Panasonic cs-re18skua, cs-re24skua installation

PRINTED IN MALAYSIA
ACXF60-01100
ENGLISH
Is there any gas leakage at fl are nut
connections?
Has the heat insulation been carried out at fl are
nut connection?
board fi rmly?
Is the connection cable being clamped fi rmly?
Is the drainage ok?
(Refer to “Check the drainage” section)
Is the earth wire connection properly done?
Is the indoor unit properly hooked to the
installation plate?
Is the power supply voltage complied with rated
value?
Is there any abnormal sound?
Is the cooling operation normal?
Is the thermostat operation normal?
Is the remote control’s LCD operation normal?
CHECK ITEMS
Connecting The Piping to Indoor
PUSH PUSH
PUSH PUSH
3 4
5
6
ACXF60-01100
Required tools for Installation Works
1 2
HOW TO FIX INSTALLATION PLATE
The mounting wall must be strong and solid enough to prevent it from the vibration.
SELECT THE BEST LOCATION
(Refer to “Select the best location” section)
The center of installation plate should be at more than 1 at right and left of the wall. The distance from installation plate edge to ceiling should more than 2. From installation plate left edge to unit’s left side is 3. From installation plate right edge to unit’s right is 4.
b : For left side piping, piping connection for liquid should be about 5 from this line.
: For left side piping, piping connection for gas should be about 6 from this line.
1. Mount the installation plate on the wall with 5 screws or more (at least 5 screws). (If mounting the unit on the concrete wall, consider using anchor bolts.)
Always mount the installation plate horizontally by aligning the marking-off line with the thread and using a level gauge.
2. Drill the piping plate hole with ø2 3/4" (ø70 mm) hole-core drill.
Line according to the left and right side of the installation plate. The meeting point of the extended line is the center of the hole. Another method is by putting measuring tape at position as shown in the diagram above. The hole center is obtained by measuring the distance namely 5 1/16" (128 mm) for left and right hole respectively.
Drill the piping hole at either the right or the left and the hole should be slightly slanting to the outdoor side.
AB
C
D
CUTTING AND FLARING THE PIPING
1. Please cut using pipe cutter and then remove the burrs.
2. Remove the burrs by using reamer. If burrs is not removed, gas leakage may be caused. Turn the piping end down to avoid the metal powder entering the pipe.
3. Please make fl are after inserting the fl are nut onto the copper pipes.
1. To cut
When properly fl ared, the internal surface of the fl are will evenly shine and be of even thickness. Since the fl are part comes into contact with the connections, carefully check the fl are fi nish.
Improper fl aring
Inclined
Surface
damaged
Cracked Uneven
thickness
3. To fl are
Bar
Red arrow mark
Handle
Core
Yok e
Clamp handle
Bar
0 –
1
/32"
(0 - 0.5 mm)
Copper pipe
Reamer
2. To remove burrs
Point down
Pipe
TO DRILL A HOLE IN THE WALL AND INSTALL A SLEEVE OF PIPING
19
/32" (15 mm)
Putty or caulking compound
ø2
3
/4" (ø70 mm)
through hole
Indoor
Outdoor
Sleeve for tube assembly
Approx. 7/32" - 9/32" (5 - 7 mm)
Bushing for tube assembly
Wall
CONNECT THE CABLE TO THE INDOOR UNIT
5
1. The inside and outside connection cable can be connected without
removing the front grille.
2. Unscrew the conduit cover and fi x the conduit connector to conduit
cover with lock nut, then secure it against chassis.
3. Connecting wire between indoor unit and outdoor unit should be
UL listed or CSA approved 4 conductor wires minimum AWG16 in accordance with local electric codes.
Ensure the colour of wires of outdoor unit and terminal number are the same as the indoor's repectively.
WARNING
This equipment must be properly earthed.
Earth lead wire shall be Yellow/Green (Y/G) in colour and shall be longer than other lead wires as shown in the fi gure for electrical safety in case of the slipping.
Earth Wire longer than others AC wires for safety reason
Terminal Board
Holder
Indoor and outdoor connection cable
3
Please follow the steps below to take out front grille if necessary such as when servicing.
1. Set the vertical airfl ow direction louvers to the horizontal position.
2. Slide down the 3 caps on the front grille as shown in the illustration at right, and then remove the 4 mounting screws.
3. Pull the lower section of the front grille towards you to remove the front grille.
Open front panel and remove air fi lters. (Drainage checking can be carried out without removing the front grille.)
Pour a glass of water into the drain tray-styrofoam.
Ensure that water fl ows out from drain hose of the indoor unit.
Operate the unit at cooling/heating operation mode for fi fteen minutes or more.
Measure the temperature of the intake and discharge air.
Ensure the difference between the intake temperature and the discharge is more than 46.4°F (8°C) during Cooling operation or more than 57.2°F (14°C) during Heating operation.
Discharge air
1 Philips screw driver 2 Level gauge 3 Electric drill, hole core drill (ø2
3
/4"(ø70 mm))
4 Hexagonal wrench (
5
/32" (4 mm)) 5 Spanner 6 Pipe cutter
7 Reamer 8 Knife 9 Gas leak detector 10 Measuring tape 11 Thermometer 12 Megameter
13 Multimeter 14 Torque wrench
13.3 Ibf•ft (18 N•m (1.8 kgf•m))
31.0 Ibf•ft (42 N•m (4.3 kgf•m))
40.6 Ibf•ft (55 N•m (5.6 kgf•m))
47.9 Ibf•ft (65 N•m (6.6 kgf•m))
73.8 Ibf•ft (100 N•m (10.2 kgf•m)) 15 Vacuum pump 16 Gauge manifold
Wall
Wall
Wall
Installation plate 1
2 screw
More than 1
More than 1
Measuring Tape
Indoor unit
9 17/32"
(241.5 mm)
Drain tray­styrofoam
3
CONNECT THE PIPING
Please make fl are after inserting fl are nut (locate at joint portion of tube assembly) onto the copper pipe. (In case of using long piping)
Connect the piping
Align the center of piping and suffi ciently tighten the fl are nut with fi ngers.
Further tighten the fl are nut with torque wrench in specifi ed torque as stated in the table.
Decide piping length and then cut by using pipe cutter. Remove burrs from cut edge. Make fl are after inserting the fl are nut (locate at valve) onto the copper pipe. Align center of piping to valve and then tighten with torque wrench to the specifi ed torque as stated in the table.
Torque wrench
Spanner or Wrench
More than
2
2
9
/
16
"
(65 mm)
or more
8 ft (2.4 m)
or more
(Left and right are identical)
Floor / Grade level
• Carry out insulation after checking for gas leaks and secure with vinyl tape.
Vinyl tape
This illustration is for
explanation purposes only.
The indoor unit will actually face
a different way.
It is advisable to avoid more than 2 blockage directions. For better ventilation & multiple-outdoor installation, please consult authorized dealer/specialist.
Installation plate 1
Sleeve (
)
Bushing-Sleeve (
)
Bend the pipe as closely on the wall as possible, but be careful that it doesn’t break.
Saddle (
)
Example: For RE18SKUA If the unit is installed at 41 ft (12.5 m) distance, the quantity of additional
refrigerant should be 3.28 oz (100 g) .... (41 - 24.6) ft x 0.2 oz/ft = 3.28 oz.
((12.5 - 7.5) m x 20 g/m = 100 g).
Conduit (Power supply cord ())
Attached accessories
Control Board cover
Remote control holder fi xing screws
6
Remote control holder
5
Remote control
3
Additional drain hose
Gas side piping (
)
Conduit (Connection cable)
Putty (
)
(Gum Type Sealer)
Installation parts you should purchase ()
Vinyl tape (wide) ()
• Apply after carrying out a drainage test.
• To carry out the drainage test, remove the air fi lters and pour water into the heat exchanger.
Liquid side piping (
)
Chassis
Conduit Connector
Conduit Cover
Lock Nut
Rear Side of Indoor Unit
Pressure test to system to 400 PSIG with dry nitrogen, in stages. Thoroughly leak check the system. If the pressure holds, release the nitrogen and proceed to section 4.
WARNING
Do not install outdoor unit near handrail of veranda. When installing air-conditioner unit on veranda of a high rise building, child may climb up to outdoor unit and cross over the handrail causing an accident.
Do not use unspecifi ed cord, modifi ed cord, joint cord or extension cord for power supply cord. Do not share the single outlet with other electrical appliances. Poor contact, poor insulation or over current will cause electrical shock or fi re.
Do not tie up the power supply cord into a bundle by band. Abnormal temperature rise on power supply cord may happen.
Do not insert your fi ngers or other objects into the unit, high speed rotating fan may cause injury.
Do not sit or step on the unit, you may fall down accidentally.
Keep plastic bag (packaging material) away from small children, it may cling to nose and mouth and prevent breathing.
When installing or relocating air conditioner, do not let any substance other than the specifi ed refrigerant, eg. air etc. mix into refr igeration cycle (piping). Mixing of air etc will cause abnormal high pressure in refrigeration cycle and result in explosion, injury etc.
Do not add or replace refrigerant other than specifi ed type. It may cause product damage, burst and injury etc.
For R410A model, use piping, fl are nut and tools which is specifi ed for R410A refrigerant. Using of existing (R22) piping, fl are nut and tools may cause abnormally
high pressure in the refrigerant cycle (piping), and possibly result in explosion and injury.
Thickness for copper pipes used with R410A must be more than 1/32"
(0.8 mm)
. Never use copper pipes thinner than 1/32" (0.8 mm).
It is desirable that the amount of residual oil is less than 0.0008 oz/ft (40 mg/10 m).
Engage authorized dealer or specialist for installation. If installation done by the user is incorrect, it will cause water leakage, electrical shock or fi re.
Install according to this installation instructions strictly. If installation is defective, it will cause water leakage, electrical shock or fi re.
Use the attached accessories parts and specifi ed parts for installation. Otherwise, it will cause the set to fall, water leakage, fi re or electrical shock.
Install at a strong and fi rm location which is able to withstand the set’s weight. If the strength is not enough or installation is not properly done, the set will drop and cause injury.
For installation work, follow all electrical, building, plumbing, local codes, regulations and these installation instructions. If electrical circuit capacity is not enough or a defect is found in electrical work, it will cause electrical shock or fi re.
Do not use spliced wires for indoor / outdoor connection cable. Use the specifi ed indoor / outdoor connection cable, refer to instruction 5 INDOOR/OUTDOOR UNIT ELECTRICAL WIRING and connect tightly for indoor/outdoor connection. Clamp the cable so that no external force will have impact on the terminal. If connection or fi xing is not perfect, it will cause heat-up or fi re at the connection.
Wire routing must be properly arranged so that control board cover is fi xed properly. If control board cover is not fi xed perfectly, it will cause fi re or electrical shock.
This equipment must installed with an Earth Leakage Circuit Breaker (ELCB) or Ground Fault Current Interrupter (GFCI) or Appliance Leakage Current Interrupter (ALCI) that has been certifi ed by an NRTL Certifi ed Testing Agency and that is suitable for the voltages and amperages involved. Otherwise, if may cause electrical shock and fi re in case of equipment breakdown.
During installation, install the refrigerant piping properly before running the compressor. Operation of compressor without fi xing refrigeration piping and valves at opened condition will cause suck-in of air, abnormal high pressure in refrigeration cycle and result in explosion, injury etc.
During pump down operation, stop the compressor before removing the refrigeration piping. Removal of refrigeration piping while compressor is operating and valves are opened will cause suck-in of air, abnormal high pressure in refrigeration cycle and result in explosion, injury etc.
Tighten the fl are nut with torque wrench according to specifi ed method. If the fl are nut is over-tightened, after a long period, the fl are may break and cause refrigerant gas leakage.
After completion of installation, confi rm there is no leakage of refrigerant gas. It may generate toxic gas when the refrigerant comes into contact with fi re.
Ventilate if there is refrigerant gas leakage during operation. It may cause toxic gas when the refrigerant comes into contact with fi re.
This equipment must be properly earthed. Earth line must not be connected to gas pipe, water pipe, earth of lightning rod and telephone. Otherwise, it may cause electrical shock in case of equipment breakdown or insulation breakdown.
CAUTION
Do not install the unit at place where leakage of fl ammable gas may occur. In case gas leaks and accumulates at surrounding of the unit, it may cause fi re.
Do not release refrigerant during piping work for installation, re-installation and during repairing a refrigeration parts. Take care of the liquid refrigerant, it may cause frostbite.
Do not install this appliance in a laundry room or other location where water may drip from the ceiling, etc.
Do not touch the sharp aluminium fi n, sharp parts may cause injury.
Carry out drainage piping as mentioned in installation instructions. If drainage is not perfect, water may enter the room and damage the furniture.
Select an installation location which is easy for maintenance.
Power supply connection to the room air conditioner. Power supply cord shall be UL listed or CSA approved 3 conductor with minimum AWG12 wires. Power supply point should be in an easily accessible place for power disconnection in case of emergency. In some countries, permanent connection of this air conditioner to the power supply is prohibited. Fix power supply connection to a circuit breaker for the permanent connection. Use NRTL approved fuse or circuit breaker (rating refers to name plate) for the permanent connection.
Installation work. It may take two people to carry out the installation work.
 Do not install the unit in excessive oil fume areas such as kitchens,
workshops etc.
 There should not be any heat source or steam near the unit.  There should not be any obstacles blocking the air circulation.  A place where air circulation in the room is good.  A place where drainage can be easily done.  A place where noise prevention is taken into consideration.  Do not install the unit near a doorway.  Ensure the spaces indicated by arrows from the wall, ceiling, fence
or other obstacles.
 Recommended installation height for indoor unit shall be at least
8 ft (2.4 m).
 If an awning is built over the unit to prevent direct sunlight or rain,
be careful that heat radiation from the condenser is not obstructed.
 There should not be any animal or plant which could be affected by
hot air discharged.
 Keep the spaces indicated by arrows from wall, ceiling, fence or
other obstacles.
 Do not place any obstacles which may cause a short circuit of the
discharged air.
 If piping length is over the [piping length for additional gas],
additional refrigerant should be added as shown in the table.
 Recommended installation height for outdoor unit should be above
the seasonal snow level.
 Be careful not to locate outdoor unit directly under a roof line where
falling snow or ice can cause damage or dripping water can increase ice accumulation and defrost cycles.
INDOOR UNIT
OUTDOOR UNIT
SELECT THE BEST LOCATION
Model
Capacity
(Btu/h)
Piping size
Std.
Length
Max.
Elevation
Min. Piping Length
Max. Piping Length
Additional
Refrigerant
Piping Length
for add.
gas
Gas Liquid
RE18SKUA
17200
1/2"
(
12.7 mm) 1/4"
(
6.35 mm)
24.6 ft (
7.5 m)
49.2 ft (
15 m)
9.8 ft
(
3 m)
65.6 ft (
20 m)
0.2 oz/ft (
20 g/m)
24.6 ft
(
7.5 m)
RE24SKUA
22000
5/8"
(
15.88 mm)
Piping direction Attention not to bend
up drain hose
(Front side)
Right Rear
Right bottom
Left Rear
Left bottom
Left
Indoor/Outdoor Unit Installation Diagram
Insulation of piping connections
Attaching the remote control holder to the wall
Model
Dimension
123456
RE18SKUA, RE24SKUA
23
7
/32"
(590 mm)
3 7/32"
(82 mm)
21 7/32"
(539 mm)
20 15/16"
(532 mm)
6 21/32"
(169 mm)
8 5/8"
(219 mm)
Model A B C D
RE18SKUA, RE24SKUA
24 1/8"
(613 mm)
5 5/32"
(131 mm)
5/8"
(16 mm)
14 3/16"
(360.5 mm)
HOW TO TAKE OUT FRONT GRILLE
When reinstalling the front grille, fi rst set the vertical airfl ow direction louver to the horizontal position and then carry out above steps 2 - 3 in the reverse order.
AUTO SWITCH OPERATION
CHECK THE DRAINAGE
EVALUATION OF THE PERFORMANCE
Connecting The Piping to Outdoor
Gas Leak Checking
Do not overtighten, over tightening may cause gas leakage.
Piping size Torque
1/4" (6.35 mm) 13.3 Ibf•ft [18 N•m (1.8 kgf•m)]
3/8" (9.52 mm) 31.0 Ibf•ft [42 N•m (4.3 kgf•m)]
1/2" (12.7 mm) 40.6 Ibf•ft [55 N•m (5.6 kgf•m)]
5/8" (15.88 mm) 47.9 Ibf•ft [65 N•m (6.6 kgf•m)]
3/4" (19.05 mm) 73.8 Ibf•ft [100 N•m (10.2 kgf•m)]
No. Accessories part Qty. No. Accessories part Qty.
1
Installation plate
1
5
Remote control holder
1
2
Installation plate fi xing screw
5
6
Remote control holder fi xing screw
2
3
Remote Control
1
7
Drain elbow
1
4
Battery
2
8
Drain hose adapter
1
1. Connect a charging hose with a push pin to the Low side of a charging set and the service port of the 3-way valve.
2. Connect the micron gauge between vacuum pump and service port of outdoor units.
3. Turn on the power switch of the vacuum pump and make sure that connect digital micron gauge and to pull down to a value of 500 microns.
4. To make sure micron gauge a value 500 microns and close the low side valve of the charging set and turn off the vacuum pump.
5. Disconnect the vacuum pump house from the service port of the 3-way valve.
6. Tighten the service port caps of the 3-way valve at a torque of 13.3 Ibf•ft (18 N•m) with a torque wrench.
7. Remove the valve caps of both of the 2-way valve and 3-way valve. Position both of the valves to “Open” using a hexagonal wrench (5/32" (4 mm)).
8. Mount valve caps onto the 2-way valve and the 3-way valve.
Be sure to check for gas leakage.
WHEN INSTALLING AN AIR CONDITIONER, BE SURE TO EVACUATE THE AIR INSIDE THE INDOOR UNIT AND PIPES in the following procedure.
4
EVACUATION OF THE EQUIPMENT
Gas side
Liquid side
Outdoor unit
Three-way valve
Indoor unit
Vacuum
pump
Close
Close
If micron gauge value does not descend 500 microns, take the following measures:
- If the leak stops when the piping connections are tightened further, continue working from step 3.
- If the leak does not stop when the connections are retightened, repair location of leak.
- Do not release refrigerant during piping work for installation and reinstallation.
- Be careful with the liquid refrigerant, it may cause frostbite.
Two-way valve
The below operations will be performed by pressing the “AUTO” switch.
1. AUTO OPERATION MODE The Auto operation will be activated immediately once the Auto Switch is pressed
and released before 5 sec..
2. TEST RUN OPERATION (FOR PUMP DOWN/SERVICING PURPOSE) The Test Run operation will be activated if the Auto Switch is pressed continuously for
more than 5 sec. to below 8 sec..
A “pep” sound will occur at the fi fth sec., in order to identify the starting of Test Run
operation.
3. HEATING TRIAL OPERATION Press the “AUTO” switch continuously for more than 8 sec. to below 11 sec. and release when a “pep
pep” sound is occured at eight sec. (However, a “pep” sound is occurred at fi fth sec..) then press Remote controller “A/C Reset” button once. Remote controller signal will activate operation to force heating mode.
4. REMOTE CONTROLLER RECEIVING SOUND ON/OFF The ON/OFF of Remote controller receiving sound can be change over by the following steps: a) Press “AUTO” switch continuously for more than 16 sec. to below 21 sec..
A “pep”, “pep”, “pep”, “pep” sound will occur at the sixteenth sec..
b) Press the “A/C Reset” button once. Remote controller signal will activate the Remote controller sound
setting mode.
c) Press the “AUTO” switch once to select Remote controller receiving sound ON/OFF. A “peep” sound
indicates receiving sound ON, and a “pep” sound indicates receiving sound OFF.
If a drain elbow is used, the unit should be placed on a stand
which is taller than 1
3
/16" (30 mm).
If the unit is used in an area where temperature falls below
32°F (0°C) for 2 or 3 days in succession, it is recommended not to use a drain elbow, for the drain water freezes and the fan will not rotate.
Hose
Drain elbow 7
Install the hose at an angle so that the water smoothly fl ows out.
DISPOSAL OF OUTDOOR UNIT DRAIN WATER
1
31
/
32
"
(50 mm)
or more
3
15
/
16
"
(100 mm)
or more
3
15
/
16
"
(100 mm)
or more
39
3
/
8
"
(1000 mm)
or more
11
13
/
16
"
(300 mm)
or more
5 1/16"
(128 mm)
9
17
/32
(241.5 mm)
5
1
/16"
(128 mm)
5 1/16" (128 mm)
Applicable piping kit
Piping size
Gas Liquid
CZ-3F5, 7BP 3/8" (9.52 mm) 1/4" (6.35 mm)
CZ-4F5, 7, 10BP 1/2" (12.7 mm) 1/4" (6.35 mm)
CZ-52F5, 7, 10BP 5/8" (15.88 mm) 1/4" (6.35 mm)
SAFETY PRECAUTIONS
Read the following “SAFETY PRECAUTIONS” carefully before installation.
Electrical work must be installed by a licensed electrician. Be sure to use the correct rating of the power plug and main circuit for the model to be installed.
The caution items stated here must be followed because these important contents are related to safety. The meaning of each indication used is as below. Incorrect installation due to ignoring of the instruction will cause harm or damage, and the seriousness is classifi ed by the following indications.
WARNING
This indication shows the possibility of causing death or serious injury.
CAUTION
This indication shows the possibility of causing injury or damage to properties only.
The items to be followed are classifi ed by the symbols:
Symbol with white background denotes item that is PROHIBITED.
Symbol with dark background denotes item that must be carried out.
Carry out test running to confi rm that no abnormality occurs after the installation. Then, explain to user the operation, care and maintenance as stated in instructions. Please remind the customer to keep the operating instructions for future reference.
Cover for the bottom piping
Tape it with piping in a position as mentioned
in Fig. below.
Cover for the right piping
Piping
Drain hose
Cover for the left piping
Drain hose
Sleeve for piping hole
Indoor unit
Hooks at installation plate
Piping
1. FOR THE RIGHT REAR PIPING
Cover for the
bottom piping Cover for the bottom piping
Tape it with piping
in a position as
mentioned in Fig.
below.
Piping
Drain hose
Cover for the left piping
Cover for piping
In case of the cover is cut, keep the cover at the rear of chassis as shown in the illustration for future reinstallation. (Left and 2 bottom covers for piping.)
How to keep the cover
marking
Installation plate
Unit’s hook
Guide surface
Connection cable
About
2
3
/
4
" - 3
5
/
32
"
(70 - 80 mm)
Connection cable
Gas side piping
Liquid side piping
Drain hose
2. FOR THE RIGHT BOTTOM PIPING
3. FOR THE EMBEDDED PIPING
(This can be used for left rear piping and bottom piping also.)
Right Rear piping
Right and Right Bottom piping
Install the indoor unit
Hook the indoor unit onto the upper portion of installation plate. (Engage the indoor unit with the upper edge of the installation plate). Ensure the hooks are properly seated on the installation plate by moving it in left and right.
Insert the connection cable
Secure the Indoor Unit
1. Press the lower left and right side of the unit against the installation plate until hooks engages with their slot (sound click).
To take out the unit, push
the
marking at the bottom unit, and pull it slightly towards you to disengage the hooks from the unit.
Step-1
Pull out the Indoor piping
Step-2
Install the Indoor Unit
Step-3
Secure the Indoor Unit
Step-4
Insert the connection cable
Step-1
Pull out the Indoor piping
Step-2
Install the Indoor Unit
Step-3
Insert the connection cable
Step-4
Secure the Indoor Unit
Step-1
Replace the drain hose
Step-2
Bend the embedded piping
• Use a spring bender or equivalent to bend the piping so that the piping is not crushed.
Step-3
Pull the connection cable into Indoor Unit
• The inside and outside connection cable can be connected without removing the front grille.
Step-4
Cut and fl are the embedded piping
• When determining the dimensions of the piping, slide the unit all the way to the left on the installation plate.
• Refer to the section “Cutting and fl aring the piping”.
Step-5
Install the Indoor Unit
Step-6
Connection the piping
• Please refer to “Connecting the piping” column in outdoor unit section. (Below steps are done after connecting the outdoor piping and gas-leakage confi rmation.)
Step-7
Insulate and fi nish the piping
• Please refer to “Piping and fi nishing” column of outdoor section and “Insulation of piping connection” column as mentioned in indoor/outdoor unit installation.
Step-8
Secure the Indoor Unit
How to pull the piping and drain hose out, in case of the embedded piping.
In case of left piping how to insert the connection cable and drain hose.
2 27/32" (72 mm)
More than
18
1
/
2
" (470 mm)
More than
45
9
/
32
"
(1150 mm)
More than 27
9
/16"
(700 mm)
Indoor unit drain hose
3/4" (20 mm) nominal PVC pipe
- Install incline downward more than 1°
- Apply PVC glue at the join.
Drain hose adapter
8
Close join by Vinyl Tape ( )
Remarks : Make sure indoor unit drain hose & 3/4" (20 mm) nominal PVC pipe are fully inserted to drain hose adapter
8
.
Rear view for left piping installation
Drain cap
Drain hose
Adjust the piping slightly downwards.
Drain hose
Connection cable
PVC tube for drain hose
Indoor unit
Piping
Cable
Apply putty or caulking material to seal the wall opening.
Connection cable
Piping
PVC tube (VP-65) for piping and connection cable
PVC tube for drain hose (VP-30)
PVC tube for drain hose (VP-20)
Drain hose from main unit
Replace the drain hose
Cable
45°
Drain hose
Piping
Sleeve for piping hole
Drain hose
Piping
Connection cable
More than 45
9
/32"
(1150 mm)
(For the right piping, follow the same procedure)
Join indoor drain hose to 3/4" (20 mm) nominal PVC pipe size by using drain hose adapter
8
when necessary.
Drain hose adapter 8 usage
INDOOR UNIT INSTALLATION
4
1. Please carry out insulation at pipe connection portion as mentioned in Indoor/Outdoor Unit Installation Diagram. Please wrap the insulated piping end to prevent water from going inside the piping.
2. If drain hose or connecting piping is in the room (where dew may form), please increase the insulation by using POLY-E FOAM with thickness 1/4" (6 mm) or above.
PIPING INSULATION
6
After selecting the best location, start installation to Indoor/Outdoor Unit Installation Diagram.
1. Fix the unit on concrete or rigid frame fi rmly and horizontally by bolt nut ø
13
/32" (ø10 mm).
2. When installing at roof, please consider strong wind and earthquake. Please fasten the installation stand fi rmly with bolt or nails.
SELECT THE BEST LOCATION
(Refer to “Select the best location” section)
1
INSTALL THE OUTDOOR UNIT
2
INDOOR UNIT
OUTDOOR UNIT
1. Insert the piping sleeve to the hole.
2. Fix the bushing to the sleeve.
3. Cut the sleeve until it extrudes about 19/32" (15 mm) from the wall.
CAUTION
When the wall is hollow, please be sure to use the sleeve for tube assembly to prevent dangers caused by mice biting the connection cable.
4. Finish by sealing the sleeve with putty or caulking compound at the fi nal stage.
Terminals on the indoor unit 1 2 3
Colour of wires (Connecting wire)
Terminals on the outdoor unit 1 2 3
For best strength of INDOOR unit installation, it is highly recommended to locate “ ” at 5 position as shown.
WARNING
RISK OF FIRE
JOINING OF WIRES MAY CAUSE OVERHEATING AND FIRE.
OR
OR
OR
Wire stripping
No loose strand when inserted
WIRE STRIPPING, CONNECTING REQUIREMENT
Conductor
fully inserted
Conductor
over inserted
Conductor not
fully inserted
ACCEPT PROHIBITED PROHIBITED
Use complete wire without joining.
Use approved socket and plug with earth pin.
Wire connection in this area must follow to national wiring rules.
Do not joint wires
13/32" ± 1/16"
(10±1 mm)
Indoor/outdoor connection terminal board
7
/32" (5 mm)
or more
(gap between wires)
Piping
Piping
Shock absorber
Intake grille
Do not turn over the unit without it’s shock absorber during pull out the piping.
It may cause intake grille damage.
Use shock absorber during pull out the piping to protect the intake grille from damage.
p
u
l
l
o
u
t
t
h
e
p
i
p
i
n
g
p
u
l
l
o
u
t
t
h
e
p
i
p
i
n
g
Cap
Screw
(Move the vane to upward)
Vane
Cap
Vane
Front grille
CONNECT THE CABLE TO THE OUTDOOR UNIT
5
1. Remove control board cover (Resin and Metal).
2. Remove particular plate.
3. Remove plugs.
4. Fix the conduit connectors to the knockout holes with lock-nuts, then secure them against the side panel.
5. All wires pass through conduits & particular plate’s opening hole.
6. Connecting wire between indoor unit and outdoor unit should be UL listed or CSA approved 4 conductor wires minimum AWG16 in accordance with local electric codes.
7. Wire connection to the power supply (208/230V 60Hz) through circuit breaker.
Connect the UL listed or CSA approved wires minimum AWG14 to the terminal board, and connect the other end of the wires to ELCB / GFCI.
8. Connect the power supply cord and connecting wire between indoor unit and outdoor unit according to the diagram below.
9. Secure the wire onto the control board with the holder (clamper).
10. After completing wiring connections, reattach the particular plate and control board cover (metal and resin) to the original position with the screws.
11. For wire stripping and connection requirement, refer to instruction 5 of indoor unit.
Earth lead wire shall be Yellow/Green (Y/G) in colour and should be longer than other lead wires as shown in the fi gure for electrical safety in case of slipping.
Holder
Power supply
cord
Indoor &
outdoor
connection
cable
Earth wire longer than other AC wires for safety reasons
Earth wire longer than other AC wires for safety reasons
Control Board Cover (Metal)
Lock Nuts
Knockout Holes
Front Panel
Connecting wires
Control Board Cover (Resin)
WARNING
This equipment must be properly earthed.
Connectors
Particular Plate
Particular Plate Opening hole
Plugs
Outdoor Unit
Terminal Terminal
Indoor Unit
Disconnect Switch Field supply
Grounding wire
Grounding wire min AWG16
Power Supply Single Phase 208/230V 60Hz min AWG14
208/230V min AWG16
208/230V min AWG16
208/230V min AWG16
Terminal
Board
1
2
3
1
2
3
L1 L2