Before operating the unit, please read these operating
instructions thoroughly and keep them for future reference.
The included Installation Instructions should be kept and read
by the installer before installation.
Remote control is packaged in the indoor unit and removed
by the installer before installation.
Comment utiliser l’appareil
Climatiseur
Avant d’utiliser l’appareil, veuillez lire ce mode d’emploi dans
son intégralité et conservez-le pour toute référence ultérieure.
Le manuel d’installation inclus doit être conservé et lu par
l’installateur avant l’installation.
La télécommande est emballée dans l’unité intérieure et
retirée par l’installateur avant l’installation.
Instrucciones de funcionamiento
Climatizador de aire
Antes de utilizar la unidad, sírvase leer atentamente estas
instrucciones de funcionamiento y conservarlas para futuras
consultas.
El instalador debe guardar y leer las Instrucciones de
instalación incluidas antes de la instalación.
El mando a distancia viene embalado en la unidad interior y
debe ser retirado por el instalador antes de la instalación.
2-41
42-77
78-113
EspañolFrançaisEnglish
ACXF55-22540
A new built-in Network Adaptor that allows you to control
TIMER
OFF
TIMER
ON
your heatpump from everywhere.
Flexibility to connect
Single Split System or
Multi Split System Air
Conditioner to suit your
needs.
For complete product features,
please refer to catalogue.
Use remote
control within 8 m
from the remote
control receiver of
the indoor unit.
Quick Guide
B
Inserting the batteries
3
1
2
B
B
A
Pull out the back cover
1
of remote control.
Insert AAA or R03
2
batteries.
Close the cover.
3
2
A
Clock setting
Press
1
CLOCK
the time
• Press
CLOCK
and hold for
approximately 5
seconds to show
time in 12-hour
(am/pm) or 24 hour
indication.
Confi rm
2
and
.
SET
set
.
Thank you for purchasing Panasonic
Air Conditioner.
Table of contents
Safety precautions
System Overview .................... 17
How to use ......................... 18-27
Network Adaptor Q&A ........ 28-29
To learn more .......................... 30
Cleaning instructions ............... 31
Troubleshooting ................. 32-34
Information ......................... 35-36
Copyright ............................ 37-41
...................
4-16
Accessories
• Remote control
• AAA or R03 batteries × 2
• Remote control holder
• Screws for remote control
holder × 2
The illustrations in this manual are for
explanation purposes only and may differ
from the actual unit. They are subject
to change without notice for future
improvement.
English
B
Basic operation
Press
1
to start/stop the
operation.
POWER
• Please note that
the
indication
is on display to
start the unit.
Select the desired
MODE
Press
2
the desired mode.
AUTOHEAT
DRY
to select
COOL
3
temperature.
Up
Down
Selection range:
16.0 °C ~ 30.0 °C /
60 °F ~ 86 °F.
• Press and hold
for
approximately 10 seconds
to switch the temperature
indication in °C or °F.
3
Safety precautions
Air inlet
Air inlet
Air outlet
Air outlet
To prevent personal injury, injury to others
or property damage, please comply with the
following:
Incorrect operation due to failure to follow
instructions below may cause harm or damage,
the seriousness of which is classifi ed as below:
This appliances is not intended for accessibility
by the general public.
This sign
Air inlet
warns of
death or
serious injury.
This sign
warns of
injury or
damage to
property.
Power supply
Air outlet
WARNING
CAUTION
The instructions to be followed are classifi ed by
the following symbols:
This symbol denotes an
action that is PROHIBITED.
These symbols denote
actions COMPULSORY.
Indoor unit
Air outlet
Remote control
Outdoor unit
4
Air inlet
WARNING
Indoor unit and outdoor unit
This appliance can be used by
children aged from 8 years and above
and persons with reduced physical,
sensory or mental capabilities or
lack of experience and knowledge
if they have been given supervision
or instruction concerning use of
the appliance in a safe way and
understand the hazards involved.
Children shall not play with the
appliance. Cleaning and user
maintenance shall not be made by
children without supervision.
Please consult authorised dealer or
specialist to clean the internal parts,
repair, install, remove and reinstall the
unit. Improper installation and handling
will cause leakage, electric shock or
fi re.
Confi rm with authorised dealer or
specialist on usage of any specifi ed
refrigerant type. Using refrigerant type
other than the specifi ed may cause
product damage, burst and injury etc.
Do not use means to accelerate
the defrosting process or to clean,
other than those recommended by
manufacturer.
Any unfi t method or using incompatible
material may cause product damage,
burst and serious injury.
Do not install the unit in a potentially
explosive or fl ammable atmosphere.
Failure to do so could result in fi re.
Do not insert your fi ngers
or other objects into the air
conditioner indoor or outdoor
unit, rotating parts may cause
injury.
Do not touch the outdoor unit during
lightning, it may cause electric shock.
Do not expose yourself directly to cold
air for a long period to avoid excess
cooling.
Do not sit or step on the unit,
you may fall down accidentally.
Remote control
Do not allow infants and small children
to play with the remote control to
prevent them from accidentally
swallowing the batteries.
Network Adaptor (activated)
Do not use the indoor unit near to
any medical equipment or automatic
control equipment (automatic door,
wire alarms, etc.).
(Radio wave from indoor unit may
interfere with the equipment and may
cause incident due to malfunction)
Keep at least 15 cm away from the
indoor unit if you have a cardiac
pacemaker.
(Radio wave from indoor unit may
interfere with the operation of
pacemaker)
Power supply
Do not use a modifi ed
cord, joint cord,
extension cord or
unspecifi ed cord to
prevent overheating and
fi re.
To prevent overheating, fi re or electric
shock:
•
Do not share the same power outlet
with other equipment.
•
Do not operate with wet hands.
•
Do not over bend the power supply
cord.
•
Do not operate or stop the unit by
inserting or pulling out the power
plug.
If the supply cord is damaged, it must
be replaced by the manufacturer,
service agent or similarly qualifi ed
persons in order to avoid a hazard.
It is strongly recommended to be
installed with Earth Leakage Circuit
Breaker (ELCB) or Residual Current
Device (RCD) to prevent electric shock
or fi re.
To prevent overheating, fi re or electric
shock:
•
Insert the power plug properly.
•
Dust on the power plug should be
periodically wiped with a dry cloth.
Stop using the product if any
abnormality/failure occurs and
disconnect the power plug or turn off
the power switch and breaker.
(Risk of smoke/fi re/electric shock)
Examples of abnormality/failure
•
The ELCB trips frequently.
•
Burning smell is observed.
•
Abnormal noise or vibration of the unit
is observed.
•
Water leaks from the indoor unit.
•
Power cord or plug becomes
abnormally hot.
•
Fan speed cannot be controlled.
•
The unit stops running immediately
even if it is switched on for operation.
•
The fan does not stop even if the
operation is stopped.
Contact your local dealer immediately
for maintenance/repair.
This equipment must be earthed to
prevent electrical shock or fi re.
Prevent electric shock by switching off
the power supply and unplug:
-Before cleaning or servicing,
-When extended non-use, or
-During abnormally strong lightning
activity.
EnglishSafety precautions
5
Safety precautions
CAUTION
Indoor unit and outdoor unit
Do not wash the indoor unit with water,
benzine, thinner or scouring powder to
avoid damage or corrosion at the unit.
Do not use for preservation of precise
equipment, food, animals, plants,
artwork or other objects. This may
cause quality deterioration, etc.
Do not use any combustible equipment
in front of the airfl ow outlet to avoid fi re
propagation.
Do not expose plants or pet directly to
airfl ow to avoid injury, etc.
Do not touch the sharp
aluminium fi n, sharp parts may
cause injury.
Do not switch ON the indoor unit when
waxing the fl oor. After waxing, aerate
the room properly before operating the
unit.
Do not install the unit in oily and smoky
areas to prevent damage to the unit.
Do not dismantle the unit for cleaning
purpose to avoid injury.
Do not step onto an unstable bench
when cleaning the unit to avoid injury.
Do not place a vase or water container
on the unit. Water may enter the unit
and degrade the insulation. This may
cause an electric shock.
Do not open window or door for
long time during operation, it may
lead to ineffi cient power usage and
uncomfortable temperature changes.
Prevent water leakage by ensuring
drainage pipe is:
-Connected properly,
-Kept clear of gutters and containers, or
-Not immersed in water
After a long period of use or use with
any combustible equipment, aerate the
room regularly.
After a long period of use, make
sure the installation rack does not
deteriorate to prevent the unit from
falling down.
Remote control
Do not use rechargeable (Ni-Cd)
batteries. It may damage the remote
control.
To prevent malfunction or damage of
the remote control:
•
Remove the batteries if the unit is not
going to be used for a long period of
time.
•
New batteries of the same type must
be inserted following the polarity
stated.
Network Adaptor (activated)
Check the following requirements in
advanced (At home):
•
Insert the power supply thoroughly.
Ensure no dust builds up on the
power supply.
(This can cause fi re due to ignition in
the power supply’s of poor contact)
•
Check the status of timer activation
set by other persons.
(Unexpected run-stop operation may
cause harm to human body, pets, and
plants)
•
There should be no abnormality in the
air conditioner. Even though there is a
change of wind direction, no adverse
effect on the persons nor the rooms.
(Ensure no objects that easy to fl y or
drop, etc. Object fall due to wind may
cause fi re, injury, etc.)
6
Check the following requirements
before and during operation from
outside:
•
Do inform the inside person of the
air conditioner operating setting’s
condition.
(This may cause harm to human body
due to sudden changes of outside
temperature and room temperature)
-
Temperature adjustment can be
operated by remote control.
-
If inside the room with an infant,
physically handicapped person,
elderly person, etc. who are not
able to control the temperature by
themselves, please do not use this
application.
•
Please check the setting and
operating conditions.
(Sudden change of outside-room
temperature may cause harm to
human body, pets, and plants)
Power supply
Do not disconnect the plug by pulling
the cord to prevent electric shock.
WARNING
This appliance is fi lled with R32
(mild fl ammable refrigerant).
If the refrigerant is leaked and
exposed to an external ignition
source, there is a risk of fi re.
Indoor unit and outdoor unit
The appliance shall be installed, and/
or operated in a room with fl oor area
larger than Amin (m²) and keep away
from ignition sources, such as heat/
sparks/open fl ame or hazardous areas
such as gas appliances, gas cooking,
reticulated gas supply systems or
electric cooking appliances, etc.(Refer
to Table A of Installation instructions
table for Amin (m²))
Be aware that refrigerant may not
contain an odour, highly recommended
to ensure suitable fl ammable
refrigerant gas detectors are present,
operating and able to warn of a leak.
Keep any required ventilation openings
clear of obstruction.
Do not pierce or burn as the appliance
is pressurized. Do not expose the
appliance to heat, fl ame, sparks, or
other sources of ignition. Else it may
explode and cause injury or death.
English
Safety precautions
7
Safety precautions
Precaution for using R32
refrigerant
The basic installation work procedures are the
same as conventional refrigerant (R410A, R22)
models.
Since the working pressure is higher
than that of refrigerant R22 models,
some of the piping and installation and
service tools are special. Especially,
when replacing a refrigerant R22
model with a new refrigerant
R32 model, always replace the
conventional piping and fl are nuts with
the R32 and R410A piping and fl are
nuts on the outdoor unit side.
For R32 and R410A, the same fl are
nut on the outdoor unit side and pipe
can be used.
The mixing of different refrigerants
within a system is prohibited. Models
that use refrigerant R32 and R410A
have a different charging port thread
diameter to prevent erroneous
charging with refrigerant R22 and for
safety.
Therefore, check beforehand. [The
charging port thread diameter for R32
and R410A is 1/2 inch.]
Must always ensure that foreign matter
(oil, water, etc.) does not enter the
piping. Also, when storing the piping,
securely seal the opening by pinching,
taping, etc. (Handling of R32 is similar
to R410A.)
•
Operation, maintenance, repairing
and refrigerant recovery should be
carried out by trained and certifi ed
personnel in the use of fl ammable
refrigerants and as recommended
by the manufacturer. Any personnel
conducting an operation, servicing
or maintenance on a system or
associated parts of the equipment
should be trained and certifi ed.
•
Any part of refrigerating circuit
(evaporators, air coolers, AHU,
condensers or liquid receivers) or
piping should not be located in the
proximity of heat sources, open
fl ames, operating gas appliance or an
operating electric heater.
•
The user/owner or their authorised
representative shall regularly check
the alarms, mechanical ventilation
and detectors, at least once a
year, where as required by national
regulations, to ensure their correct
functioning.
•
A logbook shall be maintained. The
results of these checks shall be
recorded in the logbook.
•
In case of ventilations in occupied
spaces shall be checked to confi rm
no obstruction.
•
Before a new refrigerating system
is put into service, the person
responsible for placing the system
in operation should ensure that
trained and certifi ed operating
personnel are instructed on the
basis of the instruction manual
about the construction, supervision,
operation and maintenance of the
refrigerating system, as well as the
safety measures to be observed, and
the properties and handling of the
refrigerant used.
•
The general requirement of trained
and certifi ed personnel are indicated
as below:
a) Knowledge of legislation,
regulations and standards relating
to fl ammable refrigerants; and,
b) Detailed knowledge of and skills in
handling fl ammable refrigerants,
personal protective equipment,
refrigerant leakage prevention,
handling of cylinders, charging,
leak detection, recovery and
disposal; and,
8
c) Able to understand and to apply in
practice the requirements in the
national legislation, regulations
and Standards; and,
d) Continuously undergo regular and
further training to maintain this
expertise.
e) Air-conditioner piping in the
occupied space shall be installed
in such a way to protect against
accidental damage in operation
and service.
f) Precautions shall be taken to avoid
excessive vibration or pulsation to
refrigerating piping.
g) Ensure protection devices,
refrigerating piping and fi ttings are
well protected against adverse
environmental effects (such as
the danger of water collecting
and freezing in relief pipes or the
accumulation of dirt and debris).
h) Expansion and contraction of
long runs piping in refrigerating
systems shall be designed and
installed securely (mounted
and guarded) to minimize the
likelihood hydraulic shock
damaging the system.
i) Protect the refrigerating system
from accidental rupture due to
moving furniture or reconstruction
activities.
j) To ensure no leaking, fi eld-made
refrigerant joints indoors shall be
tightness tested. The test method
shall have a sensitivity of 5 grams
per year of refrigerant or better
under a pressure of at least 0.25
times the maximum allowable
pressure (>1.04 MPa, max
4.15 MPa). No leak shall be
detected.
1. Installation (Space)
•
Product with fl ammable refrigerants,
shall be installed according to
the minimum room area, Amin
(m²) mentioned in Table A of the
Installation Instructions.
•
In case of fi eld charge, the effect
on refrigerant charge caused by
the different pipe length has to be
quantifi ed, measured and labelled.
•
Must ensure the installation of pipework shall be kept to a minimum.
Avoid use dented pipe and do not
allow acute bending.
•
Must ensure that pipe-work shall be
protected from physical damage.
•
Must comply with national gas
regulations, state municipal rules and
legislation. Notify relevant authorities
in accordance with all applicable
regulations.
•
Must ensure mechanical connections
be accessible for maintenance
purposes.
•
In cases that require mechanical
ventilation, ventilation openings shall
be kept clear of obstruction.
•
When disposal of the product, do
follow to the precautions in #12 and
comply with national regulations.
Always contact to local municipal
offi ces for proper handling.
English
Safety precautions
9
Safety precautions
2. Servicing
2-1. Service personnel
•
The system is inspected, regularly
supervised and maintained by
a trained and certifi ed service
personnel who is employed by the
person user or party responsible.
•
Ensure the actual refrigerant charge
is in accordance with the room size
within which the refrigerant containing
parts are installed.
•
Ensure refrigerant charge not to leak.
•
Any qualifi ed person who is involved
with working on or breaking into
a refrigerant circuit should hold
a current valid certifi cate from an
industry-accredited assessment
authority, which authorizes their
competence to handle refrigerants
safely in accordance with an industry
recognised assessment specifi cation.
•
Servicing shall only be performed
as recommended by the equipment
manufacturer. Maintenance and
repair requiring the assistance of
other skilled personnel shall be
carried out under the supervision of
the person competent in the use of
fl ammable refrigerants.
•
Servicing shall be performed only as
recommended by the manufacturer.
2-2. Work
•
Prior to beginning work on systems
containing fl ammable refrigerants,
safety checks are necessary to
ensure that the risk of ignition
is minimised. For repair to the
refrigerating system, the precautions
in #2-2 to #2-8 must be followed
before conducting work on the
system.
•
Work shall be undertaken under
a controlled procedure so as to
minimize the risk of a fl ammable gas
or vapour being present while the
work is being performed.
•
All maintenance staff and others
working in the local area shall be
instructed and supervised on the
nature of work being carried out.
•
Avoid working in confi ned spaces.
Always ensure away from source, at
least 2 meter of safety distance, or
zoning of free space area of at least 2
meter in radius.
•
Wear appropriate protective
equipment, including respiratory
protection, as conditions warrant.
•
Keep all sources of ignition and hot
metal surfaces away.
10
2-3. Checking for presence of
refrigerant
•
The area shall be checked with an
appropriate refrigerant detector prior
to and during work, to ensure the
technician is aware of potentially
fl ammable atmospheres.
•
Ensure that the leak detection
equipment being used is suitable for
use with fl ammable refrigerants, i.e.
non sparking, adequately sealed or
intrinsically safe.
•
In case of leakage/spillage happened,
immediately ventilate area and stay
upwind and away from spill/release.
•
In case of leakage/spillage happened,
do notify persons down wind of
the leaking/spill, isolate immediate
hazard area and keep unauthorized
personnel out.
2-4. Presence of fi re extinguisher
•
If any hot work is to be conducted
on the refrigerating equipment or
any associated parts, appropriate
fi re extinguishing equipment shall be
available at hand.
•
Have a dry powder or CO2 fi re
extinguisher adjacent to the charging
area.
2-5. No ignition sources
•
No person carrying out work in
relation to a refrigerating system
which involves exposing any pipe
work that contains or has contained
fl ammable refrigerant shall use any
sources of ignition in such a manner
that it may lead to the risk of fi re
or explosion. He/She must not be
smoking when carrying out such
work.
•
All possible ignition sources, including
cigarette smoking, should be kept
suffi ciently far away from the site of
installation, repairing, removing and
disposal, during which fl ammable
refrigerant can possibly be released
to the surrounding space.
•
Prior to work taking place, the area
around the equipment is to be
surveyed to make sure that there
are no fl ammable hazards or ignition
risks.
•
“No Smoking” signs shall be
displayed.
2-6. Ventilated area
•
Ensure that the area is in the open
or that it is adequately ventilated
before breaking into the system or
conducting any hot work.
•
A degree of ventilation shall continue
during the period that the work is
carried out.
•
The ventilation should safely
disperse any released refrigerant and
preferably expel it externally into the
atmosphere.
English
Safety precautions
11
Safety precautions
2-7. Checks to the refrigerating
equipment
•
Where electrical components are
being changed, they shall be fi t
for the purpose and to the correct
specifi cation.
•
At all times the manufacturer’s
maintenance and service guidelines
shall be followed.
•
If in doubt consult the manufacturer’s
technical department for assistance.
•
The following checks shall be applied
to installations using fl ammable
refrigerants.
-
The actual refrigerant charge
is in accordance with the room
size within which the refrigerant
containing parts are installed.
-
The ventilation machinery and
outlets are operating adequately
and are not obstructed.
-
If an indirect refrigerating circuit is
being used, the secondary circuit
shall be checked for the presence
of refrigerant.
-
Marking to the equipment continues
to be visible and legible. Markings
and signs that are illegible shall be
corrected.
-
Refrigerating pipe or components
are installed in a position where
they are unlikely to be exposed to
any substance which may corrode
refrigerant containing components,
unless the components are
constructed of materials which
are inherently resistant to being
corroded or are properly protected
against being so corroded.
2-8. Checks to electrical devices
•
Repair and maintenance to electrical
components shall include initial safety
checks and component inspection
procedures.
•
Initial safety checks shall include but
not limit to:-
-
That capacitors are discharged: this
shall be done in a safe manner to
avoid possibility of sparking.
-
That there no live electrical
components and wiring are
exposed while charging, recovering
or purging the system.
-
That there is continuity of earth
bonding.
•
At all times the manufacturer’s
maintenance and service guidelines
shall be followed.
•
If in doubt consult the manufacturer’s
technical department for assistance.
•
If a fault exists that could compromise
safety, then no electrical supply shall
be connected to the circuit until it is
satisfactorily dealt with.
•
If the fault cannot be corrected
immediately but it is necessary to
continue operation, an adequate
temporary solution shall be used.
•
The owner of the equipment must be
informed or reported so all parties are
advised thereinafter.
12
3. Repairs to sealed components
•
During repairs to sealed components,
all electrical supplies shall be
disconnected from the equipment
being worked upon prior to any
removal of sealed covers, etc.
•
If it is absolutely necessary to have
an electrical supply to equipment
during servicing, then a permanently
operating form of leak detection shall
be located at the most critical point
to warn of a potentially hazardous
situation.
•
Particular attention shall be paid
to the following to ensure that by
working on electrical components, the
casing is not altered in such a way
that the level of protection is affected.
This shall include damage to cables,
excessive number of connections,
terminals not made to original
specifi cation, damage to seals,
incorrect fi tting of glands, etc.
•
Ensure that apparatus is mounted
securely.
•
Ensure that seals or sealing materials
have not degraded such that they
no longer serve the purpose of
preventing the ingress of fl ammable
atmospheres.
•
Replacement parts shall be in
accordance with the manufacturer’s
specifi cations.
NOTE: The use of silicon sealant may
inhibit the effectiveness of some types
of leak detection equipment.
Intrinsically safe components do not
have to be isolated prior to working on
them.
4. Repair to intrinsically safe
components
•
Do not apply any permanent inductive
or capacitance loads to the circuit
without ensuring that this will not
exceed the permissible voltage and
current permitted for the equipment
in use.
•
Intrinsically safe components are
the only types that can be worked
on while live in the presence of a
fl ammable atmosphere.
•
The test apparatus shall be at the
correct rating.
•
Replace components only with
parts specifi ed by the manufacturer.
Unspecifi ed parts by manufacturer
may result ignition of refrigerant in the
atmosphere from a leak.
5. Cabling
•
Check that cabling will not be
subject to wear, corrosion, excessive
pressure, vibration, sharp edges or
any other adverse environmental
effects.
•
The check shall also take into
account the effects of aging or
continual vibration from sources such
as compressors or fans.
6. Detection of fl ammable
refrigerants
•
Under no circumstances shall
potential sources of ignition be used
in the searching or detection of
refrigerant leaks.
•
A halide torch (or any other detector
using a naked fl ame) shall not be
used.
English
Safety precautions
13
Safety precautions
7. The following leak detection
methods are deemed
acceptable for all refrigerant
systems
•
No leaks shall be detected when
using detection equipment with a
sensitivity of 5 grams per year of
refrigerant or better under a pressure
of at least 0.25 times the maximum
allowable pressure (>1.04 MPa, max
4.15 MPa), for example, a universal
sniffer.
•
Electronic leak detectors may be
used to detect fl ammable refrigerants,
but the sensitivity may not be
adequate, or may need re-calibration.
(Detection equipment shall be
calibrated in a refrigerant-free area.)
•
Ensure that the detector is not a
potential source of ignition and is
suitable for the refrigerant used.
•
Leak detection equipment shall be
set at a percentage of the LFL of the
refrigerant and shall be calibrated
to the refrigerant employed and the
appropriate percentage of gas (25 %
maximum) is confi rmed.
•
Leak detection fl uids are also suitable
for use with most refrigerants,
for example, bubble method and
fl uorescent method agents. The use
of detergents containing chlorine shall
be avoided as the chlorine may react
with the refrigerant and corrode the
copper pipe-work.
•
If a leak is suspected, all naked
fl ames shall be removed/
extinguished.
•
If a leakage of refrigerant is found
which requires brazing, all of the
refrigerant shall be recovered from
the system, or isolated (by means
of shut off valves) in a part of the
system remote from the leak. The
precautions in #8 must be followed to
remove the refrigerant.
8. Removal and evacuation
•
When breaking into the refrigerant
circuit to make repairs – or for
any other purpose – conventional
procedures shall be used. However,
it is important that best practice
is followed since fl ammability is
a consideration. The following
procedure shall be adhered to:
remove refrigerant -> purge the circuit
with inert gas -> evacuate -> purge
with inert gas -> open the circuit by
cutting or brazing.
•
The refrigerant charge shall be
recovered into the correct recovery
cylinders.
•
The system shall be purged with OFN
to render the appliance safe.
•
This process may need to be
repeated several times.
•
Compressed air or oxygen shall not
be used for this task.
•
Purging shall be achieved by
breaking the vacuum in the system
with OFN and continuing to fi ll until
the working pressure is achieved,
then venting to atmosphere, and
fi nally pulling down to a vacuum.
•
This process shall be repeated until
no refrigerant is within the system.
•
When the fi nal OFN charge is used,
the system shall be vented down to
atmospheric pressure to enable work
to take place.
•
This operation is absolutely vital if
brazing operations on the pipe work
are to take place.
•
Ensure that the outlet for the
vacuum pump is not close to any
potential ignition sources and there is
ventilation available.
OFN = oxygen free nitrogen,
type of inert gas.
14
9. Charging procedures
•
In addition to conventional
charging procedures, the following
requirements shall be followed.
-
Ensure that contamination of
different refrigerants does not occur
when using charging equipment.
-
Hoses or lines shall be as short as
possible to minimize the amount of
refrigerant contained in them.
-
Cylinders shall be kept in an
appropriate position according to
the instructions.
-
Ensure that the refrigerating system
is earthed prior to charging the
system with refrigerant.
-
Label the system when charging is
complete (if not already).
-
Extreme care shall be taken not to
over fi ll the refrigerating system.
•
Prior to recharging the system it shall
be pressure tested with OFN (refer
to #7).
•
The system shall be leak tested on
completion of charging but prior to
commissioning.
•
A follow up leak test shall be carried
out prior to leaving the site.
•
Electrostatic charge may accumulate
and create a hazardous condition
when charging and discharging the
refrigerant.To avoid fi re or explosion,
dissipate static electricity during
transfer by grounding and bonding
containers and equipment before
charging/discharging.
10. Decommissioning
•
Before carrying out this procedure,
it is essential that the technician
is completely familiar with the
equipment and all its details.
•
It is recommended good practice that
all refrigerants are recovered safely.
•
Prior to the task being carried
out, an oil and refrigerant sample
shall be taken in case analysis is
required prior to re-use of recovered
refrigerant.
•
It is essential that electrical power
is available before the task is
commenced.
a) Become familiar with the
equipment and its operation.
b) Isolate system electrically.
c) Before attempting the procedure
ensure that:
•
mechanical handling equipment is
available, if required, for handling
refrigerant cylinders;
•
all personal protective equipment
is available and being used
correctly;
•
the recovery process is supervised
at all times by a competent person;
•
recovery equipment and cylinders
conform to the appropriate
standards.
d) Pump down refrigerant system, if
possible.
e) If a vacuum is not possible, make
a manifold so that refrigerant can
be removed from various parts of
the system.
f) Make sure that cylinder is situated
English
Safety precautions
on the scales before recovery
takes place.
g) Start the recovery machine and
operate in accordance with
instructions.
h) Do not over fi ll cylinders. (No more
than 80 % volume liquid charge).
15
Safety precautions
i) Do not exceed the maximum
working pressure of the cylinder,
even temporarily.
j) When the cylinders have been
fi lled correctly and the process
completed, make sure that the
cylinders and the equipment are
removed from site promptly and all
isolation valves on the equipment
are closed off.
k) Recovered refrigerant shall not be
charged into another refrigerating
system unless it has been cleaned
and checked.
•
Electrostatic charge may accumulate
and create a hazardous condition
when charging or discharging the
refrigerant.To avoid fi re or explosion,
dissipate static electricity during
transfer by grounding and bonding
containers and equipment before
charging/discharging.
11. Labelling
•
Equipment shall be labelled stating
that it has been de-commissioned
and emptied of refrigerant.
•
The label shall be dated and signed.
•
Ensure that there are labels on the
equipment stating the equipment
contains fl ammable refrigerant.
12. Recovery
•
When removing refrigerant from
a system, either for servicing or
decommissioning, it is recommended
good practice that all refrigerants are
removed safely.
•
When transferring refrigerant
into cylinders, ensure that only
appropriate refrigerant recovery
cylinders are employed.
•
Ensure that the correct number of
cylinders for holding the total system
charge are available.
•
All cylinders to be used are
designated for the recovered
refrigerant and labelled for that
refrigerant (i.e. special cylinders for
the recovery of refrigerant).
•
Cylinders shall be complete with
pressure relief valve and associated
shut-off valves in good working order.
•
Recovery cylinders are evacuated
and, if possible, cooled before
recovery occurs.
•
The recovery equipment shall be
in good working order with a set of
instructions concerning the equipment
that is at hand and shall be suitable
for the recovery of fl ammable
refrigerants.
•
In addition, a set of calibrated
weighing scales shall be available
and in good working order.
•
Hoses shall be complete with leakfree disconnect couplings and in good
condition.
•
Before using the recovery machine,
check that it is in satisfactory working
order, has been properly maintained
and that any associated electrical
components are sealed to prevent
ignition in the event of a refrigerant
release.Consult manufacturer if in
doubt.
•
The recovered refrigerant shall be
returned to the refrigerant supplier
in the correct recovery cylinder, and
the relevant Waste Transfer Note
arranged.
•
Do not mix refrigerants in recovery
units and especially not in cylinders.
•
If compressors or compressor oils are
to be removed, ensure that they have
been evacuated to an acceptable
level to make certain that fl ammable
refrigerant does not remain within the
lubricant.
•
The evacuation process shall be
carried out prior to returning the
compressor to the suppliers.
•
Only electric heating to the
compressor body shall be employed
to accelerate this process.
•
When oil is drained from a system, it
shall be carried out safely.
16
System Overview
Panasonic
Download from app store
Panasonic Comfort Cloud
app (free)
Network
Adaptor
Indoor Unit
Items you need to prepare
(purchase and subscribe separately)
Router
Internet
Smartphone
• Requires the APP to work with a smartphone with Android 4.4 and above, or iOS 9 and
above.
However, there is no guarantee that the APP will work well with all Android OS version.
• The Network Adaptor is designed specifi cally as a terminal for “Panasonic Comfort Cloud”
app.
• The Wireless LAN network coverage must reach the air conditioner installation location.
Specifi cation
Network AdaptorWireless LAN Module (built-in)
ModelDNSK-P11
Input VoltageDC 5V (From Air Conditioner Indoor Unit)
Current ConsumptionTx/Rx max. 290/100 mA
Wireless LAN standardIEEE 802.11 b/g/n
Frequency range2.4 GHz band
EncryptionWPA2-PSK (TKIP/AES)
EnglishSafety precautions / System Overview
Precaution
• Do NOT disassemble or alter this Network Adaptor in any way.
• Do NOT remove this Network Adaptor from the appliance product during operations.
• Data transmitted and received over radio waves may be intercepted and monitored.
Maximum radio-frequency power transmitted in the frequency bands
Type of wirelessFrequency bandMax. EIRP (dBm)
WLAN2412 - 2472 MHz20 dBm
17
How to use
Indicator
TIMER
ON
TIMER
OFF
POWER
TIMER
nanoe X
To adjust airfl ow direction
Upper direction
AIR SWING
Lateral direction
• Do not adjust the fl ap by hand.
To adjust fan speed
AUTO
FAN
• For AUTO, the indoor fan speed is automatically
adjusted according to the operation mode.
• To have low noise priority operation, select the
lowest fan speed
.
To switch between powerful/quiet
POWERFUL:
To reach temperature quickly
• This operation stops automatically after 20 minutes.
QUIET:
To enjoy quiet operation
• This operation reduces airfl ow noise.
To enjoy freshness and cleaner environment
18
Not used
in normal
operations.
Press to restore
the remote
control to default
setting.
Press to ON/ OFF
Wireless LAN
features.
• This operation provides clean air, moisturises your
skin and hair, deodorizes odours in the room.
• This operation can be activated when the unit is turn
on or off by pressing the nanoe™X button. During
nanoe™X individual operation, the fan speed will be
based on remote control setting.
• If nanoe™X is activated before the unit is turn off,
nanoe™X operation will resume once the unit is turn
on, this includes to ON Timer.
To improve humidity and moisture level
(Not applicable for Multi split system)
MILD DRY
•
This operation reduces air dryness during COOL mode
only.
See "To learn more..." for details.
To maximise comfort while sleeping
This operation provides you with a comfortable environment while sleeping. It will
automatically adjust the sleep pattern temperature during the activation period. The indoor
unit indicator will dim when this operation is activated. This is not applicable if the indicator
brightness has been manually dimmed.
•
SLEEP
(Cancel)
This operation is incorporated with the activation
timer (0.5, 1, 2, 3, 4, 5, 6, 7, 8 or 9 hours).
This operation can be set together with timer.
Sleep operation has the priority over OFF
timer.
•
This operation can be cancelled by pressing
the respective button until the sleep timer
reaches 0.0h.
To set the timer
2 sets of ON and OFF timers are available to turn ON or OFF the unit at different preset time.
2
1
TIMER
ON
TIMER
OFF
1
Select ON or OFF
timer
• Each time pressed:
2
Set the time
Cancel
3
Example:
OFF at 22:00
TIMER
OFF
2
• To cancel ON or OFF timer, press
TIMER
OFF
or
to select respective or then
CANCEL
press
.
• If timer is cancelled manually or due to
power failure, you can restore the timer
again by pressing
respective
TIMER
TIMER
ON
or
or then press
• The nearest timer setting will be displayed
and will activate in sequence.
• Timer operation is based on the clock set
in the remote control and repeats daily
once set. For clock setting, please refer to
OFF
to select
SET
TIMER
ON
.
Quick Guide.
3
Confi rm
SET
EnglishHow to use
Operating conditions
Use this air conditioner in the temperature range indicated in the table.
cancelled by pressing the respective button again.
SLEEP
•
Cannot be selected at the same time.
•
Cannot be activated during MILD DRY.
2
19
How to use
App InstallationTo connect network
• Press
• Wireless LAN LED
point.
Fast blinkThe unit is establishing the connection.
Slow blinkThe unit is not securing the connection.
No blink (stays on)The unit has established the connection.
• It can establish the connection to the unit even if the unit is turned OFF.
App Installation
to communicate with the home wireless LAN access point.
blinks to indicate the connection status to home access
For Android user (Android 4.4 and above)
• Open
GET IT ON
Google
Play
.
• Search for “Panasonic Comfort Cloud” app.
• Download and install.
For iOS user (iOS 9 and above)
Download on the
• Open
App
Store
.
• Search for “Panasonic Comfort Cloud” app.
• Download and install.
Note
• The app user interface image may change for version upgrade without notifi cation.
• There is no charge for using this application. However, other charges may be incurred for
connection and operation.
Starting “Panasonic Comfort Cloud”
Create New Panasonic ID
Use “Panasonic Comfort Cloud” app as an option to control the air conditioner.
Login
Please enter your Panasonic ID and password.
Panasonic ID
Panasonic ID
Password
Password
Remember me
Forgot ID/Password
Create new Panasonic ID
View an example
• For new user, select Create new Panasonic
ID to register.
• For registered user, login using your
Panasonic ID and password.
20
Login
App Setting
Before setting
• Confi rm the wireless router is connected to the network correctly.
• Confi rm the Wireless LAN of the smartphone is activated.
• Smartphone and air conditioner should be connected to the same wireless router.
Add new air conditioner device
• Air conditioner need to be registered before using “Panasonic Comfort Cloud” app.
12
My House
30.0 C
Bedroom 1
Home
4
Add new air conditioner
Follow the guide to set up Wireless LAN of the
air -condiƟoner.
1. Connect air - condiƟoner to the server via
wireless LAN router.
2. Use smartphone to register air -condiƟoner to
the server.
Add new device
Which appliances do you want to add?
Air conditioner
Air to water heat pump
Cancel
5
3
Add new air conditioner
Please choose the following:
Newly purchased air-condiƟoner
Others (Air -condiƟoner used before)
Add new air conditioner
Please choose the following:
Built-in wireless module
CHECK
SETUP
STATUS LINK POWER
Externalwirelessadaptor
External wireless adaptor
Cancel
English
How to use
Cancel
Start
Cancel
21
How to use
Setting connection network
1
Ensure Wireless LAN LED is ON, point
the remote control to air conditioner and
press Wireless LAN
button until the
Wireless LAN LED changed to blinking.
Connection Guide
Step 1
Make sure smartphone is connect ed to same
wireless network.
When Wireless LAN LED is ON, tap “Next”.
1. Point the remote cont rol to air
and press the “Wireless LAN” buƩon once.
2. When Wireless LAN LED is blinking, tap “Next”.
Wireless
Wireless LAN
LANbuƩon
buƩon
3
Select the preferred router support
Step 2
Step 2
SET
CANCEL
Next
Cancel
-
condiƟoner
Wireless LAN
LED
Step 3Step 1
Step 3
connectivity mode.
Connection Guide
Step 1
The router supports WPS.
Connect with WPS mode
Step 2
Step 3
2
When Wireless LAN LED is blinking,
select the preferred connection setup
mode.
to router is successful, the Wireless LAN
LED changed from blinking to ON.
Connection Guide
Step 1
Step 2
Step 3
2
Ensure Wireless LAN LED is ON. Press
and hold the Wireless LAN
for 5 seconds until “1” is shown on the
remote control and press
button
SET
pointing
to the air conditioner.
Connection Guide
Step 1
If Wireless LAN LED is OFF during the connecƟon
setup, please press “Wireless LAN” buƩon once
to enable the Wireless LAN before proceeding to
step 1 .
1. Press and hold “Wireless LAN” buƩon for 5 secs
unƟl easy seƫng “ 1 ” is show n.
2. Point remote control to air-condiƟoner and
press “SET” buƩon once.
3. AŌer step 1 & 2 have been done, tap “Next”.
4
If the Wireless LAN LED keep blinking,
Step 2
Next
Cancel
Step 3
SET
CANCEL
check the wireless router connection.
Connection Guide
Step 1
Step 2
Step 3
English
How to use
When the connecƟon of air-condiƟoner to router
is successful, the Wireless LAN LED changes from
blinking to ON.
*It may take up to few minutes be fore changes
to ON.
Select the SSID of your wireless router. Enter the password to connect the air conditioner
to the wireless router.
Connection Guide
Step 1
Next, setup the wireless network connecƟon of
air-condiƟoner.
To wireless network settingsTo wireless network settings
4
When connection of air conditioner to router is successful, the Wireless LAN LED will
Step 2
Cancel
Step 3
Connection Guide
Step 1
Connect the network adaptor to the wireless
router.
Select your wireless router
router SSID1
router SSID2
router SSID3
router SSID4
router SSID5
Other
MAC address of target device
d8-61-62-2e-44-da
Note:
Select 2.4 GHz band if the wireless router
supports both 2.4 GHz and 5 GHz band.
Step 2
Cancel
Step 3
Connection Guide
Step 1Step 2Step 3
ŶƚĞƌĂŶĚƐĞůĞĐƚƚŚĞĨŽůůŽǁŝŶŐŝŶĨŽƌŵĂƟŽŶŽĨƚŚĞ
wireless router.
Network name (SSID)
Network name (SSID)
Security
WPA2
Password
Password
OK
Cancel
Connection Guide
Connection Guide
Step 1
tep
tep 2
Step 2
Connecttheair-condiƟonerto the
C
wirelessrouter.
w
Selectyour wirelessrouter
Panasonic-factory-wireless-ap-00
MAC address of target device
AC address of target devic
d8-61-62-2e-44-c0
Note:
Select 2.4 GHz band if the wireless router
supports both 2.4 GHz and 5 GHz band.
upports both 2.4 GHz and 5 GHz band.
Ɵ
anasonic-factory-wireless-ap-0
Enter the password of the selected
wireless router.
Password
Password
CancelOK
2-2e-44-
t 2.4 GHz band if the wirel
Cancel
Cance
changed from blinking to ON. If the Wireless LAN LED is ON, connect the smartphone to
wireless router. (return to this application after completing the wireless network settings to
continue the setup)
• If the Wireless LAN LED keep blinking, check the wireless router connection.
Connection Guide
Step 1
When the connecƟon of air-condiƟoner to
router is successful, the Wireless LAN LED
changes from blinking to ON.
*It may take up to few minutes before changes
to ON.
Step 2
Step 3
^ĞƫŶŐƐ
Wi-Fi
router SSID1
CHOOSE A NETWORK...
router SSID2
router SSID3
router SSID4
Other...
Wi-Fi
Connection Guide
Step 1
Searching for air-condiƟoner.
Please wait…
Step 2
Step 3
Step 3
tep
r
English
How to use
If the Wireless LAN LED is ON, connect the
smartphone to wireless router. (return to this
network are available, you will be asked before joining a
new network.
If Wireless LAN LED keep blinking, tap “Check”
Check
Cancel
Cancel
25
How to use
Select the air-conditioner and set the password
Select the air conditioner model to
1
register the device.
2
Set a password for new air conditioner
model to complete the registration.
Connection Guide
Step 1
Select the air-condiƟoner for registraƟon
Unregistered air-condiƟoner
Registered air-condiƟoner
3
Password must be 8-15 characters with
Step 2
CS-HZ25UKE-5
CancelRegister
Retry searching…
Retry searching…
Step 3
letters and number.
Note
• Keep password for future used on
additional user registration.
Device password settings
Step 1
Model :
CS-HZ25UKE-5
Step 2
Step 3
Connection Guide
Step 1
*If Wireless LAN LED is OFF, please press
“Wireless LAN” buƩon once to enable the
Wireless LAN before proceed for step 1 .
1. Press and hold “Wireless LAN” buƩon for 5 secs
unƟl easy seƫng “1” is shown.
2. Press “up” or “down”unƟl device registraƟon
“3” is shown.
3. Point remote cont rol to air-condiƟoner and
press “SET” buƩon once.
AŌer step 1 ~3 have been done, tap “Next”.
Step 2
Next
Cancel
Step 3
SET
CANCEL
26
Input the password to complete the registraƟon.
Password must be 8-15 characters with leƩers
and numbers.
Password
password
Re-enter password
Register
Cancel
Registration completed
1
Once connection is established between
the app and the new air conditioner
through the registration process, set the
preferred name for this air conditioner to
helps identify it.
• By registered the new name of air
conditioner, the function of “Panasonic
Comfort Cloud” app is ready to be used.
New air conditioner settings
Step 3Step 1Step 2
Model :CSHZ25UKE
-
Model :
-
CS HZ25UKE-5
Enter your preferred name for th is air-condiƟoner
Air condiƟoner name
-CS HZ25UKE-5
Register
Cancel
2
Beside operation control, this application
can monitor the estimated energy
consumption and do comparison for
different time frame by referring to the
statistic’s graph.
User’s manual can be
found under Menu tab.
My Home
Living Room
Cool
16.May 15:50
. 0
C
SET
Powerful
Quiet
2223
Statistic
25
Weekly timer
English
How to use
27
Network Adaptor Q & A
Initial setting
“Panasonic Comfort
Cloud” app cannot
be installed in
smartphone.
Air conditioner and
router cannot be
connected.
Register additional
air conditioner to
“Panasonic Comfort
Cloud” app.
Register additional
user to control the
Network Adaptor.
Wireless connection
Wireless signal is
disconnected or
interrupted.
Suspicious
unauthorized access
to the unit.
Check if OS of the smartphone is compatible.
The APP is not guaranteed to work with all versions of Android
OS.
Ensure the router’s LAN signal reaches the unit, the SSID is
not hidden, the MAC address setup is enabled for the unit, the
router’s dual band signal is enabled for 2.4GHz connection.
There is a possibility that you are using a smartphone or wireless
router that is not supported or connection method is different.
Refer to the smartphone and router installation manual for detail.
Set the additional unit setting follow to the fi rst unit initial setup.
It is recommended to name each of the registered air conditioner
units for easy to distinguish.
Download “Panasonic Comfort Cloud” app and create new
Panasonic ID.
Follow initial setting. Once the air conditioner is registered, input
the preset device password (set by fi rst user).
Approval from administrator (fi rst user) is required to complete the
registration.
For administrator approval, select the
Choose “Owner” and select “User List” to approve additional user.
There is a possibility of connection network is not stable. Check
the signal strength by:-
• Confi rm the air conditioner operation is stopped and press the
Wireless LAN
(“1” is displayed)
• Press the
• Press the
• After 5 seconds, the signal strength is shown on the indoor unit
Wireless LAN LED.
Strong: Blink 3 times with an interval
Moderate: Blink 2 times with an interval
Weak: Blink once with an interval
No signal: OFF
• It will stop automatically after 10 minutes. To stop immediately,
press the Wireless LAN
• Reset the air conditioner unit to manufacturing default condition
by referring to “To transfer or dispose the air conditioner” method
at next page. Complete by initial connection setup.
button for 5 seconds.
button until “4” is displayed.
SET
button and operation stops.
button.
Menu
.
28
Others
Replacement of router.
Change of
smartphone’s model.
Change of control
board of the indoor
unit.
Change of Network
Adaptor/Wireless LAN
module of indoor unit.
To transfer or dispose
the air conditioner.
From “Panasonic Comfort Cloud” app, select
Menu
. Choose
“Owner” and select “Change router settings”.
Ensure the smartphone compatability. Install “Panasonic
Comfort Cloud” app and login using your Panasonic login ID and
password. Complete by initial connection setup.
Change the control board and then, use “Panasonic Comfort
Cloud” app to select
Menu
. Choose “Owner” and “Replace
device”. This shall be performed by authorized service dealer.
Change the Network Adaptor/Wireless LAN module and then,
use “Panasonic Comfort Cloud” app to select
Menu
. Choose
“Owner” and “Change router settings”. This shall be performed by
authorized service dealer.
Reset the air conditioner unit to manufacturing default condition.
• Confi rm the Wireless LAN LED of the indoor unit is ON/blinking
and press the Wireless LAN
button for 5 seconds. (“1” is
displayed)
• Press the button until “5” is displayed.
• Press the
SET
button for 3 seconds and operation stops.
• The Wireless LAN LED will light off. (Factory reset complete)
To unregistered the air conditioner unit from “Panasonic Comfort
Cloud” app, select the Menu and choose “Device list” to delete the
set unit.
• It is possible to operate the indoor units individually or simultaneously. The priority of
operation is placed on the fi rst unit that turned on.
• During operation, HEAT and COOL modes cannot activate at the same time for different
indoor units.
• The power indicator blinks to indicate the indoor unit is standing by for different operation
mode.
AUTO : During operation, the POWER indicator will blinks at initial.
Single
Multi
HEAT : The POWER indicator blinks at the initial stage of this operation. Unit takes a while
COOL : Provides effi cient comfort cooling to suit your needs.
DRY: Unit operates at low fan speed to give a gentle cooling operation.
• Unit selects operation mode every 10 minutes according to the setting and room
temperatures.
• Unit selects operation mode every 3 hours according to setting temperature,
outdoor temperature and room temperature.
to warm up.
• For system which HEAT mode has been locked, if operation mode other than
HEAT is selected, the indoor unit stops and the POWER indicator blinks.
Energy saving temperature setting
Operating the unit within the recommended temperature range may save energy.
HEAT : 20.0 °C ~ 24.0 °C /
COOL : 26.0 °C ~ 28.0 °C /
68 °F ~ 75 °F.
79 °F ~ 82 °F.
Air fl ow direction
In COOL/DRY mode:
If AUTO is set, the fl ap swings left/right and up/down automatically.
In HEAT mode:
If AUTO is set, the horizontal fl ap is fi xed at the predetermined position. The vertical fl ap
swings left/right after the temperature rises.
In MILD DRY (Not applicable for Multi split system):
When vertical airfl ow direction is set to AUTO, it stops at lower position to avoid cold air
contact. However, you can adjust the fl ap direction manually.
Auto restart control
If power is resumed after a power failure, the operation will restart automatically after a
period of time with previous operation mode and airfl ow direction.
• This control is not applicable when TIMER is set.
30
Loading...
+ 86 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.