PRINTED IN MALAYSIA
F615165
ENGLISH
Is there any gas leakage at fl are nut
connections?
Has the heat insulation been carried out at fl are
nut connection?
Is the connecting cable being fi xed to terminal
board fi rmly?
Is the connecting cable being clamped fi rmly?
Is the drainage ok?
(Refer to “Check the drainage” section)
Is the earth wire connection properly done?
CHECK ITEMS
Is the indoor unit properly hooked to the
installation plate?
Is the power supply voltage complied with rated
value?
Is there any abnormal sound?
Is the cooling operation normal?
Is the thermostat operation normal?
Is the remote control’s LCD operation normal?
Is the Air purifying fi lter installed?
1. To cut
When properly fl ared, the internal surface of the
fl are will evenly shine and be of even thickness.
Since the fl are part comes into contact with the
connections, carefully check the fl are fi nish.
Improper fl aring
Inclined
Surface
damaged
Cracked Uneven
thickness
3. To fl are
Bar
Red arrow mark
Handle
Core
Yok e
Clamp handle
Bar
0 –
1
/32"
Copper
pipe
Reamer
2. To remove burrs
Point down
Pipe
F615165
•
Read the following “SAFETY PRECAUTIONS” carefully before installation.
•
Electrical work must be installed by a licensed electrician. Be sure to use the correct rating of the power plug and main circuit for the model to be installed.
•
The caution items stated here must be followed because these important contents are related to safety. The meaning of each indication used is as below.
Incorrect installation due to ignoring of the instruction will cause harm or damage, and the seriousness is classifi ed by the following indications.
The items to be followed are classifi ed by the symbols:
•
Carry out test running to confi rm that no abnormality occurs after the installation. Then, explain to user the operation, care and maintenance as stated in
instructions. Please remind the customer to keep the operating instructions for future reference.
Required tools for Installation Works
INDOOR UNIT
1
2
HOW TO FIX INSTALLATION PLATE
The mounting wall shall be strong and solid enough to prevent it from the vibration.
SELECT THE BEST LOCATION
(Refer to “Select the best location” section)
The center of installation plate should be at more than 1 at right and left of the wall.
The distance from installation plate edge to ceiling should more than 2.
From installation plate left edge to unit’s left side is 3.
From installation plate right edge to unit’s right is 4.
b : For left side piping, piping connection for liquid should be about 5 from this line.
: For left side piping, piping connection for gas should be about 6 from this line.
1. Mount the installation plate on the wall with 5 screws or more (at least 5 screws).
(If mounting the unit on the concrete wall, consider using anchor bolts.)
Always mount the installation plate horizontally by aligning the marking-off line with the thread and
using a level gauge.
2. Drill the piping plate hole with ø2
3
/4" hole-core drill.
Line according to the left and right side of the installation plate. The meeting point of the extended line is
the center of the hole. Another method is by putting measuring tape at position as shown in the diagram
above. The hole center is obtained by measuring the distance namely 5
1
/16" for left and right hole
respectively.
Drill the piping hole at either the right or the left and the hole should be slightly slanting to the outdoor
side.
INDOOR UNIT INSTALLATION
4
OUTDOOR UNIT
1
SELECT THE BEST LOCATION
(Refer to “Select the best location” section)
After selecting the best location, star t installation to Indoor/Outdoor Unit Installation Diagram.
1. Fix the unit on concrete or rigid frame fi rmly and horizontally by bolt nut (ø
13
/32").
2. When installing at roof, please consider strong wind and earthquake.
Please fasten the installation stand fi rmly with bolt or nails.
2
INSTALL THE OUTDOOR UNIT
CUTTING AND FLARING THE PIPING
1. Please cut using pipe cutter and then remove the burrs.
2. Remove the burrs by using reamer. If burrs is not removed, gas leakage may be caused.
Turn the piping end down to avoid the metal powder entering the pipe.
3. Please make fl are after inserting the fl are nut onto the copper pipes.
TO DRILL A HOLE IN THE WALL AND
INSTALL A SLEEVE OF PIPING
1. Insert the piping sleeve to the hole.
2. Fix the bushing to the sleeve.
3. Cut the sleeve until it extrudes about
19
/32" from the wall.
4. Finish by sealing the sleeve with putty
or caulking compound at the fi nal stage.
CONNECT THE CABLE TO THE INDOOR
UNIT
5
1. The inside and outside connecting cable can be connected without
removing the front grille.
2. Unscrew the conduit cover and fi x the conduit connector to conduit
cover with lock nut, then secure it against chassis.
3. Connecting wire between indoor unit and outdoor unit should be
UL listed or CSA approved 4 conductor wires minimum AWG16
in accordance with local electric codes.
Ensure the colour of wires of outdoor unit and terminal number
are the same as the indoor's repectively.
This equipment must be properly earthed.
Earth lead wire shall be Yellow/Green (Y/G) in colour and
shall be longer than other lead wires as shown in the
fi gure for electrical safety in case of the slipping.
3
Terminals on the indoor unit 1 2 3
Colour of wires (connecting wire)
Terminals on the outdoor unit 1 2 3
HOW TO TAKE OUT FRONT GRILLE
Please follow the steps below to take out front grille if necessary such as when
servicing.
1. Set the vertical airfl ow direction louvers to the horizontal position.
2. Slide down the 2 caps on the front grille as shown in the illustration at right,
and then remove the 2 mounting screws.
3. Pull the lower section of the front grille towards you to remove the front grille.
AUTO SWITCH OPERATION
The below operations will be performed by pressing the “AUTO” switch.
1. AUTO OPERATION MODE
The Auto operation will be activated immediately once the Auto Switch is pressed
and release before 5 sec..
2. TEST RUN OPERATION (FOR PUMP DOWN/SERVICING PURPOSE)
The Test Run operation will be activated if the Auto Switch is pressed continuously
for more than 5 sec. A “pep” sound will occur at the fi fth sec., in order to identify
the starting of Test Run operation.
3. REMOTE CONTROLLER RECEIVING SOUND ON/OFF
The ON/OFF of Remote controller receiving sound can be change over by the following steps:
a) Press AUTO switch continuously until “pep pep pep pep” sound is heard (about 16 sec.).
b) Release the Auto switch button.
c) Press the remote controller “AC RESET” button once, “pep” sound will occur.
d) Press Auto switch again. Everytime Auto switch is pressed (within 60 sec. interval), remote
controller receiving sound status will be reversed between ON and OFF.
Long “peep” sound indicates that remote controller receiving sound is ON.
Short “pep” sound indicates that remote controller receiving sound is OFF.
1 Philips screw driver
2 Level gauge
3 Electric drill, hole core drill (ø2
3
/4")
4 Hexagonal wrench (
5
/32")
5 Spanner
6 Pipe cutter
7 Reamer
8 Knife
9 Gas leak detector
10 Measuring tape
11 Thermometer
12 Megameter
13 Multimeter
14 Torque wrench
13.3 Ibf.ft
31.0 Ibf.ft
40.6 Ibf.ft
47.9 Ibf.ft
73.8 Ibf.ft
15 Vacuum pump
16 Gauge manifold
Cover for
the bottom
piping
Tape it with piping in a
position as mentioned
in Fig. below.
Cover for
the right
piping
Piping
Drain hose
Cover for
the left
piping
Right and Right Bottom piping
6
1. Please carry out insulation at pipe connection portion as mentioned in Indoor/Outdoor Unit Installation
Diagram. Please wrap the insulated piping end to prevent water from going inside the piping.
2. If drain hose or connecting piping is in the room (where dew may form), please increase the insulation by
using POLY-E FOAM with thickness 1/4" or above.
PIPING INSULATION
Pressure test to system to 400 PSIG with dry nitrogen, in stages. Thoroughly leak check the system.
If the pressure holds, release the nitrogen and proceed to section 4.
Gas Leak Checking
1. Connect a charging hose with a push pin to the Low side of a charging set and the service port of the
3-way valve.
2. Connect the micron gauge between vacuum pump and service port of outdoor units.
3. Turn on the power switch of the vacuum pump and make sure that connect digital micron gauge
and to pull down to a value of 500 microns.
4. To make sure micron gauge a value 500 microns and close the low side valve of the charging set and
turn off the vacuum pump.
5. Disconnect the vacuum pump house from the service port of the 3-way valve.
6. Tighten the service port caps of the 3-way valve at a torque of 13.3 Ibf.ft with a torque wrench.
7. Remove the valve caps of both of the 2-way valve and 3-way valve. Position both of the valves to “Open”
using a hexagonal wrench (5/32").
8. Mount valve caps onto the 2-way valve and the 3-way valve.
•
Be sure to check for gas leakage.
Install the indoor unit
Hook the indoor unit onto the
upper portion of installation
plate. (Engage the indoor
unit with the upper edge of
the installation plate). Ensure
the hooks are properly seated
on the installation plate by
moving it in left and right.
Drain hose
Sleeve for
piping hole
Indoor unit
Hooks at
installation
plate
Piping
WHEN INSTALLING AN AIR CONDITIONER, BE SURE TO EVACUATE THE AIR INSIDE THE INDOOR
UNIT AND PIPES in the following procedure.
4
EVACUATION OF THE EQUIPMENT
3
CONNECT THE PIPING
Please make fl are after inserting fl are nut (locate at
joint portion of tube assembly) onto the copper pipe.
(In case of using long piping)
Connect the piping
•
Align the center of piping and suffi ciently tighten the
fl are nut with fi ngers.
•
Further tighten the fl are nut with torque wrench in
specifi ed torque as stated in the table.
Decide piping length and then cut by using pipe cutter.
Remove burrs from cut edge.
Make fl are after inserting the fl are nut (locate at valve) onto
the copper pipe.
Align center of piping to valve and then tighten with torque
wrench to the specifi ed torque as stated in the table.
CONNECT THE CABLE TO THE
OUTDOOR UNIT
5
1. Remove Top panel.
2. Remove Control Board Cover (Resin and Metal).
3. Remove Plugs.
4. Fix the conduit connectors to the knockout holes with
lock-nuts, then secure them against the side panel.
5. All wires pass through conduits.
6. Connecting wire between indoor unit and outdoor unit
should be UL listed or CSA approved 4 conductor
wires minimum AWG16 in accordance with local
electric codes.
7. Wire connection to the power supply (208/230V 60Hz)
through circuit breaker.
•
Connect the UL listed or CSA approved wires
minimum AWG14 to the terminal board, and
connect the other end of the wires to ELCB / GFCI.
8. Connect the power supply cord and connecting wire
between indoor unit and outdoor unit according to the
diagram below.
9. Secure the wire onto the control board with the
holder (clamper).
10. After completing wiring connections, reattach
the control board cover (Metal and Resin) and
the top panel to the original position with the
screws.
11. For wire stripping and connection requirement,
refer to instruction 5 of indoor unit.
This equipment must be properly earthed.
•
Earth lead wire shall be Yellow/Green (Y/G) in
colour and shall be longer than other lead wires
as shown in the fi gure for electrical safety in
case of the slipping.
Air purifying fi lter 7
Air fi lter
1
3
2
Example: For S9NKUW-1
If the unit is installed at 32.8 ft distance, the quantity of additional refrigerant
should be 1.64 oz .... (32.8 - 24.6) ft x 0.2 oz/ft = 1.64 oz.
Attached accessories
Rear Side of Indoor Unit
Decide piping length and then cut by using pipe cutter. Remove burrs from cut edge.
Make fl are after inserting the fl are nut (locate at valve) onto the copper pipe.
Align center of piping to valve and then tighten with torque wrench to the specifi ed torque as stated in the
table.
Holder
Power
supply
cord
Indoor &
outdoor
cable
connection
Terminal
Board
Earth wire
longer than
others
AC wires
for safety
reason
Earth wire
longer than
others
AC wires
for safety
reason
Control Board
Metal Cover
Top Panel
Power
Supply
Wires
Lock Nuts
Knockout
Holes
Plugs
Side Panel
Connectors
Control Board
Cover (Resin)
Terminals on the indoor unit
Colour of wires (connecting cable)
Terminals on the outdoor unit
(power supply cord)
1 2 3
L1 L2 1 2 3
POWER SUPPLY
Hall Union
Flare Nut
Pipe Size
Reducer
Packing
Torque Wrench for Flare
Nut and Pipe Size Reducer
Wrench
(Adjustable Wrench)
Applicable to
Gas side of
CS-S12NKUW-1
(Connection pipe)
(Auxiliary pipe)
Female side
Male side
Hall Union
Flare Nut
(Auxiliary pipe)
(Connection pipe)
Applicable to
Liquid and Gas side of
CS-S9NKUW-1
Liquid side of
CS-S12NKUW-1
Torque Wrench
for Flare Nut
Wrench
(Adjustable Wrench)
Male side Female side
• Pipe size reducer (CZ-MAIP) for outdoor Multi connection CS-S12NKUW-1
SAFETY PRECAUTIONS
WARNING
This indication shows the possibility of causing death or serious injury.
CAUTION
This indication shows the possibility of causing injury or damage to properties only.
Symbol with white background denotes item that is PROHIBITED.
Symbol with dark background denotes item that must be carried out.
No. Accessories par t Qty. No. Accessories par t Qty.
1
Installation plate
1
5
Remote control
holder
1
2
Installation plate fi xing
screw
5
6
Remote control
holder fi xing screw
2
3
Remote Control
1
7
Air purifying fi lter
1
4
Battery
2
Piping direction Attention not to bend
up drain hose
(Front side)
Right
Rear
Right bottom
Left
Rear
Left bottom
Left
Indoor/Outdoor Unit Installation Diagram
Applicable piping kit
Piping size
Gas Liquid
CZ-3F5, 7BP
3/8" (9.52 mm) 1/4" (6.35 mm)
CZ-4F5, 7, 10BP
1/2" (12.7 mm) 1/4" (6.35 mm)
CZ-52F5, 7, 10BP 5/8" (15.88 mm)
1/4" (6.35 mm)
Do not install the unit in excessive oil fume areas such as kitchen,
workshop and etc.
There should not be any heat source or steam near the unit.
There should not be any obstacles blocking the air circulation.
A place where air circulation in the room is good.
A place where drainage can be easily done.
A place where noise prevention is taken into consideration.
Do not install the unit near a door way.
Ensure the spaces indicated by arrows from the wall, ceiling, fence or
other obstacles.
Recommended installation height for indoor unit shall be at least 8.2 ft.
If an awning is built over the unit to prevent direct sunlight or rain,
be careful that heat radiation from the condenser is not obstructed.
There should not be any animal or plant which could be affected by
hot air discharged.
Keep the spaces indicated by arrows from wall, ceiling, fence or
other obstacles.
Do not place any obstacles which may cause a short circuit of the
discharged air.
If piping length is over the [piping length for additional gas], additional
refrigerant should be added as shown in the table.
INDOOR UNIT
OUTDOOR UNIT
SELECT THE BEST LOCATION
Model
Capacity
(Btu/h)
Piping size
Std.
Length
(ft)
Max.
Eleva-
tion
(ft)
Min.
Piping
Length
(ft)
Max.
Piping
Length
(ft)
Additional
Refrige-
rant (oz/ft)
Piping
Length
for add.
gas (ft)
Gas Liquid
S9NKUW-1
8500 3/8"
1/4"
24.6
16.4 9.8 49.2 0.2 24.6
S12NKUW-1
11900 1/2" 16.4 9.8 49.2 0.2 24.6
1
31
/32"
or more
2
9
/
16
"
or more
(Left and right are identical)
• Carry out insulation after
checking for gas leaks and
secure with vinyl tape.
Vinyl tape
• This illustration is for
explanation purposes only.
The indoor unit will actually face
a different way.
3
15
/
16
"
or more
39
3
/
8
"
or more
3
15
/
16
"
or more
11
13
/
16
"
or more
It is advisable to
avoid more than 2
blockage directions.
For better ventilation
& multiple-outdoor
installation, please
consult authorized
dealer/specialist.
Installation plate 1
Sleeve (
)
Bushing-Sleeve (
)
Bend the pipe as
closely on the wall as
possible, but be careful
that it doesn’t break.
Saddle (
)
Conduit
(Power supply cord (
))
Control Board cover
Remote control holder fi xing screws
6
Remote control holder
5
Remote
control
3
Additional drain hose
Gas side piping (
)
Conduit
(Connecting cable)
Putty (
)
(Gum Type Sealer)
Installation parts you
should purchase ()
Vinyl tape (wide) ()
• Apply after carrying
out a drainage test.
• To carry out the
drainage test,
remove the air fi lters
and pour water into
the heat exchanger.
Liquid side piping (
)
Insulation of piping connections
Attaching the remote control holder to the wall
(This can be used for left rear piping and bottom piping also.)
Rear view for left piping installation
Drain cap
Drain hose
Replace the drain hose
Adjust the piping slightly
downwards.
Drain hose
Connecting cable
Sleeve for piping hole
Drain hose
Piping
Connecting
cable
More than 45
9
/32"
•
How to pull the piping and drain hose out, in case of
the embedded piping
.
PVC tube
for drain
hose
Indoor unit
2
27
/32"
Piping
Cable
Apply putty or
caulking material
to seal the wall
opening.
Connecting cable
Piping
More than
18
1
/
2
"
More than
45
9
/
32
"
PVC tube (VP-65) for piping
and connecting cable
PVC tube for drain hose (VP-30)
PVC tube for
drain hose (VP-20)
More than 27
9
/16"
Drain hose
from main unit
•
In case of left piping how to insert
the connecting cable and drain hose.
Cable
45°
Drain
hose
Piping
(For the right piping, follow the same
procedure)
Model A B C D
S9NKU-1, S12NKU-1
22 7/16" 4 1/8" 23/32" 12 19/32"
AB
C
D
Connecting The Piping to Indoor
Do not overtighten, over tightening may cause gas leakage.
Piping size Torque
1/4" 13.3 Ibf.ft
3/8" 31.0 Ibf.ft
1/2" 40.6 Ibf.ft
5/8" 47.9 Ibf.ft
3/4" 73.8 Ibf.ft
Connecting The Piping to Outdoor
Torque
wrench
Spanner
or Wrench
Connecting The Piping to Outdoor Multi
Gas side
Liquid side
Outdoor unit
Three-way valve
Indoor unit
Vacuum
pump
Close
Close
CAUTION
•
If micron gauge value does not descend 500 microns, take the following measures:
- If the leak stops when the piping connections are tightened fur ther, continue working from step 3.
- If the leak does not stop when the connections are retightened, repair location of leak.
- Do not release refrigerant during piping work for installation and reinstallation.
- Be careful with the liquid refrigerant, it may cause frostbite.
1. Open the front panel.
2. Remove the air fi lters.
3. Put the air purifying fi lter into place as shown in illustration at right.
INSTALLATION OF AIR
PURIFYING FILTER
•
Open front panel and remove air fi lters.
(Drainage checking can be carried out without removing the
front grille.)
•
Pour a glass of water into the drain tray-styrofoam.
•
Ensure that water fl ows out from drain hose of the indoor unit.
Drain
traystyrofoam
CHECK THE DRAINAGE
•
Operate the unit at cooling operation mode for fi fteen
minutes or more.
•
Measure the temperature of the intake and discharge air.
•
Ensure the difference between the intake temperature and
the discharge is more than 46.4°F.
Discharge air
EVALUATION OF THE PERFORMANCE
Cap
Screw
(Move the vane
to upward)
Vane
When reinstalling the front grille, fi rst set
the vertical airfl ow direction louver to the
horizontal position and then carry out
above steps 2 - 3 in the reverse order.
Cap
Vane
Front grille
WARNING
Do not install outdoor unit near handrail of veranda. When installing air-conditioner unit on veranda of a high rise building, child may climb up to outdoor unit and
cross over the handrail causing an accident.
Do not use unspecifi ed cord, modifi ed cord, joint cord or extension cord for power supply cord. Do not share the single outlet with other electrical appliances. Poor
contact, poor insulation or over current will cause electrical shock or fi re.
Do not tie up the power supply cord into a bundle by band. Abnormal temperature rise on power supply cord may happen.
Do not insert your fi ngers or other objects into the unit, high speed rotating fan may cause injury.
Do not sit or step on the unit, you may fall down accidentally.
Keep plastic bag (packaging material) away from small children, it may cling to nose and mouth and prevent breathing.
When installing or relocating air conditioner, do not let any substance other than the specifi ed refrigerant, eg. air etc. mix into refrigeration cycle (piping).
Mixing of air etc will cause abnormal high pressure in refrigeration cycle and result in explosion, injury etc.
Do not add or replace refrigerant other than specifi ed type. It may cause product damage, burst and injury etc.
●
For R410A model, use piping, fl are nut and tools which is specifi ed for R410A refrigerant. Using of existing (R22) piping, fl are nut and tools may cause abnormally
high pressure in the refrigerant cycle (piping), and possibly result in explosion and injury.
●
Thickness or copper pipes used with R410A must be more than 1/32". Never use copper pipes thinner than 1/32".
●
It is desirable that the amount of residual oil is less than 0.0008 oz/ft..
Engage authorized dealer or specialist for installation. If installation done by the user is incorrect, it will cause water leakage, electrical shock or fi re.
Install according to this installation instructions strictly. If installation is defective, it will cause water leakage, electrical shock or fi re.
Use the attached accessories parts and specifi ed parts for installation. Otherwise, it will cause the set to fall, water leakage, fi re or electrical shock.
Install at a strong and fi rm location which is able to withstand the set’s weight. If the strength is not enough or installation is not properly done, the set will drop
and cause injury.
For installation work, follow all electrical, building, plumbing, local codes, regulations and these installation instructions. If electrical circuit capacity is not enough or a
defect is found in electrical work, it will cause electrical shock or fi re.
Do not use spliced wires for indoor / outdoor connection cable. Use the specifi ed indoor / outdoor connection cable, refer to instruction 5 INDOOR/OUTDOOR
UNIT ELECTRICAL WIRING and connect tightly for indoor/outdoor connection. Clamp the cable so that no external force will have impact on the terminal. If connection
or fi xing is not perfect, it will cause heat-up or fi re at the connection.
Wire routing must be properly arranged so that control board cover is fi xed properly. If control board cover is not fi xed perfectly, it will cause fi re or electrical shock.
This equipment must installed with an Earth Leakage Circuit Breaker (ELCB) or Ground Fault Current Interrupter (GFCI) or Appliance Leakage Current Interrupter
(ALCI) that has been certifi ed by an NRTL Certifi ed Testing Agency and that is suitable for the voltages and amperages involved. Otherwise, if may
cause electrical shock and fi re in case of equipment breakdown.
During installation, install the refrigerant piping properly before running the compressor. Operation of compressor without fi xing refrigeration piping and valves at opened
condition will cause suck-in of air, abnormal high pressure in refrigeration cycle and result in explosion, injury etc.
During pump down operation, stop the compressor before removing the refrigeration piping. Removal of refrigeration piping while compressor is operating and valves
are opened will cause suck-in of air, abnormal high pressure in refrigeration cycle and result in explosion, injury etc.
Tighten the fl are nut with torque wrench according to specifi ed method. If the fl are nut is over-tightened, after a long period, the fl are may break and cause refrigerant
gas leakage.
After completion of installation, confi rm there is no leakage of refrigerant gas. It may generate toxic gas when the refrigerant comes into contact with fi re.
Ventilate if there is refrigerant gas leakage during operation. It may cause toxic gas when the refrigerant comes into contact with fi re.
This equipment must be properly earthed. Earth line must not be connected to gas pipe, water pipe, earth of lightning rod and telephone. Otherwise, it may
cause electrical shock in case of equipment breakdown or insulation breakdown.
CAUTION
Do not install the unit at place where leakage of fl ammable gas may occur. In case gas leaks and accumulates at surrounding of the unit, it may cause fi re.
Do not release refrigerant during piping work for installation, re-installation and during repairing a refrigeration parts. Take care of the liquid refrigerant, it may
cause frostbite.
Do not install this appliance in a laundry room or other location where water may drip from the ceiling, etc.
Do not touch the sharp aluminium fi n, sharp parts may cause injury.
Carry out drainage piping as mentioned in installation instructions. If drainage is not perfect, water may enter the room and damage the furniture.
Select an installation location which is easy for maintenance.
Power supply connection to the room air conditioner.
Power supply cord shall be UL listed or CSA approved 3 conductor with minimum AWG14 wires.
Power supply point should be in an easily accessible place for power disconnection in case of emergency.
In some countries, permanent connection of this air conditioner to the power supply is prohibited.
Fix power supply connection to a circuit breaker for the permanent connection.
Use NRTL approved fuse or circuit breaker (rating refers to name plate) for the permanent connection.
Installation work.
It may take two people to carry out the installation work.
•
IMPORTANT (only for S9NKUW-1)
This product has been designed and manufactured to meet ENERGY STAR® criteria for energy effi ciency when matched with appropriate coil components. However,
proper refrigerant charge and proper air fl ow are critical to achive rated capacity and effi ciency. Installation of this product should follow the manufacturer’s
refrigerant charging and air fl ow instructions. Failure to confi rm proper charge and airfl ow may reduce energy effi ciency and shorten equipment life.
Two-way valve