Read through the Installation Instructions before you proceed with the installation.
In particular, you will need to read under the “IMPORTANT!” section at the top of the page.
Nominal Capacity
F616469
IMPORTANT!
Please Read Before Starting
This air conditioning system meets strict safety and
operating standards. As the installer or service person, it is
an important part of your job to install or service the
system so it operates safely and efficiently.
For safe installation and trouble-free operation, you
must:
● Carefully read this instruction booklet before beginning.
● Follow each installation or repair step exactly as shown.
● This air conditioner shall be installed in accordance with
National Wiring Regulations.
● Pay close attention to all warning and caution notices
given in this manual.
This symbol refers to a hazard or
WARNING
CAUTION
If Necessary, Get Help
These instructions are all you need for most installation
sites and maintenance conditions. If you require help for a
special problem, contact our sales/service outlet or your
certified dealer for additional instructions.
In Case of Improper Installation
The manufacturer shall in no way be responsible for
improper installation or maintenance service, including
failure to follow the instructions in this document.
SPECIAL PRECAUTIONS
WARNING
ELECTRICAL SHOCK CAN CAUSE
SEVERE PERSONAL INJURY OR DEATH.
ONLY A QUALIFIED, EXPERIENCED
ELECTRICIAN SHOULD ATTEMPT TO
WIRE THIS SYSTEM.
•Do not supply power to the unit until all wiring and tubing
are completed or reconnected and checked.
•Highly dangerous electrical voltages are used in this
system. Carefully refer to the wiring diagram and these
instructions when wiring. Improper connections and
inadequate grounding can cause accidental injury or death.
•Ground the unit following local electrical codes.
•Connect all wiring tightly. Loose wiring may cause over-
heating at connection points and a possible fire hazard.
•To prevent possible hazards from insulation failure,
the unit must be grounded.
•This equipment is strongly recommended to be installed
with Earth Leakage Circuit Breaker (ELCB) or Residual
Current Device (RCD). Otherwise, it may cause electrical
shock and fire in case of equipment breakdown or
insulation breakdown.
unsafe practice which can result
in severe personal injury or death.
This symbol refers to a hazard or
unsafe practice which can result
in personal injury or product or
property damage.
When Wiring
When Transporting
Be careful when picking up and moving the indoor and
outdoor units. Get a partner to help, and bend your knees
when lifting to reduce strain on your back. Sharp edges or
thin aluminum fins on the air conditioner can cut your
fingers.
When Installing…
Select an installation location which is rigid and strong
enough to support or hold the unit, and select a location for
easy maintenance.
…In a Room
Properly insulate any tubing run inside a room to prevent
“sweating” that can cause dripping and water damage to
walls and floors.
Keep the fire alarm and the air
CAUTION
…In Moist or Uneven Locations
Use a raised concrete pad or concrete blocks to provide a
solid, level foundation for the outdoor unit. This prevents
water damage and abnormal vibration.
…In an Area with High Winds
Securely anchor the outdoor unit down with bolts and a
metal frame. Provide a suitable air baffle.
…In a Snowy Area (for Heat Pump-type Systems)
Install the outdoor unit on a raised platform that is higher
than drifting snow. Provide snow vents.
outlet at least 5 feet (1.5 m) away
from the unit.
When Connecting Refrigerant Tubing
•Ventilate the room well, in the event that is refrigerant gas
leaks during the installation. Be careful not to allow
contact of the refrigerant gas with a flame as this will
cause the generation of poisonous gas.
•Keep all tubing runs as short as possible.
•Use the flare method for connecting tubing.
•Apply refrigerant lubricant to the matching surfaces of
the flare and union tubes before connecting them, then
tighten the nut with a torque wrench for a leak-free
connection.
•Check carefully for leaks before starting the test run.
WARNING
•When performing piping work do not mix air
except for specified refrigerant (R410A) in
refrigeration cycle. It causes capacity down, and
risk of explosion and injury due to high tension
inside the refrigerant cycle.
•Check for a leaking refrigerant!
Refrigerant gas may produce a toxic gas if it
comes in contact with fire.
•Do not add or replace refrigerant other than
specified type. It may cause product damage,
burst and injury etc.
2
•Do not leak refrigerant while piping work for an
installation or re-installation, and while repairing
refrigeration parts.
Handle liquid refrigerant carefully as it may cause
frostbite.
When Servicing
•Turn the power OFF at the main power box (mains)
before opening the unit to check or repair electrical
parts and wiring.
•Keep your fingers and clothing away from any moving
parts.
•Clean up the site after you finish, remembering to check
that no metal scraps or bits of wiring have been left inside
the unit being serviced.
CAUTION
•Do not touch the air inlet or the sharp
aluminum fins of the outdoor unit. You
may get injured.
•Ventilate any enclosed areas when installing or
testing the refrigeration system. Escaped
refrigerant gas, on contact with fire or heat, can
produce dangerously toxic gas.
•Confirm after installation that no refrigerant gas
is leaking. If the gas comes in contact with a
burning stove, gas water heater, electric room
heater or other heat source, it can cause the
generation of poisonous gas.
WARNING
•This product must not be modified or
disassembled under any circumstances.
Modified or disassembled unit may cause fire,
electric shock or injury.
•Do not clean inside the indoor and outdoor units
by users. Engage authorized dealer or specialist
for cleaning.
•In case of malfunction of this appliance, do not
repair by yourself. Contact to the sales dealer or
service dealer for a repair.
Check of Density Limit
The room in which the air conditioner is to be
installed requires a design that in the event of
refrigerant gas leaking out, its density will not exceed
a set limit.
The refrigerant (R410A), which is used in the air
conditioner, is safe, without the toxicity or combustibility of
ammonia, and is not restricted by laws imposed to protect
the ozone layer. However, since it contains more than air,
it poses the risk of suffocation if its density should rise
excessively. Suffocation from leakage of refrigerant is
almost non-existent. With the recent increase in the
number of high density buildings, however, the installation
of multi air conditioner systems is on the increase
because of the need for effective use of floor space,
individual control, energy conservation by curtailing heat
and carrying power, etc.
Most importantly, the multi air conditioner system is able
to replenish a large amount of refrigerant compared to
conventional individual air conditioners. If a single unit of
the multi air conditioner system is to be installed in a
small room, select a suitable model and installation
procedure so that if the refrigerant accidentally leaks out,
its density does not reach the limit (and in the event of an
emergency, measures can be made before injury can
occur).
Others
CAUTION
•Do not sit or step on the unit, you may fall
down accidentally.
•Do not touch the air inlet or the sharp
aluminum fins of the outdoor unit. You may
get injured.
•Do not stick any object into the FAN
CASE.
You may be injured and the unit may be
damaged.
ASHRAE and the International Mechanical Code of the
ICC as well as CSA provide guidance and define
safeguards related to the use of refrigerants, all of which
define a Refrigerant Concentration Level (RCL) of
25 pounds (11.3 kg) per 1,000 cubic feet (28.3 m3) for
R410A refrigerant.
For additional guidance and precautions related to
refrigerant safety, please refer to the following documents:
International Mechanical Code 2012 (IMC-2012)
(or more recently revised)
ASHRAE 15
ASHRAE 34
Refer to the Operating Instructions attached to the
optional Timer Remote Controller or optional Highspec Wired Remote Controller.
4
1. GENERAL
This booklet briefly outlines where and how to install the
air conditioning system. Please read over the entire set of
instructions for the indoor and outdoor units and make
sure all accessory parts listed are with the system before
beginning.
1-1. Tools Required for Installation (not supplied)
1. Flathead screwdriver
2. Phillips head screwdriver
3. Knife or wire stripper
4. Tape measure
5. Carpenter’s level
6. Sabre saw or keyhole saw
7. Hacksaw
8. Core bits
9. Hammer
10. Drill
11. Tube cutter
12. Tube flaring tool
13. Torque wrench
14. Adjustable wrench
15. Reamer (for deburring)
1-2. Accessories Supplied with Unit
Table 1-1 (Low Silhouette Ducted)
Part NameFigureQ’tyRemarks
Washer8
Flare
insulator
Insulating
tape
For suspending indoor
unit from ceiling
For gas and liquid
2
tubes
For gas and liquid
2
tubes flare nuts
1-3. Type of Copper Tube and Insulation Material
If you wish to purchase these materials separately from a
local source, you will need:
1. Deoxidized annealed copper tube for refrigerant
tubing.
2. Foamed polyethylene insulation for copper tubes as
required to precise length of tubing. Wall thickness of
the insulation should be not less than 5/16˝(8 mm).
3. Use insulated copper wire for field wiring. Wire size
varies with the total length of wiring. Refer to 4.
ELECTRICAL WIRING for details.
CAUTION
Check local electrical codes and regulations before
obtaining wire.
limitations.
Also, check any specified instructions or
1-4. Additional Materials Required for Installation
1. Refrigeration (armored) tape
2. Insulated staples or clamps for connecting wire (See
your local codes.)
3. Putty
4. Refrigeration tubing lubricant
5. Clamps or saddles to secure refrigerant tubing
6. Scale for weighing
Drain
insulator
Hose band
Packing
Packing
Drain hose
Operating
Instructions
Installation
Instructions
Warranty
card
Band
Short-circuit
connection
1For drain hose joint
1For securing drain hose
For drain hose joint
1
(hard material)
For drain hose joint
1
(soft material)
1
1
1
1
For inter-unit control
1
wiring
For high static pressure
(Located on the
1
back of the electrical
component box lid. )
● Use 3/8˝(M10) for suspension bolts.
● Suspension bolts and nuts are field supply.
5
2. SELECTING THE INSTALLATION SITE
2-1. Indoor Unit
AVOID:
● areas where leakage of flammable gas may be
expected.
● places where large amounts of oil mist exist.
● direct sunlight.
● locations near heat sources which may affect the
performance of the unit.
● locations where external air may enter the room
directly. This may cause “condensation” on the air
discharge ports, causing them to spray or drip water.
● locations where the remote controller will be splashed
with water or affected by dampness or humidity.
● installing the remote controller behind curtains or
furniture.
● locations where high-frequency emissions are
generated.
DO:
● select an appropriate position from which every corner
of the room can be uniformly cooled.
● select a location where the ceiling is strong enough to
support the weight of the unit.
● select a location where tubing and drain pipe have the
shortest run to the outdoor unit.
● allow room for operation and maintenance as well as
unrestricted air flow around the unit.
● install the unit within the maximum elevation difference
above or below the outdoor unit and within a total
tubing length (L) from the outdoor unit as detailed in
the installation manual packed with the outdoor unit.
● allow room for mounting the remote controller about
3.3 ft. (1 m) off the floor, in an area that is not in direct
sunlight or in the flow of cool air from the indoor unit.
● If the indoor unit is installed on the ceiling where the
temperature or humidity inside is high (over
86°F(30°C)/RH: 70%), add insulating material to the
surface of the unit to avoid dew condensation.
9-27/32”
(250 mm)
25-19/32”
(650 mm)
Fig. 2-1
6
3. HOW TO INSTALL THE INDOOR UNIT
■Low Silhouette Ducted Type (F2 Type)
Unit: inch (mm)
3-1. Required Minimum Space for Installation and
Service
● The minimum space for installation and service is
shown in Fig. 3-1 and Table 3-1.
● Space between the unit and the ceiling should be more
than 3/4”(19.05 mm). (Fig. 3-1)
Table 3-1 Unit: inch (mm)
Type7, 9, 12, 15, 182436, 48, 54
A (Length) 34-9/64 (867)42-1/64 (1,067) 57-3/4 (1,467)
● It is recommended that space be provided
(23-5/8” × 23-5/8”) (600 × 600 mm) for checking and
servicing the electrical system.
● The detailed dimensions of the indoor unit is shown in
Fig. 3-2 and Table 3-2.
Table 3-2
TypeABCDEF
7, 9, 12, 15, 18
24
36, 48, 54
inch 34-9/6431-1/217-23/32 (Pitch 5-29/32 × 3)2-51/6423-5/16
mm867800450 (Pitch 150 × 3)71592
inch 42-1/6439-3/829-17/32 (Pitch 5-29/32 × 5)53/6431-3/16
It is important that you use extreme care in
supporting the indoor unit inside the ceiling. Ensure
that the ceiling is strong enough to support the
weight of the unit. Before hanging the unit, test the
strength of each attached suspension bolt.
(1) When placing the unit inside the ceiling, determine
the pitch of the suspension bolts referring to the
dimensional data as shown in Fig. 3-1 and Table 3-2.
Tubing must be laid and connected inside the ceiling
when suspending the unit. If the ceiling is already
constructed, lay the tubing into position for connection
to the unit before placing the unit inside the ceiling.
(2) Screw in the suspension bolts allowing them to
protrude from the ceiling (Fig. 3-3). (Cut the ceiling
material, if necessary.)
(3) Thread the 3 hexagonal nuts and 2 washers (field
supply) onto each of the 4 suspension bolts (Figs. 3-5
and 3-6). Use 1 nut and 1 washer for the upper part,
and 2 nuts and 1 washer for the lower part, so that
the unit will not fall off the suspension lugs.
Suspension bolt
Hexagonal nut
Double nuts
Fig. 3-6
● This shows an example of installation.
Air outlet duct
Air outlet grille
Suspension
bolt
Indoor unit
Bolt anchor
Air intake duct
Air intake grille
Ceiling material
Fig. 3-7
3-3. Installing the Drain Pipe
(1) Prepare standard hard PVC pipe (O.D. 1-17/64" (O.D.
32 mm)) for the drain and use the supplied hose band
to prevent water leaks.
The PVC pipe must be purchased separately.
The transparent drain part on the unit allows you to
check drainage. (Fig. 3-8)
CAUTION
● Do not use adhesive tape at the drain connection
port on the indoor unit.
● Insert the drain pipe until it contacts the socket,
and then secure it tightly with the hose band.
● Do not use the supplied drain hose bent at a 90°
angle. (The maximum permissible bend is 45°.)
8
● Tighten the hose clamps so their locking nuts face
upward. (Fig. 3-8)
Align the wire of hose band without separating from the drain
hose and tighten so that it does not contact the bead.
Drainage check
section on drain port
(transparent)
Drain hose
(supplied)
Bead
Hard PVC
socket
VP-25
(not supplied)
Packing
(supplied)
Hard PVC pipe
VP-25
(not supplied)
PVC
adhesive
Fig. 3-8
(2) After connecting the drain pipe securely, wrap the
supplied packing and drain pipe insulator around the
pipe, then secure it with the vinyl clamps. (Fig. 3-9)
Drain insulator (supplied)
● Do not install the pipe with an upward slant from the
connection port. This will cause the drain water to flow
backward and leak when the unit is not operating.
(Fig. 3-12)
Upward slant
Prohibited
Fig. 3-12
● Do not apply force to the piping on the unit side when
connecting the drain pipe. The pipe should not be
allowed to hang unsupported from its connection to the
unit. Fasten the pipe to a wall, frame, or other support
as close to the unit as possible. (Fig. 3-13)
Support pieces
Fig. 3-13
Vinyl clamps
Fig. 3-9
N OT E
(field supply)
Make sure the drain pipe has a downward slant (1/100 or
more) and that there are no water traps.
CAUTION
● Do not install an air bleeder as this may cause
water to spray from the drain pipe outlet. (Fig. 3-10)
Air bleeder
Prohibited
Fig. 3-10
● If it is necessary to increase the height of the drain
pipe, the section directly after the connection port
can be raised a maximum of 1.64 ft. (500 mm). Do
not raise it any higher than 1.64 ft. (500 mm), as
this could result in water leaks. (Fig. 3-11)
Good
11-13/16" (300 mm) or less
19-11/16" (500 mm) or less
Fig. 3-11
9
Loading...
+ 19 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.