Panasonic g2-k installation

SIMPLE VENTILATION SOLUTIONS
AirCycler® g2-k
Installation & User’s Guide
VENTILATION MADE BREEZY!™
a breeze to install • a breeze to use
TABLE OF CONTENTS
AirCycler® g2-k Introduction Safety Considerations Installation Considerations
AirCycler® g2-k Wiring Diagram
Damper Location & Damper Installation Choose a Fresh Air Location
AirCycler® g2 Controller Location
1.0 Theory of Operation
1.1 Operation Details
1.2 Operation Examples
2.0 AirCycler® g2 Operation
2.1 Reading the AirCycler® g2
2.2 Normal Operation Display
2.3 Entering Setup Mode
3.0 Setup Options
4.0 Calculated Flow Set Up
4.1 Setting Measured Supply Air Flow
4.2 Setting Measured Exhaust Air Flow
4.3 Setting Code Required Constant Air Flow
4.4 Setting Optional Mixing Time
4.5 Setting Operation Hours
4.6 Setting Exhaust Fan Delay Time
5.0 Calculated Time Set Up
5.1 Setting Number of Minutes Per Hour of Supplied Air Flow
5.2 Setting Minutes of Exhaust Fan Run Time Required
5.3 Setting Optional Mixing Time
5.4 Setting Operation Hours
5.5 Setting Current Time
5.6 Setting Exhaust Fan Delay Time
6.0 Viewing Current Status & Settings
6.0 Currrent Status
6.1 Current Settings
6.2 Setting Current Time
7.0 Installation Testing Guide
Appendix A: Troubleshooting & Tips
Appendix B: ASHRAE 62.2 Reference Chart
AIRCYCLER® G2-K INTRODUCTION
The AirCycler® g2-k Whole House Mechanical Ventilation System includes the AirCycler® g2 Furnace Fan Timer, FanConnect™ Bath/Fan Light Switch with remote fan control, and a motorized fresh air damper.
The AirCycler® g2 is a furnace fan timer and ventilation controller with outputs for operating a motorized fresh air damper and the FanConnect™ exhaust fan switch*. This product provides whole house supply ventilation through cen-
tral furnace fan integration as well as whole house exhaust ventilation.
SAFETY CONSIDERATIONS
Read and follow manufacturer’s instructions carefully. Follow all local electrical codes during installation. All wiring must conform to local and national electrical codes. Improper wiring or installation may result in personal injury or product and property damage.
INSTALLATION CONSIDERATIONS
The AirCycler® g2 requires 24VAC (R and C terminals) to be connected for proper operation. The controller will not operate without these two connections.
The wires (R, C, & W ) from the air handler to the thermostat can run parallel with the wiring from the AirCycler® g2 to the air handler. The fan wire (G) must be interrupted by the AirCycler® g2. Some thermostats do not require a common (C) connection. The AirCycler® g2 requires this for power, which must be wired to the furnace.
RECORD ALL SETTINGS ON THE INSTALL STICKER PROVIDED. LIMITED
WARRANTY WILL BE VOID IF THE STICKER IS NOT PRESENT.
3
AC DOC 8.5
REV 10/24/2014
AIRCYCLER® G2-K WIRING DIAGRAM
KEY
R - 24VAC Power
C - Common
Gt - Fan From Thermostat
Gf - Fan To Furnace
V - Vent
Ex - Exhaust Fan
Vnc - Normal Closed Vent
(To power spring-return
dampers that are
normally open)
4 AC DOC 8.5
REV 10/24/2014
DAMPER LOCATION
The fresh air damper can be located anywhere in the inlet duct. Minimize the length of the inlet duct to improve air ow and improve system eciency. It is recommended that the damper be as close to the return air plenum and the AirCycler® g2 controller as possible, and the inlet duct connect to the return plenum upstream of the system lter, and down- stream of any duct mounted sensors.
DAMPER INSTALLATION
The damper may be installed in any position. It is recommended to install it with the motor at the12 o’clock position if mounted horizontally. Air may ow through in either direction, although it is recommended to install with the crimped end as the outlet. Use care to avoid distorting the damper housing and provide adequate support.
CHOOSE A FRESH AIR LOCATION
ASHRAE recommends that the fresh air intake be located at least 10 ft. from any source of pollutants, such as auto exhaust, dryer exhaust, exhaust from any fuel-burning appliances, etc. Avoid installation near odor sources such as garbage bins or barbecue grills. A minimum of 3 ft. above ground is recommended to avoiding ingress of leaf litter, grass clippings, etc. Do not use a crawl space, basement, or attic as a source of intake air. Always be sure to comply with local building codes and requirements regarding fresh air inlets.
Thermostat
AirCycler®
G2
Filter
Main Return Duct
Motorized Damper
Outside Air Duct
AIRCYCLER® g2 CONTROLLER LOCATION
The AirCycler® g2 controller can be installed near the thermostat or out of view on/near the air handler unit. See the wiring diagram on page 4.
Warning: Before installing the AirCycler®, turn o all power to the furnace. There may be more than one power to disconnect. Electrical shock can cause injury or death.
5
AC DOC 8.5
REV 10/24/2014
1.0 THEORY OF OPERATION
No need for additional ventilation forced by AirCycler® g2.
1.1 OPERATION DETAILS
The AirCycler® g2 Furnace Fan Timer is integrated with the home’s central furnace fan so that any time the central fan is turned on by the thermostat to provide heating or cooling, the AirCycler® g2 opens the motorized damper to let in a measured amount of fresh air. The fresh air is then distributed uniformly throughout the home through the existing ductwork.
When ventilation requirements are met, the damper is closed to prevent over-ventilation.
Should regular heating and cooling cycles not run long enough to meet the desired or required ventilation, the AirCycler® g2 can turn on the smaller and more economical bathroom exhaust fan (or other exhaust fan) through the optional FanConnect™ Switch.
With no need to run the large central fan to provide additional ventilation, homeowner complaints of cold air or noisy operation are eliminated and eciency is drastically improved.
1.2 OPERATION EXAMPLES
ONE HOUR VENTILATION (MINUTES)
VENTILATION REQUIREMENTS = 30 CFM CONTINUOUS OR 1,800 CF/HR
NORMAL CENTRAL FAN OPERATION ONLY
0
15
30
45
CENTRAL FAN
DAMPER
OPEN
20 MINUTES OF
HEATING/COOLING
20 MIN x 90 CFM
= 1,800 CF
VENTILATION
REQUIREMENT
COMPLETE
= NORMAL OPERATION
Enough ventilation took place during normal heating/cooling cycles to meet ventilation requirements for the hour.
DAMPER
CLOSED
= OCCUPANT ACTIVITY/AIRCYCLER® G2 FORCED EXHAUST
60
6 AC DOC 8.5
REV 10/24/2014
Loading...
+ 11 hidden pages