Panasonic AFPX-C14RD, AFPX-C14PD, AFPX-C14T, AFPX-C14P, AFPX-C30RD Specifications

...
FP-X Series
Strengthened Product Lineup to Meet Diversified Demands
Programmable Controllers
01/2008
High performance
Inside of FP-X
Comment
memory
Program
memory
Independent
Max.
3 Ports
Ethernet
PLC-Link
Computer
Link
Modbus-RTU
General purpose serial
communications
Maximum number of I/O points
Since up to 8 expansion units can be connected to 1 control unit, the maxi­mum number of I/O points is 300. Furthermore, with the add-on cassette and expansion FP0 adapter connected, the number of I/O points can be in­creased to 382.
High-speed operation
The 32-bit RISC processor provides the top-level processing speed in compact PLCs. The scan time is 2ms or less for 5000 steps*¹. A high-speed PLC is indis­pensable for enhancing the functionality of equipment.
*1 Basic instructions: 40%, Data transfer and operation instructions: 60%
Up to 3 channels
3 channels are available with a combination of a communication cas­sette (2-channel type) and the tool port.
The combinations of a wide variety of communication functions can support diversified applications.
Ethernet
With a communication cassette (Ethernet type), inspection data, production data and error information can be easily collected.
Modbus-RTU
Communications with equipment compatible with Modbus-RTU (binary), a worldwide de-facto standard, are available without programming. E.g. tem­perature controllers and inverters.
PLC link
With a communication cassette (RS485 type), bit data/word data can be easily shared among up to 16 FP-X units.
MEWTOCOL-COM master/slave
Easy communications with equipment compatible with Matsushita’s open protocol “MEWTOCOL” are available without programming. E.g. displays, machine vision systems, temperature controllers and power meters.
General purpose serial communications
Commands are generated/transmitted in accordance with the communication protocol of the target equipment.
Or, nonprocedural data receiving is available. E.g. measuring instruments, barcode readers and RF-ID.
Large capacity program memory
FP-X, which is equipped with 32k steps*² program memory, is ideal for fully covering the increasing functions, such as communications, positioning and analog control. The ample program capacity can also support future equipment modifications.
*2 C14: 16k steps
Multi-axial positioning
Network
SCADA system
Displays
Temperature control
Data processing
Multi-point I/O
Measuring instrument
Increase in
number and
complexity
of programs
Independent comment memory
The FP-X features an independent comment memory which facilitates program management and maintenance. Comments document a PLC project and help programmers understand the code long after the program was written.
multiple functions and strengthened lineup
High performance
Reduction of total scan time
E.g. ST, AN or OR E.g. floating point operation instructions
Faster operation of basic instructions
Faster operation of high-level instructions
Network
2
01/2008
Positioning
Product lineup
14 points
30 points
60 points
16 points
30 points
(Without a power
supply section)
(Without a power
supply section)
(Without a power
supply section)
AC
Relay output NPN output PNP output
DC AC DC AC DC
Control unit
Expansion unit
3-axis Control with C14 4-axis Control with C30/C60
100kHz x
2 axes
20kHz x
2 axes
XY Table + Processing Head Semiconductor Wafer Takeout Blade
Control unit: 18 types
(14, 30 or 60 points) x (relay, NPN or PNP) x (AC or DC)
43 combinations (number of I/O points)
14 to 300 points
Add-on cassette: 16 types
Digital I/O, Pulse I/O, Analog I/O, Communication (RS485, RS232C, Ethernet), External memory
Built-in 4-axis pulse output (transistor output type)
The transistor output type C14 comes with 3-axis while C30/60 comes with 4-axis pulse output built-in the control unit.
The multi-axis control, which previously required a higher-level PLC or additional positioning unit, or 2 or more PLC
units, can now be achieved with only 1 FP-X transistor output type unit in a small space at a low cost. In addition, as
this type does not require a pulse I/O cassette needed for a relay output type, other function expansion cassettes such
as communication or analog input can be attached for more diversified applications.
Expansion unit: 9 types
(16 points) x (relay, NPN or PNP)
(30 points) x (Relay, NPN or PNP) x (AC or DC)
FP-X meets a variety of requirements
Product lineup
Positioning
2
01/2008
4
The highly expandable lineup satisfies a wide range of demands.
Product lineup
DC power supply AC power supply DC power supply AC power supply
AFPX-C14RD AFPX-C14R
AFPX-C14TD (NPN) AFPX-C14PD (PNP)
AFPX-C14T (NPN) AFPX-C14P (PNP)
8-point input of 24VDC 6-point output of 2A relay
8-point input of 24VDC 6-point output of 2A relay
8-point input of 24VDC
0.5A/5 to 24VDC 6-point output of transistor
8-point input of 24VDC
0.5A/5 to 24VDC 6-point output of transistor
Program capacity: 16k steps
2-point potentiometer
AFPX-E16R
AFPX-E16T (NPN) AFPX-E16P (PNP)
8-point input of 24VDC 8-point output of 2A relay
8-point input of 24VDC
0.5A/5 to 24VDC 8-point output of transistor
Remarks: 2 or more E16’s cannot be connected serially because they cannot supply the power to other units.
DC power supply AC power supply DC power supply AC power supply
AFPX-C30RD AFPX-C30R
AFPX-C30TD (NPN) AFPX-C30PD (PNP)
AFPX-C30T (NPN) AFPX-C30P (PNP)
16-point input of 24VDC 14-point output of 2A relay
16-point input of 24VDC 14-point output of 2A relay
16-point input of 24VDC
0.5A/5 to 24VDC 14-point output of transistor
16-point input of 24VDC
0.5A/5 to 24VDC 14-point output of transistor
Program capacity: 32k steps 2-point potentiometer, equipped with a USB communication port
DC power supply AC power supply DC power supply AC power supply
AFPX-C60RD AFPX-C60R
AFPX-C60TD (NPN) AFPX-C60PD (PNP)
AFPX-C60T (NPN) AFPX-C60P (PNP)
32-point input of 24VDC 28-point output of 2A relay
32-point input of 24VDC 28-point output of 2A relay
32-point input of 24VDC
0.5A/5 to 24VDC 28-point output of transistor
32-point input of 24VDC
0.5A/5 to 24VDC 28-point output of transistor
Program capacity: 32k steps 4-point potentiometer, equipped with a USB communication port
DC power supply AC power supply DC power supply AC power supply
AFPX-E30RD AFPX-E30R
AFPX-E30TD (NPN) AFPX-E30PD (PNP)
AFPX-E30T (NPN) AFPX-E30P (PNP)
16-point input of 24VDC 14-point output of 2A relay
16-point input of 24VDC 14-point output of 2A relay
16-point input of 24VDC
0.5A/5 to 24VDC 14-point output of transistor
16-point input of 24VDC
0.5A/5 to 24VDC 14-point output of transistor
Remarks: Addition of up to 8 units is possible in­cluding E16 and EFP0.
Application cassette
AFPX-IN4T3
Input/Output cassette (4-point input of 24VDC, NPN 0.3A/3-point output of 24VDC)
AFPX-IN8
Input cassette (8-point input of 24VDC)
AFPX-TR8
Output cassette (NPN 0.3A/8-point output of 24VDC)
AFPX-TR6P
Output cassette (PNP 0.5A/6-point output of 24VDC)
AFPX-PLS
Pulse I/O cassette (High-speed counter input: single phase 80kHz 2ch., 2-phase 30kHz 1ch.) (Pulse output: 1 axis 100kHz < CW/CCW, pulse + sign >) *Cannot be built into a transistor output type.
AFPX-AD2
Analog input cassette (2 points, 0 to 10 V/0 to 20mA 12-bit non-insulated)
AFPX-A21
Analog I/O cassette Input: 2ch. (0 to 5V/0 to 10V or 0 to 20mA 12-bit insulated) Output: 1ch. (0 to 10V or 0 to 20mA 12-bit insulated)
AFPX-DA2
Analog output cassette 2ch. (0 to 10V or 0 to 20mA 12-bit insulated 2ch.)
AFPX-TC2
Thermocouple input cassette, (K/J type, resolution: 0.2°C, insulated 2ch.)
AFPX-MRTC
Master memory cassette with a real-time clock* (32k steps program memory + real-time clock in year/month/day/hour/minute) *Real-time clock requires an optional battery. (Real-time clock Calendar timer)
Communication cassette
AFPX-COM1
Communication cassette (RS232C 1ch.)
AFPX-COM2
Communication cassette (RS232C 2ch.)
AFPX-COM3
Communication cassette (RS485/422 selectable 1ch. insulated)
AFPX-COM4
Communication cassette (RS485 1ch. insulated + RS232C 1ch.)
AFPX-COM5
Communication cassette (Ethernet 1ch. + RS232C 1ch.)
AFPX-COM6
Communication cassette (RS485 2ch. insulated)
AFPX-EFP0
Up to 3 FP0 expansion units can be connected. Please refer to page 7 for details.
Add-on cassette
Expansion FP0 adapter
NEW
NEW
NEW
NEW
NEW
NEW
Control unit
Relay ouput Transistor ouput
Expansion unit
Relay ouput Transistor ouput
01/2008
5
Name and function of each part
FP-X series
RS232C tool port
Expansion Unit
(Model: Relay output type AFPX-E16R)
Add-on Cassette
(Model: Analog input cassette AFPX-AD2)
I/O status monitor LED
Connector for expansion unit
Securing hole
Connector for expansion unit
Connector for double-stacked mounting
* Only the communication cassette can be upper.
Input/output terminals or communication signal terminals
Input terminals
Output terminals
* Use the two opposite diagonal holes
for mounting when a communication cassette is double-stacked.
Control Unit
(Model: Relay output type AFPX-C30R)
I/O status monitor LED
Add-on cassette interface cover
Connector for add-on cassette
Connector for battery
Input terminals
Power terminals
Output terminals
RUN/PROG. mode selection switch
Potentiometer
(DC powered type has no service power output)
24V DC service power output terminals C14: 0.15A C30, C60: 0.4A
USB communication port (excluding C14R)
Connector for expansion unit
Connector for expansion unit
01/2008
C14
C30, C6 0
C14
32k
10k
16k
FP0
FP-X
C30/C60
FP-X
10k 20k 30k
steps
Processing speed of the basic instructions
(ST, OR, AND, OT etc)
0.5 1.0
0.32µsec
0.9µsec
µsec
FP-X
FP0
Max. 8 units
E30 E30 E30C60
6
Equipped with an independent comment memory
Equipped with an independent comment memory separate from the program memory. All of the 100,000 I/O comments, 5000 lines of line-space comments and 5000 lines of remark comments are saved in the FP-X together with the programs.
Input comments do not decrease the program capacity.
The high-level basic performance provides sufficient room for future equipment expansion.
Abundant program capacity—32k steps (16k steps for C14)
The program capacity of 32k steps, exceeding the capacity of most compact PLCs, can flexibly handle a wide variety of applications requiring future equipment expan­sion. An adequate comment area has of course been reserved. Free comment entry makes the program easy to understand during verification.
High-speed scan at
0.32µsec for instruction processing
High-speed processing is often required for small-scale equipment control such as serial data communication, network construction or PID temperature control. High­speed scanning at 0.32µsec/step (basic instruction) easily meets such require­ments.
E.g. With a 5k step program consisting of 40% basic instructions and 60% applied instructions (data transfer and operation instructions)
Scan time: 1.9ms (measured time)
Abundant number of I/O points—Maximum 300
(up to 382 points possible by using FP0 expansion units and add-on cassettes)
When the user is unable to predict the number of I/O points required in the future for his machine or equipment, he may be unsure when selecting a PLC model. FP-X solves user concerns by providing a maximum of 300 I/O channels. This number can even be increased up to 382 points by using the add-on cassettes and FP0 expansion units.
Up to 8 expansion units (E16R, E30R, EFP0) can be connected.
Max. 300 channels
FP-X series
High capacity, ultra high-speed processing
Program capacity
01/2008
OK
C60 E16 E16 C60 E16 E30
NG
OK
E30 E30C60
Max. 7 units (210 points) Max. 96 points
E30 E30C60
7
When further expansion or functions are required, use the existing FP0 expansion units
All control units can be expanded by up to 3 FP0 expansion units via an adapter. Applications can be expanded by using [Transistor outputs], [analog input/outputs], [thermocouple input] and [I/O link (network)].
Only 1 E16 can be connected serially. E16 can be sandwiched with E30*
* E30 requires an external
power supply
Expansion FP0 adapter (AFPX-EFP0)*
The panel surface look clean due to the uniform unit height of 90mm.
* Only 1 expansion FP0 adapter unit can be attached to a control unit.
Up to 7 FP-X expansion units can be used when the expansion FP0 adapter is attached.
In addition to the supplied 8cm expansion cable, 30cm and 80cm tpyes are available as options, allowing the units to be arranged more freely. (Total expansion cable length: 160cm max.)
Connection by using the cable included with each expansion unit.
The units can be mounted very close to each other with the cable bent inside between the units in order to save space.
Note: Total expansion cable length: 160cm max.
An 80-cm expansion cable is also available as an option.
Product number Specifications
FP0-E8X 8ch. DC input, MIL connector
FP0-E16X 16ch. DC input, MIL connector
FP0-E8YT/-E8YP 8ch. transistor output, MIL connector
FP0-E8YRS 8ch. relay output, screw terminal block
FP0-E16YT/­E16YP
16ch. transistor output, MIL connector
FP0-E32T/-E32P
16ch. DC input, 16ch. transistor output, MIL connector
FP0-E8RS
4ch. DC input, 4ch. relay output, screw terminal block
FP0-E16RS
8ch. DC input, 8ch. relay output, screw terminal block
FP0-E32RS
16ch DC input, 16ch relay output screw terminal block
Product number Specifications
FP0-A21 Analog 2ch. input, 1ch. output
FP0-A80 Analog 8ch. input
FP0-A04V Analog (voltage) 4ch. output
FP0-A04I Analog (current) 4ch. output
FP0-TC4 Thermocouple 4ch. input
FP0-TC8 Thermocouple 8ch. input
FP0-RTD6 6ch RTD input
FP0-IOL I/O link unit
FP0-CCL CC-link unit
FP0-DPS2 PROFIBUS remote I/O unit
We also have other units. Please refer to the part number list at the end of this catalog.
FP-X series
Great expandability
01/2008
C14
A, upper
A, lower
C30 C60
B
(Not attachable)
A, upper
A, lower
A, upper
A, lower
B C
Add-on Cassette
Communication Cassette
(Only one of these cassettes can be attached.)
Part number Specifications
Attachable position (see the figure below)
A, lower A, upper
B C
Application Cassette
Only a backup battery can be attached.
I/O cassette
Input cassette
Output cassette
Pulse I/O cassette
Analog input cassette
Analog output cassette
Analog I/O cassette
Thermocouple input cassette
Master memory cassette
(Only one cassette can be attached.)
AFPX-IN4T3
AFPX-IN8
AFPX-TR8
AFPX-TR6P
AFPX-PLS
AFPX-AD2
AFPX-DA2
AFPX-A21
AFPX-TC2
AFPX-MRTC
AFPX-COM1
AFPX-COM2
AFPX-COM3
AFPX-COM4
AFPX-COM5
AFPX-COM6
8-point input of 24VDC, Bi-direction (Sink/Source)
8-point output of 24VDC, NPN transistor 0.3A
6-point output of 24VDC, PNP transistor 0.5A
A: Available, N/A: Not available
4-point input of 24VDC, Bi-direction (Sink/Source)
3-point output of 24VDC, NPN transistor 0.3A
High-speed counter input: single phase 80kHz 2ch or 2-phase 30kHz 1ch
Pulse output: 1 axis 100kHz (CW/CCW, Pulse + Sign)
2-point analog input, 0 to 10V or 0 to 20mA, 12-bit, 2ms/2ch
2-point analog output, 0 to 10V or 0 to 20mA, 12-bit, 2ms/2ch
2-point analog input, 0 to 5V, 0 to 10V or 0 to 20mA, 12-bit, 2ms/2ch
1-point analog output, 0 to 10V or 0 to 20mA, 12-bit, 1ms/1ch
2-point thermocouple input, K/J type, Resolution: 0.2oC, 200ms/2ch, channels insulated
32k steps program memory + all comment saving/transfer, calendar timer (real-time clock)
RS232C 1ch
RS232C 2ch
RS485/RS422 selectable 1ch
RS485 1ch + RS232C 1ch
Ethernet 1ch + RS232C 1ch
RS485 2ch
(Cannot be used with a transistor output type control unit.)
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
N/A
N/A
N/A
N/A
N/A
N/A
N
E
W
N
E
W
N
E
W
N
E
W
N
E
W
N
E
W
8
Easily removable (2 screws to secure the unit)
Only section A has an upper side available to attach the cassette. No add-on cassettes can be attached to section C. Only a back­up battery can be attached.
 
“Require slightly more functions”, “Want to add functions to the existing equipment” —The rich variety of add-on cassettes helps solve these requirements.
Max. number of at­tachable cassettes
The add-on cassette easily adds small quantities of functions and I/O points.
C14 2 cassettes
C30, C60 3 cassettes
Attachment position (see the table above)
FP-X series
Add-on cassette (lineup)
01/2008
Loading...