Panasonic
Spilt Wall-mounted Type
SERVICE MANUAL
Models
CS-UV5RKP/CU-UV5RKP
CS-UV9RKP/CU-UV9RKP
No.TE15030901
4. WIRING DIAGRAM ...........8
5. EXPLOSION VIEW ······12
6. PARTS LIST ·············14
CONTENTS
1. IMPORTANT NOTICE ···························· 1
2. SPECIFICATION ························ 2
3. OPERATION DETAILS ··········· 4

IMPORTANT NOTICE
This service manual is intended for use by individuals possessing adequate
backgrounds of electrical, electronic and mechanical experience. Any
attempt to repair the appliance may result in personal injury and property
damage. The manufacturer or seller cannot be responsible for the
interpretation of this information, nor can it assume any liability in
connection with its use.
The information, specifications and parameter are subject to change due to
technical modification or improvement without any prior notice. The
accurate specifications are presented on the nameplate label.
How to order spare parts
To have your order filled promptly and correctly, please furnish the
following information:
1. Model No. with Indoor or Outdoor
2. No. in the Explosion View
3. Part Name
4. The quantity you ordered
TCL Air Conditioner Service ManualTCL Air Conditioner Service ManualTCL Air Conditioner Service Manual
Air Conditioner Service Manual
1

Model
Indoor CS-UV5RKP CS-UV9RKP
Outdoor CU-UV5RKP CU-UV9RKP
Performance Test Condition
Power supply
Phase.Hz 50 50
V 220 220
Cooling
Capacity
KW 1.52 2.49
BTU/h 5200 8500
KJ/h 5512 9010
Running Current A 1.8 3.7
Input Power W 405 830
EER
W/W 3.75 3.00
Btu/h/W 12.80 10.24
Power Factor % 98 99
Indoor Noice(H/L) dB-A 37 40
Outdoor Noice(H/L) dB-A 50 50
Max Current(A)/Max Input Power (W) 2.3/520 4.8/1070
Starting Current(A) 11 20
Compressor
Type Rotary Rotary
Motor Type Single phase induction Single phase induction
Output Power W 395 660
Indoor Fan
Type Cross flow Cross flow
Material ASG30 ASG30
Motor Type PG PG
Input power W 40 27
Output power W 22 15
Speed
Lo rpm 1000 1000
Me rpm 1170 1170
Hi rpm 1270 1270
Outdoor Fan
Type Axial flow Axial flow
Material ASG20 ASG20
Motor Type AC AC
Input Power W 45 45
Output Power W 25 25
Speed HI rpm 895 895
Moisture Removal L/h(Pth) 0.55 0.56
Indoor Airflow
Lo m³/min(π³/min) 5.5 7.5
Me m³/min(π³/min) 6.7 8.5
HI m³/min(π³/min) 8 9.7
Outdoor Airflow HI m³/min(π³/min) 23.5 23.5
SPECIFICATION
Air Conditioner Service Manual
2

Model
Indoor CS-UV5RKP CS-UV9RKP
Outdoor CU-UV5RKP CU-UV9RKP
Refrigeration
Cycle
Control Device
Rotary Rotary
Refrigerant Oil cm³ 180 350
Refrigerant Type g(oz) R410A R410A
Dimension
Height(I/D / O/D) mm(Inch) 718/600 770/600
Width(I/D / O/D) mm(Inch) 240/232 240/232
Depth(I/D / O/D) mm(Inch) 180/500 180/500
Weight Net(I/D / O/D) kg(Ib
)
6.7/19.7 6.9/24.0
Paping
Pipe Diameter(Liquid / Gas) mm(Inch) 6.35/9.52 6.35/9.52
Standard length m(π) 5 5
Length range(min-max) m(π) (3-15) (3-15)
I/D & O/D Height different m(π) 5 5
Additional Gas Amount g/m(oz/) 20 20
Length for Additional Gas m(π) 12 12
Drain Hose
Inner Diameter mm 15 15
Lenghth mm 600 600
Indoor Heat
Exchanger
Fin Material Hydrophilic aluminium Hydrophilic aluminium
Fin Type window window
Row x Stage x FPI 2x 362 x16.9 2x 403 x16.9
Size(W x H x L) mm 25.4x231x544 25.4x231x604
Outdoor Heat
Exchanger
Fin Material Hydrophilic aluminium Hydrophilic aluminium
Fin Type window window
Row x Stage x FPI 1x 451 x19.5 1x 385 x16.9
Size(W x H x L) mm 588x449x11.6 602x462x18.2
Air filter
Meterial PP+ABS PP+ABS
Type Anti-dust Anti-dust
Power Supply 220V 220V
Power Supply cord A 15 15
Themostat Sensor Sensor
Protection Device OLP OLP
Indoor operation Range
Maximum
℃
Dry bulb 32 32
Wet bulb 23 23
Minimum
℃
Dry bulb 21 21
Wet bulb 15 15
Outdoor operation Range
Maximum
℃
Dry bulb 43 43
Wet bulb 26 26
Minimum
℃
Dry bulb 21 21
Wet bulb 15 15
Air Conditioner Service Manual
3

Air Conditioner Service Manual
REMOTE CONTROL INSTRUCTION
Note: Each mode and relevant function will be further specified in following pages.
Remote Control
The remote controller is not presetted as Cooling Only Air Conditioner or Heat Pump by
manufacturer.Each time after the remote controller replace batteries or is energized, the arrowhead
will flashes on the front of Heator Coolon LCD of the remote controller.User can preset the
remote controller type depending on the air conditioner type you have purchased as follows:Press
any button when the arrowhead flashes on the front of Cool , Cooling Only is set.Press any button
when the arrowhead flashes on the front of Heat, Heat Pump is set.If you dont press any button
within 10 seconds, the remote controller is preset as Heat Pump automatically.Note :If the air
conditioner you purchased is a Cooling Only one, but you preset the remote controller as Heat
Pump, it doesnt bring any matter. But if the air conditioner you purchased is a Heat Pump one, and
you preset the remote controller as Cooling Only, then you CAN NOT preset the Heating
operation with the remote controller.
4

Air Conditioner Service Manual
Electronic controller
NOTES:
RT-------Room Temperature.
IPT------Indoor Pipe Temperature.
ST------indoor Setting Temperature.
OPT---Outdoor Pipe Temperature.
CRT---Compensated Room Temperature
1) The initial RT determines A/C working mode and setting temperature (ST), the mode is
determined effective only once unless A/C shut-down then re-started. If from other modes
switches to automatic mode (including mode conversion after shutdown), it should be that the
compress stop more than 3 min then temperature judgment and automatic mode are conducted (it
can conduct immediately from fan mode switched to automatic, the indoor fan stops, three minutes
later the response is made and start up). Within 3 min, the output as: Showing the room
temperature, indoor fans starts (or anti-cold airflow), the outdoor fan stops;
2) With auto re-start controller, once being turned off or in case of an accidently power cut, the A/C is
able to retain and restore the original mode when being turned on or the power supply is resumed,
if the auto restart function activated. power-down after power-on; while if the auto restart function
isn’t activated, the A/C enters standby state.
Cooling-only
Under automatic mode (including from automatic converted into Dry mode), when the temperature
UP or DOWN signals from the remote controller is received, the setting temperature ST adjusts
correspondingly to the current room temperature plus or minus 1℃, the automatic regulating
temperature range is ± 2℃.
2.Cooling mode
1) The control of the compressor
a.
When RT-ST≥1℃,the compressor is running.
b.
When RT-ST<-1℃,the compressor is off.
c.
When -1℃≤RT-ST<1℃, the compressor keeps its original state.
2) Outdoor fan motor and the compressor run simultaneously (except for defrosting).
3) The control of indoor fan motor:
a.
Indoor fan motor can operate by automatic, low, middle, and high airflow speed circularly.
b.
Indoor fan motor automatic airflow speed control, it works as shown in Figure 1:
Figure 1 Cooling automatic airflow
When the temperature change leads the fan speed variation, the switch can only be made orderly,
and every grade of air flow speed runs 1 minute at least.

Air Conditioner Service Manual
3. Dry mode
While select to this mode, the air conditioner operates for 3 minutes according to cooling mode firstly
(ST set at 7℃) , and then takes the detected backflow air temperature minus 2℃ as a new set
temperature (the minimum value of 5℃) and runs according to cooling mode, indoor fan operates at
low-speed, at this moment the setting operation of Fan speed is invalid but Swing is adjustable.
4. Fan mode
1) Indoor fan motor is running at setting speed (the speed is same as that of heating).
2) Vane motor control: running according to the setting condition.
3) The outdoor unit doesn’t work under fan mode.
1) Under sleep mode, the indoor fan motor is running at a low speed, except that the power light
and sleep light are on, timer light is on/off according to the setting state, running light is off. LED will
be off after displaying 30S.
(1) From Cool mode to Sleep mode, one hour later, the operates Temp.=ST+1°C,another one
hour later, the operates Temp.=ST+2°C,after then unchanged.
(2) From Heating mode to Sleep mode, one hour later, the operates Temp.= ST-1°C,another one
hour later, the operates Temp.=ST-2°C,after then unchanged.
3) the machine will automatically shut up after running 10 hours under sleep mode.
Timer on start-up and sleep mode are implemented at the same time, and the sleep mode can not be
functioned.
The timing scale is between 10min to 24h, when the time fixed is less than “10” hours, the displayed
time is shown by 0.5 hour as the unit, when the time fixed is more than or equal to “10” hours, the
displayed time is shown by 1 hour as the unit.
7. Emergency switch. (ON/OFF)
1) When stand-by, to operate by pressing the emergency switch as follows:
To Press the emergency switch in three seconds, the buzzer rings once, and to release, the machine
runs into cooling mode; if to holding on, the buzzer rings twice, then the machine runs into heating
mode, while when the machine is on, to press the Emergency switch, the buzzer rings once and then
the machine shut down.
2) The machine is running mandatorily as the selected mode within 30min after emergency operation,
indoor fan motor running in high-speed, and stepping vane swinging. The machine runs into
automatic mode 30min later, the selected mode unchanged, the set temperature to be 23° C, the
rotate speed of indoor fan motor is automatic, and stepping vane swinging also.
3) To press the emergency button when the machine operating, then the machine runs into stand-by.
4) Under emergency operation, the function of Compressor’s time-delay protection, anti-frosting
protection in cooling mode, Overheating protection in heating mode, sensor fault protection and
defrost operate are effective.
5) Under emergency operation, once effective signal from remote controller is received, then the
A/C exits form the emergency mode, and operate according to the setting value from remote controller.
1) The PCB retains the setting parameters in case of power off. When the power supply is resumed,
the machine, which has been started up the power-off memory function, is able to restore into the

Air Conditioner Service Manual
original running state automatically.
2) To press the emergency button and power on the unit, and hold on f o r 10 seconds, The buzzer
will ring three times, after this operation, the auto restart function is activated
3) To close auto restart function while it is activated, repeat process as above 2), the buzzer will ring
9. Protection/ Troubleshooting.
1) Compressor’s protection:
a.The PCB which has Auto-restart function, once this function is started up, the compressor goes
along 3min delay protection when power on. If the PCB hasn’t been started up Auto-restart
function, even when the PCB is power-on, the compressor doesn’t process 3 min delay function.
b.The compressor’s 3 min interval protection: the compressor can’t start-up until it stops 3 min later.
(except for defrosting process).
c.After the compressor started, the compressor’s state isn’t subjected to the changes on ST,RT in 3min.
2) Anti-frosting protection of indoor evaporator (cooling mode):
If IPT ≤ 0 ℃ detected in consecutive 3 min, compressor and outdoor fan motor stopped, indoor fan
motor runs at high-speed forcibly; if IPT ≥ 5 ℃ detected 3min later, then outdoor fan mot or a n d
co m pr es s o r activated, indoor fan motor restores the original state.
3) The following table shows the fault protections. When failures happens, the PCB alarms and
buzzer rings three times. Failure code appears, and the PCB operates protection procedures.
Failure code: For the machine with LED display, the code shows on LED, for machine without LED,
the code reflects by the running light.
When failure happened, the code is displayed statically, if there are several failure codes should be
reported at the same time, then failure codes appears one by one every eight seconds
correspondingly.
a.
Sensor’s failure protection: when the sensor’s temperature is out of the range -50 ≤ T ≤ 110 ℃,
then sensor failure is determined. Once RT, IPT sensor failures appear, the compressor stops and
indoor and outdoor fan motors shut off. Remote controller doesn’t response to any signal except for
shutdown. During failure the machine can run in fan mode. After the failure is settled, the PCB
restores to standby status.
b.
Failure protection of Indoor PG fan motor: If there is no feedback signal of rotate speed within 5s,
the indoor fan motor stops, meanwhile, the compressor, outdoor fan motor, four-way valve and
auxiliary electric heater etc. cut down. 10 seconds later, the indoor fan motor restarts again, once
there is no feedback signal of rotate speed within 5 seconds either, then the machine stops and
goes into indoor fan motor failure protection, buzzer rings three times, and running light flashes at 6
times per 8 seconds. When the failure is confirmed, once there is feedback signal, the failure is
relieved automatic.

Air Conditioner Service Manual
WIRING DIAGRAM
INDOOR UNIT:CS-UV5RKP CS-UV9RKP
OUTDOOR UNIT:CU-UV5RKP CU-UV9RKP