Panasonic 2318 User Manual

Addressable or conventional
Fire alarm systems
Combination heat
detector 2318
General
Heat detector 2318 is a conventional com­bination heat detector, i.e. it "gives an alarm" at a certain fixed temperature (58°C) and/or at a certain temperature increase within a certain time, ("rate-of-rise").
The sensing element is a thermistor.
Addressable or conventional
The detector can be plugged in a conventional base 2324 connected to a conventional zone line (or plugged in an addressable base 2330 connected to a COM loop).
Product applications
This conventional heat detector can be used in the systems EBL500 / 512 / 128 / 1000 /
2000. The detector is intended for indoor use and
in dry premises. Product applications are small rooms where
the temperature can be expected to rise rapidly in case of a fire or places where smoke detectors can not be used.
For more details, see Planning Instructions and Connection diagrams.
Panasonic Electric Works Fire & Security Technology Europe AB Citadellsvägen 23, SE-211 18 Malmö, Sweden Tel: +46 (0)40 697 70 00 • Fax: +46 (0)40 697 70 99 info@mfstech.com • www.panasonic-fire-security.com
Type number
2318 Combination heat detector
Technical data
Voltage (V DC) rated
allowed normal
Current consumption at nom. volt. (mA)
quiescent (detector only) active (detector only)
Ambient temperature (°C) operating
storage Ambient humidity (% RH) max. 95, non condensing Ingress Protection rating (estimated) IP51
Alarm temp. (fixed temp. part) Weight (g) 85
Colour grey (N8, Muncell colour code) Approvals CE; EN54/5, response grade 1.
24 15-30 24
Depending on the type of base it is plugged into. For more details see EBL512 Planning Instructions.
0.03 min. 3
-10 to +50
-25 to +70
58°C
All technical features and data are subject to changes without notice, resulting from continuous development and improvement.
Product Leaflet Date of issue Revision / Date of revision
MEW00449 2003-09-17 2 / 2006-08-31