Panasonic 1740 User Manual

Fire alarm systems
Alert annunciation
Controller for the Alert Annunciation function
Compact size
Alert annunciation controller
When the Alert Annunciation (AA) function shall be used in system EBL500. The unit is required for the related manoeuvres, i.e. to acknowledge / reset the alarms. For a detailed description of the Alert Annunciation function, see system EBL500 Planning and Operating Instructions. The unit shall be mounted close to the c.i.e. (or an ext. FBP / Presentation unit) where the fire alarms will be presented.
LEDs, push buttons etc.
The designation texts for the LEDs and push buttons on the front are in Swedish.
The unit has the following LEDs:
Larm, indicating fire / AA alarm.
Drift, indicating that the unit is in
operation, i.e. the AA function is enabled in the system. Normally a time channel is used to enable this function.
Räddningstjänsten larmad, indicating
that the "Fire brigade tx" output is activated in the c.i.e. because:
- the activated fire alarm is not alarm
- the AA function has been ended, e.g. the acknowledge or investigation time has run out, etc.
Kvittering, indicating that the AA alarm
has been acknowledged.
an AA
Compact size
The compact size enclosure is made of grey high impact ABS. Fitted with a supple­mentary "O" ring gasket, it will comply with IP61, in respect of dust and moisture. The unit has no door, i.e. the front is accessed directly, when required. The push buttons are disabled until they are supposed to be used. The unit shall be wall mounted.
Miscellaneous
The LED "Kvittering" (Acknowledge) can be turned on by the push button "Kvittering" (Acknowledge) or by an input, i.e. a programmable output in the c.i.e. This is set via a jumper "JP1" in the unit. The unit is power supplied from the c.i.e. or an external power supply. One supplementary compression gland can be used for cable entry when required.
Product application
1740 is intended to be used in the fire alarm system EBL500 but can be used in the systems EBL1000 / 2000 / 512 / 128 as well.
The 1740 controller is intended to succeed the alert annunciation controller 2232.
The unit has the following push buttons:
Kvittering, used to acknowledge an AA
alarm.
Återställning, used to reset an AA
alarm.
Panasonic Electric Works Fire & Security Technology Europe AB Citadellsvägen 23, SE-211 18 Malmö, Sweden Tel: +46 (0)40 697 70 00 • Fax: +46 (0)40 697 70 99 info@mfstech.com • www.panasonic-fire-security.com
Type number
1740 Alert annunciation controller.
Technical data
Voltage (V DC) nominal Current consumption at nom. volt. (mA) quiescent active2
Ambient temperature (°C) operating storage Ambient humidity (% RH) max. 90, non condensing Ingress Protection rating (estimated) IP61 (with the "O" ring gasket)
Inputs
1. Operation
2. Fire
3. Fire brigade alerted
4. Acknowledged Outputs
1. Acknowledge
2. Reset Size W x H x D (mm) 220 x 145 x 50 Weight, (g) 400 Colour (high impact ABS) Grey (RAL 7035) Approvals CE; Conforms to EN54-2 and –4 whenever applicable. Conforms to
1
See input 1 below.
10 40
0 to +40
-40 to +70
24 V DC, (voltage input, 19-30 V DC, via a time channel) General fire alarm (normally open contact) Fire brigade tx activated (normally open contact) Alert annunciation acknowledged (normally open contact)
Relay contacts for 1 A @ 24 V DC. Push button "Kvittering" activated (normally open)
Push button "Återställning" activated (normally open)
SBF 110:6.
1
LED "Drift" turned on.
2
LED "Kvittering" or LED "Räddningstjänsten larmad" turned on.
All technical features and data are subject to changes without notice, resulting from continuous development and improvement.
Product Leaflet Date of issue Revision / Date of revision
MEW00279 2002-10-21 3 / 2006-08-31