Fire alarm systems
External Fire Brigade
Panel 1828
• Control (key required) and indicating panel for the fire brigade personnel, etc.
• Compact size
Ext. Fire Brigade Panel
This unit (S/W V1.2) is primarily intended
to be used by the fire brigade personnel, i.e.
for pre-warning, co-incidence, fire and
heavy smoke / heat alarm presentation.
Point or zone alarm presentation and fire
alarm reset are as in the c.i.e. it is connected
to. You can scroll amongst two or more
alarms in the system. All or selected alarms
will be presented in a display
characters with back-light). An alarm text
will be presented together with each alarm,
if programmed in the c.i.e. Furthermore,
>
617 texts for selected alarms can be stored
in the unit and will in such a case be shown,
instead of the texts sent from the c.i.e. for
these alarms. A built-in buzzer
like in the c.i.e. Any fault in the system will
be presented as "General fault in system"
and the buzzer will sound. The unit is
power supplied via the c.i.e. or ext. power
supply.
(LCD, 2x40
will sound
LEDs, push buttons etc.
The unit has the following LEDs:
• Fire and Alarms queued, indicating
pre-warning, co-incidence, fire and
heavy smoke / heat alarm
• Operation, indicating that the unit is
connected to a c.i.e. and power
supplied, i.e. it is in operation.
• Extinguishing, indicating activated
output for Extinguishing equipment.
• Ventilation, indicating activated output
for Ventilation equipment.
• Fire brigade tx, indicating activated
output for Fire brigade tx (routing
equipm.).
The unit has the following push buttons:
• Alarms queued, used to scroll amongst
the alarms.
• Silence buzzer, used to silence the
buzzer
(it will re-sound for a new
alarm.
• Silence alarm devices, used to silence
the alarm devices
for a new alarm.
• Reset, used to reset the fire alarms.
The designation texts on the front are in
1828SE in Swedish but a neutral front for
other languages is available (1828CC).
(they will re-sound
Compact size
The compact size enclosure is made of grey
high impact ABS. Fitted with a supplementary "O" ring gasket, it will comply with
IP61, in respect of dust and moisture. A key
is required to get access to the push buttons
and they are disabled until they are supposed
to be used. A key is not required
alarm presentation and to silence the buzzer.
Two compression glands are attached. The
unit shall be wall mounted.
for the
SW mode and address setting
The display and the push buttons are used to
set the SW mode and address, see the
opposite side of this page.
Product application
The 1828 unit is intended for indoor use and
in dry premises. SW mode 1826/28 - 1587
is intended to be used in the systems
EBL512 and EBL128 SW mode 1826/28 –
1582 in the systems EBL500 / 512 / 1000 /
2000.
Panasonic Electric Works Fire & Security Technology Europe AB
Citadellsvägen 23, SE-211 18 Malmö, Sweden
Tel: +46 (0)40 697 70 00 • Fax: +46 (0)40 697 70 99
info-fste@eu.pewg.panasonic.com • www.panasonic-fire-security.com
Type numbers
1828 External Fire Brigade Panel (S/W V1.2). 1828SE / 1828CC: Designation texts on
the front in Swedish / see below. NOTE! In Swedish convention (SBF): No
"General fault" presentation.
1582 External FBP interface board. (Required in EBL512 / 500 when SW mode 1826/28
– 1582 shall be used.)
1587 External FBP / DU interface board. (Required in EBL512 when SW mode 1826/28
– 1587 shall be used. EBL512 software V>
2.3.2 1 required.)
2431 Connection board. (Required in EBL1000. SW mode 1826/28 – 1582 only.)
4552 RS485 Transceiver component / comm. module. (Required in EBL128. SW mode
1826/28 – 1587 only. EBL128 software V>
1
Only required if the new function ("General fault" presentation) shall be used.
NOTE! The number of ext. FBPs that can be power supplied via the c.i.e. / board / external power
supply, is depending on all other units connected to the same c.i.e. / board / ex ternal power supply.
to 1200 m cable can be used.
1828CC is a unit with a neutral front where the designation texts by production are made separately and
put into a transparent "text slot" for the LED and push button respectively. CC=Country Code.
The ext. FBP 1828 can run in one of two different SW modes:
a) 1828 in SW mode 1826/28 – 1587 has the highest performance with regard to functionality, respon se
time, ability to store fire alarms, etc. and is an alternative to the ext. Presentation display 2428, the
Display unit 2236 and a compact size alternative to the ext. FBP 2426 but not as a spare part
in this SW mode, requires an Ext. FBP / DU interface board 1587
dimensions, etc. are not the same.
This mode is always used when the ext. FBP is connected to EBL128.
b) 1828 in SW mode 1826/28 - 1582 is an alternativ e to the ext. Presentation display 2428, the Display
unit 2236 and a compact size spare part
look, dimensions, etc. are not the same. 1828, in this SW mode, requires an Ext. FBP interface board
1582 in the EBL512 / EBL500 c.i.e.
to the ext. FBP 2426, i.e. the performance is the same3 but the
1.0.5 1 required.)
in the EBL512 c.i.e. and the look,
2
Up
, since 1828,
Technical data
Voltage (V DC)
rated
allowed
normal (in the system)
normal (in the system by battery back-up)
Current consumption at norm. volt. (mA)
Ext. FBP 1828
quiescent / active
Ambient temperature (°C)
operating
storage
Ambient humidity (% RH) max. 90, non condensing
Ingress Protection rating (estimated) IP61 (with the "O" ring gasket)
Size W x H x D (mm) 220 x 145 x 50
Weight (g) 750
Colour (high impact ABS) Grey (RAL 7035)
Approvals CE; Conforms with EN54-2 and –4 whenever applicable.
2
On each 1582 board are up to eight addresses available and on each 1587 board up to sixteen addresses. In EBL128
are up to four addresses
3
Note! The alarm presentation will be as in the c.i.e. that ext. FBP is connected to, not as in 2425 / 2426. The 1828
front does not hold any LED "Zone/Detector not reset".
available.
24
12-30
24
21-27
26 (at 24 V), 48 (at 12 V) / 49 (at 24 V), 88 (at 12 V)
0 to +40
-40 to +70
Conforms with SS3654 edition 1.
All technical features and data are subject to changes without notice, resulting from continuous development and improvement.
Product Leaflet Date of issue Revision / Date of revision
MEW00336 2003-04-15 4 / 2007-01-29