Panasonic U-96MF1U9, U-96MF1U9E, U-72MF1U9, U-72MF1U9E User Manual

Order No. TD831158-11CE
3WAY VRF System
U-72MF1U9E
* U-96MF1U9 U-96MF1U9E
Model No. Outdoor Unit
Model Name
Refrigerant R410A is used in the outdoor units. * Salt-Air Damage Resistant Specifications.
Indoor Units
Class 24 36 48 54
U1
4-Way Cassette
4-Way Cassette 60×60
Y1
U-72MF1U9 U-72MF1U9E* U-96MF1U9E*
7 9 12 15 18
*
9672Class
U-96MF1U9
S-12MY1U6 S-18MY1U6
19
Section
1
2
3
4
S-24MU1U6 S-36MU1U6S-12MU1U6 S-18MU1U6
5
D1
1-Way Cassette
Low Silhouette Ducted
F1
Slim Low Static Ducted
M1
High Static Pressure
E1
Ducted
Ceiling
T1
Wall Mounted
K1
Floor Standing
P1
Concealed Floor
R1
Standing
** Necessary to install the External Electronic Expansion Valve Kit (Optional:CZ-P56SVK1U)
85464869258002
S-07MD1U6 S-09MD1U6 S-12MD1U6
S-07MF1U6 S-09MF1U6 S-12MF1U6 S-15MF1U6 S-18MF1U6
S-07MM1U6 S-09MM1U6 S-12MM1U6
S-12MT1U6 S-18MT1U6 S-24MT1U6
S-07MK1U6 S-09MK1U6 S-12MK1U6
S-07MP1U6 S-09MP1U6 S-12MP1U6 S-15MP1U6 S-18MP1U6 S-24MP1U6
S-07MR1U6 S-09MR1U6 S-12MR1U6 S-15MR1U6 S-18MR1U6 S-24MR1U6
S-15MM1U6 S-18MM1U6
S-18MK1U6
S-19MS1U6**S-24MK1U6
S-24MF1U6
REFERENCE NO.
S-36MF1U6 S-48MF1U6
S-36ME1U6 S-48ME1U6
TD831158-02
S-54MF1U6
6
7
8
IMPORTANT! Please Read Before Starting
This air conditioning system meets strict safety and operating standards. As the installer or service person, it is an important part of your job to install or service the system so it operates safely and efficiently.
For safe installation and trouble-free operation, you must:
Carefully read this instruction booklet before beginning. Follow each installation or repair step exactly as shown. Observe all local, state, and national electrical codes. Pay close attention to all warning and caution notices
given in this manual.
This symbol refers to a hazard or
WARNING
CAUTION
If Necessary, Get Help
These instructions are all you need for most installation sites and maintenance conditions. If you require help for a special problem, contact our sales/service outlet or your certified dealer for additional instructions.
In Case of Improper Installation
The manufacturer shall in no way be responsible for improper installation or maintenance service, including failure to follow the instructions in this document.
SPECIAL PRECAUTIONS
WARNING
Do not supply power to the unit until all wiring and tubing • are completed or reconnected and checked.
Highly dangerous electrical voltages are used in this • system. Carefully refer to the wiring diagram and these instructions when wiring. Improper connections and inadequate grounding can cause accidental injury or death.
Ground the unit following local electrical codes. Connect all wiring tightly. Loose wiring may cause
overheating at connection points and a possible fire hazard.
To prevent possible hazards from insulation failure, • the unit must be grounded.
When Transporting
Be careful when picking up and moving the indoor and outdoor units. Get a partner to help, and bend your knees when lifting to reduce strain on your back. Sharp edges or
When Wiring
ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH. ONLY A QUALIFIED, EXPERIENCED ELECTRICIAN SHOULD ATTEMPT TO WIRE THIS SYSTEM.
unsafe practice which can result in severe personal injury or death.
This symbol refers to a hazard or unsafe practice which can result in personal injury or product or property damage.
thin aluminum fins on the air conditioner can cut your fingers.
When Installing…
Select an installation location which is rigid and strong enough to support or hold the unit, and select a location for easy maintenance.
…In a Room
Properly insulate any tubing run inside a room to prevent “sweating” that can cause dripping and water damage to
walls and floors.
Keep the fire alarm and the air
CAUTION
…In Moist or Uneven Locations
Use a raised concrete pad or concrete blocks to provide a solid, level foundation for the outdoor unit. This prevents water damage and abnormal vibration.
…In an Area with High Winds
Securely anchor the outdoor unit down with bolts and a metal frame. Provide a suitable air baffle.
…In a Snowy Area (for Heat Pump-type Systems)
Install the outdoor unit on a raised platform that is higher than drifting snow. Provide snow vents.
outlet at least 5 feet away from the unit.
When Connecting Refrigerant Tubing
Ventilate the room well, in the event that is refrigerant • gas leaks during the installation. Be careful not to allow contact of the refrigerant gas with a flame as this will cause the generation of poisonous gas.
Keep all tubing runs as short as possible.• Use the flare method for connecting tubing.• Apply refrigerant lubricant to the matching surfaces of
the flare and union tubes before connecting them, then tighten the nut with a torque wrench for a leak-free connection.
Check carefully for leaks before starting the test run.
When performing piping work do • not mix air except for specified refrigerant (R410A) in refrigeration cycle. It causes capacity down, and risk of explosion and injury due to high tension inside the
WARNING
Do not leak refrigerant while piping work for an • installation or re-installation, and while repairing refrigeration parts. Handle liquid refrigerant carefully as it may cause
frostbite.
refrigerant cycle. Refrigerant gas leakage may • cause fire. Do not add or replace refrigerant
other than specified type. It may cause product damage, burst and injury etc.
i
When Servicing
Turn the power OFF at the main power box (mains) • before opening the unit to check or repair electrical parts and wiring.
Keep your fingers and clothing away from any moving • parts.
Clean up the site after you finish, remembering to check • that no metal scraps or bits of wiring have been left inside the unit being serviced.
WAR NI NG
Do not clean inside the indoor and • outdoor units by users. Engage authorized dealer or specialist for cleaning.
In case of malfunction of this • appliance, do not repair by yourself. Contact to the sales dealer or service dealer for a repair.
Others
CAUTION
CAUTION
Do not touch the air inlet or the
• sharp aluminum fins of the outdoor unit. You may get injured. Ventilate any enclosed areas when • installing or testing the refrigeration system. Escaped refrigerant gas, on contact with fire or heat, can produce dangerously toxic gas.
Confirm after installation that no • refrigerant gas is leaking. If the gas comes in contact with a burning stove, gas water heater, electric room heater or other heat source, it can cause the generation of poisonous gas.
Do not touch the air inlet or the
• sharp aluminum fins of the outdoor unit. You may get injured. Do not sit or step on the unit, • you may fall down accidentally.
Do not stick any object into the • FAN CASE. You may be injured and the unit may be damaged.
Check of Density Limit
The room in which the air conditioner is to be installed requires a design that in the event of refrigerant gas leaking out, its density will not exceed a set limit.
The refrigerant (R410A), which is used in the air conditioner, is safe, without the toxicity or combustibility of ammonia, and is not restricted by laws imposed to protect the ozone layer. However, since it contains more than air, it poses the risk of suffocation if its density should rise excessively. Suffocation from leakage of refrigerant is almost non-existent. With the recent increase in the number of high density buildings, however, the installation of multi air conditioner systems is on the increase because of the need for effective use of floor space, individual control, energy conservation by curtailing heat and carrying power, etc. Most importantly, the multi air conditioner system is able to replenish a large amount of refrigerant compared to conventional individual air conditioners. If a single unit of the multi air conditioner system is to be installed in a small room, select a suitable model and installation procedure so that if the refrigerant accidentally leaks out, its density does not reach the limit (and in the event of an emergency, measures can be made before injury can occur).
ASHRAE and the International Mechanical Code of the ICC as well as CSA provide guidance and define safeguards related to the use of refrigerants, all of which define a Refrigerant Concentration Level (RCL) of 25 pounds per 1,000 cubic feet for R410A refrigerant. For additional guidance and precautions related to refrigerant safety, please refer to the following documents:
International Mechanical Code 2009 (IMC-2009) (or more recently revised) ASHRAE 15 ASHRAE 34
ii

Precautions for Installation Using New Refrigerant

1. Care regarding tubing
1-1. Process tubing
Material: Use C1220 phosphorous deoxidized copper specified in JIS H3300 “Copper and Copper Alloy Seamless Pipes and Tubes.” For tubes of ø7/8" (ø22.22 mm) or larger, use C1220 T-1/2H material or H material, and do not bend the tubes.
Tubing size: Be sure to use the sizes indicated in the table below.
Use a tube cutter when cutting the tubing, and be sure to remove any flash. This also applies to distribution joints (optional).
When bending tubing, use a bending radius that is 4 times the outer diameter of the tubing or larger.
Use sufficient care in handling the tubing. Seal the tubing ends with caps or tape to
Copper tube
Copper tube
CAUTION
Outer diameter 1/4 (6.35) 3/8 (9.52) 1/2 (12.7) 5/8 (15.88) 3/4 (19.05)
Wall thickness 1/32 (0.8) 1/32 (0.8) 1/32 (0.8) 5/128 (1.0)
Material
Outer diameter
Wall thickness
prevent dirt, moisture, or other foreign substances from entering. These substances can result in system malfunction.
Unit: in. (mm)
OMaterial
over 5/128 (1.0)
Unit: in. (mm)
1/2 H, H
7/8 (22.22) 1-1/8 (28.58) 1-3/8 (34.92) 1-5/8 (41.28)
5/128 (1.0) 5/128 (1.0) 3/64 (1.1) over
3/64 (1.20)
1-2.
Prevent impurities including water, dust and oxide from entering the tubing. Impurities can cause R410A refrigerant deterioration and compressor defects. Due to the features of the refrigerant and refrigerating machine oil, the prevention of water and other impurities becomes more important than ever.
2. Be sure to recharge the refrigerant only in liquid form.
2-1.
Since R410A is a non-azeotrope, recharging the refrigerant in gas form can lower performance and cause defects in the unit.
2-2. nce decreases when gas leaks, collect the remaining
Since refrigerant composition changes and performa refrigerant and recharge the required total amount of new refrigerant after fixing the leak.
3. Different tools required
3-1.
Tool specifications have been changed due to the characteristics of R410A. Some tools for R22- and R407C-type refrigerant systems cannot be used.
R407C tools
New
Item
Manifold gauge Yes No Types of refrigerant, refrigerating machine
Charge hose Yes
Vacuum pump Use a conventional vacuum pump if it is equipped
Leak detector Leak detectors for CFC and HCFC that
Flaring oil For systems that use R22, apply mineral oil (Suniso oil)
* Using tools for R22 and R407C and new tools for R410A together can cause defects.
compatible
tool?
with R410A?
Yes
Yes No
Yes No
No
Yes
oil, and pressure gauge are different.
To resist higher pressure, material must be changed.
with a check valve. If it has no check valve, purchase and attach a vacuum pump adapter.
react to chlorine do not function because R410A contains no chlorine. Leak detector for HFC134a can be used for R410A.
to the flare nuts on the tubing to prevent refrigerant leakage. For machines that use R407C or R410A, apply synthetic oil (ether oil) to the flare nuts.
Remarks
Manifold gauge
Vacuum pump
Outlet Inlet
iii
3-2. Use R410A exclusive cylinder only.
New refrigerant R410A cannot be used for earlier models
1. Compressor specifications are different.
If recharging a R22 or R407C compressor with R410A, durability will significantly decrease since some of the materials used for compressor parts are different.
2. Existing tubing cannot be used (especially R22).
Completely cleaning out residual refrigerating
machine oil is impossible, even by flushing.
Val ve
Single-outlet valve
(with siphon tube) Liquid refrigerant should be recharged with the cylinder standing on end as shown.
Liquid
3. Refrigerating machine oil differs (R22).
Since R22 refrigerating machine oil is mineral oil, it does not dissolve in R410A. Therefore, refrigerating machine oil discharged from the compressor can cause compressor damage.
R22 refrigerating machine oil Mineral oil (Suniso oil)
R407C refrigerating machine oil Synthetic fluid (ether oil)
R410A refrigerating machine oil Synthetic fluid (ether oil)
iv

Contents

Section 1: OUTLINE OF 3WAY VRF SYSTEM ......................................................................
Line-up ............................................................................................................
1. 1-2
Features of 3WAY VRF SYSTEM ....................................................................
2. 1-4
Salt-Air Damage Resistant Specifications .......................................................
3. 1-7
Section 2: DESIGN OF 3WAY VRF SYSTEM ........................................................................
Model Selecting and Capacity Calculator .......................................................
1. 2-2
System Design .............................................................................................
2. 2-18
3. 2-24
Electrical Wiring ............................................................................................
4. 2-32
Installation Instructions .................................................................................
5. 2-40HOW TO PROCESS TUBING ......................................................................
6. 2-44AIR PURGING ..............................................................................................
7. 2-47Optional Parts ...............................................................................................
Section 3: Control of 3WAY VRF SYSTEM ...........................................................................
Main Operating Functions
1. Wireless Remote Controller
2. Timer Remote Controller
3. Simplified Remote Controller
4. System Controller
5. Schedule Timer
6. Intelligent Controller (CZ-256ESMC1U)
7. Communication Adaptor (CZ-CFUNC1U)
8. Remote Sensor
9. LonWorks Interface (CZ-CLNC1U)
10.
Refer to the 2WAY VRF SYSTEM TECHNICAL DATA (TD831157)
*
Section 4: 3WAY VRF SYSTEM UNIT SPECIFICATIONS .....................................................
Outdoor Unit ..................................................................................................
1.
2.
4-Way Cassette Type (U1 Type)
3.
4-Way Cassette 60×60 Type (Y1 Type)
4.
1-Way Cassette Type (D1 Type)
5.
Low Silhouette Ducted Type (F1 Type)
6.
Slim Low Static Ducted Type (M1 Type)
7.
High Static Pressure Ducted Type (E1 Type)
8.
Ceiling Type (T1 Type)
9.
Wall Mounted Type (K1 Type)
10.
Floor Standing Type (P1 Type)
11. Concealed Floor Standing Type (R1 Type)
12. Intaking Fresh Air of 4-Way Casstte Type and Slim Low Static Ducted Type
Refer to the 2WAY VRF SYSTEM TECHNICAL DATA (TD831157)
Section 5: TEST RUN .............................................................................................................
Section 6: ELECTRICAL DATA ..............................................................................................
Section 7: PCB AND FUNCTIONS ........................................................................................
Section 8: CAPACITY TABLE ................................................................................................
*
1. 5-2
Preparing for Test Run ....................................................................................
2. 5-3
Test Run Procedure ........................................................................................
3. 5-4
Main Outdoor Unit PCB Setting ......................................................................
4. 5-6
Auto Address Setting ......................................................................................
5. 5-12
Remote Controller Test Run Settings ...........................................................
6. 5-12
Caution for Pump Down ................................................................................
7. 5-13
Meaning of Alarm Messages ........................................................................
1. 6-2
Outdoor Unit ...................................................................................................
2.
Indoor Unit
Refer to the 2WAY VRF SYSTEM TECHNICAL DATA (TD831157)
*
1. 7-2
Outdoor Unit Control PCB ...............................................................................
2.
Indoor Unit Control PCB Switches and Functions
Refer to the 2WAY VRF SYSTEM TECHNICAL DATA (TD831157)
*
1. 8-2
Capacity Ratio of Outdoor Unit ......................................................................
2. 8-10
Cooling Capacity of Indoor Unit ....................................................................
vi
1-1
2-1
3-1
4-1
4-3
5-1
6-1
7-1
8-1
Outline of 3WAY VRF SYSTEM
2
Contents

1. OUTLINE OF 3WAY VRF SYSTEM

1. Line-up ............................................................................................................................... 1-2
. Features of 3WAY VRF SYSTEM .......................................................................................
3. Salt-Air Damage Resistant Specifications .......................................................................
1-4
1-7
1
2
3
4
5
6
7
1 - 1
8
Outline of 3WAY VRF SYSTEM

1. Line-up

Indoor units
Type 9 191815127 3624 48 54
4-Way Cassette
(U1 Type)
4-Way Cassette
60 X 60 (Y1 Type)
1-Way Cassette
(D1 Type)
Low Silhouette Ducted (F1 Type)
S-07MD1U6 S-09MD1U6 S-12MD1U6
S-07MF1U6 S-12MF1U6 S-15MF1U6 S-18MF1U6S-09MF1U6 S-24MF1U6
S-12MU1U6 S-18MU1U6
S-12MY1U6 S-18MY1U6
S-24MU1U6 S-36MU1U6
S-36MF1U6 S-48MF1U6 S-54MF1U6
1
2
3
4
5
Slim Low Static Ducted (M1 Type)
High Static Pressure Ducted (E1 Type)
Ceiling
(T1 Type)
Wall Mounted
(K1 Type)
Floor Standing
(P1 Type)
Concealed Floor Standing (R1 Type)
S-07MM1U6 S-12MM1U6 S-15MM1U6 S-18MM1U6S-09MM1U6
S-18MT1U6S-12MT1U6 S-24MT1U6
S-07MK1U6 S-09MK1U6 S-12MK1U6
S-07MP1U6 S-12MP1U6 S-15MP1U6 S-18MP1U6S-09MP1U6 S-24MP1U6
S-07MR1U6 S-12MR1U6 S-15MR1U6 S-18MR1U6S-09MR1U6 S-24MR1U6
S-19MS1U6
*
S-24MK1U6S-18MK1U6
S-36ME1U6
S-48ME1U6
6
7
8
* Necessary to install the External Electronic Expansion Valve Kit (Optional:CZ-P56SVK1U).
1 - 2
1. Line-up
Outdoor units
Type
Capacity: BTU/h (kW)
Cooling / Heating
U-72MF1U9 U-72MF1U9E
Outline of 3WAY VRF SYSTEM
72
72,000 (21.1)
/ 81,000 (23.7)
*
Air intake
Air intake
Air
intake
37-1/2
Outdoor Unit
Type
Capacity: BTU/h (kW)
Cooling / Heating
U-96MF1U9 U-96MF1U9E
Air intake
(Ceiling panel dimensions)
35
Air discharge
(Maximum dimensions)
1
82-9/16
2
unit : in.
96
96,000 (28.1)
/ 108,000 (31.6)
*
Air intake
Air intake
Air
intake
37-1/2
3
4
Air intake
Outdoor Unit
Outdoor unit model name ended with letters "U9E". Refer to the Section 1 "3. Salt-Air Damage Resistant Specifications".
*
1 - 3
(Ceiling panel dimensions)
82-9/16
35
Air discharge
(Maximum dimensions)
unit : in.
5
6
7
8

2. Features of 3WAY VRF SYSTEM

2-1. Outline of 3WAY VRF SYSTEM
System example
CONCENTRATION
Outline of 3WAY VRF SYSTEM
Since all pipings are concentrated into one pipe shaft, you can minimize piping space and construction labor
1
2
3
4
CONNECTION
System limitations
Maximum number of combined outdoor units Maximum tonnage of combined outdoor units Maximum number of connectable indoor units Indoor/outdoor unit capacity ratio Maximum actual piping length Maximum level difference (when outdoor unit is lower) Maximum total piping length
* Panasonic makes it possible to link outdoor
unit together for a large capacity (24-Ton).
If indoor/outdoor units need servicing, a ball valve (field supply) cuts off non-operational units to let other units stay running.
3 24-Ton 40 50~130% 492ft 164 (131) ft 984 ft
Solenoid valve kit
Indoor unit
ADDITION
If your indoor capacity load changes in the future, it’s easy to add on both indoor and outdoor units using the same pipings.
If the additional installment of outdoor and indoor units are
*
expected, the size of refrigerant piping should be decided according to the total capacity after the addition.
5
6
7
8
Combination of outdoor units
The DC inverter unit can be used independently or in combination.
CAUTION
Total tonnage
Type (ton)
6
8
R407C models and R22 models must not be used in combination with each other.
6 8 12 14 18 20 22 24
1
11 231
12231
1 - 4
2. Features of 3WAY VRF SYSTEM
Dimensions
Outline of 3WAY VRF SYSTEM
6, 8 Ton
Air intake
6-Ton 8-Ton
U-72MF1U9, U-72MF1U9E U-96MF1U9, U-96MF1U9E
Dimensions of unit combinations
* *
Air intake
74 (Ceiling panel dimensions)
35
(Ceiling panel dimensions)
Air intake
31-1/8
(Installation hole pitch)
35
(Ceiling panel dimensions)
Top view
12, 14 Ton
4
(Ceiling panel dimensions)
Air intake
35
35
37-1/2
36-1/4
(Installation hole pitch)
(Ceiling panel dimensions)
4
35
(Maximum dimensions)
Unit: in.
36-1/4
37-1/2
1
2
3
(Installation hole pitch)
35
(Ceiling panel dimensions)
(Installation hole pitch)
31-1/8
7-7/8
(Installation hole pitch)
70-1/8
(Installation hole pitch)
Top view
18, 20, 22, 24 Ton
113 (Ceiling panel dimensions)
(Ceiling panel dimensions)
(Installation hole pitch)
109-1/16 (Installation hole pitch)
35
31-1/8
Top view
31-1/8
44
(Ceiling panel dimensions)
8/7-78/7-731-1/8
(Installation hole pitch)
35
31-1/8
(Installation hole pitch)
(Ceiling panel dimensions)
(Maximum dimensions)
Unit: in.
35
36-1/4
37-1/2
(Installation hole pitch)
(Ceiling panel dimensions)
Unit: in.
4
5
6
7
(Maximum dimensions)
8
*
Outdoor unit model name ended with letters "U9E". Refer to the Section 1 "3. Salt-Air Damage Resistant Specifications".
1 - 5
Outline of 3WAY VRF SYSTEM
2. Features of 3WAY VRF SYSTEM
Capacity control
The compressor combination (DC inverter compressor + constant-speed compressor) allows smooth capacity control from
0.6-Ton to 24-Ton.
1
2
3
Realization of smooth capacity control from 0.6-Ton to 24-Ton
Capacity control is possible smoothly with a DC inverter compressor. The right graph shows the image of the operating combination of compres­sors in case of 24-Ton system. In actual operation, the combination will be changed by operating condition, operating time amount, priority of com­pressor and so on.
Comp. HP Unit1(main) Unit2(sub1) Unit3(sub2)
DC comp. 4.0 4.0 4.0
AC comp. 5.0 5.0 5.0
*24 Ton = U-96MF1U9 (U-96MF1U9E) Type x 3
Unit 1
DC1
AC1
Unit 2
DC2
AC2
Unit 3
DC3
AC3
Capacity
(Ton)
24
20
16
12
In case of 24-Ton system
DC1
DC1
DC1
8
4
DC1 DC2
DC1
DC2
DC3
Example of 3 unit connection
DC2
DC3
AC1
DC2
DC3
AC1
AC2
LOAD
DC2
DC3
AC1
AC2
AC3
---
>
4
5
6
7
8
1 - 6
3. Salt-Air Damage Resistant Specifi cations
Specifications
Relevant Parts Material Standard Specifications
Outline of 3WAY VRF SYSTEM
Salt-Air Damage Resistant
Specifications
Outdoor unit model name ended
with letters "U9E".
Outer box/side plate/ drain pan between the stud
Base frame
Fan guard
Fin Aluminum
Tube Copper No treatment Zinc rich treatment (whole)
Tube plate
Exchanger
Heat
Propeller fan
Fan
Installation frame
Electrical component box
Tapping screws
Hot-dip zinc-coated steel sheet
Hot-dip aluminum-zinc coated steel sheet
Resin (Polypropylene) No treatment
Hot-dip zinc-coated steel sheet
Resin
Aluminum
Hot-dip zinc-coated steel sheet
--
Hot-dip zinc-coated steel sheet
Hot-dip zinc-coated steel sheet
SUS410
Polyester powder double coating (both sides)( m)40
No treatment
No treatment
No treatment
No treatment
No treatment
No treatment
Motor maker's standard spec.Motor
Polyester powder double coating (both sides) m)120(
No treatment
Hexavalent chromium-free coating
Polyester powder double coating (both sides) ( m)120
Polyester powder double coating (both sides) ( m)120
No treatment
Zinc rich treatment
Zinc rich treatment (whole)
No treatment
Urethane coating
Urethane coating
Motor maker's spec. for salt-air damage resistant (urethane coating)
Polyester powder double coating (both sides) 120 m)(
Polyester powder coating( 120 m)
Hexavalent chromium-free coating + urethane coating
(m)30
(m)30
1
2
3
Stud supplementary bracket
Accumulator Receiver tank
Welded portion Copper tube No treatment Urethane coating
Outer surface Copper tube No treatment Urethane coating
Refrigeration
cycle tube
Fixing bracket
Notes:
1 Consult us before introducing a salt-air damage resistant model as it requires a special treatment. 2 The specifications are subject to change without notice for development. 3 Contact us for the delivery schedule.
Hot-dip zinc-coated steel sheet
Steel Epoxy coating + alkyd coating
Hot-dip zinc-coated steel sheet
No treatment
No treatment
No treatment
Polyester powder double coating ( 120 m)
Dessicant coating
Zinc rich double coating + urethane coating m)70(
Polyester powder double coating (both sides) m)80(
m) 30 (PC board --
4
5
6
7
8
1 - 7
– MEMO –
1 - 8
Design of 3WAY VRF SYSTEM
Contents

2. DESIGN OF 3WAY VRF SYSTEM

1. Model Selecting and Capacity Calculator ........................................................................2-2
2-21-1. Operating Range .............................................................................................................
2-31-2. Procedure for Selecting Models and Calculating Capacity ...........................................
2-41-3. Tubing Length .................................................................................................................
2-61-4. Tubing Size ......................................................................................................................
2-81-5. Installation Standards ......................................................................................................
2-91-6. Straight Equivalent Length of Joints ...............................................................................
2-101-7. Check of limit density ....................................................................................................
2-11................................................................8-1 Calculation of Actual Capacity of Indoor Unit
2-15................................9-1 Capacity Correction Graph According to Temperature Condition
2-161-10. ...Capacity Correction Graph According to Tubing Length and Elevation Difference
................................................................................................................. 2-182. System Design
2-182-1. System Example............................................................................................................
2-20.......2-2. Example of Tubing Size Selection for Extension and Additional Charge Amount
2-23............................................................................................2-3. Installing Distribution Joint
2-243. Electrical Wiring ..............................................................................................................
2-243-1. General Precautions on Wiring .....................................................................................
Recommended Wire Length and Wire Diameter for Power Supply System ..................
4-5. 2-33Precautions When Installing in Heavy Snow Areas ......................................................
4-6. Dimensions of Wind Ducting
4-7. Dimensions of Snow Ducting
Indoor Unit
Refer to the 2WAY VRF SYSTEM TECHNICAL DATA (TD831157)
*
Distribution Joint Kits
Solenoid Valve Kit for 3WAY VRF System ......................................................................
.....................................................................................................
2 - 1
2-243-2.
2-253-3. Wiring System Diagrams ...............................................................................................
2-283-4. Important Note When Wiring for Common Type ..........................................................
2-313-5. Important Note When Wiring for Y1 Type ....................................................................
2-324. Installation Instructions ..................................................................................................
2-32Outdoor Unit ..................................................................................................................
2-324-1. Selecting the Installation Site for Outdoor Unit ............................................................
2-33.....................................................................2-4 Removing Fin Guard for Heat Exchanger
2-33.......................................................................3-4 Shield for Horizontal Exhaust Discharge
2-33.........................................................4-4 Installing the Outdoor Unit in Heavy Snow Areas
2-34Reference diagram for air-discharge chamber (field supply).......................................
2-35Reference diagram for snow-proof ducting (field supply)............................................
2-364-8. Transporting the Outdoor Unit .....................................................................................
2-364-9. Installing the Outdoor Unit ............................................................................................
2-374-10. Remove the Brackets Used for Transport ..................................................................
2-374-11. Routing the Tubing ......................................................................................................
2-384-12. Prepare the Tubing......................................................................................................
2-384-13. Connect the Tubing.....................................................................................................
2-405. HOW TO PROCESS TUBING ..........................................................................................
2-405-1. Connecting the Refrigerant Tubing ..............................................................................
2-415-2. Connecting Tubing Between Indoor and Outdoor Units .............................................
2-425-3. Insulating the Refrigerant Tubing .................................................................................
2-435-4. Taping the Tubes ..........................................................................................................
2-435-5. Finishing the Installation ................................................................................................
2-446. AIR PURGING .................................................................................................................
2-44Air Purging with a Vacuum Pump (for Test Run) Preparation ..................................
2-477. Optional Parts ..................................................................................................................
2-477-1. 2-517-2.
1
2
3
4
5
6
7
8

1. Model Selecting and Capacity Calculator

1-1. Operating Range
Heating and Cooling
77
75
68
59
Design of 3WAY VRF SYSTEM
1
2
3
4
50
41
32
23
14
Outdoor air intake temp. F (WB)
5
-4 50 59
Operating range
68 77 86
Indoor air intake temp. F (DB)
Cooling
113
104
95
86
95
Heating
77
68
59
50
5
6
7
8
77
57
59
Operating range
68 77
68
59
50
41
Outdoor air intake temp. F (DB)
32
23
14
50
Indoor air intake temp. F (WB)
41
32
23
14
Outdoor air intake temp. F (WB)
5
-4 50
Operating range
68 77 86 95
59
Indoor air intake temp. F (DB)
86
2 - 2
Design of 3WAY VRF SYSTEM
1. Model Selecting and Capacity Calculator
1-2. Procedure for Selecting Models and Calculating Capacity
Model Selection Procedure
Select the model and calculate the capacity for each refrigerant system according to the procedure shown below.
Calculation of the indoor air-conditioning load
Calculate the maximum air-conditioning load for each room or zone.
Selection of an air conditioning system
Select the ideal air conditioning system for air conditioning of each room or zone.
Design of the control system
Design a suitable control system for the selected air conditioning system.
Preliminary selection of indoor and outdoor units
Make preliminary selections that are within the allowable range for the system
Check of the tubing length and elevation difference
Check that the length of refrigerant tubing and the elevation difference are within the allowable
ranges.........................................................................................................................................
Calculation of the corrected outdoor unit capacity
Capacity correction coefficient for model................................................................................
Capacity correction coefficient for outdoor temperature conditions...........................
Capacity correction coefficient for tubing length and elevation difference........................
Heating capacity correction coefficient for frosting/defrosting..........................................
Calculation of the corrected capacity for each indoor unit
Capacity correction coefficient for indoor temperature conditions....................................
Capacity distribution ratio based on the tubing length and elevation difference..............
Calculation of the actual capacity for each indoor unit
Calculate the corrected indoor/outdoor capacity ratio, based on the corrected outdoor unit capacity and the total corrected capacity of all indoor units in the same system. Use the result to
calculate the capacity correction coefficient for the indoor units.................................
Multiply the corrected capacity of each indoor unit by the capacity correction coefficient to calcu-
late the actual capacity for each indoor unit...........................................................................
Recheck of the actual capacity for each indoor unit
If the capacity is inadequate, reexamine the unit combinations.
Example 1: Increasing the outdoor unit capacity....................................................................
Example 2: Increasing the indoor unit capacity......................................................................
Increasing the tubing size........................................................................................................
Design of tubing
Create a tubing design which minimizes the amount of additional refrigerant charge as much as
possible...........................................................................................................................
If tubing extension for additional unit is expected in the future, create the tubing design with adequate consideration for this extension. Select the tubing size for the main tube (LA) up to the No. 1 distribution joint based on the rated cooling capacity of the outdoor unit. Select tubing sizes after the distribution point based on the total rated cooling capacity of the connected indoor units. Increasing the tubing size of the wide tubes can reduce the loss of capacity caused by longer tubing lengths. (Only the main wide tube with the largest tube diameter (main tube LA and main tubes after the distribution point that are the same size as LA) can be changed.) In this case, it is
necessary to recalculate the actual indoor unit capacities.....................................................
Calculation of additional refrigerant charge amount
Calculate the additional refrigerant charge from the diameters and lengths of the refrigerant tub­ing. Even if the wide tubing diameter was increased, determine the additional refrigerant charge
based only on the narrow tubing size.....................................................................................
Check the minimum indoor capacity (limit density) with respect to the amount of refrigerant. If the limit density is exceeded, be sure to install ventilation equipment or take other corrective steps.
Design of electrical wiring capacity
Select a wiring capacity according to the method of power supply.......................................
2 - 3
.
........
2-4 ~ 2-10
2-4
2-11
2-11, 13, 15
2-11, 14 2-11, 13
2-11, 14 2-11, 14
2-11 ~ 2-15
2-12
2-18 2-19 2-20
2-4 ~ 2-6
2-20
2-21
2-22
2-24
1
2
3
4
5
6
7
8
Design of 3WAY VRF SYSTEM
1. Model Selecting and Capacity Calculator
1-3. Tubing Length
Select the installation location so that the length and size of refrigerant tubing are within the allowable range shown in the figure below.
1.
2. Main distribution tubes LC – LH are selected according to the capacity after the
The outdoor connection main tubing (LO portion) is determined by the total capacity of the
3. outdoor units that are connected to the tube ends.
4.
Main tubing length LM = LA + LB … < 262 ft
distribution joint.
Sizes of indoor unit connection tubing 1 – 40 are determined by the connection tubing sizes on the indoor units.
_
1
2
3
4
5
6
7
8
L5
H3
C
LM
Balance tubing (ø3/8")
Explanation of symbols
Distribution joint (purchased separately)
Ball valve (field supply)
T-joint (field supply)
Solidly welded shut (pinch weld)
Note: Do not use commercially available T-joints for the liquid tubing and parts.
Be sure to use special R410A distribution joints (CZ: purchased separately) for outdoor
*
unit connections and tubing branches.
LO
AB
LA
LF
LB LC
Max.1.3 ft
Max.1.3 ft
LG
L4
For extension
For extension
LD
4
LH
1
L1
L2
T-joint tubing (header joint system)
LE L3
5
6
3
2
40
7
Solenoid valve kit
R410A distribution joint CZ-P900PH1U CZ-P224BH1U (for indoor unit) CZ-P680BH1U (for indoor unit) CZ-P1350BH1U
H1
H2
(for outdoor unit)
(for indoor unit)
Table 2-1 Ranges that Apply to Refrigerant Tubing Lengths and to Differences in Installation Heights
Length (ft.)ContentsMarkItem
<
492
<
574
<
131
<
*2
262ML
<
98
<
984
<
32
<
164
<
131
<
49
<
13
<
6.6
Allowable tubing length
Allowable elevation difference
Allowable length of joint tubing
L = Length, H = Height
L (L2 – L4)
,2...
1
L1+
+
1
A+B
L1
40
2
40
+
...
+LF+LG+LH
L5
H1
H2 H3
L3
Max. tubing length
Difference between max. length and min. length from the No. 1 distribution joint
Max. length of main tubing (at max. diameter)
Max. length of each distribution tube
Total max. tubing length including length of each distribution tube (only liquid tubing)
Distance between outdoor units
When outdoor unit is installed higher than indoor unit
When outdoor unit is installed lower than indoor unit Max. difference between indoor units Max. difference between outdoor units
T-joint tubing (field-supply); Max. tubing length between the first T-joint and solidly welded-shut end point
Actual length
Equivalent length
NOTE
1:
The outdoor connection main tubing (LO portion) is determined by the total capacity of the outdoor units that are connected to the tube ends.
2:
If the longest tubing length (L1) exceeds 295 ft. (equivalent length), increase the sizes of the main tubes (LM) by 1 rank for the discharge tubes, suction tubes, and narrow tubes. (field supplied)
3:
If the longest main tube length (LM) exceeds 164 feet, increase the main tube size at the portion before 164 ft. by 1 rank for the suction tubes and discharge tubes. (field supplied)
(For the portion that exceeds 164 feet, set based on the main tube sizes (LA) listed in the table on the following page.)
4: If the tubing length (LA) is less than 16.4 feet, it is recommended that the suction tube be increased by 1 rank.
2 - 4
1. Model Selecting and Capacity Calculator
Refrigerant Charge Amount at Shipment (for outdoor unit)
DC
(oz)
Additional Refrigerant Charge
Additional refrigerant charge amount is calculated from the liquid tubing total length as follows.
Amount of Refrigerant Charge Per ft., According to Liquid Tubing Size
(in. (mm))
ø1/4" (ø6.35)
ø3/8" (ø9.52)
ø1/2" (ø12.7)
ø5/8" (ø15.88)
ø3/4" (ø19.05)
ø7/8" (ø22.22)
U-72MF1U9
U-72MF1U9E
416
Liquid tubing size
Amount of refrigerant
charge (oz/ft.)
0.279
0.602
1.38
1.99
2.78
3.93
U-96MF1U9
U-96MF1U9E
416
Required amount of additional refrigerant charge = [(Amount of
additional refrigerant charge per ft. of each size of liquid tube ×
its tube length) + (...) + (...)] + [Necessary amount of additional
refrigerant charge per outdoor unit + (...) + (...)]
* Always charge accurately using a scale for weighing.
Design of 3WAY VRF SYSTEM
1
Table 2-1-1 Necessary Amount of Refrigerant Charge Per Outdoor Unit
Further charge a certain amount listed below in addition to the amount of refrigerant charge.
U-72MF1U9
U-72MF1U9E
42 oz/unit
NOTE
If the tubing length (LA) is less than 16.4 feet, it is necessary to add 71 oz/unit of refrigerant in addition to 42 oz.
System Limitations
Max. capacity allowable connected outdoor units 288,000 BTU/h (24-Ton, 84 kW)
*1: Up to 3 units can be connected if the system has been extended.
U-96MF1U9
U-96MF1U9E
42 oz/unit
*1
3Max. No. allowable connected outdoor units
40Max. connectable indoor units
50 – 130 %Max. allowable indoor/outdoor capacity ratio
2
3
4
5
6
2 - 5
7
8
1
Design of 3WAY VRF SYSTEM
1. Model Selecting and Capacity Calculator
1-4. Tubing Size
Table 2-2 Main Tubing Size (LA)
BTU/h
(kW)
Total system tonnage
Combined outdoor models
Suction tubing
Discharge tubing
Liquid tubing
72,000
(21.1)
ø3/4"
(ø19.05)
ø5/8"
(ø15.88)
96,000
(28.1)
8
ø7/8"
(ø22.22)
ø3/4"
(ø19.05)
ø3/8"
(ø9.52)
139,000
(40.7)
12
U-72MF1U9(E)U-96MF1U9(E)U-72MF1U9(E) U-72MF1U9(E)
ø1/2"
(ø12.7) (ø15.88)
168,000
(49.2)
14
U-96MF1U9(E) U-72MF1U9(E)
ø1-1/8"
(ø28.58)
ø7/8"
(ø22.22)
203,000
(59.5)
186
U-72MF1U9(E) U-72MF1U9(E) U-72MF1U9(E)
ø5/8"
240,000
(70.3)
20
U-96MF1U9(E) U-72MF1U9(E) U-72MF1U9(E)
ø1-1/8"
(ø28.58)
264,000
U-96MF1U9(E) U-96MF1U9(E) U-72MF1U9(E)
ø1-3/8"
(ø34.92)
(ø19.05)
*1: If future extension is planned, select the tubing diameter based on the total tonnage after extension.
However extension is not possible if the resulting tubing size is two ranks higher. *2: The balance tube (outdoor unit tube) diameter is ø3/8" (ø9.52). *3: Type 1 tubing should be used for the refrigerant tubes. *4: If the length of the longest tube (L1) exceeds 295 ft. (equivalent length), increase the main tube (LM) size by 1 rank for the
suction, discharge, and liquid tubes. (Use field-supply reducers.) (Select from Table 2-2 and Table 2-7.) *5: If the longest main tube length (LM) exceeds 164 ft., increase the main tube size at the portion before 164 ft. by 1 rank for
the suction tubes and discharge tubes.
(For the portion that exceeds 164 ft., set based on the main tube sizes (LA) listed in the table above.)
(77.4)
22
ø3/4"
Unit: in. (mm)
288,000
(84.4)
24
U-96MF1U9(E) U-96MF1U9(E) U-96MF1U9(E)
2
3
4
5
6
7
8
Size of tubing (LO) between outdoor units
Select the size of tubing between outdoor units based on the main tubing size (LA) as given in the table above.
Table 2-3 Main Tubing Size After Distribution (LB, LC...)
Total capacity after distribution
Tubing size
Total capacity after distribution
Tubing size
Below BTU/h
Over BTU/h
Suction tubing
Discharge tubing
Liquid tubing
Below BTU/h
Over BTU/h
Suction tubing
Discharge tubing
Liquid tubing
24.200
(ø15.88) (ø19.05) (ø19.05) (ø22.22)
ø1/2" ø5/8" ø5/8" ø3/4"
ø3/8" ø3/8" ø3/8" ø3/8"
258.000
238.900 258.000
ø1-3/8" ø1-3/8" ø1-3/8"
ø1-1/8" ø1-1/8" ø1-1/8"
(ø19.05) (ø19.05) (ø19.05)
54.600
24.200
(ø15.88) (ø19.05) (ø22.22)(ø12.70)
334.400
85.300
54.600 ø3/4"ø3/4"ø5/8"
(ø15.88)
334.400
(ø34.92)(ø34.92)(ø34.92)
(ø28.58)(ø28.58)(ø28.58)
ø3/4"ø3/4"ø3/4"
102.400
Table 2-4 Outdoor Unit Tubing Connection Size ( A – D )
BTU/h
(kW)
Suction tubing
Discharge tubing
Liquid tubing
Balance tubing
72,000
(21.1)
1
*
ø3/4"
*
(ø19.05)
Brazing connection
ø5/8"
(ø15.88)
Brazing connection
ø3/8" (ø9.52)
1
Flare connection
ø3/8" (ø9.52)
Flare connection
96,000
(28.1)
2
*
ø7/8"
*
(ø22.22)
ø3/4"
(ø19.05)
ø3/8" (ø9.52)
Unit: in. (mm)
2
*1
*2
2 - 6
143.300
124.200
(ø28.58)
ø7/8"
ø1/2"
(ø12.70)
85.300
(ø9.52)(ø9.52)(ø9.52)(ø9.52)
124.200
102.400
(ø28.58)
ø3/4"
(ø19.05)
ø1/2"
(ø12.70)
The outdoor unit connection tubing (LO) is
*1:
determined by the total capacity of the outdoor units connected to the tube ends. The tubing size is selected based on the table of main tube sizes after the branch.
If the total capacity of the indoor units con-
*2:
nected to the tube ends is different from the total capacity of the outdoor units, then the main tube size is selected based on the total capacity of the outdoor units. (For LA, LB, and LF in particular)
If the size of tubing (LA) is less than 16.4 feet, it is recommended that the tubing diameter be larger than ø7/8" (ø22.22).
If the size of tubing (LA) is less than 16.4 feet, it is recommended that the tubing diameter be larger than ø1-1/8" (ø28.58).
162.400
143.300
(ø28.58)
ø7/8" ø7/8" ø1-1/8"
(ø22.22) (ø22.22)
ø1/2"
200.600
162.400 ø1-1/8"ø1-1/8"ø1-1/8"ø1-1/8"ø7/8"
(ø28.58)
(ø15.88)(ø12.70)
Unit: in. (mm)
238.900
200.600 ø1-1/8"
(ø28.58)
(ø28.58)
ø5/8"ø5/8"
(ø15.88)
1. Model Selecting and Capacity Calculator
Table 2-5 Amount of Refrigerant Charge
Liquid tubing size Amount of refrigerant
(in. (mm)) charge (oz/ft.)
ø1/4" (ø6.35) 0.279
ø3/8" (ø9.52) 0.602
ø1/2" (ø12.7) 1.38
ø5/8" (ø15.88) 1.99
ø3/4" (ø19.05) 2.78
ø7/8" (ø22.22) 3.93
Design of 3WAY VRF SYSTEM
Table 2-6 Indoor Unit Tubing Connection Size ( 1– 40 )
Indoor unit type
Distribution joint-solenoid valve kit tubing
Solenoid valv kit-Indoor unit tubing connection
*1: For the solenoid valve kits, use type 160 with parallel specifications. Branch the tubing before and after the solenoid valve kits.
Table 2-7 Refrigerant tubing (Existing tubing can be used.)
ø1/4" (ø6.35) t1/32 (t0.8)
ø3/8" (ø9.52) t1/32 (t0.8) ø1-1/8" (ø28.58) t5/128 (t1.0)
ø1/2" (ø12.7) t1/32 (t0.8)
ø5/8" (ø15.88) t5/128 (t1.0)
ø3/4" (ø19.05)
Suction tubing Discharge tubing Liquid tubing
e
Gas tubing
Liquid tubing
Material O Material 1/2H • H
over t5/128 (t1.0)
7
Tubing size (in. (mm))
9
ø7/8" (ø22.22) t5/128 (t1.0)
ø1-3/8" (ø34.92)
ø1-5/8" (ø41.28)
12 15 18 19 24 36 48 54
ø5/8" (ø15.88)
ø1/2" (ø12.7)
ø3/8" (ø9.52)
ø1/2" (ø12.7)
ø1/4" (ø6.35)
over t3/64 (t1.20)
t3/64 (t1.1)
*
When bending the tubes, use a bending radius that is at least 4 times the outer diameter of the tubes. In addition, take sufficient care to avoid crushing or damaging the tubes when bending them.
ø5/8" (ø15.88)
ø3/8" (ø9.52)
Unit: in. (mm)
1
2
3
4
2 - 7
5
6
7
8
1. Model Selecting and Capacity Calculator
1-5. Installation Standards
Relationship between A/C units and refrigerant tubing
Design of 3WAY VRF SYSTEM
1
2
3
Room
Indoor unit
Hallway
Solenoid
valve kit
Liquid
Room
Indoor unit
Gas tube
tube
Solenoid valve kit
Outdoor unit Outdoor unit Indoor unit
Install the solenoid valve kit 98 ft. or less from the indoor unit. In quiet locations such as hospitals, libraries, and hotel rooms, the refrigerant noise may be somewhat noticeable. It is recom-
mended that the solenoid valve kit be installed inside the corridor ceiling, at a location outside the room.
Hallway
Common solenoid valve kit
Multiple indoor units under group control can utilize a solenoid valve kit in common. Categories of connected indoor unit capacities are determined by the solenoid valve kit.
Type of solenoid valve kit Total capacity of indoor units (BTU/h)
160 19.000 < Total capacity
56 7.500
If the capacity range is exceeded, use 2 solenoid valves connected in parallel.
4-tube layout 3-tube layout 2-tube layout
Suction tube
Discharge tube
Liquid tube
Solenoid valve kit
54.600
Room
Indoor unit
Suction tube
Discharge tube
Liquid tube
Balance tube
Desirable Undesirable
Room
Indoor unit
Total capacity 19.000
(2) When adding ball valve for outdoor unit
1. Location: Install the ball valve at the main tube of the distribution joint.
4
5
6
7
8
Outdoor unit for extension
Ball valve (for extension)
(Planned expansion)
Main tube of distribution joint
Balance tube
Discharge tube
Less than 1.3 ft
Distribution joint
(Suction tube)
Main tube
Liquid tube
To indoor unit
2. Installation requirements
• Be sure to install the ball valve up-grade to prevent the inadvertent flow of oil.
• Install the ball valve at the shortest distance (within 1.3 ft.) from the main tube. If the diameter of the ball valve is smaller than that of the main tube, use a reducer or the like to reduce the size of the tubing at that location.
NOTE
• If the ball valve is installed at the outdoor unit (including extension for outdoor unit), face the service port of the valve toward the outdoor unit side (see above illustration; dotted line) and allow a distance of over 1.6 ft from the outdoor unit. If the ball valve is installed between the indoor unit (including extension for indoor unit) and the main tube, face the ball valve toward the indoor unit side (see above illustration; dotted line).
• Use a field supply ball valve.
2 - 8
Design of 3WAY VRF SYSTEM
1. Model Selecting and Capacity Calculator
1-6. Straight Equivalent Length of Joints
Design the tubing system by referring to the following table for the straight equivalent length of joints.
Table 2-8 Straight Equivalent Length of Joints
Gas tubing size (in.(mm))
90° elbow
45° elbow
U-shape tube bent (R2–23/64–3–15/16 in.)
T r ap bend
Y-branch distr ibution joint Equivalent length conversion not needed.
Ball v alve f or ser vice Equivalent length conversion not needed.
1/2"
(12.7)
0.8 0.9 1
7.5 9.2 10.5 15.4
5/8"
(15.88)
1 1.1 1.4 1.9 2.5 2.8
3 3.4 4.1 5.6 7.4 8.4
3/4"
(19.05)
1.6
1.2
4.7
1-1/8"
(28.58)
1.4
7/8"
(22.22)
12.5 19.2 22.3
1-3/8"
(34.92)
1.8 2.0
Unit: ft.
1-5/8"
(41.28)
1
2
3
4
5
6
7
2 - 9
8
1. Model Selecting and Capacity Calculator
Check of limit density
Design of 3WAY VRF SYSTEM
1
2
WARNING
1-7. Check of limit density
When installing an air conditioner in a room, it is neces­sary to ensure that if the refrigerant gas accidentally leaks out, its density does not exceed the limit level for that room.
CAUTION
Always check the gas den­sity limit for the room in which the unit is installed.
Pay special attention to any location, such as a basement, etc., where leaking refrigerant can accumulate, since refrig­erant gas is heavier than air.
3
4
5
6
7
8
2 - 10
Design of 3WAY VRF SYSTEM
1. Model Selecting and Capacity Calculator
1-8. Calculation of Actual Capacity of Indoor Unit
Calculating the actual capacity of each indoor unit
Because the capacity of a multi air-conditioner changes according to the temperature conditions, tubing length, elevation dif­ference and other factors, select the correct model after taking into account the various correction values. When selecting The model, calculate the corrected capacities of the outdoor unit and each indoor unit. Use the corrected outdoor unit capacity and the total corrected capacity of all the indoor units to calculate the actual final capacity of each indoor unit.
1. Outdoor unit capacity correction coefficient
Find the outdoor unit capacity correction coefficient for the following items.
(1) Capacity correction for the outdoor unit model
The capacity correction coefficient is 1.00.
(2)
Capacity correction for the outdoor unit temperature conditions Cooling:
Heating:
(3) Capacity correction for the outdoor unit tubing length and elevation difference
From the graph of capacity change characteristics on page 2-14, use the tubing length and elevation difference to find the capacity correction coefficient. The outdoor unit correction coefficient is the value which corresponds to the most demanding indoor unit.
(4) Capacity correction for outdoor unit frosting/defrosting during heating
From the table on page 2-13, find the capacity correction coefficient.
From the graph of capacity characteristics on page 2-13 ( Graph of Outdoor Unit Capacity Characteristics), use the outdoor temperature to find the capacity correction coefficient. From the graph of capacity characteristics on page 2-15, use the outdoor temperature to find the capacity correction coefficient. * Indoor air intake temperature should be set to 68 °FDB.
1
2. Indoor unit capacity correction coefficients
Find the indoor unit capacity correction coefficient for the following items.
(2) Capacity correction for the indoor unit temperature conditions
From the graph of capacity characteristics on page 2-14 ( Graph of Indoor Unit Capacity Characteristics), use the indoor temperature to find the capacity correction coefficient.
(3) Capacity distribution ratio based on the indoor unit tubing length and elevation difference First, in the same way as for the outdoor unit, use the tubing length and elevation difference for each indoor unit to find the correction coefficient from the graph of capacity change characteristics on page 2-14. Then divide the result by the outdoor unit correction coefficient to find the capacity distribution ratio for each indoor unit.
Capacity distribution ratio for each indoor unit (3) = Correction coefficient for that indoor unit / Correction coefficient for the outdoor unit
3. Calculating the corrected capacities for the outdoor unit and each indoor unit
The corrected capacities for the outdoor unit and each indoor unit are calculated form the formula below.
<Cooling>
Outdoor unit corrected cooling capacity (5) = Outdoor unit rated cooling capacity × Correction coefficient for model ((1)
Page 2-11) × Correction coefficient for outdoor temperature conditions ((2) Page 2-13) × Correction coefficient for tubing length and elevation difference ((3) Page 2-14)
* However, if the outdoor unit corrected cooling capacity [5] is greater than 100%, then the outdoor unit corrected cooling
capacity [5] is considered to be 100%.
Corrected cooling capacity of each indoor unit (5) = Rated cooling capacity for that indoor unit × Correction coefficient for indoor temperature conditions at that indoor unit ((2) Page 2-14) × Distribution ratio based on tubing length and elevation dif­ference at that indoor unit ((3) Page 2-14)
However, the corrected cooling capacity of each indoor unit is found as shown below. If (2) < 100% and (2) × (3) > 100%: Corrected cooling capacity for that indoor unit [5] = Rated cooling capacity for that indoor unit If (2) >100%: Corrected cooling capacity for that indoor unit (5) = Rated cooling capacity for that indoor unit × (2)
2
3
4
5
6
7
2 - 11
8
Design of 3WAY VRF SYSTEM
1. Model Selecting and Capacity Calculator
<Heating>
Outdoor unit corrected heating capacity (5) = Outdoor unit rated heating capacity × Correction coeffi cient for model ((1)
Page 2-11) × Correction coeffi cient for outdoor temperature conditions ((2) Page 2-15) × Correction coeffi cient for tubing length and elevation difference ((3) Page 2-14) × Correction coeffi cient for frosting/defrosting ((4) Page
* However, if the outdoor unit corrected heating capacity [5] is greater than 100%, then the outdoor unit corrected heating
capacity is considered to be 100%.
Corrected heating capacity of each indoor unit (5) = Rated heating capacity for that indoor unit × Correction coeffi cient for
indoor temperature conditions at that indoor unit ((2) Page 2-14) × Distribution ratio based on tubing length and elevation difference at that indoor unit.
However, the corrected heating capacity of each indoor unit is found as shown below. If (2) < 100% and (2)
100%: Corrected heating capacity for that indoor unit (5) = Rated heating capacity for that indoor unit × (2)
If (2)
* Characteristic graphs are shown on the pages listed above next to each correction item. Find each correction coeffi cient
from the appropriate conditions.
× (3) > 100%: Corrected heating capacity for that indoor unit (5) = Rated heating capacity for that indoor unit
2-13)
1
2
3
4
5
6
7
4. Calculating the actual indoor unit capacity based on the indoor/outdoor corrected capacity ratio
Calculate the actual capacity of each indoor unit from the values (found in (3)) for the corrected outdoor unit capacity and the corrected capacity of each indoor unit.
<Cooling capacity>
Corrected indoor/outdoor capacity ratio during cooling (Ruc) = Total corrected cooling capacity of all indoor units in that system / Corrected outdoor unit cooling capacity
If the corrected outdoor unit cooling capacity is greater than or equal to the total corrected unit cooling capacity of all indoor units in that system (Ruc
Actual cooling capacity of each indoor unit (7) = Corrected cooling capacity of each indoor unit (5) (In other words, the cor­rection coeffi cient (6), based on the corrected indoor/outdoor capacity ratios for each indoor unit, is 1.)
If the corrected outdoor unit cooling capacity is less than the total corrected unit cooling capacity of all indoor units in that sys­tem (Ruc > 1), then:
(Actual cooling capacity of each indoor unit (7)) = (Corrected cooling capacity of each indoor unit (5)) × (0.25 × Ruc + 0.75) / Ruc (In other words, the correction coeffi cient (6), based on the corrected indoor/outdoor capacity ratios for each indoor unit, is the underlined part in the formula above.)
<Heating capacity>
Corrected indoor/outdoor capacity ratio during heating (Ruh) = Total corrected heating capacity of all indoor units in that system / Corrected outdoor unit heating capacity
If the corrected outdoor unit heating capacity is greater than or equal to the total corrected unit heating capacity of all indoor units in that system (Ruh
Actual heating capacity of each indoor unit (7) = Corrected heating capacity of each indoor unit (5)
(In other words, the correction coeffi cient (6), based on the corrected indoor/outdoor capacity ratios for each indoor unit, is 1.)
If the corrected outdoor unit heating capacity is less than the total corrected unit heating capacity of all indoor units in that sys­tem (Ruh > 1), then:
(Actual heating capacity of each indoor unit (7)) = (Corrected heating capacity of each indoor unit (5)) × (0.1 × Ruh + 0.9) / Ruh (In other words, the correction coeffi cient (6), based on the corrected indoor/outdoor capacity ratios for each indoor unit, is the underlined part in the formula above.)
1), then:
1), then:
8
2 - 12
Design of 3WAY VRF SYSTEM
1. Model Selecting and Capacity Calculator
Refer to the graph below for the correction coeffi cients for Ruc and Ruh.
Indoor unit capacity correction coefficient for Ruc (cooling) Indoor unit capacity correction coefficient for Ruh (heating)
1.0
0.9
0.8
0.7
0.6
0.5
Indoor unit capacity correction coefficient
0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9
Corrected indoor/outdoor capacity ratio (Ruc or Ruh)
NOTE
When Ruc or Ruh is less than or equal to 1.0, the indoor unit capacity correction coefficient for both Ruc and Ruh is 1.0.
2.0
1
5. Graph of capacity correction coefficients
Graph of outdoor unit capacity characteristics (1 – (2))
Outdoor unit cooling capacity characteristics
120
110
100
90
80
Rate of cooling capacity change (%)
23 32 41 50 59 68 77 86 95 104 113
Outdoor air intake temp. (°F DB) Outdoor air intake temp. (°F WB)
Outdoor unit heating capacity correction coeffi cient during frosting/defrosting (1 – (4))
Outdoor intake air
(°FWB RH85%)
temp.
Correction coefficient 0.97 0.97 0.97 0.96 0.94 0.91 0.89 0.87 0.87 0.87 0.88 0.89 0.91 0.92 0.95 1.0
* To calculate the heating capacity with consideration for frosting/defrosting operation, multiply the heating capacity found
from the capacity graph by the correction coeffi cient from the table above.
4 5 1417212324283032333537394142
Outdoor unit heating capacity characteristics
120
110
100
90
80
70
60
50
40
Rate of heating capacity change (%)
-4 5 142332415059
2
3
4
5
6
2 - 13
7
8
1. Model Selecting and Capacity Calculator
Graph of indoor unit capacity characteristics (2 – (2))
Indoor unit cooling capacity characteristics Indoor unit heating capacity characteristics
Design of 3WAY VRF SYSTEM
1
2
3
4
120
110
100
90
80
57 59 60 62 64 66 68 69 71 73 75 77 59 60 62 64 66 68 69 71 73 75 77 78
Indoor air intake temp. ( °F WB)
Rate of cooling capacity change (%)
indicates the rating point. indicates the rating point.
110
105
100
95
90
Indoor air intake temp. ( °F DB)
Rate of heating capacity change (%)
80
Graph of capacity change characteristics resulting from tubing length and elevation difference (1 / 2 – (3))
<Cooling>
Base capacity change rate
164
131
98
66
100
33
%
0
-33
Elevation difference (ft)
-66
-98
-131 0 98 66 33 131 164 197 230 262 295 328 361 394 427 459 492
96
98
92 90 88 86 84 82 80 78 76
94
*1
Equiv
alent length (ft)
The positive side for the elevation difference indicates that the outdoor unit is installed at a higher position than the indoor units. The negative side indicates the opposite.
<Heating>
Base capacity change rate
164
131
98
66
33
0
-33
Elevation difference (ft)
-66
-98
-131 0 98 66 33 131 164 197 230 262 295 328 361 394 427 459 492
Equivalent length (ft)
5
6
7
8
The capacity loss that is caused by the tubing length can be reduced by increasing the sizes of the discharge tubes and suc-
tion tubes. Refer to Table 2-9 and make the appropriate changes. However be sure that the total length does not exceed the maximum. * The only sizes which can be increased are the LM (main tube with the largest diameter) gas tubes, and the changes are
limited to those shown in Table 2-9. In addition, note that the additional refrigerant charge is determined only by the narrow-tube size.
Table 2-9 Equivalent Length Correction Coeffi cient when the Size of the Discharge Tubes and Suction Tubes (LM)
is Increased
Standard tubing diameter (gas tube, in.(mm))
Tubing diameter after change (gas tube,in.(mm))
Equivalent length correction coefficient
ø1/2"
(ø12.7)
ø5/8" ø3/4" ø7/8" ø1-1/8" ø1-3/8"
(ø15.88) (ø19.05) (ø22.22) (ø28.58) (ø34.92)
ø5/8"
(ø15.88) (ø19.05) (ø22.22) (ø28.58)
0.4 0.5 0.6
ø3/4" ø7/8" ø1-1/8"
* If the size of the discharge tubes and suction tubes (LM) have been increased, apply the correction coeffi cient from Table
2-9 and calculate the equivalent length of the LM section.
Equivalent length of tubing after size increase = Standard tubing equivalent length × Equivalent length correction coeffi cient
2 - 14
Design of 3WAY VRF SYSTEM
1. Model Selecting and Capacity Calculator
1-9. Capacity Correction Graph According to Temperature Condition
Capacity characteristics
(The corrected capacity for specifi c temperature conditions can be found from the graphs below.)
< Cooling > < Heating >
6-Ton 8-Ton
130
Indoor air intake temp. (WB) = 71 FIndoor air intake temp. (WB) = 71 F
Indoor air intake temp. (WB) = 72°F
120
110
WB = 67°F
100
90
WB = 61°F
80
Capacity ratio (%)
120
110
100
90
80
70
Indoor air intake temp. (WB) = 72°F
60
WB = 67°F
50
40
WB = 61°F
Input ratio (%)
30
20
10
14 23 32 41 50 59 68 77 86 95
104 113
130
120
110 110
100
90
80
70
60
Capacity ratio (%)
50
40
130
120
100
90
Input ratio (%)
80
70
60
50
- 4
Indoor air intake temp. (°F DB)
61
70
79
61
70
79
5 142332415059
130
120
100
90
80
70
60
Capacity ratio (%)
50
40
130
120
110110
100
90
Input ratio (%)
80
70
60
50
- 4
5 142332415059
Indoor air intake temp. (°F DB)
61
70
79
61
1
70
79
2
Heating capacity correction coeffi cients for frost/defrost operation
Outdoor intake air temp.
4 5 1417212324283032333537394142
(°F WB RH85%)
Correction coefficient 0.97 0.97 0.97 0.96 0.94 0.91 0.89 0.87 0.87 0.87 0.88 0.89 0.91 0.92 0.95 1.0
* The heating capacity when frost/defrost operation is considered is calculated by multiplying the heating capacity found
from the capacity graph by the correction coeffi cient from the table above.
3
4
5
6
7
2 - 15
8
1
2
3
Design of 3WAY VRF SYSTEM
1. Model Selecting and Capacity Calculator
Rated performance values
Item Cooling Heating
Cooling capacity
Type
72 72,000(21.1) 5.30 81,000(23.7) 5.79
96 96,000(28.1) 7.75 108,000(31.6) 8.6
BTU/h(kW)
1-10. Capacity Correction Graph According to Tubing Length and Elevation Difference
Capacity change characteristics
<Cooling>
Base capacity change rate
164
131
98
66
100
33
%
0
–33
Elevation difference (ft)
–66
–98
–131
0 33 66 98 131 164 197 230 262 295 328 361 394 427 459 4920 33 66 98 131 164 197 230 262 295 328 361 394 427 459 492
96
98
92 90 88 86 84 82 80 78 76
94
*1
Equivalent length (ft)
Power consumptionkWHeating capacity
BTU/h(kW)
Power consumption
kW
4
5
6
7
8
<Heating>
Base capacity change rate
164
131
98
66
33
0
–33
–66
Elevation difference (ft)
–98
–131
0 33 66 98 131 164 197 230 262 295 328 361 394 427 459 492
Equivalent length (ft)
NOTE
The positive side for the elevation difference indicates that the outdoor unit is installed at a higher position than the indoor units. The negative side indicates the opposite.
*1 Sample calculations
(System: 8 Ton, 164ft equivalent length, 49ft elevation difference The cooling capacity and heating capacity for this system are found as shown below.)
Cooling operation
From the graph, the base capacity change rate is found to be
92.0%.
×
96,000 BTU/h
(28.1kW
Heating operation
From the graph, the base capacity change rate is found to be
97.2%. Because the calculation result exceeds 97.2%, the capacity change rate is 97.2%.
(31.6kW
×
92.0% = 88,320 BTU/h
92.0% = 25.8kW)
×
97.2% = 105,000 BTU/h108,000 BTU/h
×
97.2% = 30.7kW) Heating capacity is
Capacity change rate is 92.0%. Cooling capacity is 88,320 BTU/h (28.1 kW)
105,000 BTU/h (30.7 kW)
2 - 16
Loading...
+ 145 hidden pages