Panasonic CU3E19RBU5 User Manual

M
ulit System Outdoor Submittal Data
CU-3E19RBU-5
Multi System Outdoor Unit
Job Name: Location: Engineer: Submitted to: Submitted by: Reference:
General Data
Power (V/P/Hz) 208/230/1/60
Circuit Ampacity (A) 15 Fuse Size, Max.(A) 30
Compressor DC Twin Rotary (Inverter Driven) No. Used 1 Output Power (W) 1.30K
Outdoor Unit
Fan Type Propeller Motor Type DC Motor (8 poles) Output Power (W) 60 Airflow CFM 1447 Cooling / 1634 Heating Coil Type Aluminum (Blue Coated) Fin Type - Pipe Type Corrugated Fin Rows - F.P.I. 2 - 19 Tube Size (in) 3/8”
Approval: Date: Construction: Unit#: Drawing#:
Refrigerant R410A
R410a Pre Charge oz 93.2 oz Refrigerant Control Electronic Expansion Valve Refrigerant Tubing Connections Flare Line Length, Max (ft.) 164’ Line Height Difference, Max (ft.) 49.2’ Line Size (in. O.D. Discharge) 1/4” x 3 Line Size (in. O.D. Suction) 3/8” x 3 Pre-charge, tube length @ shipment
Dimensions (HxWxD)
Outdoor Unit (Uncrated) (in.) 31-5/16 x 34-15/32 x 12-5/8
Weight (lbs.)
(Outdoor) Net 159 lbs
98.4’
Performance Data @ AHRI Standard Conditions (208/230V)
High Heat @ 47F 26,000 BTU Low Heat @ 17F 20,800 BTU
Cooling
Total Capacity (BTU/H) 19,000 (6,100 - 24,800) Sensible Capacity (BTU/H) 18,000
Latent Capacity (BTU/H) 1,000 SEER 22 Amps (A) 7.4 - 6.7 Max. Amps (A) 15 Power Inputs (KW) 1.51 Max. Inputs (W) 1,510 Outdoor Sound Rating (dB-A) High 50
Heating
Total Capacity (BTU/H) 26,000 (5,500 - 28,400) HSPF 10.5 Amps (A) 10.1 - 9.1 Power Inputs (KW) 2,060 Outdoor Sound Rating (dB-A) 52
Operating Range
Cooling (Max) Cooling (Min) 14F DB/ - WB Heating (Max) 75.2F DB/64F WB Heating (Min)
114F DB/78F WB
-5F DB/-6.8F WB
Dimensions
Space necessary for
3-15/16 (10 cm)
Anchor Bolt Pitch
14-3/16 (360.5) x 24-9/64 (613)
<Side View> <Side View>
Unit: inch (mm)
installation
3-15/16 (10 cm)
39-3/8 (100 cm)
1-5/64
(27.5)
<Top View>
(5-5/32
(131))
<Front View>
24-9/64 (613)
34-15/32 (875)
5-5/32
(131)
15/16 (23.8)
3-3/4
(95)
2-3/64
(52)
3-17/64
1-21/32
(42)
(25)
63/64
(83)
3-19/32
1-1/2
5-7/32
1-39/64
43/64
(91.2)
(38)
(132.5)
(41)
(17)
(3-3/16
14-3/16 (360.5)
(81))
3-3/8 X 1/8 = 10-1/8
(6-37/64
2-21/64
(59)
(85.7 x 3 = 257.1)
(85.7 x 3 = 257.1)
3-3/8 X 1/8 = 10-1/8
(210))
(8-17/64
(167))
12-5/8 (320)
31-5/16 (795)
Panasonic North America Air Conditioning Division
1690 Roberts Blvd., NW, Suite 110 Kennesaw, GA 30144 us.panasonic.com/aircon