MVA Series units are direct drive vertical and
multi-position Air Handlers delivering nominal cooling capacities of 1.5 to 5 tons.Units
may be specified with hot water or electric heating coils to meet space cooling loads or heating
loads or both. Two styles of unit orientation are
available for maximum flexibility.
How to Use this Manual:
This manual gives instructions regarding installation, operation and maintenance for the
MVA Series air handling units.
Use these instructions in conjunction with
other appropriate instructions, including but
not limited to those instructions supplied with
the outdoor unit. Installation must comply
with all applicable local codes.
SAFETY WARNING:
Installer should pay particular attention to
the following words:
NOTE–intended to clarify or make installation easier.
CAUTION–given to prevent equipment
damage.
WARNING–to alert installer that personal
injury and/or equipment damage may
result if installation procedure is not
properly followed.
GENERAL
Installation and maintenance are to be performed only by qualified personnel who are familiar with local codes and regulations and are
experienced with HVAC equipment of this type.
WARNING: Sharp edges, coil surfaces
and rotating fans are a potential injury
hazard – avoid contact.
WARNING: Hazardous voltage – Disconnect and Lock Out all incoming power
sources before servicing or installing unit.
ELECTRIC SHOCK CAN CAUSE DEATH.
WARNING: This equipment may be installed well above finished floor—Use extreme caution when working at heights.
UNPACKING-CHECK FOR DAMAGE!
Immediately inspect each unit for damage upon receipt.
Inspect units for external and concealed
damage immediately.
File any damage claims in accordance
with the Freight Damage Policy and
Terms and Conditions.
Do not repair damaged units without
written authorization.
Protect stored units from damage.
035-000039-001Page 1 of 32MVA IOM 1.3 9-10-2014
Page 2
THIS PAGE INTENTIONALLY LEFT BLANK
035-000039-001Page 2 of 32MVA IOM 1.3 9-10-2014
Page 3
MVA Series Air Handling Unit
Installation, Operation and Maintenance
Manual
/ŶƐƚĂůůĂƟŽŶ ^ƚĂƌƚ-Up
and Service
/ŶƐƚƌƵĐƟŽŶƐ
TopicPage
SAFETYCONSIDERATIONS
PRODUCT NOMENCLATURE
UNPACKING
INSTALLATION
Pre-installation
Rigging
Unpackaging
Service Clearances
Return Air & Unit Orientation
Vertical to Horizontal Conversion (EEV)
Unit Suspension or Floor Mount
Condensate Drain
Ductwork
Refrigerant Piping
Electric Heater Accessory
Electrical
START-UP
Fan Airflow Step-Up
Airflow Data
SERVICE
Fan & Fan Motor
Filters
Access Panels
Coil & Drain Pan Service
ELECTRICAL RATINGS
DIMENSIONS
Startup Report
1, 5
6-7
8
8
8
8
8
8,11
9
10
8,12,13
12
12
14
14-15
16-21
22-23
23-24
23-24
25-28
25-26
27
27
28
29
30
31
035-000039-001Page 3 of 32MVA IOM 1.3 9-10-2014
Page 4
THIS PAGE INTENTIONALLY LEFT BLANK
035-000039-001Page 4 of 32MVA IOM 1.3 9-10-2014
Page 5
DANGER
NEVER enter an enclosed fan cabinet or reach into
a unit while the fan is running.
LOCK OPEN AND TAG the fan motor power disconnect switch before working on a fan. Take fuses
with you and note removal on tag. Electric shock
can cause personal injury or death.
LOCK OPEN AND TAG the electric heat coil power
disconnect switch before working on or near heaters.
Failure to follow these warnings could lead to personal injury or death.
WARNING
CHECK the assembly and component weights to
be sure that the rigging equipment can handle
them safely.
Note also, the centers of gravity and any specific
rigging instructions.
CHECK for adequate ventilation so that fumes will
not migrate through ductwork to occupied spaces
when welding or cutting inside air-handling unit
cabinet or plenum.
WHEN STEAM CLEANING COILS be sure that
the area is clear of personnel.
DO NOT attempt to handle access covers and removable panels on outdoor units when winds are
strong or gusting until you have sufficient help to
control them. Make sure panels are properly secured while repairs are being made to a unit.
DO NOT remove access panel fasteners or open
access doors until fan is completely stopped. Pressure developed by a moving fan can cause excessive force against the panel which can injure personnel.
DO NOT work on dampers until their operators are
disconnected.
BE SURE that fans are properly grounded before
working on them.
Failure to follow these warnings could result in personal injury or equipment damage.
2. Do not stack unit components or accessories during storage. Stacking can cause
damage or deformation.
3. If unit is to be stored for more than 2 weeks
prior to installation, observe the following
precautions:
a. Choose a dry storage site that is rea-
sonably level and sturdy to prevent undue stress or permanent damage to the
unit structure or components. Do not
store unit on vibrating surface. Damage
to stationary bearings can occur. Set
unit off ground if in heavy rain area.
b. Remove all fasteners and other small
parts from jobsite to minimize theft. Tag
and store parts in a safe place until
needed.
c. Cover entire unit with a tarp or plastic
coverall. Extend cover under unit if
stored on ground. Secure cover with
adequate tie-downs or store indoors.
Be sure all coil connections have protective shipping caps.
d. Monthly — Remove tarp from unit, en-
ter fan section through access door or
through fan inlet, and rotate fan and
motor slowly by hand to redistribute the
bearing grease and to prevent bearing
corrosion.
Rigging — Do not remove shipping skids or
protective covering until unit is ready for final
placement. Use slings and spreader bars as applicable to lift unit. Do not lift unit by coil connec-
tions or headers.
Do not remove protective caps from coil
piping connections until ready to connect
piping.
WARNING-AUXILIARYDRAINPAN
RECOMMMENDED:
This product has an auxiliary condensate drain
which should be piped to a condensate overflow
sensor or safe drain location or both to protect
the equipment and property from damage in the
case of condensate overflow.
In addition, the International Mechanical Code
(IMC) section 307.2.3 requires the use of auxiliary drain pans.Many municipalities have
adopted this code.
This practice represents the standard for professional installation whether or not this code has
been adopted in a specific municipality or territory. As such, water damages that would have
been prevented had an auxiliary pan been deployed will not be considered for compensation.
This position is taken regardless of whether the
source of the moisture was specified as a potential failure mode in the applicable building
code or not. A freeze burst, cracked drain pan,
failed weld, or corrosion induced leak are some
of the potential failure modes that are mitigated
when an auxiliary pan is properly installed. Professional installers recognize the value of protecting customer assets against foreseeable
events.Customers who choose to avoid the
cost of common protective measures waive their
right to seek damages when those foreseeable
events occur. If the product is located above a
living space or where damage may result from
condensate overflow, install a watertight pan of
corrosion-resistant metal beneath the unit to
catch over-flow which may result from clogged
drains or from other reasons. Provide proper
drain piping for this auxiliary pan. Consult local
codes for additional precautions before installation.
Unpackaging
1. Remove all packaging and any foreign material from unit.
2. Check blower wheel for free rotation.
3. Check copper lines, coil etc. for internal or
hidden damage.
Return Air and Unit Orientation
Units may be positioned in several configura-
tions depending on the return air configuration selected—see Figure 1.
NOTE: Right and left return units are not
recommended for horizontal installation.
Service Clearance
inches) of clearance. This allows substantial freedom in the positioning of the unit to
best serve the requirements of the structure.
Unit Support
Floor mounting: Unit may be mounted on a
housekeeping pad, floor, platform or plenum.
Provide a suitable isolation pad to minimize
sound transmission to the structure.CAU-
TION! Make sure to allow enough elevation to permit construction of the condensate trap.Also allow enough elevation
and clearance for opening the filter door
(removes to the front). See Service Clear-
ances.
The fan coil is completely serviceable from
the front. Units are approved for 0” (zero
035-000039-001Page 8 of 32MVA IOM 1.3 9-10-2014
Page 9
INSTALLATION
NOTE:
Electronic Expansion Valve (EEV)
must be oriented vertically, and is
shipped for vertical cabinet orientation.
For horizontal cabinet orientation,
follow procedure to rotate the EEV
assembly. Refer to Figure 2.
Return Configurations and
Unit Orientations
WARNING
FOR HORIZONTAL CABINET ORIENTATION, EEV MUST BE ROTATED TO
VERTICAL POSITION! Failure to reorient the EEV can result in improper
unit operation or equipment damage
or dangerous condition.
Figure 1
035-000039-001Page 9 of 32MVA IOM 1.3 9-10-2014
Page 10
INSTALLATION—VERTICAL TO HORIZONTAL CONVERSION—EEV ROTATION
WARNING
FOR HORIZONTAL CABINET
ORIENTATION,EEV MUST
BE ROTATED TO VERTICAL
POSITION!Failure to reorient the EEV in VERTICAL
position can result in improper unit operation or equipment damage or dangerous
condition.
CONVERSION PROCEDURE:
1. UNIT IS SHIPPED WITH NITROGEN
CHARGE. IF UNIT HAS ALREADY BEEN
CHARGED WITH REFRIGERANT, REMOVE REFRIGERANT CHARGE PER LOCAL CODES BEFORE PERFORMING CONVERSION PROCEDURE.
2. REMOVE PIPING PLUGS AND SAVE FOR LATER USE. NITROGEN WILL DISCHARGE FROM
COIL.
3. REMOVE PIPING GROMMETS; REMOVE LIQUID INLET CAP FOR HORIZONTAL POSITION.
4. REMOVE BLOWER PANEL, LEFT AND RIGHT
COIL PANELS
5. SECURE EEV BRACKET WITH WRENCH AND
TURN COUPLING FLANGE NUT COUNTER
CLOCKWISE WITH 3/4" WRENCH TO LOOSEN
AND DISCONNECT COUPLING. THE COUPLING TAIL NUT SHOULD BE ALLOWED TO
TURN FREELY.
6. REPOSITION EXPANSION VALVE ASSEMBLY
AS SHOWN IN FIGURE 2d. ENSURE EXPANSION VALVE IS VERTICAL WITHIN +/- 15 DEG
WITH UNIT INSTALLED IN HORIZONTAL POSITION
7. REATTACH COUPLING AND
TIGHTEN TO 10-12 FT LBS
WHILE SECURING EEV BRACKET WITH WRENCH.
8. AS AN ALTERNATIVE TO
STEP 5 COUPLING MAY BE
TIGHTENED UNTIL NO
THREADS ARE SHOWING
AND COUPLING IS BOTTOMED OUT. THEN TURN
AN ADDITIONAL 60 DEG
(OR ONE HEX FLAT) TO
TIGHTEN.
9. REINSTALL FRONT
PANELS, GROMMETS,
AND PIPING PLUGS.
Figure 2a-
Vertical
Orientation
Figure 2b-
Vertical
Orientation
Figure 2d-Horizontal
Orientation
EEV BRACKET
Detail A-
EEV Detail
EEV INVERTICAL
ORIENTATION
Figure 2c-Vertical
Orientation, Panels
Removed
035-000039-001Page 10 of 32MVA IOM 1.3 9-10-2014
Page 11
INSTALLATION—SERVICE CLEARANCES
035-000039-001Page 11 of 32MVA IOM 1.3 9-10-2014
Page 12
INSTALLATION
Install the unit so that it is level or pitches
slightly –(1/8 inch) – toward the condensate
drain connection.
Anchor the unit to the plenum or platform
through the bottom flange using 2ea #10 sheet
metal screws on each side (4 screws total).
Ceiling Suspension: Mount the unit in ceilingsuspended horizontal orientation per suspension details (Figure 4). Unit is NOT intended
to be wall mounted. Consult a qualified structural engineer for special mounting considerations.
WARNING
INSURE THAT THE UNIT IS ADEQUATELYSUPPORTEDFROM
STRUCTURE TO PREVENT DAMAGE
OR INJURY CAUSED BY FALLING
EQUIPMENT! If uncertain about how
to connect to the structure, consult a
qualified structural engineer.
Install the unit so that it pitches slightly –(1/8
inch) – toward the condensate drain connection.
NOT TO SCALE
MAINTAIN THESE DIMENSIONS FOR ADEQUATE TRAP
SEAL:
A = 3.5” MINIMUM
B = 2.0” MINIMUM
NOTES:
1. CONDENSATE DRAIN PIPING RECOMMENDATIONS:
A. MINIMUM 3/4” Φ PIPE SIZE
B. COPPER OR PVC PIPE MATERIAL
C. USE DIELECTRIC UNION FOR DISSIMILAR METALS.
D. INSULATE PER PROJECT SPECIFICATIONS.
2. PAD OR PLENUM HEIGHT AS REQUIRED TO INSTALL
TRAP AND CONDENSATE DRAIN PIPING.
3. AVOID BLOCKING FILTER SERVICE ACCESS WHEN
INSTALLING CONDENSATE DRAIN PIPING.
Fig. 3 — Condensate Drain
Condensate Drain
Install a trapped condensate drain line at unit drain
connection. All MVA units have 3/4 in. FPT condensate main and auxiliary drain connections.
Provide adequate trap clearance (trap depth) beneath the unit as indicated in Fig. 3. Provide
freeze-up protection as required to insure reliable
condensate drainage. Freeze protection
measures are customer-supplied and installed.
Pipe to condensate drain using PVC or copper or
other suitable material. Pitch drain piping downward at a minimum slope of 1/8 inch per foot.
Pipe auxiliary drain to “tell tale” drain location or
floor drain to clearly indicate when condensate
drain service is required. Alternately, use a fieldprovided condensate overflow detection device in
the auxiliary drain connection to provide alarm or
other controls action when the drain pan fills to the
level of the auxiliary drain.
Placing Unit In Ductwork
1. Utilize flexible transitions on supply and return
connections to reduce noise and vibration transmission to the structure.
2. When the connecting return air duct is
smaller than the coil inlet opening, construct
the transition piece so that the vertical and
horizontal dimensions of the transition piece
do not increase more then one inch for every seven inches of length of the transition
piece.
2. Provide at least three feet of straight
duct work preceding the unit inlet.
Duct Insulation and Vapor Proofing:
Properly select and install duct insulation as
required by the application.
All externally insulated duct work must have
an adequate vapor seal for summer operation. This is particularly important where the
duct is exposed to highly humid conditions
in such places as attics, vented crawl spaces, unconditioned basements, and utility
rooms. The vapor seal prevents condensation of moisture in the insulating material
and subsequent loss of its insulating value.
035-000039-001Page 12 of 32MVA IOM 1.3 9-10-2014
Page 13
Figure 4
CEILING SUSPENSION DETAILS
035-000039-001Page 13 of 32MVA IOM 1.3 9-10-2014
Page 14
INSTALLATION
CAUTION
Direct-expansion coils are shipped pressurized
with dry nitrogen. Release pressure from the coil
through valves in protective caps before removing caps.
Do not leave piping open to the atmosphere unnecessarily. Water and water vapor are detrimental to the refrigerant system. Until the piping
is complete, recap the system and charge with
nitrogen at the end of each workday. Clean all
piping connections before soldering joints.
Failure to follow these procedures could result in
personal injury or equipment damage.
Refrigerant Piping
Refrigerant Coils: Direct-expansion coils
have liquid and suction line connections
through the front of the cabinet. CAUTION:
Use proper care when brazing including use
of heat sink (wet cloth or other method) to prevent damage to liquid line and suction line
components.
Fig. 5 — Heater Accessory Installed
(right side panel not shown)
Size and install refrigerant lines in accordance
with the condensing unit manufacturer’s instructions. Provide insulation on the suction
line, to prevent condensation. Provide insulation on the liquid line if unit to be used for heat
pump service or if otherwise required.
System Design Regulation
When connecting MVA units in the VRF system (mix or all), keep indoor/outdoor unit
capacity ratio with the range of 50% to
130%. For other conditions, refer to the VRF
System standard piping design regulations.
Electric Heater Accessory
The electric heater may be factory-installed or
field-installed. See Figures 5 through 8.
Removal Procedure:
To remove the electric heater,
1. Disconnect and lock out electrical power
from the unit. Remove heater access panel.
Disconnect power wires from the power
switch—DANGER! - MAKE SURE there is no
voltage on these wires before disconnecting!
2. Disconnect 2 harness connectors at the
blower deck.
3. Remove 2 screws holding heater support
feet to the blower deck.
4. Remove 4 screws that mount the heater to
the heater bulkhead. Handle heater carefully
to avoid damaging the wire heating elements.
Remove heater from the unit.
Fig. 6 — Heater Accessory Installed
(right side and heater access panels
not shown)
DANGER
WARNING: Hazardous voltage. Only qualified
personnel must install the electrical service. Disconnect and Lock Out all incoming power sources
before connecting to electrical service.
WARNING: This appliance must be permanently
grounded in accordance with the National Electrical
Code and local code requirements.
WARNING: For use with copper conductors only.
035-000039-001Page 14 of 32MVA IOM 1.3 9-10-2014
Page 15
INSTALLATION
Install Procedure:
To install the electric heater,
1. Disconnect and lock out electrical power from
the unit. Remove heater access panel. Disconnect field power wires from the unit power wires.
DANGER! - MAKE SURE there is no voltage
supply to the unit before proceeding!
2. Disconnect and discard 1 harness connector at
the blower deck.
3. Remove blank plate from heater access panel
(covers square hole for breaker style power
switches).
4. Remove SAT sensor and sensor holder from
heater bulkhead and reposition on unit discharge
ductwork routing through auxiliary SAT sensor
hole on top panel.
5. Install SAT 3 feet after the first 90 degree turn
in the discharge ductwork.
6. Remove plate on the heater bulkhead (4
screws).
7. Install heater by carefully supporting the heater
and inserting it into the opening in the heater bulkhead. NOTE: Make sure to guide the pin into the
hole at the back of the heater shroud. Secure the
heater to the bulkhead with 4 screws.
8. Connect 2 wiring harnesses (male) to the
DANGER
WARNING: Hazardous voltage. Only qualified
personnel must install the electrical service. Disconnect and Lock Out all incoming power sources
before connecting to electrical service.
matching female receptacles in the blower deck.
9. Connect field wiring to the breaker-style power
switches on the front of the heater. WARNING! Be
sure to provide the appropriate wire size and
branch circuit protection as required by the unit
nameplate!
10. Install the heater access panel.
11. Install the silicone cover “boot” over the top of
the power switches. This protects them from dust
buildup. The switches may be activated through the
flexible boot material.
12. Mark the nameplate label with the matching
heater kW rating. Label is located on the exterior of
the front top panel.
13. Update EEPROM settings to values shown in
the table. Refer to test run manual for detailed in-
Item CodeNew Settings
070001
380002
3C-001
COVER
BOOT
HEATER
ACCESS
PANEL
H
G
I
R
HEATER
ASSEMBLY
POWER
SWITCH(ES)
HEATER
SHROUD
PIN
E
D
I
S
T
Fig. 8 — Heater
Accessory
Installed
HEATER
SHROUD
HEATER
BULKHEAD
Fig. 7 — Heater Accessory Removal
(right side and heater access panels
not shown for clarity)
035-000039-001Page 15 of 32MVA IOM 1.3 9-10-2014
Page 16
INSTALLATION-ELECTRICAL
DANGER
DANGER
WARNING: Hazardous voltage. Only qualified
personnel must install the electrical service. Disconnect and Lock Out all incoming power sources
before connecting to electrical service.
WARNING: This appliance must be permanently
grounded in accordance with the National Electrical
Code and local code requirements.
WARNING: For use with copper conductors only.
Typical wiring diagrams are shown on the following
pages FOR REFERENCE. Always refer to the wiring diagram on the air handling unit for actual wiring.
NOTE: CHECK MOTOR RATING PLATE FOR
CORRECT LINE VOLTAGE.
Connect electrical service to unit. Refer to unit wiring diagram.
NEVER enter an enclosed fan cabinet or reach into
a unit while the fan is running.
LOCK OPEN AND TAG the fan motor power disconnect switch before working on a fan. Take fuses
with you and note removal on tag. Electric shock
can cause personal injury or death.
LOCK OPEN AND TAG the electric heat coil power
disconnect switch before working on or near heaters.
Failure to follow these warnings could lead to personal injury or death.
CAUTION
Use only copper conductors for field-installed electrical wiring. Unit terminals are not designed to
accept other types of conductors.
Do not allow wiring to touch the refrigerant tubing,
compressor, or any moving parts of the fan.
Make wiring connections in accordance with the
system wiring system diagram and these instructions. Wrong wiring may cause improper operation
or unit damage!
Power Wiring
For power supply connection, route field power wiring L1 and L2 and connect either:
1. Unit Without EH: to field-provided and installed
disconnect switch and from switch to power
entry (unit side) and to unit power leads inside
the unit electrical section; or
2. Unit With EH: into the unit through power entry
(unit side) and then to the factory installed power switch inside the electrical section (see Figure 9). Note: power switch looks like a circuit
breaker but does not provide overload pro-tection. Power switch provided only with electric heater (field kit or factory installed). NOTE:
When electric heat greater than 10kW is provided, two power supply circuits are required,
as shown on the wiring diagram.
Refer to nameplate or Electrical Ratings (page 30)
for FLA, maximum overcurrent protection device
(MOPD) and minimum circuit ampacity (MCA). Also
refer to wiring diagram affixed to unit to make control and power wiring connections. For new heater
installation, mark the nameplate label with the
matching heater kW rating. Label is located on the
exterior of the front top panel.
Unauthorized changes in the internal wiring can be
very dangerous. The manufacturer will accept no
responsibility for any damage or malfunction that
occurs as a result of such unauthorized changes.
other convenient location. Control voltage wiring
leads exit the bottom of the control box and are
ready for field-connection.
CAUTION! To prevent malfunction of the air conditioner caused by electrical noise, route control wiring
and inter-unit control wiring SEPARATELY FROM
THE POWER WIRING!
POWER
SWITCH
NOTE: Installer is responsible for power wiring and
branch circuit over current protection.
Control Voltage Wiring
Control voltage wiring may enter the unit at the control box located behind the blower access door, or
035-000039-001Page 16 of 32MVA IOM 1.3 9-10-2014
Unit with Electric Heat
Figure 9
Page 17
INSTALLATION-ELECTRICAL
control wiring
DANGER
General
Provide strain relief where field wiring passes
through cabinet. Wiring within the cabinet has
been positively located and supported so that it
does not pass over sharp metal edges or come in
contact with moving parts. After servicing, position
wiring properly in the original supports.
All field-installed wiring, including the electrical
ground, MUST comply with the National Electrical
Code (NEC) as well as applicable local codes. In
addition, all field wiring must conform to the Class
II temperature limitations described in the NEC.
Refer to factory wiring diagrams installed in the
unit. Use the MCA and MOPD from the nameplate
or electric heat nameplate or Electrical Ratings
(page 30) to size power supply wiring and overcurrent protection device. Installation must comply
with NEC and local codes.
For communicating controls, refer to Figures 10
through 13 for max lengths, sizing and intercon-
Building System Wiring Diagram
(multiple indoor & outdoor units)
WARNING: Hazardous voltage. Only qualified
personnel must install the electrical service. Disconnect and Lock Out all incoming power sources
before connecting to electrical service.
WARNING: This appliance must be permanently
grounded in accordance with the National Electrical
Code and local code requirements.
WARNING: For use with copper conductors only.
CAUTION
Loose wiring may cause the terminal to overheat
or result in unit malfunction or cause a fire hazard.
Insure that all wiring is tightly connected!
nections. Refer to the condensing unit operation manual for more details.
Figure 10
NOTE: See table below for wire requirements
for lines above marked “A”, “B”, “C” and “D”.
Control wiring
(A) Inter- unit (be tween
outdoor a nd indoor units)
AWG #18(0.75 mm2)AWG#18 (0.75 mm2)
Max. 3,280 ft.Max. 1,640 ft.
(C) Control wiring for group
control
AWG #18(0.75 mm2)AWG#18 (0.75 mm2)
Max. 650 ft. (Total)Max. 980 ft.
035-000039-001Page 17 of 32MVA IOM 1.3 9-10-2014
(B) Remote control wiring
(D) Inter- outdoor unit
control wiring
Page 18
INSTALLATION-ELECTRICAL
Figure 11
Inter-Unit Control Wiring
Do not install the inter-unit control wiring
in a way that forms a loop.
Figure 12
Inter-Unit Control Wiring
Do not install inter-unit control wiring with splices or “star branch” pattern. Star branch wiring
causes misaddress setting errors.
Figure 13
Branched Inter-Unit Control Wiring
If branching the inter-unit control wiring,
the number of branch points should be
16 or fewer. (Branches less than 3.3 ft.
are not included in the total branch number.)
035-000039-001Page 18 of 32MVA IOM 1.3 9-10-2014
Page 19
INSTALLATION-ELECTRICAL (cont’d)
TYPICAL WIRING DIAGRAM—
Unit sizes 18 & 24
TYPICAL WIRING—MVA18, MVA24
035-000039-001Page 19 of 32MVA IOM 1.3 9-10-2014
Page 20
INSTALLATION-ELECTRICAL (cont’d)
TYPICAL WIRING DIAGRAM—
Unit sizes 30, 36, 42, 48 & 60
TYPICAL WIRING—MVA30, MVA36,
MVA42, MVA48, MVA60
035-000039-001Page 20 of 32MVA IOM 1.3 9-10-2014
Page 21
INSTALLATION-ELECTRICAL (cont’d)
TYPICAL WIRING DIAGRAMS—
Electric Heat: 3-6kW and 8-9.5kW
3
TYPICAL WIRING—ELECTRIC HEAT
TYPICAL WIRING—ELECTRIC HEAT
035-000039-001Page 21 of 32MVA IOM 1.3 9-10-2014
Page 22
START-UP
Pre-Startup
Building Envelope—All building windows and doors should
be installed and closed before starting unit. During summer
construction, avoid unit sweating by allowing for gradual pull
down: use reduced capacity and use maximum available
airflow.
Temperature Controls-Check that unit is connected to the
controls system and communicating properly.
Outside Air and Freeze Protection
WARNING: Insure that the property is protected against
freezing conditions Failure to provide freeze protection
may result in property damage. Freeze protection
measures are customer-provided and installed and include
but are not limited to low-limit thermostats, automatic temperature controls, and outside air dampers.
Startup
1. Insure electrical installation agrees with the unit nameplate (voltage, branch circuit protection, wire size).
2. Close all panels and access doors. Make sure filter media is clean before starting unit. Replace filter if necessary.
3. Verify that discharge ductwork and input plenum are in
place and secure.
4. Apply power to unit. If unit is equipped with on-board
power switch(es), turn switch(es) to the “On” position.
5. Insure that controls system has power and is operational.
6. Force control system to send fan on signal and speed
signal. Refer to unit wiring diagram and electrical section
for fan speed control arrangement.
7. Fan should start and run. Make sure fan operates without significant noise or vibration.
8. Allow control system to start condensing unit, or as required for the installation.
9. Complete the checklist on the Start-Up Report.
10. Follow additional startup procedures for the system as
required by the condensing unit.
Fig. 14 — Fan Wheel Rotation—
FORWARD CURVED FAN
Fan Airflow Step-Up
If the duct system ESP is higher than planned and increased
Air Handler ESP is needed, shift the terminals as shown in
Figure 15.
Refer to Airflow tables and curves for airflow performance.
1. Data at sea level w/ 1" throw-away filter and dry coil.
As Shipped
0.0000.1000.2000.3000.4000.500
0.0000.1000.2000.3000.4000.500
0.0000.1000.2000.3000.4000.500
0.0000.1000.2000.3000.4000.500
0.0000.1000.2000.3000.4000.500
0.0000.1000.2000.3000.4000.500
0.0000.1000.2000.3000.4000.500
Higher Fan Setting
ESP
ESP
ESP
ESP
ESP
ESP
ESP
Areas not recommend for operation due to excess velocity
035-000039-001Page 23 of 32MVA IOM 1.3 9-10-2014
Page 24
Airflow Performance Curves
MVA18
0.50
0.45
0.40
0.35
0.30
0.25
0.20
0.15
0.10
0.05
External Static Pressure ( inch W.G.)
0.00
400500600700800900
M
L
Airflow (SCFM)
HTH
exessive airflow
Area not re commen ded for use for
MVA30
0.50
0.45
0.40
0.35
0.30
0.25
0.20
0.15
0.10
0.05
External Static Pressu re ( inch W.G.)
0.00
60070 080090 01000110012 00 1 30 0
Airflow (SCFM)
MVA24
0.50
0.45
0.40
0.35
0.30
0.25
0.20
0.15
0.10
0.05
External Static Pressure ( inch W.G.)
0.00
6007008 009 00100 01100
Airflow (SCFM)
HTHML
exessive airflow
Area not rec ommen ded for use for
MVA36
0.50
0.45
0.40
0.35
0.30
0.25
HTHML
0.20
0.15
0.10
0.05
External Static Pressu re ( inch W.G.)
0.00
80090 01000 1 1001200130014 00 1 500
Airflow (SCFM)
HTHML
MVA42
0.50
0.45
0.40
0.35
0.30
0.25
0.20
0.15
0.10
0.05
External Static Pressu re ( inch W.G.)
0.00
80010 00120014 0016001800
Airflow (SCFM)
0.50
0.45
0.40
0.35
0.30
0.25
0.20
0.15
0.10
0.05
External Static Pressu re ( inch W.G.)
0.00
120 01400160 0180 020 00220 02400
MVA48
0.50
0.45
0.40
0.35
0.30
0.25
HTHML
0.20
0.15
0.10
0.05
External Static Pressu re ( inch W.G.)
0.00
100 012001400160018002000
Airflow (SCFM)
HTHML
MVA60
HTHML
Airflow (SCFM)
035-000039-001Page 24 of 32MVA IOM 1.3 9-10-2014
Page 25
DANGER
NEVER enter an enclosed fan cabinet or reach
into a unit while the fan is running.
LOCK OPEN AND TAG the fan motor power disconnect switch before working on a fan. Take fuses with you and note removal on tag. Electric
shock can cause personal injury or death.
LOCK OPEN AND TAG the electric heat coil power disconnect switch before working on or near
heaters.
Failure to follow these warnings could lead to personal injury or death.
SERVICE
General
1. Review Safety Considerations at beginning of
these instructions. Good safety habits are important tools when performing service procedures.
2. To make speed measurements, use a laser-style
tachometer.
Fan Motor Replacement
WARNING: Shut off motor power and lock out power
supply.
MOTOR
HARNESS &
CONNECTORS
Figure 16
MOTOR
HARNESS &
CONNECTORS
Remove Blower/Motor Assembly
Procedure:
1. Disconnect wiring harness plugs from motor (Fig.
16 and 17).
2. Remove blower mounting bolts, which secure the
blower rails upward against the blower deck
(2ea).
3. Remove motor/wheel assembly from the MVA
unit by sliding out (Figure 18).
4. See Figure 19. Loosen shaft set screw (opposite
motor side) and motor mount tightening screw
until motor can be removed.
5. Remove motor. Install new motor (Fig. 20), tighten motor mount bolt, then locate fan wheel and
tighten shaft set screw.
6. Reverse steps 1-4 to reinstall fan. Make sure
that the two clips at the back hold the blower rails
up against the blower deck.
7. Spin fan by hand to make sure there is no rubbing or interference.
8. Close unit access doors, remove lockout/tag out
and restore the unit to operation.
Figure 17
035-000039-001Page 25 of 32MVA IOM 1.3 9-10-2014
Page 26
DANGER
NEVER enter an enclosed fan cabinet or reach
into a unit while the fan is running.
LOCK OPEN AND TAG the fan motor power disconnect switch before working on a fan. Take fuses with you and note removal on tag. Electric
shock can cause personal injury or death.
LOCK OPEN AND TAG the electric heat coil power disconnect switch before working on or near
heaters.
Failure to follow these warnings could lead to personal injury or death.
Fan System Periodic Maintenance
1. Use of a Preventive Maintenance program is
strongly recommended to insure that the unit operates safely and efficiently.
2. Motor bearings are permanently sealed and do not
require lubrication.
3. Clean the fan’s flow area - maintenance interval in
accordance with the degree of contamination.
4. The fan wheel can be cleaned with a moist cloth.
5. Do not use any aggressive, paint solvent cleaning
agents when cleaning.
6. Never use a high-pressure cleaner or water-spray
for cleaning - particularly when the fan is running.
MOTOR/
BLOWER
SLIDES OUT
Figure 18
Coil Cleaning
DETERGENT — Spray mild detergent solution on
coils with garden-type sprayer. Rinse with fresh water.
Check to ensure condensate line is free. Excess water
from cleaning may flood unit if condensate line is
plugged.
Figure 19
Figure 20
035-000039-001Page 26 of 32MVA IOM 1.3 9-10-2014
Page 27
SERVICE—Filters
Filters
FILTER SECTIONS — Open or remove
filter panel to replace old filter with a new
filter. See physical data tables for filter
data. See Figure 21.
Figure 21
Figure 22
Access Panels
The 3 sections of the unit can be reached
using the front access panels, removable
using 5/16” socket or driver or flat head
screwdriver. See Figure 22.
035-000039-001Page 27 of 32MVA IOM 1.3 9-10-2014
Page 28
SERVICE-Coil Removal and Reinstallation Procedure
1. Perform procedure on the ground for safety.If
working at heights USE EXTREME CAUTION observe all FALL SAFETY considerations. Under all
conditions, LOCK OUT all power supplies before
performing this procedure.WARNING! Coil section can be heavy—use proper lifting equipment.
2. Isolate coil and reclaim refrigerant.Disconnect
unit from piping. Remove supply piping to allow
access into the coil section from the front.
3. Remove blower access door and coil access
doors.
4. Carefully remove temperature sensors from the
coil and set them aside, clear of the coil & drain
pan assembly. Disconnect electronic expansion
valve (EEV) wiring from the EEV.
5. Remove 4 screws on the drain pan side of the
cabinet (right side shown in Fig. 23). Remove 4
screws from coil support side of the cabinet (left
side shown in Fig. 23).
6. Slide coil & drain pan assembly out of the unit (Fig
19).
7. Coil can be detached from drain pan using 5/16”
driver, 2 screws. Coil can be detached from coil
support using 5/16” driver, 4 screws.
8. Follow instructions in reverse to install new coil.
9. Re-install sensors back in original positions. CAUTION! Be sure to place sensors in correct locations for proper unit
operation.
10. Re-install wiring to EEV.
11. Re-install unit access panels.
12. Return unit to service.
COIL SUPPORT
DRAIN PAN
Figure 23
035-000039-001Page 28 of 32MVA IOM 1.3 9-10-2014
Page 29
UNIT ELECTRICAL RATINGS
035-000039-001Page 29 of 32MVA IOM 1.3 9-10-2014
Page 30
UNIT DIMENSIONS
MVA18-60 Elec Heat Ready
RH Drain Connections—Configuration B
035-000039-001Page 30 of 32MVA IOM 1.3 9-10-2014
Page 31
MVA Series Air Handling Unit
Start-up Report
Job NameCity
Sales Order #Unit Tag
Model NumberSerial Number
InstallerQuantity of Units
STARTUP REPORT
GroupChecklist ItemYesNo
Does electrical service correspond to unit nameplate?
-Nameplate Rated FLA motor current: Rated_______ Measured__________
Does all field wiring conform to unit wiring diagram?
Is field-provided freeze protection present? (if required)
Is fan wheel turning the correct direction?
Is the filter clean?
Is unit properly supported?
Is unit installed level (necessary for proper condensate drainage)?
Is properly sized condensate trap present?
Is the condensate disposal system operating correctly?
Is auxiliary external condensate drain pan installed or auxiliary drain connection
utilized as recommended by IOM? (not required for valid warranty)
CRITICAL! For Horizontal Unit Orientation: Is the EEV in vertical orientation?
Is the DX system charged per the condensing unit instructions?
Is unit piping correct and insulated to prevent condensation?
Are the refrigerant pipe lines properly insulated?
Are there any leaks detected: interior to unit or at connections?
035-000039-001Page 31 of 32MVA IOM 1.3 9-10-2014
Page 32
MVA Series Air Handling Unit
Installation, Operation and Maintenance Manual
035-000039-001Page32of32MVA IOM 1.3 9-10-2014
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.