This air conditioning system meets strict safety and
operating standards. As the installer or service person, it
is an important part of your job to install or service the
system so it operates safely and efficiently.
For safe installation and trouble-free operation, you
must:
Carefully read this instruction booklet before beginning.
Follow each installation or repair step exactly as shown.
Observe all local, state, and national electrical codes.
Pay close attention to all warning and caution notices
given in this manual.
This symbol refers to a hazard or
WARNING
CAUTION
If Necessary, Get Help
These instructions are all you need for most installation
sites and maintenance conditions. If you require help for a
special problem, contact our sales/service outlet or your
certified dealer for additional instructions.
In Case of Improper Installation
The manufacturer shall in no way be responsible for
improper installation or maintenance service, including
failure to follow the instructions in this document.
SPECIAL PRECAUTIONS
WARNING
Do not supply power to the unit until all wiring and tubing •
are completed or reconnected and checked.
Highly dangerous electrical voltages are used in this •
system. Carefully refer to the wiring diagram and these
instructions when wiring. Improper connections and
inadequate grounding can cause accidental injury or death.
•
Ground the unit following local electrical codes.
Connect all wiring tightly. Loose wiring may cause •
overheating at connection points and a possible fire
hazard.
To prevent possible hazards from insulation failure, •
the unit must be grounded.
When Transporting
Be careful when picking up and moving the indoor and
outdoor units. Get a partner to help, and bend your knees
when lifting to reduce strain on your back. Sharp edges or
When Wiring
ELECTRICAL SHOCK CAN CAUSE
SEVERE PERSONAL INJURY OR DEATH.
ONLY A QUALIFIED, EXPERIENCED
ELECTRICIAN SHOULD ATTEMPT TO
WIRE THIS SYSTEM.
unsafe practice which can result
in severe personal injury or death.
This symbol refers to a hazard or
unsafe practice which can result
in personal injury or product or
property damage.
thin aluminum fins on the air conditioner can cut your
fingers.
When Installing…
Select an installation location which is rigid and strong
enough to support or hold the unit, and select a location
for easy maintenance.
…In a Room
Properly insulate any tubing run inside a room to prevent
“sweating” that can cause dripping and water damage to
walls and floors.
Keep the fire alarm and the air
CAUTION
…In Moist or Uneven Locations
Use a raised concrete pad or concrete blocks to provide a
solid, level foundation for the outdoor unit. This prevents
water damage and abnormal vibration.
…In an Area with High Winds
Securely anchor the outdoor unit down with bolts and a
metal frame. Provide a suitable air baffle.
…In a Snowy Area (for Heat Pump-type Systems)
Install the outdoor unit on a raised platform that is higher
than drifting snow. Provide snow vents.
outlet at least 5 feet away from the
unit.
When Connecting Refrigerant Tubing
Ventilate the room well, in the event that is refrigerant •
gas leaks during the installation. Be careful not to allow
contact of the refrigerant gas with a flame as this will
cause the generation of poisonous gas.
Keep all tubing runs as short as possible.•
Use the flare method for connecting tubing.•
Apply refrigerant lubricant to the matching surfaces of •
the flare and union tubes before connecting them, then
tighten the nut with a torque wrench for a leak-free
connection.
Check carefully for leaks before starting the test run.•
When performing piping work do •
not mix air except for specified
refrigerant (R410A) in refrigeration
cycle. It causes capacity down,
and risk of explosion and injury
due to high tension inside the
WARNING
Do not leak refrigerant while piping work for an •
installation or re-installation, and while repairing
refrigeration parts.
Handle liquid refrigerant carefully as it may cause
frostbite.
refrigerant cycle.
Refrigerant gas leakage may •
cause fire.
Do not add or replace refrigerant •
other than specified type. It may
cause product damage, burst and
injury etc.
i
When Servicing
Turn the power OFF at the main power box (mains) •
before opening the unit to check or repair electrical
parts and wiring.
Keep your fingers and clothing away from any moving •
parts.
Clean up the site after you finish, remembering to check •
that no metal scraps or bits of wiring have been left
inside the unit being serviced.
WAR NI NG
Do not clean inside the indoor and •
outdoor units by users. Engage
authorized dealer or specialist for
cleaning.
In case of malfunction of this •
appliance, do not repair by yourself.
Contact to the sales dealer or service
dealer for a repair.
Others
CAUTION
CAUTION
Do not touch the air inlet or the
•
sharp aluminum fins of the
outdoor unit. You may get injured.
Ventilate any enclosed areas when •
installing or testing the refrigeration
system. Escaped refrigerant gas, on
contact with fire or heat, can produce
dangerously toxic gas.
Confirm after installation that no •
refrigerant gas is leaking. If the gas
comes in contact with a burning stove,
gas water heater, electric room heater
or other heat source, it can cause the
generation of poisonous gas.
Do not touch the air inlet or the
•
sharp aluminum fins of the
outdoor unit. You may get injured.
Do not sit or step on the unit, •
you may fall down accidentally.
Do not stick any object into the •
FAN CASE.
You may be injured and the unit
may be damaged.
Check of Density Limit
The room in which the air conditioner is to be
installed requires a design that in the event of
refrigerant gas leaking out, its density will not
exceed a set limit.
The refrigerant (R410A), which is used in the air
conditioner, is safe, without the toxicity or combustibility
of ammonia, and is not restricted by laws imposed to
protect the ozone layer. However, since it contains more
than air, it poses the risk of suffocation if its density
should rise excessively. Suffocation from leakage of
refrigerant is almost non-existent.
With the recent increase in the number of high density
buildings, however, the installation of multi air
conditioner systems is on the increase because of the
need for effective use of floor space, individual control,
energy conservation by curtailing heat and carrying
power, etc.
Most importantly, the multi air conditioner system is able
to replenish a large amount of refrigerant compared to
conventional individual air conditioners. If a single unit of
the multi air conditioner system is to be installed in a
small room, select a suitable model and installation
procedure so that if the refrigerant accidentally leaks
out, its density does not reach the limit (and in the event
of an emergency, measures can be made before injury
can occur).
ASHRAE and the International Mechanical Code of the
ICC as well as CSA provide guidance and define
safeguards related to the use of refrigerants, all of which
define a Refrigerant Concentration Level (RCL) of 25
pounds per 1,000 cubic feet for R410A refrigerant.
For additional guidance and precautions related to
refrigerant safety, please refer to the following
documents:
International Mechanical Code 2009 (IMC-2009)
(or more recently revised)
ASHRAE 15
ASHRAE 34
ii
Precautions for Installation Using New Refrigerant
1. Care regarding tubing
1-1. Process tubing
Material: Use C1220 phosphorous deoxidized copper specified in JIS H3300 “Copper and Copper Alloy Seamless
Pipes and Tubes.”
For tubes of ø7/8" (ø22.22 mm) or larger, use C1220 T-1/2H material or H material, and do not bend the tubes.
Tubing size: Be sure to use the sizes indicated in the table below.
Use a tube cutter when cutting the tubing, and be sure to remove any flash. This also applies to distribution joints
(optional).
When bending tubing, use a bending radius that is 4 times the outer diameter of the tubing or larger.
Use sufficient care in handling the tubing. Seal the tubing ends with caps or tape to
Prevent impurities including water, dust and oxide from entering the tubing. Impurities can cause R410A
refrigerant deterioration and compressor defects. Due to the features of the refrigerant and refrigerating machine
oil, the prevention of water and other impurities becomes more important than ever.
2. Be sure to recharge the refrigerant only in liquid form.
2-1.
Since R410A is a non-azeotrope, recharging the refrigerant in gas form can lower performance and cause defects
in the unit.
2-2.nce decreases when gas leaks, collect the remaining
Since refrigerant composition changes and performa
refrigerant and recharge the required total amount of new refrigerant after fixing the leak.
3. Different tools required
3-1.
Tool specifications have been changed due to the characteristics of R410A.
Some tools for R22- and R407C-type refrigerant systems cannot be used.
R407C tools
New
Item
Manifold gaugeYesNoTypes of refrigerant, refrigerating machine
Charge hoseYes
Vacuum pumpUse a conventional vacuum pump if it is equipped
Leak detectorLeak detectors for CFC and HCFC that
Flaring oilFor systems that use R22, apply mineral oil (Suniso oil)
* Using tools for R22 and R407C and new tools for R410A together can cause defects.
compatible
tool?
with R410A?
Yes
YesNo
YesNo
No
Yes
oil, and pressure gauge are different.
To resist higher pressure, material must be changed.
with a check valve. If it has no check valve,
purchase and attach a vacuum pump adapter.
react to chlorine do not function because
R410A contains no chlorine. Leak detector
for HFC134a can be used for R410A.
to the flare nuts on the tubing to prevent refrigerant
leakage. For machines that use R407C or R410A, apply
synthetic oil (ether oil) to the flare nuts.
Remarks
Manifold gauge
Vacuum pump
Outlet
Inlet
iii
3-2. Use R410A exclusive cylinder only.
New refrigerant R410A cannot be used for
earlier models
1. Compressor specifications are different.
If recharging a R22 or R407C compressor with R410A,
durability will significantly decrease since some of the
materials used for compressor parts are different.
2. Existing tubing cannot be used (especially R22).
Completely cleaning out residual refrigerating
machine oil is impossible, even by flushing.
Val ve
Single-outlet valve
(with siphon tube)
Liquid refrigerant should be recharged
with the cylinder standing on end as
shown.
Liquid
3. Refrigerating machine oil differs (R22).
Since R22 refrigerating machine oil is mineral oil, it
does not dissolve in R410A. Therefore, refrigerating
machine oil discharged from the compressor can cause
compressor damage.
* Necessary to install the External Electronic Expansion Valve Kit (Optional:CZ-P56SVK1U).
1 - 2
1. Line-up
Outdoor units
Type
Capacity: BTU/h (kW)
Cooling / Heating
U-72MF1U9
U-72MF1U9E
Outline of 3WAY VRF SYSTEM
72
72,000 (21.1)
/ 81,000 (23.7)
*
Air
intake
Air intake
Air
intake
37-1/2
Outdoor Unit
Type
Capacity: BTU/h (kW)
Cooling / Heating
U-96MF1U9
U-96MF1U9E
Air
intake
(Ceiling panel dimensions)
35
Air discharge
(Maximum dimensions)
1
82-9/16
2
unit : in.
96
96,000 (28.1)
/ 108,000 (31.6)
*
Air
intake
Air intake
Air
intake
37-1/2
3
4
Air
intake
Outdoor Unit
Outdoor unit model name ended with letters "U9E". Refer to the Section 1 "3. Salt-Air Damage Resistant Specifications".
*
1 - 3
(Ceiling panel dimensions)
82-9/16
35
Air discharge
(Maximum dimensions)
unit : in.
5
6
7
8
2. Features of 3WAY VRF SYSTEM
2-1. Outline of 3WAY VRF SYSTEM
System example
CONCENTRATION
Outline of 3WAY VRF SYSTEM
Since all pipings are concentrated
into one pipe shaft, you can minimize
piping space and construction labor
1
2
3
4
CONNECTION
System limitations
Maximum number of combined outdoor units
Maximum tonnage of combined outdoor units
Maximum number of connectable indoor units
Indoor/outdoor unit capacity ratio
Maximum actual piping length
Maximum level difference (when outdoor unit is lower)
Maximum total piping length
* Panasonic makes it possible to link outdoor
unit together for a large capacity (24-Ton).
If indoor/outdoor units need servicing, a ball
valve (field supply) cuts off non-operational
units to let other units stay running.
3
24-Ton
40
50~130%
492ft
164 (131) ft
984 ft
Solenoid
valve kit
Indoor unit
ADDITION
If your indoor capacity load changes in the future, it’s easy to
add on both indoor and outdoor units using the same pipings.
If the additional installment of outdoor and indoor units are
*
expected, the size of refrigerant piping should be decided
according to the total capacity after the addition.
5
6
7
8
Combination of outdoor units
The DC inverter unit can be used independently or in combination.
CAUTION
Total
tonnage
Type (ton)
6
8
R407C models and R22 models must not be used in combination with each other.
68121418202224
1
11231
12231
1 - 4
2. Features of 3WAY VRF SYSTEM
Dimensions
Outline of 3WAY VRF SYSTEM
6, 8 Ton
Air
intake
6-Ton
8-Ton
U-72MF1U9, U-72MF1U9E
U-96MF1U9, U-96MF1U9E
Dimensions of unit combinations
*
*
Air
intake
74 (Ceiling panel dimensions)
35
(Ceiling panel dimensions)
Air
intake
31-1/8
(Installation hole pitch)
35
(Ceiling panel dimensions)
Top view
12, 14 Ton
4
(Ceiling panel dimensions)
Air
intake
35
35
37-1/2
36-1/4
(Installation hole pitch)
(Ceiling panel dimensions)
4
35
(Maximum dimensions)
Unit: in.
36-1/4
37-1/2
1
2
3
(Installation hole pitch)
35
(Ceiling panel dimensions)
(Installation hole pitch)
31-1/8
7-7/8
(Installation hole pitch)
70-1/8
(Installation hole pitch)
Top view
18, 20, 22, 24 Ton
113 (Ceiling panel dimensions)
(Ceiling panel dimensions)
(Installation hole pitch)
109-1/16 (Installation hole pitch)
35
31-1/8
Top view
31-1/8
44
(Ceiling panel dimensions)
8/7-78/7-731-1/8
(Installation hole pitch)
35
31-1/8
(Installation hole pitch)
(Ceiling panel dimensions)
(Maximum dimensions)
Unit: in.
35
36-1/4
37-1/2
(Installation hole pitch)
(Ceiling panel dimensions)
Unit: in.
4
5
6
7
(Maximum dimensions)
8
*
Outdoor unit model name ended with letters "U9E". Refer to the Section 1 "3. Salt-Air Damage Resistant Specifications".
1 - 5
Outline of 3WAY VRF SYSTEM
2. Features of 3WAY VRF SYSTEM
Capacity control
The compressor combination (DC inverter compressor + constant-speed compressor) allows smooth capacity control from
0.6-Ton to 24-Ton.
1
2
3
Realization of smooth capacity control
from 0.6-Ton to 24-Ton
Capacity control is possible smoothly with a DC
inverter compressor. The right graph shows the
image of the operating combination of compressors in case of 24-Ton system. In actual operation,
the combination will be changed by operating
condition, operating time amount, priority of compressor and so on.
1 Consult us before introducing a salt-air damage resistant model as it requires a special treatment.
2 The specifications are subject to change without notice for development.
3 Contact us for the delivery schedule.
Hot-dip zinc-coated
steel sheet
SteelEpoxy coating + alkyd coating
Hot-dip zinc-coated
steel sheet
No treatment
No treatment
No treatment
Polyester powder double coating
( 120 m)
Dessicant coating
Zinc rich double coating + urethane
coatingm)70(
Polyester powder double coating
(both sides)m)80(
m) 30 (PC board--
4
5
6
7
8
1 - 7
– MEMO –
1 - 8
Design of 3WAY VRF SYSTEM
Contents
2. DESIGN OF 3WAY VRF SYSTEM
1. Model Selecting and Capacity Calculator ........................................................................2-2
2-21-1. Operating Range .............................................................................................................
2-31-2. Procedure for Selecting Models and Calculating Capacity ...........................................
Calculation of the corrected outdoor unit capacity
Capacity correction coefficient for model................................................................................
Capacity correction coefficient for outdoor temperature conditions...........................
Capacity correction coefficient for tubing length and elevation difference........................
Heating capacity correction coefficient for frosting/defrosting..........................................
Calculation of the corrected capacity for each indoor unit
Capacity correction coefficient for indoor temperature conditions....................................
Capacity distribution ratio based on the tubing length and elevation difference..............
Calculation of the actual capacity for each indoor unit
Calculate the corrected indoor/outdoor capacity ratio, based on the corrected outdoor unit
capacity and the total corrected capacity of all indoor units in the same system. Use the result to
calculate the capacity correction coefficient for the indoor units.................................
Multiply the corrected capacity of each indoor unit by the capacity correction coefficient to calcu-
late the actual capacity for each indoor unit...........................................................................
Recheck of the actual capacity for each indoor unit
If the capacity is inadequate, reexamine the unit combinations.
Example 1: Increasing the outdoor unit capacity....................................................................
Example 2: Increasing the indoor unit capacity......................................................................
Increasing the tubing size........................................................................................................
Design of tubing
Create a tubing design which minimizes the amount of additional refrigerant charge as much as
If tubing extension for additional unit is expected in the future, create the tubing design with
adequate consideration for this extension.
Select the tubing size for the main tube (LA) up to the No. 1 distribution joint based on the rated
cooling capacity of the outdoor unit. Select tubing sizes after the distribution point based on the
total rated cooling capacity of the connected indoor units.
Increasing the tubing size of the wide tubes can reduce the loss of capacity caused by longer
tubing lengths. (Only the main wide tube with the largest tube diameter (main tube LA and main
tubes after the distribution point that are the same size as LA) can be changed.) In this case, it is
necessary to recalculate the actual indoor unit capacities.....................................................
Calculation of additional refrigerant charge amount
Calculate the additional refrigerant charge from the diameters and lengths of the refrigerant tubing. Even if the wide tubing diameter was increased, determine the additional refrigerant charge
based only on the narrow tubing size.....................................................................................
Check the minimum indoor capacity (limit density) with respect to the amount of refrigerant. If the
limit density is exceeded, be sure to install ventilation equipment or take other corrective steps.
Design of electrical wiring capacity
Select a wiring capacity according to the method of power supply.......................................
2 - 3
.
........
2-4 ~ 2-10
2-4
2-11
2-11, 13, 15
2-11, 14
2-11, 13
2-11, 14
2-11, 14
2-11 ~ 2-15
2-12
2-18
2-19
2-20
2-4 ~ 2-6
2-20
2-21
2-22
2-24
1
2
3
4
5
6
7
8
Design of 3WAY VRF SYSTEM
1. Model Selecting and Capacity Calculator
1-3. Tubing Length
Select the installation location so that the length and size of refrigerant tubing are within the allowable range shown
in the figure below.
1.
2. Main distribution tubes LC – LH are selected according to the capacity after the
The outdoor connection main tubing (LO portion) is determined by the total capacity of the
3.
outdoor units that are connected to the tube ends.
4.
Main tubing length LM = LA + LB … < 262 ft
distribution joint.
Sizes of indoor unit connection tubing 1 – 40 are determined by the connection
tubing sizes on the indoor units.
_
1
2
3
4
5
6
7
8
L5
H3
C
LM
Balance tubing
(ø3/8")
Explanation of symbols
Distribution joint
(purchased separately)
Ball valve (field supply)
T-joint (field supply)
Solidly welded shut
(pinch weld)
Note: Do not use commercially available T-joints for the liquid tubing and parts.
Be sure to use special R410A distribution joints (CZ: purchased separately) for outdoor
Table 2-1 Ranges that Apply to Refrigerant Tubing Lengths and to Differences in Installation Heights
Length (ft.)ContentsMarkItem
<
492
<
574
<
131
<
*2
262ML
<
98
<
984
<
32
<
164
<
131
<
49
<
13
<
6.6
Allowable tubing
length
Allowable elevation
difference
Allowable length of
joint tubing
L = Length, H = Height
L (L2 – L4)
,2...
1
L1+
+
1
A+B
L1
40
2
40
+
...
+LF+LG+LH
L5
H1
H2
H3
L3
Max. tubing length
Difference between max. length and min.
length from the No. 1 distribution joint
Max. length of main tubing (at max. diameter)
Max. length of each distribution tube
Total max. tubing length including length of
each distribution tube (only liquid tubing)
Distance between outdoor units
When outdoor unit is installed higher than indoor unit
When outdoor unit is installed lower than indoor unit
Max. difference between indoor units
Max. difference between outdoor units
T-joint tubing (field-supply); Max. tubing length between
the first T-joint and solidly welded-shut end point
Actual length
Equivalent length
NOTE
1:
The outdoor connection main tubing (LO portion) is determined by the total capacity of the outdoor units that
are connected to the tube ends.
2:
If the longest tubing length (L1) exceeds 295 ft. (equivalent length), increase the sizes of the main tubes (LM)
by 1 rank for the discharge tubes, suction tubes, and narrow tubes. (field supplied)
3:
If the longest main tube length (LM) exceeds 164 feet, increase the main tube size at the portion before 164 ft.
by 1 rank for the suction tubes and discharge tubes. (field supplied)
(For the portion that exceeds 164 feet, set based on the main tube sizes (LA) listed in the table on the following page.)
4: If the tubing length (LA) is less than 16.4 feet, it is recommended that the suction tube be increased by 1 rank.
2 - 4
1. Model Selecting and Capacity Calculator
Refrigerant Charge Amount at Shipment (for outdoor unit)
DC
(oz)
Additional Refrigerant Charge
Additional refrigerant charge amount is calculated from the liquid tubing total length as follows.
Amount of Refrigerant Charge Per ft., According to Liquid Tubing Size
(in. (mm))
ø1/4" (ø6.35)
ø3/8" (ø9.52)
ø1/2" (ø12.7)
ø5/8" (ø15.88)
ø3/4" (ø19.05)
ø7/8" (ø22.22)
U-72MF1U9
U-72MF1U9E
416
Liquid tubing size
Amount of refrigerant
charge (oz/ft.)
0.279
0.602
1.38
1.99
2.78
3.93
U-96MF1U9
U-96MF1U9E
416
Required amount of additional refrigerant charge = [(Amount of
additional refrigerant charge per ft. of each size of liquid tube ×
its tube length) + (...) + (...)] + [Necessary amount of additional
refrigerant charge per outdoor unit + (...) + (...)]
* Always charge accurately using a scale for weighing.
Design of 3WAY VRF SYSTEM
1
Table 2-1-1 Necessary Amount of Refrigerant Charge Per Outdoor Unit
Further charge a certain amount listed below in addition to the amount of refrigerant charge.
U-72MF1U9
U-72MF1U9E
42 oz/unit
NOTE
If the tubing length (LA) is less than 16.4 feet, it is necessary to add 71 oz/unit of refrigerant in addition to 42 oz.
*1: Up to 3 units can be connected if the system has been extended.
U-96MF1U9
U-96MF1U9E
42 oz/unit
*1
3Max. No. allowable connected outdoor units
40Max. connectable indoor units
50 – 130 %Max. allowable indoor/outdoor capacity ratio
2
3
4
5
6
2 - 5
7
8
1
Design of 3WAY VRF SYSTEM
1. Model Selecting and Capacity Calculator
1-4. Tubing Size
Table 2-2 Main Tubing Size (LA)
BTU/h
(kW)
Total system tonnage
Combined outdoor
models
Suction tubing
Discharge tubing
Liquid tubing
72,000
(21.1)
ø3/4"
(ø19.05)
ø5/8"
(ø15.88)
96,000
(28.1)
8
ø7/8"
(ø22.22)
ø3/4"
(ø19.05)
ø3/8"
(ø9.52)
139,000
(40.7)
12
U-72MF1U9(E)U-96MF1U9(E)U-72MF1U9(E)
U-72MF1U9(E)
ø1/2"
(ø12.7)(ø15.88)
168,000
(49.2)
14
U-96MF1U9(E)
U-72MF1U9(E)
ø1-1/8"
(ø28.58)
ø7/8"
(ø22.22)
203,000
(59.5)
186
U-72MF1U9(E)
U-72MF1U9(E)
U-72MF1U9(E)
ø5/8"
240,000
(70.3)
20
U-96MF1U9(E)
U-72MF1U9(E)
U-72MF1U9(E)
ø1-1/8"
(ø28.58)
264,000
U-96MF1U9(E)
U-96MF1U9(E)
U-72MF1U9(E)
ø1-3/8"
(ø34.92)
(ø19.05)
*1: If future extension is planned, select the tubing diameter based on the total tonnage after extension.
However extension is not possible if the resulting tubing size is two ranks higher.
*2: The balance tube (outdoor unit tube) diameter is ø3/8" (ø9.52).
*3: Type 1 tubing should be used for the refrigerant tubes.
*4: If the length of the longest tube (L1) exceeds 295 ft. (equivalent length), increase the main tube (LM) size by 1 rank for the
suction, discharge, and liquid tubes. (Use field-supply reducers.) (Select from Table 2-2 and Table 2-7.)
*5: If the longest main tube length (LM) exceeds 164 ft., increase the main tube size at the portion before 164 ft. by 1 rank for
the suction tubes and discharge tubes.
(For the portion that exceeds 164 ft., set based on the main tube sizes (LA) listed in the table above.)
(77.4)
22
ø3/4"
Unit: in. (mm)
288,000
(84.4)
24
U-96MF1U9(E)
U-96MF1U9(E)
U-96MF1U9(E)
2
3
4
5
6
7
8
Size of tubing (LO) between outdoor units
Select the size of tubing between outdoor units based on the main tubing size (LA) as given in the table above.
Table 2-3 Main Tubing Size After Distribution (LB, LC...)
Total capacity
after distribution
Tubing size
Total capacity
after distribution
Tubing size
Below BTU/h
Over BTU/h
Suction tubing
Discharge tubing
Liquid tubing
Below BTU/h
Over BTU/h
Suction tubing
Discharge tubing
Liquid tubing
24.200
(ø15.88) (ø19.05) (ø19.05) (ø22.22)
ø1/2"ø5/8"ø5/8"ø3/4"
ø3/8"ø3/8"ø3/8"ø3/8"
258.000
238.900 258.000
ø1-3/8"ø1-3/8"ø1-3/8"
ø1-1/8"ø1-1/8"ø1-1/8"
(ø19.05) (ø19.05) (ø19.05)
54.600
–
24.200
(ø15.88)(ø19.05)(ø22.22)(ø12.70)
334.400
85.300
54.600
ø3/4"ø3/4"ø5/8"
(ø15.88)
–
334.400
(ø34.92)(ø34.92)(ø34.92)
(ø28.58)(ø28.58)(ø28.58)
ø3/4"ø3/4"ø3/4"
102.400
Table 2-4 Outdoor Unit Tubing Connection Size ( A – D )
BTU/h
(kW)
Suction tubing
Discharge
tubing
Liquid tubing
Balance tubing
72,000
(21.1)
1
*
ø3/4"
*
(ø19.05)
Brazing connection
ø5/8"
(ø15.88)
Brazing connection
ø3/8" (ø9.52)
1
Flare connection
ø3/8" (ø9.52)
Flare connection
96,000
(28.1)
2
*
ø7/8"
*
(ø22.22)
ø3/4"
(ø19.05)
ø3/8" (ø9.52)
Unit: in. (mm)
2
*1
*2
2 - 6
143.300
124.200
(ø28.58)
ø7/8"
ø1/2"
(ø12.70)
85.300
(ø9.52)(ø9.52)(ø9.52)(ø9.52)
124.200
102.400
(ø28.58)
ø3/4"
(ø19.05)
ø1/2"
(ø12.70)
The outdoor unit connection tubing (LO) is
*1:
determined by the total capacity of the outdoor
units connected to the tube ends. The tubing
size is selected based on the table of main
tube sizes after the branch.
If the total capacity of the indoor units con-
*2:
nected to the tube ends is different from the
total capacity of the outdoor units, then the
main tube size is selected based on the total
capacity of the outdoor units.
(For LA, LB, and LF in particular)
If the size of tubing (LA) is less than 16.4 feet,
it is recommended that the tubing diameter be
larger than ø7/8" (ø22.22).
If the size of tubing (LA) is less than 16.4 feet,
it is recommended that the tubing diameter be
larger than ø1-1/8" (ø28.58).
When bending the tubes, use a bending
radius that is at least 4 times the outer
diameter of the tubes.
In addition, take sufficient care to avoid
crushing or damaging the tubes when
bending them.
ø5/8" (ø15.88)
ø3/8" (ø9.52)
Unit: in. (mm)
1
2
3
4
2 - 7
5
6
7
8
1. Model Selecting and Capacity Calculator
1-5. Installation Standards
Relationship between A/C units and refrigerant tubing
Design of 3WAY VRF SYSTEM
1
2
3
Room
Indoor unit
Hallway
Solenoid
valve kit
Liquid
Room
Indoor unit
Gas tube
tube
Solenoid
valve kit
Outdoor unitOutdoor unitIndoor unit
Install the solenoid valve kit 98 ft. or less from the indoor unit.
In quiet locations such as hospitals, libraries, and hotel rooms, the refrigerant noise may be somewhat noticeable. It is recom-
mended that the solenoid valve kit be installed inside the corridor ceiling, at a location outside the room.
Hallway
Common solenoid valve kit
Multiple indoor units under group control can utilize a solenoid valve kit in common.
Categories of connected indoor unit capacities are determined by the solenoid valve kit.
Type of solenoid valve kitTotal capacity of indoor units (BTU/h)
16019.000 < Total capacity
567.500
If the capacity range is exceeded, use 2 solenoid valves connected in parallel.
4-tube layout3-tube layout2-tube layout
Suction tube
Discharge tube
Liquid tube
Solenoid
valve kit
54.600
Room
Indoor unit
Suction tube
Discharge tube
Liquid tube
Balance tube
DesirableUndesirable
Room
Indoor unit
Total capacity 19.000
(2) When adding ball valve for outdoor unit
1. Location: Install the ball valve at the main tube of the distribution joint.
4
5
6
7
8
Outdoor unit
for extension
Ball valve (for extension)
(Planned expansion)
Main tube of distribution joint
Balance tube
Discharge tube
Less than 1.3 ft
Distribution joint
(Suction tube)
Main tube
Liquid tube
To indoor unit
2. Installation requirements
• Be sure to install the ball valve up-grade to prevent the inadvertent flow of oil.
• Install the ball valve at the shortest distance (within 1.3 ft.) from the main tube. If the diameter of the ball valve
is smaller than that of the main tube, use a reducer or the like to reduce the size of the tubing at that location.
NOTE
• If the ball valve is installed at the outdoor unit (including extension for outdoor unit), face the service port of
the valve toward the outdoor unit side (see above illustration; dotted line) and allow a distance of over 1.6 ft
from the outdoor unit. If the ball valve is installed between the indoor unit (including extension for indoor unit)
and the main tube, face the ball valve toward the indoor unit side (see above illustration; dotted line).
• Use a field supply ball valve.
2 - 8
Design of 3WAY VRF SYSTEM
1. Model Selecting and Capacity Calculator
1-6. Straight Equivalent Length of Joints
Design the tubing system by referring to the following table for the straight equivalent length of joints.
Table 2-8 Straight Equivalent Length of Joints
Gas tubing size (in.(mm))
90° elbow
45° elbow
U-shape tube bent
(R2–23/64–3–15/16 in.)
T r ap bend
Y-branch distr ibution joint Equivalent length conversion not needed.
Ball v alve f or ser viceEquivalent length conversion not needed.
1/2"
(12.7)
0.80.91
7.59.210.515.4
5/8"
(15.88)
11.11.41.92.52.8
33.44.15.67.48.4
3/4"
(19.05)
1.6
1.2
4.7
1-1/8"
(28.58)
1.4
7/8"
(22.22)
12.519.222.3
1-3/8"
(34.92)
1.82.0
Unit: ft.
1-5/8"
(41.28)
1
2
3
4
5
6
7
2 - 9
8
1. Model Selecting and Capacity Calculator
Check of limit density
Design of 3WAY VRF SYSTEM
1
2
WARNING
1-7. Check of limit density
When installing an air conditioner in a room, it is necessary to ensure that if the refrigerant gas accidentally
leaks out, its density does not exceed the limit level for
that room.
CAUTION
Always check the gas density limit for the room in
which the unit is installed.
Pay special attention to any
location, such as a basement,
etc., where leaking refrigerant
can accumulate, since refrigerant gas is heavier than air.
3
4
5
6
7
8
2 - 10
Design of 3WAY VRF SYSTEM
1. Model Selecting and Capacity Calculator
1-8. Calculation of Actual Capacity of Indoor Unit
Calculating the actual capacity of each indoor unit
Because the capacity of a multi air-conditioner changes according to the temperature conditions, tubing length, elevation difference and other factors, select the correct model after taking into account the various correction values. When selecting The
model, calculate the corrected capacities of the outdoor unit and each indoor unit. Use the corrected outdoor unit capacity and
the total corrected capacity of all the indoor units to calculate the actual final capacity of each indoor unit.
1. Outdoor unit capacity correction coefficient
Find the outdoor unit capacity correction coefficient for the following items.
(1) Capacity correction for the outdoor unit model
The capacity correction coefficient is 1.00.
(2)
Capacity correction for the outdoor unit temperature conditions
Cooling:
Heating:
(3) Capacity correction for the outdoor unit tubing length and elevation difference
From the graph of capacity change characteristics on page 2-14, use the tubing length and elevation difference to find the
capacity correction coefficient.
The outdoor unit correction coefficient is the value which corresponds to the most demanding indoor unit.
(4) Capacity correction for outdoor unit frosting/defrosting during heating
From the table on page 2-13, find the capacity correction coefficient.
From the graph of capacity characteristics on page 2-13 ( Graph of Outdoor Unit Capacity Characteristics),
use the outdoor temperature to find the capacity correction coefficient.
From the graph of capacity characteristics on page 2-15, use the outdoor temperature to find the capacity
correction coefficient.
* Indoor air intake temperature should be set to 68 °FDB.
1
2. Indoor unit capacity correction coefficients
Find the indoor unit capacity correction coefficient for the following items.
(2) Capacity correction for the indoor unit temperature conditions
From the graph of capacity characteristics on page 2-14 ( Graph of Indoor Unit Capacity Characteristics), use the indoor
temperature to find the capacity correction coefficient.
(3) Capacity distribution ratio based on the indoor unit tubing length and elevation difference
First, in the same way as for the outdoor unit, use the tubing length and elevation difference for each indoor unit to find the
correction coefficient from the graph of capacity change characteristics on page 2-14. Then divide the result by the outdoor
unit correction coefficient to find the capacity distribution ratio for each indoor unit.
Capacity distribution ratio for each indoor unit (3) = Correction coefficient for that indoor unit / Correction coefficient for the outdoor unit
3. Calculating the corrected capacities for the outdoor unit and each indoor unit
The corrected capacities for the outdoor unit and each indoor unit are calculated form the formula below.
<Cooling>
Outdoor unit corrected cooling capacity (5) = Outdoor unit rated cooling capacity × Correction coefficient for model ((1)
Page 2-11) × Correction coefficient for outdoor temperature conditions ((2)
Page 2-13) × Correction coefficient for tubing length and elevation difference
((3) Page 2-14)
* However, if the outdoor unit corrected cooling capacity [5] is greater than 100%, then the outdoor unit corrected cooling
capacity [5] is considered to be 100%.
Corrected cooling capacity of each indoor unit (5) = Rated cooling capacity for that indoor unit × Correction coefficient for
indoor temperature conditions at that indoor unit ((2) Page 2-14) × Distribution ratio based on tubing length and elevation difference at that indoor unit ((3) Page 2-14)
However, the corrected cooling capacity of each indoor unit is found as shown below.
If (2) < 100% and (2) × (3) > 100%: Corrected cooling capacity for that indoor unit [5] = Rated cooling capacity for that indoor unit
If (2) >100%: Corrected cooling capacity for that indoor unit (5) = Rated cooling capacity for that indoor unit × (2)
2
3
4
5
6
7
2 - 11
8
Design of 3WAY VRF SYSTEM
1. Model Selecting and Capacity Calculator
<Heating>
Outdoor unit corrected heating capacity (5) = Outdoor unit rated heating capacity × Correction coeffi cient for model ((1)
Page 2-11) × Correction coeffi cient for outdoor temperature conditions ((2)
Page 2-15) × Correction coeffi cient for tubing length and elevation difference
((3) Page 2-14) × Correction coeffi cient for frosting/defrosting ((4) Page
* However, if the outdoor unit corrected heating capacity [5] is greater than 100%, then the outdoor unit corrected heating
capacity is considered to be 100%.
Corrected heating capacity of each indoor unit (5) = Rated heating capacity for that indoor unit × Correction coeffi cient for
indoor temperature conditions at that indoor unit ((2) Page 2-14) × Distribution ratio based on tubing length and elevation
difference at that indoor unit.
However, the corrected heating capacity of each indoor unit is found as shown below.
If (2) < 100% and (2)
100%: Corrected heating capacity for that indoor unit (5) = Rated heating capacity for that indoor unit × (2)
If (2)
* Characteristic graphs are shown on the pages listed above next to each correction item. Find each correction coeffi cient
from the appropriate conditions.
× (3) > 100%: Corrected heating capacity for that indoor unit (5) = Rated heating capacity for that indoor unit
2-13)
1
2
3
4
5
6
7
4. Calculating the actual indoor unit capacity based on the indoor/outdoor corrected capacity ratio
Calculate the actual capacity of each indoor unit from the values (found in (3)) for the corrected outdoor unit capacity and the
corrected capacity of each indoor unit.
<Cooling capacity>
Corrected indoor/outdoor capacity ratio during cooling (Ruc) = Total corrected cooling capacity of all indoor units in that system /
Corrected outdoor unit cooling capacity
If the corrected outdoor unit cooling capacity is greater than or equal to the total corrected unit cooling capacity of all indoor units
in that system (Ruc
Actual cooling capacity of each indoor unit (7) = Corrected cooling capacity of each indoor unit (5) (In other words, the correction coeffi cient (6), based on the corrected indoor/outdoor capacity ratios for each indoor unit, is 1.)
If the corrected outdoor unit cooling capacity is less than the total corrected unit cooling capacity of all indoor units in that system (Ruc > 1), then:
(Actual cooling capacity of each indoor unit (7)) = (Corrected cooling capacity of each indoor unit (5)) × (0.25 × Ruc + 0.75)
/ Ruc
(In other words, the correction coeffi cient (6), based on the corrected indoor/outdoor capacity ratios for each indoor unit, is
the underlined part in the formula above.)
<Heating capacity>
Corrected indoor/outdoor capacity ratio during heating (Ruh) = Total corrected heating capacity of all indoor units in that system
/ Corrected outdoor unit heating capacity
If the corrected outdoor unit heating capacity is greater than or equal to the total corrected unit heating capacity of all indoor
units in that system (Ruh
Actual heating capacity of each indoor unit (7) = Corrected heating capacity of each indoor unit (5)
(In other words, the correction coeffi cient (6), based on the corrected indoor/outdoor capacity ratios for each indoor unit, is 1.)
If the corrected outdoor unit heating capacity is less than the total corrected unit heating capacity of all indoor units in that system (Ruh > 1), then:
(Actual heating capacity of each indoor unit (7)) = (Corrected heating capacity of each indoor unit (5)) × (0.1 × Ruh + 0.9) /
Ruh
(In other words, the correction coeffi cient (6), based on the corrected indoor/outdoor capacity ratios for each indoor unit, is
the underlined part in the formula above.)
1), then:
1), then:
8
2 - 12
Design of 3WAY VRF SYSTEM
1. Model Selecting and Capacity Calculator
Refer to the graph below for the correction coeffi cients for Ruc and Ruh.
Indoor unit capacity correction coefficient for Ruc (cooling)
Indoor unit capacity correction coefficient for Ruh (heating)
The positive side for the elevation difference indicates that the outdoor unit is installed at a higher position than the indoor units.
The negative side indicates the opposite.
The capacity loss that is caused by the tubing length can be reduced by increasing the sizes of the discharge tubes and suc-
tion tubes. Refer to Table 2-9 and make the appropriate changes. However be sure that the total length does not exceed the
maximum.
* The only sizes which can be increased are the LM (main tube with the largest diameter) gas tubes, and the changes are
limited to those shown in Table 2-9.
In addition, note that the additional refrigerant charge is determined only by the narrow-tube size.
Table 2-9 Equivalent Length Correction Coeffi cient when the Size of the Discharge Tubes and Suction Tubes (LM)
is Increased
Standard tubing diameter
(gas tube, in.(mm))
Tubing diameter after change
(gas tube,in.(mm))
Equivalent length correction
coefficient
ø1/2"
(ø12.7)
ø5/8"ø3/4"ø7/8"ø1-1/8"ø1-3/8"
(ø15.88)(ø19.05)(ø22.22)(ø28.58)(ø34.92)
ø5/8"
(ø15.88)(ø19.05)(ø22.22)(ø28.58)
0.40.50.6
ø3/4"ø7/8"ø1-1/8"
* If the size of the discharge tubes and suction tubes (LM) have been increased, apply the correction coeffi cient from Table
2-9 and calculate the equivalent length of the LM section.
Equivalent length of tubing after size increase
= Standard tubing equivalent length × Equivalent length correction coeffi cient
2 - 14
Design of 3WAY VRF SYSTEM
1. Model Selecting and Capacity Calculator
1-9. Capacity Correction Graph According to Temperature Condition
Capacity characteristics
(The corrected capacity for specifi c temperature conditions can be found from the graphs below.)
< Cooling >< Heating >
6-Ton8-Ton
130
Indoor air intake temp. (WB) = 71 FIndoor air intake temp. (WB) = 71 F
Indoor air intake temp. (WB) = 72°F
120
110
WB = 67°F
100
90
WB = 61°F
80
Capacity ratio (%)
120
110
100
90
80
70
Indoor air intake temp. (WB) = 72°F
60
WB = 67°F
50
40
WB = 61°F
Input ratio (%)
30
20
10
14 23 32 41 50 59 68 77 86 95
104 113
130
120
110110
100
90
80
70
60
Capacity ratio (%)
50
40
130
120
100
90
Input ratio (%)
80
70
60
50
- 4
Indoor air intake temp. (°F DB)
61
70
79
61
70
79
5 142332415059
130
120
100
90
80
70
60
Capacity ratio (%)
50
40
130
120
110110
100
90
Input ratio (%)
80
70
60
50
- 4
5 142332415059
Indoor air intake temp. (°F DB)
61
70
79
61
1
70
79
2
Heating capacity correction coeffi cients for frost/defrost operation
The positive side for the elevation difference indicates that
the outdoor unit is installed at a higher position than the
indoor units. The negative side indicates the opposite.
*1 Sample calculations
(System: 8 Ton, 164ft equivalent length, 49ft elevation
difference
The cooling capacity and heating capacity for this system are
found as shown below.)
●
Cooling operation
From the graph, the base capacity change rate is found to be
92.0%.
×
96,000 BTU/h
(28.1kW
●
Heating operation
From the graph, the base capacity change rate is found to be
97.2%.
Because the calculation result exceeds 97.2%, the capacity
change rate is 97.2%.
(31.6kW
×
92.0% = 88,320 BTU/h
92.0% = 25.8kW)
×
97.2% = 105,000 BTU/h108,000 BTU/h
×
97.2% = 30.7kW)Heating capacity is
Capacity change rate is 92.0%.
Cooling capacity is
88,320 BTU/h (28.1 kW)
105,000 BTU/h (30.7 kW)
2 - 16
Loading...
+ 145 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.