Panasonic 1735, 1736 User Manual

Fire alarm systems
Alert annunciation units
Control and indicating unit for alert annunciation
Compact size
Alert annunciation unit
When the Alert Annunciation function shall be used in the systems EBL512 & EBL128 an AA unit is required to present the AA alarms and for the related manoeuvres, i.e. to acknowledge / reset the alarms. For a detailed description of the AA function, see Planning and Operating instructions for the system respectively. Point or zone alarm presentation is as in the c.i.e. it is connected to. When there are queued alarms in the system, you can scroll amongst them. All or selected alarms will be presented in the unit's display 2x40 characters with back-light). A user definable text message will be presented together with each alarm, if programmed in the c.i.e. Furthermore, > selected alarms be stored in the unit and will in that case be shown, instead of the texts sent from the c.i.e. for these alarms. A built­in buzzer acknowledged AA alarm. The unit is power supplied via the c.i.e. or ext. power supply.
will sound to indicate a not
617 texts can for
(LCD,
LEDs, push buttons etc.
The unit has the following LEDs:
Fire and Alarms queued, indicating fire
alarm / AA alarm.
Operation, indicating that the AA
function is enabled in the system. Normally a time channel is used to enable this function.
Fire brigade alerted, indicating that the
"Fire brigade tx" output is activated in the c.i.e. because:
- the activated alarm is not
- the AA function has been ended, e.g.
the acknowledge or investigation time has run out, etc.
Panasonic Electric Works Fire & Security Technology Europe AB Citadellsvägen 23, SE-211 18 Malmö, Sweden Tel: +46 (0)40 697 70 00 • Fax: +46 (0)40 697 70 99 info@mfstech.com • www.panasonic-fire-security.com
an AA alarm
Acknowledge, indicating that the AA
alarm has been acknowledged.
The unit has the following push buttons:
Alarms queued, used to scroll amongst
the alarms.
Acknowledge, used to acknowledge an
AA alarm and hereby also silence the
buzzer.
Reset, used to reset an AA alarm. 1735 has the designation texts in Swedish. 1736 has a neutral front for other languages,
see the opposite side of this page. (This front also holds one extra LED & two extra push buttons.)
Compact size
The compact size enclosure is made of grey high impact ABS. Fitted with a supple­mentary "O" ring gasket, it will comply with IP61, in respect of dust and moisture. The unit has no door, i.e. the front is accessed directly, when required. The push buttons are disabled until they are supposed to be used. The unit shall be wall mounted. Two compression glands are attached.
SW mode and address setting
The display and the push buttons are used to set the SW mode and address.
The SW modes are described on the opposite side of this page.
Product application
The units are intended for indoor use and in dry premises. They are intended to be used in the systems EBL512 & EBL128. An External FBP / DU interface board 1587 is required in the EBL512 c.i.e. and a 4552 Transceiver component in the EBL128 c.i.e.
Type numbers
1735 Alert annunciation unit. Swedish designation texts. 1736 Alert annunciation unit. Designation texts in any language. 1587 External FBP / DU interface board in EBL512, for connection of the 1735 and
1736 units in system EBL512. (Software version >
2.2 is required.)
4552 RS485 transceiver component, for connection of up to four display units, e.g.
Alert Annunciation Units 1735 / 1736 in system EBL128.
NOTE! The number of units that can be power supplied via the c.i.e. (or an external power supply) is depending on all other units connected to the same c.i.e. / external power supply. Up to 1200 m cable can be used.
The 1736 unit has a neutral front
where the designation texts, by production, are made
separately and put into a transparent "text slot" for the LED and push button respectively.
1735 succeeds the Display unit (with alert annunciation) 2235SE but not as a spare part
, since 2235SE is connected to a COM loop and 1735 requires an Ext. FBP / DU interface board 1587 in the c.i.e.
(2235SE = Swedish designation texts.) 1736 succeeds the Display unit (with alert annunciation) 2235xx but not as a spare part
, since 2235xx is connected to a COM loop and 1736 requires an Ext. FBP / DU interface board 1587 in the c.i.e.
(2235xx = Designation texts in another language than Swedish.) The AA unit 1735 and AA unit 1736 shall run in SW mode 1735 – 1587 and SW mode 1736 –
1587 respectively.
Technical data
Voltage (V DC) rated
allowed normal (in the system)
normal (in the system by battery back-up) Current consumption at norm. volt. (mA) AA unit 1735 / 1736
quiescent / active Ambient temperature (°C)
operating storage
Ambient humidity (% RH) max. 90, non condensing Ingress Protection rating (estimated) IP61 (with the "O" ring gasket)
Size W x H x D (mm) 220 x 145 x 50 Weight (g) 1735
1736 Colour (high impact ABS) Grey (RAL 7035) Approvals CE; Conforms with EN54-2 and –4 whenever applicable.
24 12-30
24 21-27
26 (at 24 V), 48 (at 12 V) / 42 (at 24 V), 79 (at 12 V)
0 to +40
-40 to +70
687 691
Conforms with SBF 110:6.
All technical features and data are subject to changes without notice, resulting from continuous development and improvement.
Product Leaflet Date of issue Revision / Date of revision
MEW00278 2003-04-16 3 / 2006-08-31