 043 and 300 - 527) programmed in the Hexa Programming
method are grouped into 67 sections where each section co ntains four addresses (i.e. section 00 = addresses 000 - 003). Using this
method allows you to program 8 digits (4 addresses) without having to exit and reenter addresses.
Note, the keypad will not display the current data in the Hexa Streamlined Programming method.
To program using the Hexa Streamlined Section method:
1)Press [
2)The [
3)Enter 2-digit [
4)The [
5)Enter 8-digit [
ENTER] + [INSTALLERCODE] (default: see Table 1 on page 1) + [7]
ENTER] and [2ND] keys will flash to indicate you are in programming mode
SECTION] (00 - 67)
ENTER] key will remain on while the [2ND] key will be off
DATA] to program the section
6)The keypad will "beep" to indicate that the section has been programmed, data is saved and the software has advanced to the next
section
Zone 1 =Zo n e 5**Zone 9**Zone 9Zone 7Zone 13Zone 13Zone 13*
Zone 2 =Zo n e 6**Zone 10**Zone 8Zone 8Zone 14Zone 14Zone 14*
* Control panel does not distinguish between zones 13 and 14 and keypad zones 1 (zone 13) and 2 (zone 14).
** The 728EX4+ and 728DZ8+ control panels do not support any keypad zone s.
WARNING: This equipment must be installed and maintained by qualified service personnel only.
(key [2
between first and second call (see above). Second
digit determines number of rings required before
panel will answer. If [2
not answer (default value is [2
Identifies the control panel to the PC.
{
Identifies the PC to the panel.
{
ND][2ND] is entered, panel will
ND] [8]).
TELEPHONE AND ACCOUNT NUMBERS
If only one central station phone number is used, program the same number for telephone number 1 and 2. If on ly one account num be r is
required, the same number must be entered for both account "A" and "B".
[10] = the number "0"[
[11] = *[
[12] = #[
BYP] = switch from pulse to tone while dialing
MEM] = pause 4 seconds
TRBL] = end of number
Computer Telephone Number
Streamline SectionStreamline Section
02
Central Station Telephone Number 1
Streamline SectionStreamline Section
04
Central Station Telephone Number 2
Streamline SectionStreamline Section
06
Account “A” and “B” (View at addresses 032 to 035)
Streamline Section
08
(View at addresses
__/__/__/__/__/__/__/__
1 2 3 4 5 6 7 89 10 11 12 13 14 15 16
(View at addresses
__/__/__/__/__/__/__/__
1 2 3 4 5 6 7 89 10 11 12 13 14 15 16
(View at addresses
__/__/__/__/__/__/__/__
1 2 3 4 5 6 7 89 10 11 12 13 14 15 16
__/__/__/____/__/__/__
12345678
AB
008
to
015
016
024
)
to
to
03
023
05
031
07
)
)
__/__/__/__/__/__/__/__
__/__/__/__/__/__/__/__
__/__/__/__/__/__/__/__
Press the [TRBL] key to
end phone number if
less than 16 digits are
programmed.
Press the [TRBL] key to
end phone number if
less than 16 digits are
programmed.
Press the [TRBL] key to
end phone number if
less than 16 digits are
programmed.
For 3 digit account
numbers, enter “skip”
([2
ND]) as first digit.
Esprit+ - 3 - Programming Guide
Streamline SectionData
[2
ND] / [2ND]Future Use036
[2ND] / ___1st digit: Value must be entered
09
___ / ___1st digit: Communicator Format 1
___ / ___1st digit: PGM1 type
Streamline SectionData
Description
ND])
(i.e. [2
2nd digit: Time correction (see
table at right)
2nd digit: Communicator Format 2
2nd digit: PGM2 type
Description
Address
AddressTime Correction Table
[8] = Minus 4 seconds
[9] = Minus 8 seconds
[10] = Minus 12 seconds
[11] = Minus 16 seconds
[12] = Minus 20 seconds
[
BYP
[
MEM
[
TRBL
037
038
[2ND] = No adjustment
[1] = Plus 4 seconds
[2] = Plus 8 seconds
[3] = Plus 12 seconds
[4] = Plus 16 seconds
[5] = Plus 20 seconds
[6] = Plus 24 seconds
[7] = Plus 28 seconds
[1]= (1400Hz, 1800Hz, 10bps)[7]= RADIONICS with PARITY (2300Hz, 40bps)
[2]= SILENT KNIGHT fast (1400Hz, 1900Hz, 20bps)[8]= * ADEMCO express
[3]= SESCOA (2300Hz, 1800Hz, 20bps)[9]= * ADEMCO contact ID (programmable codes)
[4]= RADIONICS (40bps with 1400Hz handshake)[10]= * ADEMCO contact ID (all codes)
[5]= RADIONICS (40bps with 2300Hz handshake)[
TRBL]= * DTMF - no handshake (personal dialing)
]
= Minus 24 seconds
]
= Minus 28 seconds
]
= Minus 32 seconds
Programmable Contact ID Event Codes
All addresses from 300 to 527 (sections 11 to 67) programmed with values other than [2ND] [2ND] will report the contact ID codes corresponding to the
values programmed. Values to be programmed should be selected from this table.
CIDReporting CodeProg. ValueCIDReporting CodeProg. Value
OW TEMPERATURE[2] / [2ND]602:PERIODIC TEST[4] / [1]
OSS AIR FLOW[2] / [1]625:TIME / DATE RESET[4] / [2]
P
ROTECTION LOOP OPEN
[2] / [TRBL]
Esprit+ - 4 - Programming Guide
REPORTING CODES
All digits from [1] to [F] are valid. [2ND] = digit will not be reported except for Contact ID programmable codes. For single digi t reporting,
enter “skip” ([2
If the Contact ID Format (all codes) is selected, addresses 300 to 527 (sections 11 to 67) do not have to be programmed
(select Contact ID (all codes) - key [10] for both central station numbers at section 09 - address 038 on page 4).
ARMING (CLOSING) REPORT CODES:
Streamline
Section
1117
1218
1319
1420
ND]) as the first digit (default = [2ND] / [2ND]).
Addresses 062 to 126 are programmed using the Feature Select Programming method. In this method, every key on the keypad in each
address represents an option or feature. Pressing a key will display it on the keypad and pressing it again will extinguish the key. The ON or
OFF status of each key determines the selected feature. Addresses 080 to 085 are reserved for future use. To program using the Feature
Select Programming method:
1)Press [ENTER] + [INSTALLERCODE] (default: see Table 1 on page 1)
2)The [
3)Enter 3-digit [
4)After entering the address, the keypad will display the feature selection status. Turn the keys ON or OFF by pressing the appropriate
5)Return to step 3 to continue programming or press [
ENTER] key will flash to indicate you are in programming mode
ADDRESS] (062 - 126)
key until the desired options are set. Press the [
been accepted. The [
ENTER] key will flash to indicate that the software is awaiting the next address entry.
ENTER] key to accept, there will be a confirmation "beep" indicating the options h ave
OFFOFF - TLM disabled
OFFON - TLM generates trouble only
ONOFF - generates an alarm if armed
ONON - silent alarm becomes audible
(address 086, key [9] has to be OFF)
Reporting Options
KEY
[11] [12]
OFF OFF - Reporting disabled
OFF ON - Regular reporting
ON OFF - Split* reporting (Alarms & System)
ONON - Double reporting
Report Dialing Sequence (tel. no.)
Regular:1,2,1,2,1,2,1,2, fail to comm.
Split*:Alarms - 1,1,1,1,1,1,1,1, fail to comm
Double:1,1,1,1,1,1,1 ,1 , fa il to comm
* On alarm, all reports are made to Tel. #1 until system is
disarmed. Once disarmed, system reports are made to
Tel. #2.
System Armed[10][11]System Disarmed*
Alarm as per
individual zone
definitions
Always generate
trouble and
alarm, audible or
silent as per
individual zone
definitions
* Exception: for 24 hour zones, the tamper definition
will follow the audible/silent alarm definition of the 24
hour zone.
** Silent zones will generate a silent alarm.
System - 2,2,2,2,2,2,2,2, fail to comm
2,2,2,2,2,2,2,2, fail to comm
Tamper / Wire Fault Definitions
KEY
OFFOFF- Tamper supervision
OFFON- No alarm, trouble
ONOFF- Silent alarm.
ONON- Audible alarm.
disabled
code reported
Trouble & alarm
codes reported
Trouble & alarm
codes reported**
090:
Exclude power failure from trouble display
Zone (4, 9 or 15) enabled***
Auto arm = regular arm
N/A
N/A
N/A
No tamper bypass
N/A
Zone doubling (ATZ)****
Audible trouble warning
Duress
Keypad zone 1 supervision
Keypad zone 2 supervision
N/A
N/A
N/A
KEY
OFF/ON
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
[2ND]
[1]
[2]
[3]
[4]
[5]
[6]
[7]
[8]
[9]
[10]
[11]
[12]
[BYP]
[MEM]
[TRBL]
Enabled
N
Disabled***
N
Stay / System A
N
N/A
N
N/A
N
N/A
N
Tamper follows zone bypass definition
N
N/A
N
Enabled****
N
Enabled
N
Enabled
N
Enabled
N
Enabled
N
N/A
N
N/A
N
N/A
N
Esprit+- 11 - Programming Guide
*** NOTE 1: This feature applies to the 728+, 728DZ8+, 738+
and 748+ only. When ATZ is enabled (address 090 key [8]
ON) and zone 3 is defined as a fire zone, this zone must be
disabled. If using a 728+ or 728DZ8+, zone 4 will be
disabled. If using a 738+, zone 9 will be disabled. If using a
748+, zone 15 will be disabled.
**** NOTE 2: This feature applies to the 728+, 728DZ8+,
738+ and 748+ only.
Ta ble 6:
Zone Definition
KEY SELECT:
Intellizone = ON
Silent = ON
24Hr. / Fire = ON
Keypad zones cannot be set as 24Hr. zones.* When zone 3 is defined “24Hr.”, it becomes a fire zone
Note: Do not use the Intellizone feature and an entry delay for the same zone, otherwise an alarm may occur as a user tries
to disarm the system.
Zones that are not selected at addresses 100 to 114 become “Delay 1” zones.
KEY ACCESS PROGRAMMING
Programs features quickly, without entering addresses or sections numbers. To activate Key Access Programming, press [ENTER] followed
by the the installer code, master code or user code 1 (code required depends on the desired feature; see below). Press the key
corresponding to the desired feature. Press [
programming mode.
KeyFeature
[8]
[9]
[MEM]
[BYP]
[TRBL]
Installer Test Mode
In Installer Test mode, a confirmation beep (intermittent) indicates that the test
mode is enabled. A rejection beep indicates that the test mode is disabled. The
bell will squawk during walk testing to indicate opened, functional zones.
“Auto Arming” Time Program
Key [9] flashes. Enter 2-digit hour (00 to 23) and 2-digit minutes (00 to 59).
Panel Time Programming
[MEM] key flashes. Enter 2-digit hour (00 to 23) and 2-digit minutes (00 to 59).
Test Report
Reporting is enabled at address 086, keys [11] and [12] (see page 11). A value
must be entered at address 512 (page 8) and both telephone and account
numbers must be programmed.
Call Espload Via Telephone
Panel identifier and PC password (addresses 004 to 007 on page 3) and
computer telephone number (addresses 008 to 015 on page 3) must be
programmed.
ENTER] or [CLEAR] to exit. When communicating with Espload, it is impossible to enter
Codes that can access feature
Installer Code Only
Installer Code, Master Code or User Code 1
Installer Code, Master Code or User Code 1
Installer Code, Master Code or User Code 1
Installer Code, Master Code or User Code 1
[AWAY]
[STAY]
Answer Espload
This feature is available when using the ADP-1 adapter. In Espload, “blind dial”
must be activated in “modem setup” section and panel phone number
programmed (works also with ADP-1).
Cancel Communication Attempts
Until next reportable event.
Esprit+ - 12 - Programming Guide
Installer Code, Master Code or User Code 1
Master Code/User Code 1 only cancel calls to Espload
The Installer Code can cancel all communications
CONNECTION DIAGRAMS
The system hardware will recognize the following zone conditions:
SINGLE ZONE CONNECTIONS
Figure 3: N.C. Contacts, without EOL ResistorFigure 4: N.C. Contacts, with EOL Resistor (UL/ULC)
Address 088,[MEM] = “ON” (EOL resistor disabled)
[10] = “OFF”
[11] = “OFF”
Address 090,[8] = “OFF” (ATZ disabled)
Tamper/Wire Fault disabled.
Address 088,[MEM] = “OFF” (EOL resistor enabled)
[10] = “OFF”
[11] = “OFF”
Address 090,[8] = “OFF” (ATZ disabled)
Tamper/Wire Fault disabled.
Figure 5: N.O. Contacts, with EOL Resistor (UL/ULC)Figu re 6: N.C. Contacts, without EOL Resistor, with Tamper
Recognition
Address 088,[MEM] = “OFF” (EOL resistor enabled)
Address 090,[8] = “OFF” (ATZ disabled)
[10] = “OFF”
[11] = “OFF”
Tamper/Wire Fault disabled.
Address 088,[MEM] = “ON” (EOL resistor disabled)
[10] = (See Tamper/Wire Fault definitions on
[11] = page 11.)
Address 090,[8] = “OFF” (ATZ disabled)
Figure 7: N.C. Contacts, with EOL resistor , with Tamper and Wire
Fault Recognition (UL/ULC)
Address 088,[MEM] = “OFF” (EOL resistor enabled)
[10] = (See Tamper/Wire Fault definitions on
[11] = page 11.)
Address 090,[8] = “OFF” (ATZ disabled)
Esprit+- 13 - Programming Guide
ADVANCED TECHNOLOGY ZONE CONNECTIONS (728+, 728DZ8+, 738+ AND 748+ ONLY)
Figure 8: N.C. Contacts, without EOL ResistorFigure 9: N.C. Contacts, without EOL Resistor, with Tamper
Recognition
Address 088,[MEM] = “ON” (EOL resistor disabled)
Address 090,[8] = “ON” (ATZ enabled)
[10] = “OFF”
[11] = “OFF”
Tamper/Wire Fault disabled.
Figure 10: N.O. Contacts, with EOL Resistor, with Tamper and
Wire Fault Recognition (UL/ULC)
Address 088,[MEM] = “OFF” (EOL resistor enabled)
Address 090,[8] = “ON” (ATZ enabled)
[10] = (See Tamper/Wire Fault defintions on
[11] = page 11.)
OTHER CONNECTION DIAGRAMS
Address 088,[MEM] = “ON” (EOL resistor disabled)
[10] = (See Tamper/Wire Fault defintions on
[11] = page 11.)
Address 090,[8] = “ON” (ATZ enabled)
Figure 11: Connecting One Keypad ZoneFigure 12: Connecting Two Keypad Zones (639 only)
Esprit+ - 14 - Programming Guide
Figure 13: Connecting Two Keypad Zones Using Two Keypads
If using a 728+, please refer to
Inset 1 for the input terminals. For
the hardwired connections, refer
to Single Zone Connections on
page 13 and Advanced
T echnology Zone Connections on
page 14.
The maximium number of keypads per installation is
dependent on the auxiliary output, which is not to exceed
400mA. Refer to the Reference & Installation Manual for the
current consumption table. Refer to Figure 11, Figure 12
and Figure 13 on pages 14 and 15 for information keypad
zone connections*.
* NOTE: The 728EX4+ and 728DZ8+ control
panels do not support keypad zones.
Esprit+ - 16 - Programming Guide
Keypads
- LED Keypads 636, and 646
- LCD Keypad 642
ESPRIT 738+ / 738EX+ WIRING DIAGRAM
If using a 738+, please ref er to Inset 1 for t he
input terminals. For the hardwired
connections, refer to Single Zone Connections
on page 13 and Advanced Technology Zone
Connections on page14.
Keypads
- LED Keypads 636, and 646
- LCD Keypad 642
The maximium number of keypads per installation is
dependent on the auxiliary output, which is not to exceed
400mA. Refer to the Reference & Installation Manual for the
current consumption table. Refer to Figure 11, Figure 12
and Figure 13 on pages 14 and 15 for information keypad
zone connections.
Esprit+- 17 - Programming Guide
ESPRIT 748+ WIRING DIAGRAM
Please refer to Inset 1 for the input terminals. For
the hardwired connections, refer to Single Zone
Connections on page 13 and Advanced
Technology Zone Connections on page14.
The maximium number of keypads per installation is
dependent on the auxiliary output, which is not to exceed
400mA. Refer to the Reference & Installation Manual for the
current consumption table. Refer to Figure 11, Figure 12
and Figure 13 on pages 14 and 15 for information keypad
zone connections.