Panasonic 2P14S3R276A-1A User Manual

Panasonic Industrial Company
2P14S3R276A-1A
Air Conditioning Department
2P14S3R276A-1A
Application Cooling (C) / Heating (H) Ref. Charge Limit (C/H) 24.0 oz. 680 g
(C) 28.2 oz. 800 g
Evap. Temp. Range (C/H) 5°F to 53.6°F -15oC to 12oC
(C) 14°F to 53.6°F -10oC to 12oC
Specification Number SC-52170587-C
Rated Performance @265V
Capacity 9,165 Btu/hr Motor Input 845 Watts Current 3.4 Amperes E.E.R. 10.85 Btu/hr/ W
Compressor Data
Pump Type Rotary Displacement 13.2 cc/rev Oil ATMOS M60 or equivalent Oil Charge (Precharged) 9.1 fl. oz. 270 cc Net Weight 26.5 lb 12.0 kg
1
265/277 V, 60 Hz R-22
BTU 9,000
R
Motor Data
Motor Type Permanent Split Capacitor Locked Rotor Amperes 23 A at 277 V Winding Resistance Main: 3.914W, Aux: 2.503W Max. Continuous Current
2
Maximum Operating Conditions
Condensing Temp. 149°F 65°C Return Gas Temp. 95°F 35°C Discharge Gas Temp. 239°F 115°C Motor Wire Temp. 266°F 130°C
Performance Data @265V
Based on: Return gas Temp. 95°F 35.0°C Liquid sub-cooling 15°F 8.3°C Ambient 95°F 35.0°C
Electrical Components
Overload Protector 7100504, 7100523, 7100682 Texas Instrument part # MRA98852, MRA98967,
MRA99209
.PMET.PAVE
F°53
Run Capacitor 25 µF/370 VAC
1
F°54
Evaporating Temp. 45°F 7.2°C Condensing Temp. 130°F 54.4°C Return Gas Temp. 95°F 35.0°C Liquid Temp. 115°F 46.1°C
F°55
Ambient Temp. 95°F 35.0°C
UL file no.: SA4615; CSA file no.: LR46130, LR51349, LR66348, LR76919, LR95789, LR109092
8.73
rh/utB
sttaW
serepmA
8.29.21.34.36.3
rh/utB
sttaW
serepmA
7.29.21.34.37.3
rh/utB
sttaW
serepmA
6.29.24.34.38.3
.PMET.DNOC
F°001F°011F°021F°031F°041
o
C3.34oC9.84oC4.45oC06oC
52195058519756370586
506086067538019
0811108401018956190558
006086567548529
0953151821060215231101601
095086567058539
2
Contact Panasonic for value.
2P14S3R276A-1A
265/277 V, 60 Hz R-22
BTU 9,000
WIRING DIAGRAM
COMPRESSOR ACCESSORIES
ALTL
062142
)42.01()94.9(
seirosseccArebmuNtraP
1revoClanimreT-teksaGU0260707
2nwoddlohPLO-gnirpS0021407
3revoClanimreTU9120707
4tuN-teksaGU1260707
5revoClanimreT-tuN0030807
temmorG5180707
COMPRESSOR MOUNTING
This document sets forth certain operational parameters and conditions for operation of this product. If this product is operated outside of the parameters and conditions stated herein, buyer assumes sole and full responsibility and shall indemnify seller with respect to all product failures, and all consequences thereof. Operation of the product outside of the parameters and conditions specified herein shall serve to invalidate all seller warranties, if any, with respect to the product. Use this document as reference only. For specifications, please contact Panasonics engineering department.
Loading...