Regarding the system connected to the indoor unit model S-19MS1U6, see the following contents.
1. Additional sentences are provided in the "NOTE" under the section "Table 1-2 Ranges that Apply to Refrigerant Tubing Lengths
and to Differences in Installation Heights " on page 8 in the Installation Instructions.
7: If the tubing length which is connected to the model S-19MS1U6 is less than 8 m (26.2 ft) between the outdoor unit and
the final distribution joint, increase the size of the gas tube between them by one-rank-higher.
2. Replace the section "Table 1-7 Indoor Unit Tubing Connection Size" on page 9 in the Installation Instructions with the following table.
Table 1-7 Indoor Unit Tubing Connection Size
Indoor unit type791215181924364854
Gas tubingø1/2" (ø12.7)ø5/8" (ø15.88)
Liquid tubingø1/4" (ø6.35)ø3/8" (ø9.52)
* When connecting the gas tube for S-19MS1U6, use a field supply reducer.
3. Replace the section "Necessary Amount of Additional Refrigerant Charge for All Indoor Unit Cooling Capacity" on page 10 in the
Installation Instructions with the following table.
Necessary Amount of Additional Refrigerant Charge for All Indoor Unit Cooling Capacity
Charge a refrigerant amount calculated in the following formula according to the total amount of indoor unit cooling capacity.
Additional refrigerant amount when cooling capacity is BTU/h = Cooling capacity (BTU/h) x 1.034 x 0.001 + 10.6 (oz)
or Additional refrigerant amount when cooling capacity is kW = Cooling capacity (kW) x 1000 x 0.1 + 300 (g)
* However, calculate the cooling capacity of the indoor unit S-19MS1U6 as 0 kW.
Unit: in. (mm)
85464369760021-SP
INSTALLATION INSTRUCTIONS
2WAY VRF System Air Conditioner
This air conditioner uses the refrigerant R410A.
NOTE
External diameter of service port R410A: 5/16" (7.94mm)
*1 Necessary to install the External Electronic Expansion Valve Kit (Optional: CZ-P56SVK1U)
85464369760021CV6231977845
IMPORTANT!
Please Read Before Starting
This air conditioning system meets strict safety and
operating standards. As the installer or service person, it is
an important part of your job to install or service the system
so it operates safely and efficiently.
For safe installation and trouble-free operation, you must:
Carefully read this instruction booklet before beginning.
Follow each installation or repair step exactly as shown.
Observe all local, state, and national electrical codes.
Pay close attention to all warning and caution notices
given in this manual.
This symbol refers to a hazard or
WARNING
CAUTION
unsafe practice which can result
in severe personal injury or death.
This symbol refers to a hazard or
unsafe practice which can result
in personal injury or product or
property damage.
If Necessary, Get Help
These instructions are all you need for most installation
sites and maintenance conditions. If you require help for a
special problem, contact our sales/service outlet or your
certified dealer for additional instructions.
In Case of Improper Installation
The manufacturer shall in no way be responsible for
improper installation or maintenance service, including
failure to follow the instructions in this document.
When Transporting
Be careful when picking up and moving the indoor and
outdoor units. Get a partner to help, and bend your knees
when lifting to reduce strain on your back. Sharp edges or
thin aluminum fins on the air conditioner can cut your fingers.
When Installing…
Select an installation location which is rigid and strong
enough to support or hold the unit, and select a location for
easy maintenance.
…In a Room
Properly insulate any tubing run inside a room to prevent
“sweating” that can cause dripping and water damage to
walls and floors.
CAUTION
…In Moist or Uneven Locations
Use a raised concrete pad or concrete blocks to provide
a solid, level foundation for the outdoor unit. This prevents
water damage and abnormal vibration.
…In an Area with High Winds
Securely anchor the outdoor unit down with bolts and a
metal frame. Provide a suitable air baffle.
…In a Snowy Area (for Heat Pump-type Systems)
Install the outdoor unit on a raised platform that is higher
than drifting snow. Provide snow vents.
Keep the fire alarm and the air outlet at
least 5 feet (1.5m) away from the unit.
SPECIAL PRECAUTIONS
WARNING
ELECTRICAL SHOCK CAN CAUSE
SEVERE PERSONAL INJURY OR DEATH.
ONLY A QUALIFIED, EXPERIENCED
ELECTRICIAN SHOULD ATTEMPT TO
WIRE THIS SYSTEM.
• Do not supply power to the unit until all wiring and tubing
are completed or reconnected and checked.
•
Highly dangerous electrical voltages are used in this
system. Carefully refer to the wiring diagram and these
instructions when wiring. Improper connections and
inadequate grounding can cause accidental injury or
death.
• Ground the unit following local electrical codes.
Connect all wiring tightly. Loose wiring may cause
•
overheating at connection points and a possible fire hazard.
• To prevent possible hazards from insulation failure,
the unit must be grounded.
• This equipment is strongly recommended to be installed
with Earth Leakage Circuit Breaker (ELCB) or Residual
Current Device (RCD). Otherwise, it may cause electrical
shock and fire in case of equipment breakdown or
insulation breakdown.
When Wiring
When Connecting Refrigerant Tubing
• Ventilate the room well, in the event that is refrigerant
gas leaks during the installation. Be careful not to allow
contact of the refrigerant gas with a flame as this will
cause the generation of poisonous gas.
• Keep all tubing runs as short as possible.
• Use the flare method for connecting tubing.
Apply refrigerant lubricant to the matching surfaces of the
•
flare and union tubes before connecting them, then tighten
the nut with a torque wrench for a leak-free connection.
• Check carefully for leaks before starting the test run.
•
When performing piping work do not
mix air except for specified refrigerant
(R410A) in refrigeration cycle. It causes
capacity down, and risk of explosion
and injury due to high tension inside
the refrigerant cycle.
WARNING
Do not leak refrigerant while piping work for an installation
•
or re-installation, and while repairing refrigeration parts.
Handle liquid refrigerant carefully as it may cause frostbite.
• Check for a leaking refrigerant!
Refrigerant gas may produce a toxic
gas if it comes in contact with fire.
• Do not add or replace refrigerant other
than specified type.
It may cause product damage, burst
and injury etc.
2
When Servicing
• Turn the power OFF at the main power box (mains)
before opening the unit to check or repair electrical
parts and wiring.
• Keep your fingers and clothing away from any moving
parts.
• Clean up the site after you finish, remembering to check
that no metal scraps or bits of wiring have been left inside
the unit being serviced.
WARNING
• This product must not be
modified or disassembled under
any circumstances. Modified or
disassembled unit may cause fire,
electric shock or injury.
• Do not clean inside the indoor and
outdoor units by users. Engage
authorized dealer or specialist for
cleaning.
• In case of malfunction of this
appliance, do not repair by yourself.
Contact to the sales dealer or service
dealer for a repair.
Others
CAUTION
CAUTION
• Do not touch the air inlet or
the sharp aluminum fins of the
outdoor unit. You may get injured.
• Ventilate any enclosed areas when
installing or testing the refrigeration
system. Escaped refrigerant gas, on
contact with fire or heat, can produce
dangerously toxic gas.
• Confirm after installation that no
refrigerant gas is leaking. If the gas
comes in contact with a burning stove,
gas water heater, electric room heater
or other heat source, it can cause the
generation of poisonous gas.
• Do not sit or step on the unit,
you may fall down accidentally.
• Do not touch the air inlet or
the sharp aluminum fins of the
outdoor unit. You may get injured.
• Do not stick any object into the
FAN CASE.
You may be injured and the unit
may be damaged.
Check of Density Limit
The room in which the air conditioner is to be
installed requires a design that in the event of
refrigerant gas leaking out, its density will not exceed
a set limit.
The refrigerant (R410A), which is used in the air
conditioner, is safe, without the toxicity or combustibility of
ammonia, and is not restricted by laws imposed to protect
the ozone layer. However, since it contains more than
air, it poses the risk of suffocation if its density should
rise excessively. Suffocation from leakage of refrigerant
is almost non-existent. With the recent increase in the
number of high density buildings, however, the installation
of multi air conditioner systems is on the increase
because of the need for effective use of floor space,
individual control, energy conservation by curtailing heat
and carrying power, etc.
Most importantly, the multi air conditioner system is able
to replenish a large amount of refrigerant compared to
conventional individual air conditioners. If a single unit
of the multi air conditioner system is to be installed in
a small room, select a suitable model and installation
procedure so that if the refrigerant accidentally leaks out,
its density does not reach the limit (and in the event of
an emergency, measures can be made before injury can
occur).
ASHRAE and the International Mechanical Code of
the ICC as well as CSA provide guidance and define
safeguards related to the use of refrigerants, all of which
define a Refrigerant Concentration Level (RCL) of 25
pounds (11.3kg) per 1,000 cubic feet (28.3m3) for R410A
refrigerant. For additional guidance and precautions
related to refrigerant safety, please refer to the following
documents:
International Mechanical Code 2009 (IMC-2009)
(or more recently revised)
ASHRAE 15
ASHRAE 34
3
Precautions for Installation Using New Refrigerant
1. Care regarding tubing
1-1. Process tubing
l
Material: Use C1220 phosphorous deoxidized copper specified in JIS H3300 “Copper and Copper Alloy Seamless
Pipes and Tubes.”
l
Tubing size: Be sure to use the sizes indicated in the table below.
l
Use a tube cutter when cutting the tubing, and be sure to remove any flash. This also applies to distribution joints
(optional).
l
When bending tubing, use a bending radius that is 4 times the outer diameter of the tubing or larger.
Use sufficient care in handling the tubing. Seal the tubing ends with caps or tape to
1-2. Prevent impurities including water, dust and oxide from entering the tubing. Impurities can cause R410A
refrigerant deterioration and compressor defects. Due to the features of the refrigerant and refrigerating machine
oil, the prevention of water and other impurities becomes more important than ever.
prevent dirt, moisture, or other foreign substances from entering.
These substances can result in system malfunction.
2. Be sure to recharge the refrigerant only in liquid form.
2-1. Since R410A is a non-azeotrope, recharging the refrigerant in gas form can lower performance and cause defects
in the unit.
2-2. Since refrigerant composition changes and performance decreases when gas leaks, collect the remaining
refrigerant and recharge the required total amount of new refrigerant after fixing the leak.
3. Different tools required
3-1. Tool specifications have been changed due to the characteristics of R410A.
Some tools for R22- and R407C-type refrigerant systems cannot be used.
R407C tools
Item
Manifold gaugeYesNo
Charge hoseYesNoTo resist higher pressure, material must be changed.
Vacuum pumpYesYes
Leak detectorYesNo
Flaring oilYesNo
* Using tools for R22 and R407C and new tools for R410A together can cause defects.
New
tools?
compatible
with R410A?
Remarks
Types of refrigerant, refrigerating machine oil, and
pressure gauge are different.
Use a conventional vacuum pump if it is equipped with
a check valve. If it has no check valve, purchase and
attach a vacuum pump adapter.
Leak detectors for CFC and HCFC that react to chlorine
do not function because R410A contains no chlorine.
Leak detector for HFC134a can be used for R410A.
For systems that use R22, apply mineral oil (Suniso
oil) to the flare nuts on the tubing to prevent refrigerant
leakage. For machines that use R407C or R410A, apply
synthetic oil (ether oil) to the flare nuts.
Manifold gauge
Vacuum pump
Outlet
Inlet
4
3-2. Use R410A exclusive cylinder only.
New refrigerant R410A cannot be used for
earlier models
1. Compressor specifications are different.
If recharging a R22 or R407C compressor with
R410A, durability will significantly decrease since
some of the materials used for compressor parts are
different.
Valve
Single-outlet valve
(with siphon tube)
Liquid refrigerant should be recharged
with the cylinder standing on end as
shown.
Liquid
2. Existing tubing cannot be used (especially R22).
Completely cleaning out residual refrigerating
machine oil is impossible, even by flushing.
3. Refrigerating machine oil differs (R22).
Since R22 refrigerating machine oil is mineral oil, it
does not dissolve in R410A. Therefore, refrigerating
machine oil discharged from the compressor can
cause compressor damage.
Please Read Before Starting
Check of Density Limit
Precautions for Installation Using New Refrigerant
New refrigerant R410A cannot be used for earlier models
1. GENERAL ............................. 7
1-1. Tools Required for Installation (not supplied)
1-2. Accessories Supplied
1-3. Type of Copper Tube and Insulation Material
1-4. Additional Materials Required for Installation
1-5. Tubing Length
1-6. Tubing Size
1-7. Straight Equivalent Length of Joints
1-8. Additional Refrigerant Charge
1-9. System Limitations
1-10. Check of Limit Density
1-11. Installing Distribution Joint
1-12. Optional Distribution Joint Kits
1-13. Example of Tubing Size Selection and
Refrigerant Charge Amount
2. SELECTING THE INSTALLATION SITE .... 16
5. HOW TO PROCESS TUBING ............. 32
5-1. Connecting the Refrigerant Tubing
5-2. Connecting Tubing Between Indoor and
Outdoor Units
5-3. Insulating the Refrigerant Tubing
5-4. Taping the Tubes
5-5. Finishing the Installation
6. AIR PURGING ......................... 35
n
Air Purging with a Vacuum Pump (for Test Run)
Preparation
7. TEST RUN ............................ 38
7-1. Preparing for Test Run
7-2. Test Run Procedure
7-3. Main Outdoor Unit PCB Setting
7-4. Function Switches on P.C. Board
7-5. Auto Address Setting
7-6. Setting Test Run Remote Controller
7-7. Caution for Pump Down
7-8. Self-Diagnosis Function Table and Contents of
Alarm Display
2-1. Outdoor Unit
2-2. Shield for Horizontal Exhaust Discharge
2-3. Installing the Outdoor Unit in Heavy Snow
Areas
2-4. Precautions When Installing in Heavy Snow
Areas
2-5. Dimensions of Wind Ducting
2-6. Dimensions of Snow Ducting
3. HOW TO INSTALL THE OUTDOOR UNIT ... 22
3-1. Transporting
3-2. Installing the Outdoor Unit
3-3. Routing the Tubing
3-4. Prepare the Tubing
3-5. Connect the Tubing
4. ELECTRICAL WIRING .................. 27
4-1. General Precautions on Wiring
4-2. Recommended Wire Length and Wire
Diameter for Power Supply System
4-3. Wiring System Diagram
6
1. GENERAL
This booklet briefly outlines where and how to install the air conditioning system. Please read over the entire set of instructions for
the outdoor unit and make sure all accessory parts listed are with the system before beginning.
1-1. Tools Required for Installation (not supplied)
1. Flathead screwdriver
2. Phillips head screwdriver
3. Knife or wire stripper
4. Tape measure
5. Level gauge
6. Sabre saw or keyhole saw
7. Hacksaw
8. Core bits
9. Hammer
10. Drill
11. Tube cutter
12. Tube flaring tool
13. Torque wrench
14. Adjustable wrench
15. Reamer (for deburring)
1-2. Accessories Supplied
Table 1-1 Outdoor Unit
Part nameConnection tubing
Inner
diameter
ø1"
(ø25.4mm)
Figure
Instruction
manual
1-3. Type of Copper Tube and Insulation Material
If you wish to purchase these materials separately from a local
source, you will need:
1. Deoxidized annealed copper tube for refrigerant tubing.
2. Foamed polyethylene insulation for copper tubes as
required to precise length of tubing. Wall thickness of the
insulation should be not less than 5/16" (7.94mm).
3. Use insulated copper wire for field wiring. Wire size varies
with the total length of wiring.
“
Refer to
4. ELECTRICAL WIRING” for details.
Check local electrical codes and
CAUTION
regulations before obtaining
wire. Also, check any specified
instructions or limitations.
1-4. Additional Materials Required for Installation
1. Refrigeration (armored) tape
2. Insulated staples or clamps for connecting wire
(See your local codes.)
3. Putty
4. Refrigeration tubing lubricant
5. Clamps or saddles to secure refrigerant tubing
6. Scale for weighing
Q’ty
U-72ME2U9
(6 ton)
U-96ME2U9
(8 ton)
U-120ME2U9
(10 ton)
U-144ME2U9
(12 ton)
Outer
diameter
ø1-1/8"
(ø28.58mm)
01
01
11
11
paper
7
1-5. Tubing Length
Select the installation location so that the length and size of refrigerant tubing are within the allowable range show in the figure below.
1.
Main tubing length (maximum tubing size) LM = LA + LB …
2.Main distribution tubes LC – LH are selected according to the capacity after the distribution joint.
3. The outdoor connection main tubing (LO portion) is determined by the total capacity of the outdoor units that are
connected to the tube ends.
4.
Sizes of indoor unit connection tubing
1 – 64 are determined by the connection tubing sizes on the indoor units.
H3
C
Balance tubing
(ø1/4" (6.35mm))
No.1 distribution joint for outdoor unit
No.1 distribution joint (for indoor unit)
* Be sure to use special R410A distribution joints (CZ: optional parts) for outdoor unit connections and tubing branches.
Table 1-2 Ranges that Apply to Refrigerant Tubing Lengths and to Differences in Installation Heights
ItemMarkContentsLength
Actual length
Equivalent length
Allowable tubing
length
Allowable elevation
difference
Allowable length of
joint tubing
L1Max. tubing length
L (L2 – L4)
Difference between max. length and min.
length from the No.1 distribution joint
LMMax. length of main tubing (at maximum size)
1, 2~ 64Max. length of each distribution tube
L1 + 1 + 2~ 63 + A
+ B + LF + LG + LH
A, B + LO, C + LO
H1
Total max. tubing length including length of each distribution
tube (only liquid tubing)
Maximum tubing length from outdoor’s 1st distribution
joint to each outdoor unit
When outdoor unit is installed higher than indoor unit
When outdoor unit is installed lower than indoor unit
H2Max. difference between indoor units
H3Max. difference between outdoor units
L3
T-joint tubing (field-supply); Max. tubing length between the
first T-joint and solidly welded-shut end point
unit: ft. (m)
656 (200)*
689 (210)*
164 (50)*
-
164 (50)*
3280 (1000)
33 (10)
164 (50)
131 (40)
49 (15)*
13 (4)
6.6 (2)
*
5
2
2
4
3
6
L = Length
H = Height
NOTE
1: The outdoor connection main tubing (LO portion) is determined by the total capacity of the outdoor units that are connected to
the tube ends.
2: If the longest tubing length (L1) exceeds 295 ft. (90m) (equivalent length), increase the sizes of the main tubes (LM) by 1 rank
for gas tubes and liquid tubes. (Use a field supply reducer.) (Select the tube size from the table of main tube sizes (Table 1-3) on
the following page (LA table), and from the table of refrigerant tubing sizes (Table 1-9) on the second following page.)
3: If the longest main tubing length (LM) exceeds 164 ft. (50m), increase the main tube size at the portion before 164 ft. (50m) by 1
rank for the gas tubes. (Use a field supply reducer.)
(For the portion that exceeds 164 ft. (50m), set based on the main tube sizes (LA) listed in the table on the following page.)
4: If the tubing length marked "L" (L2 - L4) exceeds 131 ft. (40m), increase the liquid tube and gas tube by 1 rank.
5: If the total distribution tubing length exceeds 1,640ft. (500m), maximum allowable elevation difference (H2) between the indoor
units is calculated by the following formula. Make sure the indoor unit’s actual elevation difference should fall within the figure
calculated as follows.
Unit of account (feet): 15 x (2 - total tubing length(ft.) ÷ 1,640) or Unit of account (meter): 15 x (2 - total tubing length(m) ÷ 500)
6: If any of the tubing length exceeds 98ft. (30m), increase the size of the liquid and gas tubes by 1 rank.
8
1-6. Tubing Size
Table 1-3 Main Tubing Size (LA)
Between No.1 distribution joint for outdoor unit and No.1 distribution joint (for indoor unit)
BTU/h
(kW)
Total system
tonnage
Gas tubing
Liquid tubing
72,000
(21.1)
ø3/4"
(ø19.05)
96,000
(28.1)
681012141618202224262830
ø7/8"
(ø22.22)
ø3/8"
(ø9.52)
120,000
(35.2)
(ø12.7)
ø1/2"
144,000
(42.2)
168,000
(49.2)
ø1-1/8"
(ø28.58)
192,000
(56.3)
ø5/8"
(ø15.88)
216,000
(63.3)
240,000
(70.3)
264,000
(77.4)
288,000
(84.4)
ø1-3/8"
(ø34.92)
(ø19.05)
312,000
(91.4)
ø3/4"
*1: If future extension is planned, select the tubing diameter based on the total tonnage after extension.
However extension is not possible if the resulting tubing size is three ranks higher.
*2: The balance tube (outdoor unit tube) diameter is ø1/4" (6.35mm).
*3: Type 1 tubing should be used for the refrigerant tubes.
n
Size of tubing (LO) between outdoor units
Select the size of tubing between outdoor units based on the main tubing size (LA) as given in the table above.
Table 1-4 Main Tubing Size After Distribution (LB, LC...)
Total capacity
after distribution
Tubing size
Below BTU/h (kW)
Over BTU/h (kW)–
Gas tubing
Liquid tubing
24,200
(7.09)
ø1/2"
(ø12.7)
ø3/8"
(ø9.52)
54,600
(16.0)
24,200
(7.09)
ø5/8"
(ø15.88)
ø3/8"
(ø9.52)
76,800
(22.5)
54,600
(16.0)
ø3/4"
(ø19.05)
ø3/8"
(ø9.52)
102,400
(30.0)
76,800
(22.5)
ø7/8"
(ø22.22)
ø3/8"
(ø9.52)
143,300
(42.0)
102,400
(30.0)
ø1-1/8"
(ø28.58)
ø1/2"
(ø12.7)
178,800
(52.4)
143,300
(42.0)
ø1-1/8"
(ø28.58)
ø1/2"
(ø12.7)
238,900
(70.0)
178,800
(52.4)
ø1-1/8"
(ø28.58)
ø5/8"
(ø15.88)
340,000
(99.6)
238,900
(70.0)
ø1-3/8"
(ø34.92)
ø3/4"
(ø19.05)
Note: In case the total capacity of connected indoor units exceeds the total capacity of the outdoor units, select the main tubing
size for the total capacity of the outdoor units.
Unit: in. (mm)
336,000
(98.5)
Unit: in. (mm)
360,000
(ø41.28)
–
340,000
(99.6)
ø1-5/8"
(ø41.28)
ø3/4"
(ø19.05)
(105.5)
ø1-5/8"
A
Table 1-5 Outdoor Unit Tubing Connection Size (
BTU/h
(kW)
Gas tubing
Liquid tubing
Balance tubing
72,000
(21.1)
1
ø3/4" *
(ø19.05) *
ø3/8" (ø9.52)ø3/8" (ø9.52)ø1/2" (ø12.7)
1
96,000
(28.1)
2
ø7/8" *
(ø22.22)*
2
Brazing connection
Flare connection
ø1/4" (ø6.35)
Flare connection
120,000
(35.2)
–
ø1-1/8"
(ø28.58)
C
)
Unit: in. (mm)
144,000
(42.2)
ex.) type72
Balance
tube
Liquid tube
Table 1-6 Refrigerant Charge Amount at Shipment (for outdoor unit)
bending radius that is at least 4 times
the outer diameter of the tubes.
In addition, take sufficient care to
avoid crushing or damaging the tubes
when bending them.
1-3/8"
(34.92)
2.5
(0.76)
1.8
(0.55)
7.4
(2.26)
19.2
(5.85)
Unit: ft. (m)
1-5/8"
(41.28)
2.8
(0.85)
2.0
(0.61)
8.4
(2.56)
22.3
(6.80)
1-8. Additional Refrigerant Charge
Additional refrigerant charge amount is calculated from the liquid tubing total length, combination number of outdoor unit and
refrigerant amount according to all indoor unit cooling capacity.
Required amount of additional refrigerant charge
= [(Necessary amount of additional refrigerant charge per ft. (m) of each size of liquid tube x its tube length) + (...) + (...)]
+ [Necessary amount of additional refrigerant charge per outdoor unit]
+ [Necessary amount of additional refrigerant charge for all indoor unit cooling capacity]
* Always charge accurately using a scale for weighing.
Table 1-10-1 Necessary Amount of Additional Refrigerant Charge Per ft. (or per meter), According to Liquid Tubing Size
Liquid tubing size
Additional amount
Table 1-10-2 Necessary Amount of Additional Refrigerant Charge Per Outdoor Unit
Further charge a certain amount listed below in addition to the amount of refrigerant charge.
Necessary Amount of Additional Refrigerant Charge for All Indoor Unit Cooling Capacity
Charge a refrigerant amount calculated in the following formula according to the total amount of indoor unit cooling capacity.
inchø1/4"ø3/8"ø1/2"ø5/8"ø3/4"ø7/8"
(mm)(ø6.35)(ø9.52)(ø12.7)(ø15.88)(ø19.05)(ø22.22)
oz/ft.0.2790.6021.381.992.783.93
(g/m)(26)(56)(128)(185)(259)(366)
Additional refrigerant amount when cooling capacity is BTU/h = Cooling capacity (BTU/h) x 1.034 x 0.001 + 10.6 (oz)
or Additional refrigerant amount when cooling capacity is kW = Cooling capacity (kW) x 1000 x 0.1 + 300 (g)
*1: In the case of 18 ton (63.3kW) or smaller units, the number is
limited by the total capacity of the connected indoor units.
*2: Up to 3 units can be connected if the system has been extended.
*3: It is strongly recommended that you choose the unit so the load
can become between 50 and 130%.
Table 1-12 System Limitations of Total Refrigerant Amount
Combination number of outdoor unit123
g
Upper limitoz (
)1,763 (50,000)2,821 (80,000)3,703 (105,000)
Make sure the values calculated using the following formula should not exceed the maximum allowable values (Table 1-12).
Total refrigerant amount = Refrigerant charge amount at shipment (for outdoor unit)
+ Necessary amount of additional refrigerant charge per ft. (or per meter) according to liquid tubing size
+ Necessary amount of additional refrigerant charge per outdoor unit
+ Necessary amount of additional refrigerant charge for all indoor unit cooling capacity
Maximum number of connectable indoor units
when connected with minimum capacity
Total system
tonnage
Number of
indoor units
Total system
tonnage
Number of
indoor units
6201445
8251650
10321855
123920~3064
WARNING
Always check the gas density limit for the
room in which the unit is installed.
1-10. Check of Limit Density
When installing an air conditioner in a room, it is necessary to
ensure that even if the refrigerant gas accidentally leaks out, its
density does not exceed the limit level for that room.
Pay special attention to any location, such as
CAUTION
a basement, etc., where leaking refrigerant
can accumulate, since refrigerant gas is
heavier than air.
1-11. Installing Distribution Joint
(1) Refer to “HOW TO ATTACH DISTRIBUTION JOINT” enclosed
with the optional distribution joint kit
(CZ-P680PJ1U, CZ-P1350PJ1U, CZ-P160BK1U,
CZ-P680BK1U, CZ-P1350BK1U).
(2) When creating a branch using a commercially available T-joint
(header joint system), orient the main tubing so that it is either
horizontal (level) or vertical.
In order to prevent accumulation of refrigerant oil in stopped units,
if the main tubing is horizontal and directly connected to the indoor
unit, each branch tubing length should be at an angle that is
greater than horizontal.
If there are other cases, keep the main tubing horizontal (level).
If the main tubing is vertical, provide a raised starting portion for
each branch.
(3) If there are height differences between indoor units or if branch
tubing that follows a distribution joint is connected to only 1
unit, a trap or ball valve must be added to that distribution joint.
(When adding the ball valve, locate it within 1.3 ft. (40cm) of the
distribution joint.)
If a trap or ball valve is not added, do not operate the system
before repairs to a malfunctioning unit are completed.
(The refrigerant oil sent through the tubing to the
malfunctioning unit will accumulate and may damage the
compressor.)
Tube branching methods
(horizontal use & direct connection to indoor unit)
Arrow view D
15° to 30°
B
view D
Types of vertical trap specifications
(When using ball valve)
Main tubing
Ball valve
(BV: purchased
separately)
Indoor unit (1)
(When not using ball valve)
Main tubing
Indoor unit is directed downward
Indoor unit (more than 2 units)
Branch tubing is
directed upward.
More than
8 inch (20cm)
(If only 1 unit is connected, a ball valve
is also needed on this side.)
A
B
Arrow view C
A
Horizontal
Indoor unit
15° to 30°
Horizontal
line
view C
(Each unit is connected
to tubing that is either
level or is directed
downward.)
B
A
View as seen
from arrow
11
1-12. Optional Distribution Joint Kits
4-21/64
2-53/64
2-53/64
6-57/64
4-21/64
See the installation instructions packaged with the distribution joint kit for the installation procedure.
Table 1-12
Model nameCooling capacity after distributionRemarks
1. CZ-P680PJ1U232,000 BTU/h (68.0 kW) or lessFor outdoor unit
2. CZ-P1350PJ1U460,700 BTU/h (135.0 kW) or lessFor outdoor unit
3. CZ-P160BK1U76,400 BTU/h (22.4 kW) or lessFor indoor unit
4. CZ-P680BK1U232,000 BTU/h (68.0 kW) or lessFor indoor unit
5. CZ-P1350BK1U460,700 BTU/h (135.0 kW) or lessFor indoor unit
n
Tubing size (with thermal insulation)
1. CZ-P680PJ1U
For outdoor unit (Capacity after distribution joint is 232,000 BTU/h (68.0 kW) or less.)
Example:
Distribution
Joint
Reducing
Joints
Gas tubingLiquid tubing
6-59/64
(175)
5-5/16
(135)
C
C
Insulation
4-31/64
(114)
F E D C
Insulation
G
Distribution
Joint
(110)
3-13/16
(97)
G
G
H
I
HI
Reducing
Joints
(72)
Unit: in. (mm)
Table 1-13 Size of connection point on each part (Shown are inside diameters of tubing)
SizePart APart BPart CPart DPart EPart FPart GPart HPart I
in. (mm)
ø1-3/8"
(ø34.92)
ø1-1/4"
(ø31.75)
ø1-1/8"
(ø28.58)
ø1"
(ø25.4)
ø7/8"
(ø22.22)
ø3/4"
(ø19.05)
ø5/8"
(ø15.88)
ø1/2"
(ø12.7)
2. CZ-P1350PJ1U
For outdoor unit (Capacity after distribution joint is greater than 232,000 BTU/h (68.0 kW) and no more than
460,700 BTU/h (135.0 kW).)
Example:
C
D
Insulation
B
A
Distribution
Joint
Table 1-14 Size of connection point on each part (Shown are inside diameters of tubing)
SizePart APart BPart CPart DPart EPart FPart GPart HPart I
in. (mm)
ø1-3/8"
(ø34.92)
Gas tubingLiquid tubing
(175)
5-5/16
(135)
A
ø1-1/4"
(ø31.75)
B
B
C
D
E
F
ø1-1/8"
(ø28.58)
C
D
A
Reducing
Joints
(ø25.4)
(114)
ø1"
4-31/64
: Outside dimension
ø7/8"
(ø22.22)
F
Insulation
ø3/4"
(ø19.05)
G
Distribution
Joint
ø5/8"
(ø15.88)
(110)
3-13/16
(97)
G
G
H
I
(ø12.7)
HI
ø1/2"
ø3/8"
(ø9.52)
(72)
Reducing
Joints
Unit: in. (mm)
ø3/8"
(ø9.52)
12
3. CZ-P160BK1U
4-21/64
4-21/64
2-53/64
6-57/64
2-53/64
2-53/64
6-57/64
Use: For indoor unit (Capacity after distribution joint is 76,400 BTU/h (22.4 kW) or less.)
Example:
A
Insulation
(110)
3-13/16 3-13/16
(97)
B
Distribution
Joint
B
B
C
Gas tubing
C
A
(72)
2-53/64
D
Insulation
(110)
(97)
C
Distribution
Joint
C
C
D
E
Liquid tubing
DE
Unit: in. (mm)
(72)
Table 1-15 Size of connection point on each part (Shown are inside diameters of tubing)
SizePart APart BPart CPart DPart E
in. (mm)
ø3/4"
(ø19.05)
ø5/8"
(ø15.88)
ø1/2"
(ø12.7)
ø3/8"
(ø9.52)
ø1/4"
(ø6.35)
4. CZ-P680BK1U
Use: For indoor unit (Capacity after distribution joint is greater than 76,400 BTU/h (22.4 kW) and no more than 232,000 BTU/h (68.0 kW).)
Example:
D C B
Insulation
A
Distribution
Joint
(175)
5-5/16
(135)
A
Gas tubing
4-31/64
A
B
C
D
E
F
B C D
Reducing
Joints
E F
(114)
F G
Distribution
Joint
Insulation
4-21/64
(110)
3-13/16
(97)
E
E
F
G
H
E
Liquid tubing
(72)
F G H
Reducing
Joints
Unit: in. (mm)
Table 1-16 Size of connection point on each part (Shown are inside diameters of tubing)
SizePart APart BPart CPart DPart EPart FPart GPart H
in. (mm)
ø1-1/8"
(ø28.58)
ø1"
(ø25.4)
ø7/8"
(ø22.22)
ø3/4"
(ø19.05)
ø5/8"
(ø15.88)
ø1/2"
(ø12.7)
ø3/8"
(ø9.52)
ø1/4"
(ø6.35)
5. CZ-P1350BK1U
Use: For indoor unit (Capacity after distribution joint is greater than 232,000 BTU/h (68.0 kW) and no more than 460,700 BTU/h (135.0 kW).)
Example:
Insulation
B
B
A
Gas tubing
Reducing
Joints
CD
A
4-31/64
(114)
Distribution
Joint
Insulation
: Outside dimension
F
(175)
5-5/16
A
C D
(135)
B
Distribution
Joint
C
D
E
F
G
H
4-21/64
3-13/16
G
(110)
(97)
G
H
I
J
G
Liquid tubing
F
H
Reducing
Joints
Unit: in. (mm)
(72)
Table 1-17 Size of connection point on each part (Shown are inside diameters of tubing)
1-13. Example of Tubing Size Selection and Refrigerant Charge Amount
Additional refrigerant charging
Based on the values in Tables 1-3, 4, 5, 7, 10-1 and 10-2, use the liquid tubing size and length, and calculate the amount of
additional refrigerant charge using the formula below.
Unit of account (oz)
Required additional
refrigerant charge (oz)
or
g
Unit of account (
)
Required additional
refrigerant charge (g)
(a) : Liquid tubing Total length of ø7/8" (ft.) or (m) (d) : Liquid tubing Total length of ø1/2" (ft.) or (m)
(b) : Liquid tubing Total length of ø3/4" (ft.) or (m) (e) : Liquid tubing Total length of ø3/8" (ft.) or (m)
(c) : Liquid tubing Total length of ø5/8" (ft.) or (m) (f) : Liquid tubing Total length of ø1/4" (ft.) or (m)
l
Charging procedure
Be sure to charge with R410A refrigerant in liquid form.
1. After performing a vacuum, charge with refrigerant from the liquid tubing side.
At this time, all valves must be in the “fully closed” position.
2. If it was not possible to charge the designated amount, operate the system in Cooling mode while charging with refrigerant
from the gas tubing side. (This is performed at the time of the test run. For this, all valves must be in the “fully open” position.
However if only one outdoor unit is installed, a balance tube is not used. Therefore, leave the valves fully closed.)
Charge with R410A refrigerant in liquid form.
With R410A refrigerant, charge while adjusting the amount being fed a little at a time in order to prevent liquid refrigerant from
backing up.
l
After charging is completed, turn all valves to the “fully open” position.
l
Replace the tubing covers as they were before.
CAUTION
For type 72For type 96For type 120/144
Balance tube
Use a flathead screwdriver and
open by turning the part with the
screw groove to the right, from “–”
to “|”.
Necessary Amount of Additional Refrigerant Charge Per Outdoor Unit
+ Necessary amount of additional refrigerant charge for all indoor unit cooling capacity
1. R410A additional charging absolutely must be done through liquid charging.
2. The R410A refrigerant cylinder has a gray base color, and the top part is pink.
3. The R410A refrigerant cylinder includes a siphon tube. Check that the siphon tube is present.
(This is indicated on the label at the top of the cylinder.)
4. Due to differences in the refrigerant, pressure, and refrigerant oil involved in installation, it is
not possible in some cases to use the same tools for R22 and for R410A.
Balance tube
Use a flathead screwdriver and
open by turning the part with the
screw groove to the right, from “–”
to “|”.
Balance tube
Use a flathead screwdriver and
open by turning the part with the
screw groove to the right, from “–”
to “|”.
Liquid tube
Use a hex wrench
(width 5/32 inch (4mm))
and turn to the left to
open.
Gas tube
Use a flathead screwdriver and
open by turning the part with the
screw groove to the right, from “–”
to “|”.
Liquid tube
Use a hex wrench
(width 5/32 inch (4mm))
and turn to the left to
open.
Gas tube
Use a flathead screwdriver and
open by turning the part with the
screw groove to the right, from “–”
to “|”.
14
Liquid tube
Use a hex wrench
(width 5/32 inch (4mm))
and turn to the left to
open.
Gas tube
Use a flathead screwdriver and
open by turning the part with the
screw groove to the right, from “–”
to “|”.
Example:
Outdoor unit
Type 96 Type 72
B
l
Example of all outdoor units
cooling capacity
Type 72: 72,000BTU/h(21.1 kW)
Type 96: 96,000BTU/h(28.1 kW)
[Total]168,00 BTU/h(49.2 kW)
A
LB
LA
1 2 3 4
LC
l
Example of each tubing length
Main tubingDistribution joint tubing
LA = 131 ft. (40m)Outdoor sideIndoor side
LB = 16 ft. (4.9m)
LC = 16 ft. (4.9m)
A = 7 ft.
B = 7 ft.
(2.1m)
(2.1m)
1 = 98 ft.
2 = 16 ft.
3 = 16 ft.
4 = 65 ft.
l
Example of all indoor unit cooling capacity
(30m)
(4.9m)
(4.9m)
(19.8m)
[Type 48 x 3] 47,800 x 3 = 143,400 BTU/h(14.0 x 3 = 42.0 kW)
Type 48Type 48Type 48Type 36
[Type 36 x 1] 36,000 x 1 = 36,000 BTU/h(10.6 x 1 = 10.6 kW)
[Total]179,400 BTU/h(52.6 kW)
l
Obtain liquid tubing size from Tables 1-3, 4, 5, 7 and 10-1.
Main tubing
LA = ø5/8 (ft. (m)) (Total capacity of indoor unit is 179,400 BTU/h (52.6kW))
LB = ø1/2 (ft. (m)) (Total capacity of indoor unit is 131,600 BTU/h (38.6kW))
The longest tubing length in this example
(LA = 131 ft. (40m))
LC = ø3/8 (ft. (m)) (Total capacity of indoor unit is 83,800 BTU/h (24.6kW))
Distribution joint tubing
Outdoor side
Indoor side
l
Obtain additional charge amount for each tubing size and additional refrigerant charge amount for all indoor unit cooling capacity.
A – B +1 – 4 : 225 ft. × 0.602 oz/ft. = 135 oz(68.6m × 56 g/m = 3,842g)
Total 418 oz(Total 11,869g)
Additional refrigerant charge amount is 418 oz (11,869g).
Note 2: Necessary amount of additional refrigerant charge per outdoor unit is 141oz (4,000g) in combination of 2 units.
(See the Table 1-10-2.)
Note 2) Amount of additional charge for outdoor unit (combination number): 141oz(4,000g)
Note 3: Necessary amount of additional refrigerant charge for all indoor unit cooling capacity
[BTU/h][kW]
179,400 BTU/h
Cooling capacity (BTU/h) x 1.034 x 0.001 + 10.6 oz
= 179,400 x 1.034 x 0.001 + 10.6 = 196 oz
(52.6 kW)
(Cooling capacity (kW) x1000 x 0.1 + 300
= 52.6 x 1000 x 0.1 + 300 = 5,560 g)
g
Note 1) Amount of additional charge per tubing length: 418 oz(11,869g)
Note 2) Amount of additional charge for outdoor unit (combination number): 141 oz(4,000g)
Note 3) Amount of additional charge for all indoor unit cooling capacity196 oz(5,560g)
Total of additional refrigerant charge amount: 755 oz(21,429g)
Therefore, the total of additional refrigerant charge amount reaches 755 oz (21,429g).
l
Obtain overall refrigerant charge amount.
Overall refrigerant charge amount of the system indicates the calculated value shown above the additional charge amount in
addition to the total refrigerant charge amount (shown in the Table 1-6) at shipment in total cooling capacity of outdoor unit.
Refrigerant charge amount at shipment
(total cooling capacity of outdoor unit) :: [168,000BTU/h]684 oz[49.2kW] (19,400g)
Total of additional refrigerant charge amount
:
755 oz(21,429g)
Grand total1,439 oz(40,829g)
Therefore, overall refrigerant charge amount of the system reaches 1,439 oz (40,829g).
Remark:
Be sure to include the values in Table 1-10-2 Necessary Amount of Additional Refrigerant Charge Per Outdoor Unit.
CAUTION
Be sure to check the limit density for the room in which the indoor unit is installed.
15
2. SELECTING THE INSTALLATION SITE
2-1. Outdoor Unit
Example: 2 units installation
* For other installation, follow the standards of combination
installation.
AVOID:
l
heat sources, exhaust fans, etc.
l
damp, humid or uneven locations
l
indoors (no-ventilation location)
DO:
l
choose a place as cool as possible.
l
choose a place that is well ventilated.
l
allow enough room around the unit for air intake/exhaust
and possible maintenance.
l
use lug bolts or equal to bolt down unit, reducing vibration
and noise.
Exhaust fan
Hot air
Heat
Outdoor
unit
source
Fig. 2-1
Installation Space
Install the outdoor unit where there is enough space for
ventilation. Otherwise the unit may not operate properly.
Fig. 2-2 shows the minimum space requirement around
the outdoor units when 3 sides are open and only 1 side is
shuttered, with open space above the unit. The mounting
base should be concrete or a similar material that allows for
adequate drainage. Make provisions for anchor bolts, platform
height, and other site-specific installation requirements.
Wall height: Less than 1.7ft. (500mm)
Wall height:
Unlimited
* Over 2 in.
(50mm)
Over 2-3/8 in. (60mm)
Wall height: Less than 4.9 ft. (1500mm)
Over 1 ft.(300mm)
* Over 2 in. (50mm)
Over 1.7ft. (500mm)
Wall height: Unlimited
* When setting the anchor bolt to "B" or "C" (see page 19),
make enough space for installation operation.
(Space between units: Over 0.6 ft. (180mm), Space from
wall: Over 0.83 ft. (250mm))
* When installing a snow-proof ducting, make space between
the units 7-3/32” (180mm) regardless of the positions (A - C)
for installation holes.
* Make a walk-in space in front and behind the unit to ensure
ease of operation.
Fig. 2-2
l
Leave space open above the
CAUTION
unit.
l
Construct louvers or other
openings in the wall, if
necessary, to ensure adequate
ventilation.
NOTE
l
Do not do any wiring or tubing within 1 ft. (0.3m) of the front
panel, because this space is needed as a servicing space
for the compressor.
l
Ensure a base height of 4" (10cm) or more to ensure that
drainage water does not accumulate and freeze around the
bottom of the unit.
l
If installing a drain pan, install the drain pan prior to
installing the outdoor unit.
* Make sure there is at least 6" (15cm) between the outdoor
unit and the ground.
Also, the direction of the tubing and electrical wiring should
be from the front of the outdoor unit.
16
2-2. Shield for Horizontal Exhaust Discharge
It is necessary to install an air-discharge chamber (field
supply) to direct exhaust from the fan horizontally if it is
difficult to provide a minimum space of 7 ft. (2m) between the
air-discharge outlet and a nearby obstacle. (Fig. 2-3)
In regions with heavy snowfall,
CAUTION
the outdoor unit should be
provided with a solid, raised
platform and snow-proof
ducting (field supply). (Fig. 2-4)
2-3. Installing the Outdoor Unit in Heavy Snow
Areas
In locations where wind-blown snow can be a problem,
snow-proof ducting (field supply) should be fitted to the unit
and direct exposure to the wind should be avoided as much as
possible. (Fig. 2-5) The following problems may occur if proper
countermeasures are not taken:
l
The fan in the outdoor unit may stop running, causing the
unit to be damaged.
l
There may be no air flow.
l
The tubing may freeze and burst.
l
The condenser pressure may drop because of strong wind,
and the indoor unit may freeze.
Fig. 2-3
DO
2-4. Precautions When Installing in Heavy Snow
Areas
a) The platform should be higher than the maximum snow
depth. (Fig. 2-4)
b) The 2 anchoring feet of the outdoor unit should be used for
the platform, and the platform should be installed beneath
the air-intake side of the outdoor unit.
c) The platform foundation must be solid and the unit must
be secured with anchor bolts.
d) When installing on a roof subject to strong wind,
countermeasures must be taken to prevent the unit from
being overturned.
AVOID
Without snowproof ducting
(Without platform)
Fig. 2-4
Fallen snow
With snowproof ducting
(High platform)
17
Fig. 2-5
Loading...
+ 39 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.