Piping
Piping
Shock absorber
Intake grille
p
u
l
l
o
u
t
t
h
e
p
i
p
i
n
g
p
u
l
l
o
u
t
t
h
e
p
i
p
i
n
g
1. Insert the piping sleeve to the hole.
2. Fix the bushing to the sleeve.
3. Cut the sleeve until it extrudes about
19
/32" (15 mm) from the wall.
4. Finish by sealing the sleeve with putty
or caulking compound at the fi nal stage.
ACXF60-02630
Required tools for Installation Works
INDOOR UNIT
1
2
HOW TO FIX INSTALLATION PLATE
The mounting wall shall be strong and solid enough to prevent it from the vibration.
SELECT THE BEST LOCATION
(Refer to “Select the best location” section)
The center of installation plate should be at more than 1 at right and left of the wall.
The distance from installation plate edge to ceiling should more than 2.
From installation plate left edge to unit’s left side is 3.
From installation plate right edge to unit’s right is 4.
b : For left side piping, piping connection for liquid should be about 5 from this line.
: For left side piping, piping connection for gas should be about 6 from this line.
1. Mount the installation plate on the wall with 5 screws or more (at least 5 screws).
(If mounting the unit on the concrete wall, consider using anchor bolts.)
•
Always mount the installation plate horizontally by aligning the marking-off line with the thread and using
a level gauge.
2. Drill the piping plate hole with ø2
3
/4" (ø70 mm) hole-core drill.
•
Line according to the left and right side of the installation plate. The meeting point of the extended line is
the center of the hole. Another method is by putting measuring tape at position as shown in the diagram
above. The hole center is obtained by measuring the distance namely 5
1
/16" (128 mm) for left and right
hole respectively.
•
Drill the piping hole at either the right or the left and the hole should be slightly slanting to the outdoor side.
INDOOR UNIT INSTALLATION
4
OUTDOOR UNIT
1
SELECT THE BEST LOCATION
(Refer to “Select the best location” section)
•
After selecting the best location, start installation to Indoor/Outdoor Unit Installation Diagram.
1. Fix the unit on concrete or rigid frame fi rmly and horizontally with a bolt nut ø13/32" (ø10 mm).
2. When installing at roof, please consider strong wind and earthquake.
Please fasten the installation stand fi rmly with bolt or nails.
2
INSTALL THE OUTDOOR UNIT
AB
C
D
Rear view for left piping installation
Drain cap
Indoor unit
drain hose
3/4" (20 mm) nominal PVC pipe
- Install incline downward more than 1°
- Apply PVC glue at the join.
Drain hose adapter
7
Close join by Vinyl Tape ( )
Drain hose
Adjust the piping
slightly downwards.
•
How to insert the connection cable
and drain hose in the case of left
piping.
•
Join indoor drain hose to 3/4"
(20 mm) nominal PVC pipe size
by using drain hose adapter
7
when necessary.
(For right piping, follow the same
procedure)
CUTTING AND FLARING THE PIPING
1. Please cut using pipe cutter and then remove the burrs.
2. Remove the burrs by using reamer. If burrs are not removed, gas leakage may be
caused. Turn the piping end down to avoid the metal powder entering the pipe.
3. Please make fl are after inserting the fl are nut onto the copper pipes.
TO DRILL A HOLE IN THE WALL AND
INSTALL A SLEEVE OF PIPING
Putty or caulking compound
Indoor Outdoor
Sleeve
for tube
assembly
Bushing for tube
assembly
Wall
CONNECT THE CABLE TO THE INDOOR
UNIT
5
1. The inside and outside connection cable can be connected
without removing the front grille.
2. Unscrew the conduit cover and fi x the conduit connector to
conduit cover with lock nut, then secure it against chassis.
3. Connection cable between indoor unit and outdoor unit should
be UL listed or CSA approved 4 conductor wires minimum
AWG16 in accordance with local electric codes.
•
Ensure the colour of wires of outdoor unit and terminal number
are the same as the indoor's repectively.
•
Earth lead wire shall be Yellow/Green (Y/G) in colour and
shall be longer than other lead wires as shown in the fi gure
for electrical safety in case of slipping.
Holder
Wire stripping
7
/32" (5 mm)
or more
(gap between wires)
ACCEPT
PROHIBITED
Conductor
over inserted
No loose strand
when inserted
Indoor/outdoor
connecting
terminal board
Conductor
fully inserted
PROHIBITED
Conductor not
fully inserted
3
Terminals on the indoor unit 1 2 3
Colour of wires (connection cable)
Terminals on the outdoor unit 1 2 3
Please follow the steps below to take out front grille if
necessary such as when servicing.
1. Remove both left and right side decorative cover of the
front grille as shown in the illustration at right, and then
remove the 2 mounting screws.
2. Pull the lower section of the front grille towards you to
remove the front grille.
DISPOSAL OF OUTDOOR UNIT DRAIN WATER
The unit should be mounted on a stand that suits to a local environmental requirement.
•
When the Drain elbow 8 being used, please ensure to:-
- Provide a minimum clearance of 2" (50mm) to access the bottom of base pan.
- Seal the four 25/32" (20mm) diameter holes with Rubber caps
9
(refer to illustration below).
- Use a rigid or fl exible PVC pipe (local supply) to dispose drained water from the elbow or use a stainless
steel tray (local supplied) to collect and dispose water.
•
If the unit is used in an area where temperature falls below 32°F (0°C) for 2 or 3 consecutive days, it is
recommended not to use the Drain elbow
8
and Rubber caps 9, water from defrost process will trap,
freeze up and obstruct fan rotation. Water may drip from the basepan hole area during defrost function,
do not stand or place objects underneath.
The below operations will be performed by pressing the “AUTO” switch.
1. AUTO OPERATION MODE
The Auto operation will be activated immediately once the Auto Switch is
pressed and released before 5 sec..
2. TEST RUN OPERATION (FOR PUMP DOWN/SERVICING PURPOSE)
The Test Run operation will be activated if the Auto Switch is pressed
continuously for more than 5 sec. to below 8 sec..
A “pep” sound will occur at the fi fth sec., in order to identify the starting of
Test Run operation.
3. HEATING TRIAL OPERATION
Press the “AUTO” switch continuously for more than 8 sec. to below 11 sec. and release when a “pep
pep” sound is occured at eight sec. (However, a “pep” sound is heard at fi fth sec..) then press Remote
controller “A/C Reset” button once. Remote controller signal will activate operation force heating mode.
4. REMOTE CONTROLLER RECEIVING SOUND ON/OFF
The ON/OFF of Remote controller receiving sound can be changed by the following steps:
a) Press “AUTO” switch continuously for more than 16 sec. to below 21 sec..
A “pep”, “pep”, “pep”, “pep” sound will occur at the sixteenth sec..
b) Press the “A/C Reset” button once. Remote controller signal will activate the Remote controller sound
setting mode.
c) Press the “AUTO” switch once to select Remote controller receiving sound ON/OFF. A “pep” sound
indicates receiving sound ON, and a “pep” sound indicates receiving sound OFF.
CHECK THE DRAINAGE
•
Open front panel and remove air fi lters.
(Drainage checking can be carried out without removing the
front grille.)
•
Pour a glass of water into the drain tray-styrofoam.
•
Ensure that water fl ows out from drain hose of the indoor unit.
EVALUATION OF THE PERFORMANCE
ECO SENSOR
•
Operate the unit at cooling/heating operation mode for fi fteen
minutes or more.
•
Measure the temperature of the intake and discharge air.
•
Ensure the difference between the intake temperature and the
discharge is more than 46.4°F (8°C) during Cooling operation or
more than 57.2°F (14°C) during Heating operation.
•
Do not hit or violently press the sensor.
This can lead to damage and malfunction.
•
Do not place large objects near the sensor and keep heating
units or humidifi ers away from the sensors detection area.
This may lead to sensor malfunction.
Discharge air
1 Philips screw driver
2 Level gauge
3 Electric drill, hole core drill (ø2
3
/4" (ø70 mm))
4 Hexagonal wrench (5/32" (4 mm))
5 Spanner
6 Pipe cutter
7 Reamer
8 Knife
9 Gas leak detector
10 Measuring tape
11 Thermometer
12 Megameter
13 Multimeter
14 Torque wrench
13.3 Ibf•ft (18 N•m (1.8 kgf•m))
31.0 Ibf•ft (42 N•m (4.3 kgf•m))
40.6 Ibf•ft (55 N•m (5.6 kgf•m))
47.9 Ibf•ft (65 N•m (6.6 kgf•m))
73.8 Ibf•ft (100 N•m (10.2 kgf•m))
15 Vacuum pump
16 Digital Micron Gauge
Guide
surface
Connection cable
Connection
cable
Gas side
piping
Liquid side
piping
Drain hose
Drain
traystyrofoam
Cover for the
bottom piping
Tape it with piping in a
position as mentioned in
Fig. below.
Cover for
the right
piping
Piping
Drain hose
Cover for
the left
piping
Cover for the
bottom piping
Cover for the
bottom piping
Tape it with
piping in a position as
mentioned in
Fig. below.
Piping
Drain
hose
Cover
for the
left
piping
1. Press the lower left and
right side of the unit against
the installation plate until
hooks engage with their slot
(sound click).
Cover for piping
In case the cover is cut, keep the
cover at the rear of chassis as
shown in the illustration for future
reinstallation.
(Left and 2 bottom covers for piping.)
How to keep the cover
6
1. Please carry out insulation at pipe connection portion as mentioned in Indoor/Outdoor Unit Installation Diagram. Please wrap the insulated piping end to prevent water from going inside the piping.
2. If drain hose or connecting piping is in the room (where dew may form), please increase the insulation by using POLY-E FOAM with thickness 1/4" (6 mm) or above.
PIPING INSULATION
Hook the indoor unit onto the
upper portion of installation
plate. (Engage the indoor unit
with the upper edge of the
installation plate). Ensure the
hooks are properly seated
on the installation plate by
moving it in left and right.
3
CONNECT THE PIPING
Please make fl are after inserting fl are nut (locate at joint
portion of tube assembly) onto the copper pipe. (In case
of using long piping)
Connect the piping
Align the center of piping and suffi ciently tighten the
fl are nut with fi ngers.
Further tighten the fl are nut with torque wrench in
specifi ed torque as stated in the table.
Decide piping length and then cut by using pipe cutter.
Remove burrs from cut edge.
Make fl are after inserting the fl are nut (locate at valve) onto
the copper pipe.
Align center of piping to valve and then tighten with torque
wrench to the specifi ed torque as stated in the table.
CONNECT THE CABLE TO THE OUTDOOR
UNIT
5
1. Remove control board cover (Resin and Metal).
2. Remove particular plate.
3. Remove plugs.
4. Fix the conduit connectors to the knockout
holes with lock-nuts, then secure them against
the side panel.
5. All wires pass through conduits & particular
plate’s opening hole.
6. Connecting wire between indoor unit and
outdoor unit should be UL listed or CSA
approved 4 conductor wires minimum AWG16
in accordance with local electric codes.
7. Wire connection to the power supply (208/230V
60Hz) through circuit breaker.
•
Connect the UL listed or CSA approved wires
minimum AWG14 to the terminal board, and
connect the other end of the wires to ELCB /
GFCI.
8. Connect the power supply cord and connecting
wire between indoor unit and outdoor unit
according to the diagram below.
9. Secure the wire onto the control board with the
holder (clamper).
10. After completing wiring connections, reattach the
particular plate and control board cover (metal and
resin) to the original position with the screws.
11. For wire stripping and connection requirement, refer
to instruction 5 of indoor unit.
•
Earth lead wire shall be Yellow/Green (Y/G) in colour and
should be longer than other lead wires as shown in the
fi gure for electrical safety in case of slipping.
Chassis
Conduit
Connector
Conduit Cover
Lock Nut
Rear Side of Indoor Unit
Control Board
Cover (Metal)
Lock Nuts
Knockout
Holes
Front
Panel
Connecting wires
Control Board
Cover (Resin)
1. To cut
When properly fl ared, the internal surface of the
fl are will evenly shine and be of even thickness.
Since the fl are part comes into contact with the
connections, carefully check the fl are fi nish.
Improper fl aring
Inclined Surface
damaged
Cracked Uneven
thickness
3. To fl are
Bar
Handle
Core
Yok e
Clamp handle
Bar
0 –
1
/32" (0-0.5 mm)
Copper
pipe
Reamer
2. To remove burrs
Point down
Pipe
Red arrow mark
Torque
wrench
Spanner
or Wrench
Pressure test to system to 400 PSIG with dry nitrogen, in stages. Thoroughly leak check the system.
If the pressure holds, release the nitrogen and proceed to section 4.
WHEN INSTALLING AN AIR CONDITIONER, BE SURE TO EVACUATE THE AIR INSIDE THE INDOOR
UNIT AND PIPES in the following procedure.
1. Connect a charging hose with a push pin to the Low side of a charging set and the service port of the
3-way valve.
2. Connect the micron gauge between vacuum pump and service port of outdoor units.
3. Turn on the power switch of the vacuum pump and make sure that connect digital micron gauge and
to pull down to a value of 500 microns.
4. To make sure micron gauge a value 500 microns and close the low side valve of the charging set and
turn off the vacuum pump.
5. Disconnect the vacuum pump house from the service port of the 3-way valve.
6. Tighten the service port caps of the 3-way valve at a torque of 13.3 Ibf•ft (18 N•m) with a torque
wrench.
7. Remove the valve caps of both of the 2-way valve and 3-way valve. Position both of the valves to
“Open” using a hexagonal wrench (5/32" (4 mm)).
8. Mount valve caps onto the 2-way valve and the 3-way valve.
•
Be sure to check for gas leakage.
4
•
If micron gauge value does not descend 500 microns, take the following measures:
- If the leak stops when the piping connections are tightened further, continue working from step 3.
- If the leak does not stop when the connections are retightened, repair location of leak.
- Do not release refrigerant during piping work for installation and reinstallation.
- Be careful with the liquid refrigerant, it may cause frostbite.
Gas side
Liquid side
Outdoor unit
Two-way valve
Three-way valve
Indoor unit
Vacuum
pump
Close
Close
•
Read the following “SAFETY PRECAUTIONS” carefully before installation.
•
Electrical work must be installed by a licensed electrician. Be sure to use the correct rating of the power plug and main circuit for the model to be installed.
•
The caution items stated here must be followed because these important contents are related to safety. The meaning of each indication used is as below.
Incorrect installation due to ignoring of the instruction will cause harm or damage, and the seriousness is classifi ed by the following indications.
The items to be followed are classifi ed by the symbols:
•
Carry out test running to confi rm that no abnormality occurs after the installation. Then, explain to user the operation, care and maintenance as stated in
instructions. Please remind the customer to keep the operating instructions for future reference.
SAFETY PRECAUTIONS
WARNING
This indication shows the possibility of causing death or serious injury.
CAUTION
This indication shows the possibility of causing injury or damage to properties only.
Symbol with white background denotes item that is PROHIBITED.
Symbol with dark background denotes item that must be carried out.
WARNING
Do not install outdoor unit near handrail of veranda. When installing air-conditioner unit on veranda of a high rise building, child may climb up to outdoor unit and cross
over the handrail causing an accident.
Do not use unspecifi ed cord, modifi ed cord, joint cord or extension cord for power supply cord. Do not share the single outlet with other electrical appliances. Poor
contact, poor insulation or over current will cause electrical shock or fi re.
Do not tie up the power supply cord into a bundle by band. Abnormal temperature rise on power supply cord may happen.
Do not insert your fi ngers or other objects into the unit, high speed rotating fan may cause injury.
Do not sit or step on the unit, you may fall down accidentally.
Keep plastic bag (packaging material) away from small children, it may cling to nose and mouth and prevent breathing.
When installing or relocating air conditioner, do not let any substance other than the specifi ed refrigerant, eg. air etc mix into refrigeration cycle (piping). Mixing of air
etc will cause abnormal high pressure in refrigeration cycle and result in explosion, injury etc.
Do not add or replace refrigerant other than specifi ed type. It may cause product damage, burst and injury etc.
•
For R410A model, use piping, fl are nut and tools which is specifi ed for R410A refrigerant. Using of existing (R22) piping, fl are nut and tools may cause abnormally
high pressure in the refrigerant cycle (piping), and possibly result in explosion and injury.
•
Thickness or copper pipes used with R410A must be more than 1/32" (0.8 mm). Never use copper pipes thinner than 1/32" (0.8 mm).
•
It is desirable that the amount of residual oil is less than 0.0008 oz/ft (40 mg/10 m).
Engage authorized dealer or specialist for installation. If installation done by the user is incorrect, it will cause water leakage, electrical shock or fi re.
Install according to this installation instructions strictly. If installation is defective, it will cause water leakage, electrical shock or fi re.
Use the attached accessories parts and specifi ed par ts for installation. Otherwise, it will cause the set to fall, water leakage, fi re or electrical shock.
Install at a strong and fi rm location which is able to withstand the set’s weight. If the strength is not enough or installation is not properly done, the set will drop and
cause injury.
For installation work, follow all electrical, building, plumbing, local codes, regulations and these installation instructions. If electrical circuit capacity is not enough or a
defect is found in electrical work, it will cause electrical shock or fi re.
Do not use spliced wires for indoor / outdoor connection cable. Use the specifi ed indoor / outdoor connection cable, refer to instruction 5 INDOOR/OUTDOOR UNIT
ELECTRICAL WIRING and connect tightly for indoor/outdoor connection. Clamp the cable so that no external force will have impact on the terminal. If connection or
fi xing is not perfect, it will cause heat-up or fi re at the connection.
Wire routing must be properly arranged so that control board cover is fi xed properly. If control board cover is not fi xed perfectly, it will cause fi re or electrical shock.
This equipment must installed with an Earth Leakage Circuit Breaker (ELCB) or Ground Fault Current Interrupter (GFCI) or Appliance Leakage Current Interrupter
(ALCI) that has been certifi ed by an NRTL Certifi ed Testing Agency and that is suitable for the voltages and amperages involved. Otherwise, if may cause electrical
shock and fi re in case of equipment breakdown.
During installation, install the refrigerant piping properly before running the compressor. Operation of compressor without fi xing refrigeration piping and valves at
opened condition will cause suck-in of air, abnormal high pressure in refrigeration cycle and result in explosion, injury etc.
During pump down operation, stop the compressor before removing the refrigeration piping. Removal of refrigeration piping while compressor is operating and valves
are opened will cause suck-in of air, abnormal high pressure in refrigeration cycle and result in explosion, injury etc.
Tighten the fl are nut with torque wrench according to specifi ed method. If the fl are nut is over-tightened, after a long period, the fl are may break and cause refrigerant
gas leakage.
After completion of installation, confi rm there is no leakage of refrigerant gas. It may generate toxic gas when the refrigerant comes into contact with fi re.
Ventilate if there is refrigerant gas leakage during operation. It may cause toxic gas when the refrigerant comes into contact with fi re.
This equipment must be properly earthed. Earth line must not be connected to gas pipe, water pipe, earth of lightning rod and telephone. Otherwise, it may cause
electrical shock in case of equipment breakdown or insulation breakdown.
CAUTION
Do not install the unit at place where leakage of fl ammable gas may occur. In case gas leaks and accumulates at surrounding of the unit, it may cause fi re.
Do not release refrigerant during piping work for installation, re-installation and during repairing a refrigeration parts. Take care of the liquid refrigerant, it may cause
frostbite.
Do not install this appliance in a laundry room or other location where water may drip from the ceiling, etc.
Do not touch the sharp aluminium fi n, sharp par ts may cause injury.
Carry out drainage piping as mentioned in installation instructions. If drainage is not perfect, water may enter the room and damage the furniture.
Select an installation location which is easy for maintenance.
Power supply connection to the room air conditioner.
Power supply cord shall be UL listed or CSA approved 3 conductor with minimum AWG14 wires.
Power supply point should be in an easily accessible place for power disconnection in case of emergency.
In some countries, permanent connection of this air conditioner to the power supply is prohibited.
Fix power supply connection to a circuit breaker for permanent connection.
Use NRTL approved fuse or circuit breaker (rating refers to name plate) for permanent connection.
Installation work.
It may take two people to carry out the installation work.
INDOOR UNIT
OUTDOOR UNIT
Do not install the unit in excessive oil fume area such as kitchen,
workshop and etc.
There should not be any heat source or steam near the unit.
There should not be any obstacles blocking the air circulation.
A place where air circulation in the room is good.
A place where drainage can be easily done.
A place where noise prevention is taken into consideration.
Do not install the unit near the door way.
Ensure the spaces indicated by arrows from the wall, ceiling,
fence or other obstacles.
Mount with the lowest moving parts at least 8 ft (2.4 m) above fl oor
or grade level.
If an awning is built over the unit to prevent direct sunlight or rain, be
careful that heat radiation from the condenser is not obstructed.
There should not be any animal or plant which could be affected by
hot air discharged.
Keep the spaces indicated by arrows from wall, ceiling, fence or
other obstacles.
Do not place any obstacles which may cause a short circuit of the
discharged air.
If piping length is over the [piping length for additional gas],
additional refrigerant should be added as shown in the table.
Recommended installation height for outdoor unit should be above
the seasonal snow level.
Be careful not to locate outdoor unit directly under a roof line where
falling snow or ice can cause damage or dripping water can increase
ice accumulation and defrost cycles.
Attached accessories
Applicable piping kit
Piping size
Gas Liquid
CZ-3F5, 7BP 3/8" (9.52 mm) 1/4" (6.35 mm)
CZ-4F5, 7, 10BP 1/2" (12.7 mm) 1/4" (6.35 mm)
CZ-52F5, 7, 10BP 5/8" (15.88 mm) 1/4" (6.35 mm)
SELECT THE BEST LOCATION
Piping direction Do not bend up
drain hose
(Front side)
Right
Rear
Right
bottom
Left
Rear
Left bottom
Left
Indoor/Outdoor Unit Installation Diagram
WIRE STRIPPING AND CONNECTING REQUIREMENT
WARNING
This equipment must be properly earthed.
CAUTION
When the wall is hollow, please be sure
to use the sleeve for tube assembly to
prevent dangers caused by mice biting
the connection cable.
Replace the drain hose
Drain hose adapter 7 usage
Indoor and
outdoor
connection
cable
Terminal
Board
Earth wire
longer than
others
AC wires
for safety
reason